* Design and Specifications subject to change without prior notice for product improvement.
- 6 -
Dimensions
D
W
H
(1) Indoor Unit
Installation plate
Tubing hole cover
Tubing hole cover
MODEL
DIM
Wmm(inch)900(35.4")1,080(42.5")
Hmm(inch)290(11.4")290(11.4")
Dmm(inch)183(7.2")183(7.2")
9k, 12k18k, 24k
- 7 -
W
L6L5L7L8
D
L1
L2
L9L10
L3L4
H
(2) Outdoor Unit
2-way valve
Gas side
3-way valve
(9k, 12k)
Gas side
3-way valve
3-way valve
MODEL
DIM
Wmm(inch)801(31.5)870(34.3)
Hmm(inch)555(21.8)655(25.8)
Dmm(inch)262(10.3)320(12.6)
L1mm(inch)339(13.3)370(14.6)
L2mm(inch)37(1.5)25(1.0)
L3mm(inch)543.6(21.4)630(24.8)
L4mm(inch)11.4(0.45)25(1.0)
L5mm(inch)591(23.3)546(21.5)
L6mm(inch)105(4.13)162(6.4)
L7mm(inch)105(4.13)162(6.4)
L8mm(inch)72.5(2.85)54(2.1)
L9mm(inch)77(3.03)74.5(2.9)
9k, 12k18k, 24k
(18k, 24k)
L10mm(inch)86.4(3.4)79(3.1)
- 8 -
Refrigeration Cycle Diagram
• Cooling Only Models
INDOOR UNIT
HEAT
EXCHANGER
(EVAPORATOR)
GAS SIDE
OUTDOOR UNIT
CAPILLARY TUBE
LIQUID SIDE
HEAT
EXCHANGER
(CONDENSER)
COMPRESSOR
Pipe size(Diameter:ø)Piping lengthElevation
MODEL
GasLiquidRatedMaxRatedMax
9k, 12k
(Cooling Only)
18k, 24k
(Cooling Only)
For installation over rated, *a proper quantity of refrigerant should be added for each 5 foot.
a proper quantity of refrigerant
9k, 12k0.2 Oz
18k, 24k0.3 Oz
Unit precharged for 25ft. line sets.
1/2"1/4"7.62m(25ft)15m(50ft)5m(16ft)8m(26ft)
5/8"3/8"7.62m(25ft)15m(50ft)5m(16ft)8m(26ft)
Ex) 18K: When installed at a distance of 30ft, 1.5 Oz of
refrigerant should be added.
(30-25) x 0.302 = 1.5 Oz of refrigerant to add
- 9 -
• Cooling & Heating Models
INDOOR UNIT
HEAT
EXCHANGER
(EVAPORATOR)
GAS SIDE
OUTDOOR UNIT
CAPILLARY TUBE
COMPRESSOR
CHECK VALVE
HEAT
EXCHANGER
(CONDENSER)
REVERSING
VALVE
COOLING
HEATING
Pipe size(Diameter:ø)Piping lengthElevation
MODEL
9k, 12k
(Cooling & Heating)
18k, 24k
(Cooling & Heating)
For installation over rated, *a proper quantity of refrigerant should be added for each foot.
a proper quantity of refrigerant
9k, 12k0.2 Oz
18k, 24k0.3 Oz
Unit precharged for 25ft. line sets.
GasLiquidRatedMaxRatedMax
1/2"1/4"7.62m(25ft)15m(50ft)5m(16ft)8m(26ft)
5/8"3/8"7.62m(25ft)15m(50ft)5m(16ft)8m(26ft)
Ex) 18K: When installed at a distance of 30ft, 1.5 Oz of
refrigerant should be added.
