Endress and Hauser and Co FMR6XEF User Manual

TI01304F/00/EN/03.17
Products Solutions Services
Technical Information
Micropilot FMR67
Free space radar
Level measurement in bulk solids
Application
• Continuous, non-contact level measurement of bulk solids ranging from powdery to lumpy
• PTFE drip-off antenna or PTFE-plated, flush-mounted antenna
• Maximum measuring range: 125 m (410 ft)
• Temperature: –40 to +200 °C (–40 to +392 °F)
• Pressure: –1 to +16 bar (–14.5 to +232 psi)
• International explosion protection certificates
• Linearity protocol (3-point, 5-point)
Your benefits
• Innovative drip-off antenna made of PTFE for maximum system availability
• Reliable measurement thanks to improved focusing and small beam angle, particularly in silos with many internal fittings
• Large measuring ranges up to 125 m (410 ft)
• Safety by design - ensures highest safety
• Easy, guided commissioning with intuitive user interface in local language
• Reliable measurement even in variable product and process conditions
• Maximum reliability thanks to multi-echo tracking
• HistoROM configuration memory makes for easier commissioning, maintenance and diagnostics
• Antenna design not sensitive to buildup
• Purge air connection for cleaning in extreme conditions
• Alignment device for easy adaptation of sensor
• SIL2 as per IEC 61508, SIL3 for homogeneous or diverse redundancy, 3rd party approved
• Easy proof testing for SIL
• Seamless integration in process control and asset management systems
• RFID TAG - easy identification of measuring points for improved data access
• Heartbeat Technology

Table of contents

Micropilot FMR67
Important document information ............... 4
Safety symbols ............................... 4
Electrical symbols ............................. 4
Symbols for certain types of information .............. 4
Symbols in graphics ............................ 4
Symbols at the device ........................... 5
Terms and abbreviations ..................... 6
Registered trademarks ....................... 7
Function and system design ................... 8
Measuring principle ............................ 8
Input ..................................... 9
Measured variable ............................. 9
Measuring range .............................. 9
Operating frequency ........................... 9
Transmission power ............................ 9
Output .................................. 10
Output signal ............................... 10
Signal on alarm .............................. 10
Linearization ............................... 10
Galvanic isolation ............................ 11
Protocol-specific data .......................... 11
Power supply ............................. 12
Terminal assignment .......................... 12
Device plug connectors ......................... 18
Supply voltage .............................. 19
Power consumption ........................... 20
Current consumption .......................... 20
Power supply failure .......................... 20
Potential equalization ......................... 20
Cable entries ............................... 21
Cable specification ............................ 21
Overvoltage protection ......................... 21
Performance characteristics .................. 23
Reference operating conditions ................... 23
Reference accuracy ........................... 23
Measured value resolution ...................... 23
Response time .............................. 24
Influence of ambient temperature ................. 24
Installation ............................... 25
Installation conditions ......................... 25
Installation: Drip-off antenna PTFE 50 mm / 2" ......... 29
Installation: flush mount antenna .................. 30
Purge air connection for FMR67 ................... 32
Container with heat insulation .................... 33
Environment .............................. 34
Ambient temperature range ..................... 34
Ambient temperature limits ..................... 34
Storage temperature .......................... 35
Climate class ............................... 35
Altitude according to IEC61010-1 Ed.3 .............. 36
Degree of protection .......................... 36
Vibration resistance ........................... 36
Electromagnetic compatibility (EMC) ............... 36
Process .................................. 37
Process temperature, process pressure ............... 37
Dielectric constant ............................ 39
Mechanical construction .................... 40
Dimensions ................................ 40
Weight ................................... 47
Materials: GT18 housing (stainless steel, corrosion-
resistant) .................................. 48
Materials: GT19 housing (plastic) .................. 49
Materials: GT20 housing (die-cast aluminum, powder-
coated, seawater-resistant) ...................... 50
Materials: antenna and process connection ........... 51
Materials: Weather protection cover ................ 53
Operability ............................... 54
Operating concept ............................ 54
Local operation .............................. 54
Operation with remote display and operating module
FHX50 ................................... 55
Remote operation ............................ 55
System integration via Fieldgate ................... 57
Certificates and approvals ................... 58
CE mark ................................... 58
RoHS ..................................... 58
RCM-Tick marking ............................ 58
Ex approval ................................ 58
Dual seal according to ANSI/ISA 12.27.01 ............ 58
Functional safety ............................. 58
WHG ..................................... 58
Pressure equipment with allowable pressure ≤ 200
bar (2 900 psi) .......................... 58
Marine approval ............................. 59
Radio standard EN 302729-1/2 ................... 59
Radio standard EN 302372-1/2 ................... 60
FCC ...................................... 60
Industry Canada ............................. 60
CRN approval ............................... 61
Test, certificate .............................. 62
Hard-copy product documentation ................. 62
Other standards and guidelines ................... 63
Ordering information ....................... 64
Ordering information .......................... 64
3-point linearity protocol ....................... 65
5-point linearity protocol ....................... 66
Customer-specific configuration ................... 67
Services ................................... 67
2 V. 1, Rev. 3, 11-04-2017 Endress+Hauser
Micropilot FMR67
Application Packages ....................... 68
Heartbeat Diagnostics ......................... 68
Heartbeat Verification ......................... 69
Heartbeat Monitoring ......................... 70
Accessories ............................... 71
Device-specific accessories ...................... 71
Communication-specific accessories ................ 77
Service-specific accessories ...................... 78
System components ........................... 78
Supplementary documentation ............... 79
Standard documentation ........................ 79
Safety Instructions (XA) ........................ 79
Endress+Hauser V. 1, Rev. 3, 11-04-2017 3