(30-25) x 0.302 = 1.5 Oz of refrigerant to add
- 10 -
Wiring Diagram
4
3
2
1
BLDC
MOTOR
STEP
MOTOR
MAIN P.C.B
INDOOR WIRING DIAGRAM
TO OUTDOOR UNIT
DISPLAY P.C.B
(ROOM)
(PIPE)
THERMISTOR
CN-UP/DOWN
3854AR7074A
CN-MOTOR
PILLAR
TERMINAL
CN-DC/DC
CN-DISP
CN-TH
BL
BK
BR
RD
4
3
2
1
BL
BK
BR
RD
PILLAR
TERMINAL
ROOM-
THERMISTOR
CN-UP/DOWNCN-MOTOR
STEP
MOTOR
MAIN P.C.B
INDOOR WIRING DIAGRAM
3854AR7209A
BLDC
MOTOR
CN-DC/DC
CN-THCN-DISP
DISPLAY P.C.B
TO OUTDOOR UNIT
(1) Indoor Unit
1. MSS-012, MSS-018, MSH-018, MSS-024, MSH-024
2. MSS-009, MSS-012
- 11 -
(2) Outdoor Unit
MAIN P.C.B
MOTOR
TERMINAL
BLOCK
POWER
INPUT
TRANSFORMER
CAPACITOR
COMP.
G
OUTDOOR WIRING DIAGRAM
TO INDOOR UNIT
3854AR7077C
OR(BR)
BR YL
4
3
BL
BL
BK
BK
CN-TRANS
CN - FAN
RY-FAN
RY-COMP
CN- POWER
ZNR
CN-DC/DC
FUSE
3.15A
BK
TB/1
BK
YL
GN/YL
BR
RD
BR
BK
BL
BL
BR
S
R
C
H
C
F
G
RD
1
2
3
4
5(L1)
6(L2)
T/B 1
MAIN P.C.B
MOTOR
TERMINAL
BLOCK
POWER
INPUT
TRANSFORMER
CAPACITOR
G
OUTDOOR WIRING DIAGRAM
TO INDOOR UNIT
3854AR2262X
BL
4
3
BL
BL
BK
BK
CN-TRANS
RY-COMP
CN- POWER
ZNR
CN-DC/DC
FUSE
3.15A
YL
YL
RD
GN/YL
BR
BR
BR
BR
RD
RD
BR
BK
BL
BL
BR
S
R
C
H
C
F
G
1
2
3
4
5(L1)
6(L2)
COMP.
O.L.P
MAIN P.C.B
MOTOR
TERMINAL
BLOCK
POWER
INPUT
TRANSFORMER
CAPACITOR
COMP.
G
OUTDOOR WIRING DIAGRAM
TO INDOOR UNIT
3854AR7077D
OR(BR)
BR YL
4
3
BL
BL
BK
BK
CN-TRANS
CN - FAN
RY-FAN
RY-COMP
CN- POWER
ZNR
CN-DC/DC
FUSE
3.15A
BK
TB/1
BK
YL
GN/YL
BR
BR
RD
BR
BK
BL
BL
BR
S
R
C
H
F
G
1
0
2
4
6
8
BR
RD
BR
BL
1
2
3
4
5(L1)
6(L2)
C
• Cooling Only Models
1. 9k, 12k
2. 18k
3. 24k
- 12 -
• Cooling & Heating Models
4WAYVALVE
T/B 1
T/B 2
T/B 3
T/B 4
MAIN P.C.B
H.P
SWITCH
MOTOR
CRANK
CASE
HEATER
TERMINAL
BLOCK
POWER
INPUT
TRANSFORMER
THERMISTOR
(COIL)
CAPACITOR
COMP.
G
OUTDOOR WIRING DIAGRAM
TO INDOOR UNIT
3854AR7077A
OR(BR)
BR YL
4
3
BK
BK
BK
BL
BL
BK
BK
RY-4WAY
CN-TH
CN-TRANS
CN - 4WAY
CN - FAN
RY-FAN
RY-HEATER
RY-COMP
CN- POWER
ZNR
CN-DC/DC
FUSE
3.15A
WH
WH
WH
WH
RD
BK
BK
BK
RD
YL
GN/YL
BR
BR
RD
RD
BR
BK
BL
BL
BR
1
2
3
4
5(L1)
6(L2)
S
R
C
H
C
F
G
4WAYVALVE
T/B 1
T/B 2
T/B 4
T/B 3
MAIN P.C.B
MOTOR
CRANK
CASE
HEATER
TERMINAL
BLOCK
POWER
INPUT
TRANSFORMER
THERMISTOR
(COIL)
CAPACITOR
COMP.
G
OUTDOOR WIRING DIAGRAM
TO INDOOR UNIT
3854AR2262Y
BL
BR
BR
YL
4
3
BK
BK
BK
BL
BL
BK
BK
RY-4WAY
CN-TH
CN-TRANS
CN - 4WAY
CN - FAN
RY-FAN
RY-HEATER
RY-COMP
CN- POWER
ZNR
CN-DC/DC
FUSE
3.15A
WH
WH
WH
WH
RD
BK
YL
RD
RD
GN/YL
BR
BR
RD
RD
BR
BK
BL
BL
BR
1
2
3
4
5(L1)
6(L2)
S
R
C
H
C
F
G
O.L.P
4WAYVALVE
T/B 1
T/B 2
T/B 3
T/B 4
MAIN P.C.B
H.P
SWITCH
MOTOR
CRANK CASE
HEATER
TERMINAL
BLOCK
POWER
INPUT
TRANSFORMER
THERMISTOR
(COIL)
CAPACITOR
COMP.
G
OUTDOOR WIRING DIAGRAM
TO INDOOR UNIT
3854AR7077B
OR(BR)
BR YL
4
3
BK
BK
BK
BL
BL
BK
BK
RY-4WAY
CN-TH
CN-TRANS
CN - 4WAY
CN - FAN
RY-FAN
RY-HEATER
RY-COMP
CN- POWER
ZNR
CN-DC/DC
FUSE
3.15A
WH
WH
WH
WH
RD
BK
BK
BK
RD
YL
GN/YL
BR
BR
RD
BR
BK
BL
BL
BR
S
R
C
H
C
F
G
1
0
2
4
6
8
BR
RD
BR
BL
1
2
3
4
5(L1)
6(L2)
1. 12k
2. 18k
3. 24k
- 13 -
Operation Details
0
1
2
3
4
5
115
Cooling
Cooling
Horizontal
Setting point
Heating
Heating
(Close)
6
7
7
9
0
1
2
3
4
5
145
Cooling
Cooling
Horizontal
Setting point
Heating
Heating
(Close)
6
7
8
9
(1) The function of main control
1. Time delay Safety Control
• 3min.; The compressor operation is delayed for 3 minutes to balance the pressure of cycle.
(Protection of compressor)
• 5sec.;
• 2min.; The reversing valve is delayed for 2 minutes to prevent the refrigerant-gas for abnormal noise when
2. Airflow Direction Control
The indoor fan is delayed for 5 seconds, when operating initially, to prevent noises occurred by the vertical
louver and wind.
the heating operation is OFF or switched to the other operation mode while compressor is off.
While compressor is running, it takes 3~5 seconds to switch.
• This function is to swing the vertical louver up and down automatically and to set it at a fixed position.
• The procedure is as the following.
1st ; Press the ON/OFF Button to operate the unit.
2nd ; Press the Airflow Direction Control Button to swing the vertical louver up and down automatically.
3nd ; Repress the Airflow Direction Control Button to set the vertical louver at a fixed position.
<9k, 12k>
<18k, 24k>
3. Cooling Operation Mode
• When selecting the Cooling() Mode Operation, the unit will operate according to the setting by the
remote controller and the operation diagram is shown below.
INTAKE AIR TEMP.
SETTING TEMP. +1°F
(Compressor ON)
SETTING TEMP. -1°F
(Compressor OFF)
INDOOR FAN SPEEDLowLow
Selecting
fan speed
COMPRESSORONOFFONOFFON
■ Protection of the indoor heat exchanger from frosting
• Compressor and outdoor fan stop when indoor pipe temperature is below 32°F and restart at the pipe
temperature is above 45°F.