Important document information

DANGER
WARNING
CAUTION
NOTICE
A
1.
Micropilot FMR67

Safety symbols

Electrical symbols

Symbol Meaning
DANGER!
This symbol alerts you to a dangerous situation. Failure to avoid this situation will result in serious or fatal injury.
WARNING!
This symbol alerts you to a dangerous situation. Failure to avoid this situation can result in serious or fatal injury.
CAUTION!
This symbol alerts you to a dangerous situation. Failure to avoid this situation can result in minor or medium injury.
NOTE!
This symbol contains information on procedures and other facts which do not result in personal injury.
Symbol Meaning Symbol Meaning
Direct current Alternating current
Direct current and alternating current Ground connection
A grounded terminal which, as far as the operator is concerned, is grounded via a grounding system.
Protective ground connection
A terminal which must be connected to ground prior to establishing any other connections.
Equipotential connection
A connection that has to be connected to the plant grounding system: This may be a potential equalization line or a star grounding system depending on national or company codes of practice.

Symbols for certain types of information

Symbols in graphics

Symbol Meaning
Permitted
Procedures, processes or actions that are permitted.
Preferred
Procedures, processes or actions that are preferred.
Forbidden
Procedures, processes or actions that are forbidden.
Tip
Indicates additional information.
Reference to documentation
Reference to page
Reference to graphic
Visual inspection
Symbol Meaning
1, 2, 3 ... Item numbers
, 2., 3.… Series of steps
A, B, C, ... Views
A-A, B-B, C-C, ... Sections
4 V. 1, Rev. 3, 11-04-2017 Endress+Hauser
Micropilot FMR67
.
Symbol Meaning
Hazardous area
Indicates a hazardous area.
Safe area (non-hazardous area)
Indicates the non-hazardous area.