More than
3 minutes
- 14 -
Selecting
fan speed
More than
3 minutes
Selecting
fan speed
4. Auto Operation (Electronic control mode)
• The operation procedure is shown below. (Cooling & Heating Model)
Press Start/Stop Button
Select Auto Operation Mode
Check the Room temperature
Operation mode
Indoor fan speedare decided automatically by the unit electronic control.
Setting temperature
Intake-air
temperature
Operation Mode
❋ If initial mode is decided, that mode is continued without the room temperature changing.
■ Auto Operation for Cooling
Operation Condition
When Auto Operation
initial start
When pressing room
temperature setting
button during Auto
Operation
Intake-air TemperatureSetting Temperature
Over 76°F~below 78°FIntake air -1°C
Over 72°F~below 76°FIntake air -0.5°C
Over 68°F~below 72°FIntake air temperature
Over 64°F~below 86°FElectronic control
below 70°F
Heating
Over 78°F77°F
below 64°F64°F
below 64°F64°F
over 86°F86°F
Overbelow
70°F76
~
Soft Dry
°
F
Fan SpeedAir Direction Control
Controlled by
the electronic
control
Over 76°F
Cooling
In this mode,
when pressing
the vertical air
direction control
button, vertical
louver swings up
and down
automatically.
INTAKE AIR TEMP.
SETTING TEMP. +1°F
(Compressor OFF)
SETTING TEMP. -1°F
(Compressor ON)
INDOOR FAN SPEEDThe electronic control operation
COMPRESSORONOFFONOFF
- 15 -
■ Auto Operation for Soft Dry(only Heating Model)
• The Setting temperature will be same that of the auto operation for cooling.
- Compressor ON temperature; Setting temperature +2°F
- Compressor OFF temperature; Setting temperture -1°F
- Compressor OFF temperature; Setting temperature +6°F
■ Vertical louver auto operation
: In Auto operation mode, when pressing the vertical airflow direction control
button, vertical louver moves as shown below.
MODE0
MODE1
MODE2
MODE3
MODE4
MODE5
End
MODE6
Start
MODE9
(CLOSED)
- 16 -
5. Soft Dry Operation Mode
• During Soft Dry Operation, the compressor ON temperature is the setting temperature plus 2°F, the compres-
sor OFF temperature is the setting temperature minus 1°F.
• When the room temperature rises over the compressor ON temperature, the operation mode is switched to
the Cooling operation.
• When the room temperature falls between the compressor ON temperature and OFF temperature, the opera-
tion mode is switched to the Soft Dry Operation.
• The operation diagram is shown below.
INTAKE AIR TEMP.
Cooling
Operation
Soft Dry Operation
Cooling
Operation
SETTING TEMP. +2°F
(Compressor ON)
SETTING TEMP. -1
(Compressor OFF)
INDOOR FAN SPEEDLowLowLowLowLow
°
F
Selecting
fan speed
3 minutes
10 minutes
maximum
7 minutes
3 minutes
maximum
10 minutes
Selecting
fan speed
COMPRESSORONOFFONOFFONOFFON
maximum
4 minutes
- 17 -
6. Heating Operation Mode(only Heating Model)
OFFOFFLOW
ON
Selecting
fan speed
The unit will operate according to the setting conditions by the remote controller.
The operation diagram is shown below.
INTAKE AIR TEMP.
°
SETTING TEMP. +6
(Compressor OFF)
F
A
B
SETTING TEMP.
(Compressor ON)
INDOOR FAN SPEED
Selecting
fan speed
minimum
10sec.
Low
OFF
minimum
1 min.
Selecting
LowLowOFF
fan speed
minimum
10sec.
COMPRESSORONOFFONOFF
• A point; While the indoor pipe temperature is higher than 95°F, indoor fan operates at low speed. When the
indoor pipe temperature becomes lower than 95°F, indoor fan stops.
• B point; When the indoor pipe temperature is higher than 82°F, fan operates at selected fan speed.
■ Hot-Start Control
A
• The indoor fan stops until the indoor pipe temperature will be reached at 82°F.
• During heating operation, if indoor pipe temperature falls below 78°F fan stops.
• The operation diagram is shown below.
INDOOR PIPE
1min
TEMP.
82°F
78°F
INDOOR FAN SPEED
COMPRESSOR
- 18 -
■ Defrost Control
• Defrost operation is controlled by timer and sensing temperature of outdoor pipe.
• The first defrost starts only when the outdoor pipe temperature falls below 21°F after 60 minutes passed from
starting of heating operation and more than 10 minutes operation of compressor.
• Defrost ends after 12 minutes passed from starting of defrost operation or when the outdoor fan operates within 4 minutes after the outdoor pipe temperature rises over 54°F even if before 12 minutes.
• The second defrost starts only when the outdoor pipe temperature falls below 21°F after 60 minutes passed
from ending of the first defrost and more than 10 minutes operation of compressor.
OUTDOOR
PIPE TEMP.
54°F
(DEFROST OFF)
21°F
(DEFROST ON)
INDOOR FAN SPEEDONOFFONOFF
COMPRESSORONONONON
4-WAY VALVEONOFFON OFF
OUTDOOR FANONOFFONOFF
More than 60 minutes of
heating operation
More than 10 min.
running of compressor
Within
12minutes
Defrost
Within
4 minutes
More than 60 minutes of
heating operation
More than 10 min.
running of compressor
HOT-
START
Defrost
- 19 -
7. Cooling or Heating Mode with Sleep Mode Auto Control
• When selecting the Cooling() or the Heating( ) combined with the Sleep Mode Auto Control( ),
the operation diagram is as following.
■ Cooling Mode with the Sleep Mode
• The setting temperature will be automatically raised by 2°F 30 minutes later and by 4
• The operation will be stopped after 1, 2, 3, 4, 5, 6, 7 hours.
INTAKE AIR TEMP.
SETTING TEMP. +1
(Compressor ON)
SETTING TEMP. -1°F
(Compressor OFF)
INDOOR FAN SPEEDLowLowLowLowLow
COMPRESSORONOFFONOFFON
■ Heating Mode with the Sleep Mode(only Heating Model)
INTAKE AIR TEMP.
SETTING TEMP. +6°F
(Compressor OFF)
°
F
30 minutes
More than
3 minutes
2°F
More than
3 minutes
°
F 1 hour later.
30 minutes
2°F
SETTING TEMP.
(Compressor ON)
INDOOR FAN SPEEDMedLow or OFFMedLow or OFFMedLow or OFF
COMPRESSORONOFFONOFFONOFF
More than
3 minutes
More than
3 minutes
More than
3 minutes
- 20 -
8. Forced Operation
• If you lose wireless remote controller, you can operate the unit with forced operation button.
• Unit operates in low fan speed for first 15 seconds, then switched to proper operation mode according to
intake air temperature.
Press the Forced Operation Button.
Forced Operation
Button
Open the front
panel upward
• Press the Forced Operation Button once again
to stop operation.
9. Crank Case Heater Coil Control(only Heating model)
• When the power is applied to the set, the heater operates unconditionally.
• Except for the heating mode operation, the heater is always to be off.
• During the heating mode operation, the heater and compressor are operated by turns.
(Compressor ON → Heater OFF, Compressor OFF → Heater ON)
- 21 -
Test Mode
Test operation will be set by pushing the "Test key" on the main PWB Assy. Each test operation by pushing
count of "Test key" is as well as the following.
(1) Indoor
• Once push : Ignore communication error.
• Twice push : Shorten the proceeding time.(1min → 1sec)
• 3 Times push : Shorten the proceeding time.(1hour → 1sec)
• 4 Times push : All LED ON
• 5 Times push : Up/Down Step Motor ON.
• 6 Times push : Right Step Motor ON. (Not on all Models)
• 7 Times push : Left Step Motor ON.(Not on all Models)
• 8 Times push : Negative lon ON.(Not on all Models)
• 9 Times push : Reset.
Note)
For normal operation after checking by test mode, you should reset main power.
• 3 Times push : Comp. ON, Outdoor Fan ON
Reversing Valve Coil OFF(only Heating Model)
Crank Case Heater Coil OFF(only Heating Model)
• 4 Times push : Same
• 5 Times push : Error LED(Red) ON
• 6 Times push : Comp OFF, Outdoor FAN OFF
• 7 Times push : Reset
Note)
For normal operation after checking by test mode, you should reset main power.
- 22 -
Display Function
Operation Indicator
• Cooling, Soft Dry, Fan, Heating
Sleep timer Indicator
• Sleep Mode
Timer Indicator
• Timer Mode
Defrost Indicator or
Hot start Indicator
OUT
DOOR
• Hot-start, Defrost
• Compressor ON
: Cooling & Heating Model only
: only Cooling Model
• BUZZER SOUND
• Power Input or Reset : One short beep.
• When Operation Stop Button is pressed : One long beep.
• When Remote Controller Buttons except for Operation Stop are pressed : Two short beep.
• When Forced Operation Button is pressed : Two Short beep.
Self-diagnosis Function
CODE NO.DIAGNOSISOperation Indicator LED BlinksUnit Operation
Indoor room temperature thermistor or
pipe temperature thermistor Short/Open
OnceStill Operation
Outdoor pipe thermistor Short/OpenTwiceOutdoor Unit Off
Communication failure between indoor and
outdoor
Indoor fan locked 8 times Stop
• LED blinks as many times as code No. (0.5 second ON/0.5 second OFF) with 3 seconds interval.
• While the unit is off, no indication displays.
• If more than one code occurs simultaneously, bigger code No. is displayed.
5 timesStop
- 23 -
Installation
IMPORTANT!
Please read this instruction sheet completely before installing the product.
This air conditioning system meets strict safety and operating standards. As the installer or service person, it is an important
part of your job to install or service the system so it operates safely and efficiently.
WARNING
• Installation or repairs made by unqualified persons can result in hazards to you and others.
Installation MUST conform with local building codes or, in the absence of local codes, with the National Electrical Code NFPA 70/ANSI
C1-1993 or current edition and Canadian Electrical Code Part1 CSA C.22.1.
• The information contained in the manual is intended for use by a qualified service technician familiar with safety procedures and
equipped with the proper tools and test instruments.
• Failure to carefully read and follow all instructions in this manual can result in equipment malfunction, property damage, personal injury
and/or death.
CAUTION
: Improper installation, adjustment, alteration, service or maintenance can void the warranty.
The weight of the condensing unit requires caution and proper handling procedures when lifting or moving to avoid
personal injury. Use care to avoid contact with sharp or pointed edges.
Safety Precautions
• Always wear safety eye wear and work gloves when installing equipment.
• Never assume electrical power is disconnected. Check with meter and equipment.
• Keep hands out of fan areas when power is connected to equipment.
• R-22 causes frostbite burns.
• R-22 is toxic when burned.
NOTE TO INSTALLING DEALER
: The Owners Instructions and Warranty are to be given to the owner or
prominently displayed near the indoor Furnace/Air Handler Unit.
Special warnings
When wiring:
Electrical shock can cause severe personal injury or death. Only a qualified, experienced
electrician should attempt to wire this system.
• Do not supply power to the unit until all wiring and tubing are completed or reconnected and checked.
• Highly dangerous electrical voltages are used in this system. Carefully refer to the wiring diagram and these instructions when wiring.
Improper connections and inadequate grounding can cause accidental injury or death.
• Ground the unit following local electrical codes.
• Connect all wiring tightly. Loose wiring may cause overheating at connection points and a possible fire hazard.
When transporting:
Be careful when picking up and moving the indoor and outdoor units. Get a partner to help, and bend your knees when
lifting to reduce strain on your back. Sharp edges or thin aluminum fins on the air conditioner can cut your finger.
When installing...
... in a wall: Make sure the wall is strong enough to hold the unit's weight.
... in a room: Properly insulate any tubing run inside a room to prevent "sweating" that can cause dripping and water
... in moist or uneven locatinons: Use a raised concrete pad or concrete blocks provide a solid, level foundation for the
... in an area with high winds: Securely anchor the outdoor unit down with bolts and a metal frame. Provide a
... in a snowy area(for Heat Pump Model): Install the outdoor unit on a raised platform that is higher than drifting
It may be necessary to construct a strong wood or metal frame to provide added support.
damage to wall and floors.
outdoor unit. This prevents water damage and abnormal vibration.
suitable air baffle.
snow. Provide snow vents.
When connecting refrigerant tubing
• Keep all tubing runs as short as possible.
• Use the flare method for connecting tubing.
• Check carefully for leaks before starting the test run.
When servicing
• Turn the power OFF at the main power box(mains) before opening the unit to check or repair electrical parts and
wiring.
• Keep your fingers and clothing away from any moving parts.
• Clean up the site after you finish, remembering to check that no metal scraps or bits of wiring have been left inside
the unit being serviced.
- 24 -
(1) Installation Parts Provided
1. Type "A" screw
2. Installation Plate
(2) Installation of Indoor, Outdoor unit
1) Selection of the best location
1. Indoor unit.
•
There should not be any heat source or steam near
the unit.
• There should not be any obstacles to prevent the air
circulation.
• A place where air circulation in the room will be good.
• A place where drainage can be easily obtained.
• A place where noise prevention is taken into
consideration.
• Do not install the unit near the door way.
• Ensure the spaces indicated by arrows from the wall,
ceiling, fence, or other obstacles.
2. Outdoor unit
• If an awning is built over the unit to prevent direct
sunlight or rain exposure, be careful that heat
radiation from the condenser is not restricted.
• There should not be any animals or plants which could
be affected by hot air discharged.
• Ensure the spaces indicated by arrows from the wall,
ceiling, fence, or other obstacles.
3. Type "B" screw
4. Holder Remote-Controller
More than
5 cm(2")
More than eye level
More than 10 cm(4")
More than 5 cm(2")
More than
5 cm(2")
More than 10 cm(4")
Roof Top Installations
If it is necessary to install units on a roof structure, be
sure to elevate and level the units. Ensure the roof
structure and anchoring method are adequate for unit
location. Consult local codes regarding rooftop mounting.
NOTE: When condensing unit is to be installed on a
bonded guaranted roof, a release must be obtained
from the building owner to free the installer from all
liabilities.
3. Piping length and the elevation
MODEL
(Cooling Capa.)
9k, 12k1/2"1/4"15m(50ft)8m(26ft)
18k, 24k5/8"3/8"15m(50ft)8m(26ft)
Pipe Size
GASLIQUID
Max.
length
A
Max.
Elevation
B
More than 70 cm(28")
Indoor unit
A
B
Outdoor unit
- 25 -
2) Indoor Unit Installation
The mounting wall should be strong and solid enough to
protect it from the vibration.
1.Mount the installation plate on the wall with four
Type "A" screws.
(if mounting the unit on the concrete wall, consider
using anchor bolts.)
• Always mount the Installation Plate horizontally by
aligning the marking-off line by means of the thread
and a level.
2. Drill the piping hole with 70mm(2.75") dia.
holecore drill.
• Drill the Piping hole at either the right or the left and
the hole should be slightly slanted to the outdoor
side.
Installation Plate
Type "A" screw
marking-off line
Thread
Weight
The lower left and right side of Installation Plate
Left rear piping
Right rear piping
1"
(25mm)2"(51mm)
WARNING
Avoid areas where electrical wiring, conduits or
gas lines are located. Accidentally cutting a live
wire or gas line can cause death or injury.
1.8"
(46mm)
9k, 12k, 18k, 24k
2.75"(70mm)
ø
Installation plate
WALL
IndoorOutdoor
5-7mm
9k, 12k
(0.2~0.3")
1.9"
(48mm)
Hole center
18k, 24k
- 26 -
Loading...
+ 59 hidden pages
You need points to download manuals.
1 point = 1 manual.
You can buy points or you can get point for every manual you upload.