Symbols at the device

Symbol Meaning
Safety instructions
Observe the safety instructions contained in the associated Operating Instructions.
Temperature resistance of the connection cables
Specifies the minimum value of the temperature resistance of the connection cables.
Endress+Hauser V. 1, Rev. 3, 11-04-2017 5
Micropilot FMR67

Terms and abbreviations

Term/abbreviation Explanation
BA Document type "Operating Instructions"
KA Document type "Brief Operating Instructions"
TI Document type "Technical Information"
SD Document type "Special Documentation"
XA Document type "Safety Instructions"
PN Nominal pressure
MWP Maximum Working Pressure
The MWP can also be found on the nameplate.
ToF Time of Flight
FieldCare Scalable software tool for device configuration and integrated plant asset management
solutions
DeviceCare Universal configuration software for Endress+Hauser HART, PROFIBUS,
FOUNDATION Fieldbus
DTM Device Type Manager
DD Device Description for HART communication protocol
DC Relative dielectric constant ε
Operating tool The term "operating tool" is used in place of the following operating software:
FieldCare / DeviceCare, for operation via HART communication and PC
BD Blocking Distance; no signals are analyzed within the BD.
and Ethernet field devices
r
6 V. 1, Rev. 3, 11-04-2017 Endress+Hauser
Micropilot FMR67

Registered trademarks

HART®
Registered trademark of the HART Communication Foundation, Austin, USA
KALREZ®, VITON®
Registered trademark of DuPont Performance Elastomers L.L.C., Wilmington, USA
TEFLON®
Registered trademark of E.I. DuPont de Nemours & Co., Wilmington, USA
Endress+Hauser V. 1, Rev. 3, 11-04-2017 7

Function and system design

D
R
f
t
1 2
f
2
f
1
Δt
Δ
f
Micropilot FMR67

Measuring principle

The Micropilot is a "downward-looking" measuring system, operating based on the frequency modulated continuous wave method (FMCW). The antenna emits an electromagnetic wave at a continuously varying frequency. This wave is reflected by the product and received again by the antenna.
1 FMCW principle: transmission and reflection of the continuous wave
R Reference point of measurement D Distance between reference point and product surface
The frequency of this wave is modulated in the form of a sawtooth signal between two limit frequencies f1 and f2:
A0032017
2 FMCW principle: result of frequency modulation
1 Transmitted signal 2 Received signal
This results in the following difference frequency at any time between the transmitted signal and the received signal:
Δf = k Δt
where Δt is the run time and k is the specified increase in frequency modulation.
Δt is given by the distance D between the reference point R and the product surface:
D = (c Δt) / 2
where c is the speed of propagation of the wave.
In summary, D can be calculated from the measured difference frequency determine the content of the tank or silo.
Δf. D is then used to
8 V. 1, Rev. 3, 11-04-2017 Endress+Hauser
A0023771
Micropilot FMR67

Input

Measured variable

The measured variable is the distance between the reference point and the product surface. The level is calculated based on "E", the empty distance entered. Optionally, the level can be converted to other variables (volume, mass) by linearization (32 value pairs).

Measuring range Maximum measuring range

Device Antenna
FMR67 GA:
Drip-off, PTFE 50 mm / 2"
GP: PTFE flush mount 80 mm / 3"
1) Feature 070 in the product structure
1)
Usable measuring range
The usable measuring range depends on the antenna size, the medium's reflective properties, the installation position and any possible interference reflections.
Tables in preparation
For dielectric constants (DC values) of many media commonly used in various industries refer to:
the Endress+Hauser DC manual (CP01076F)
• the Endress+Hauser "DC Values App" (available for Android and iOS)
Maximum measuring range
50 m (164 ft)
125 m (410 ft)

Operating frequency

Transmission power

Approx. 80 GHz
Several FMR6x devices can be installed in one tank thanks to the short measuring duration and the high beam focus.
Peak power: 6.3 mW
• Average output power: 63 µW
Endress+Hauser V. 1, Rev. 3, 11-04-2017 9

Output

Micropilot FMR67

Output signal

HART
Signal coding FSK 0.5 mA over current signal
Data transmission rate 1 200
Galvanic isolation Yes
Bit/s
Switch output
For HART devices, the switch output is available as an option. See product structure, feature 20: "Power Supply, Output", option B: "2-wire; 4-20mA HART, switch output"
Devices with
Switch output
Function Open collector switching output
Switching behavior Binary (conductive or non-conductive), switches when the programmable switch
Failure mode non-conductive
Electrical connection values
Internal resistance RI < 880 Ω
Insulation voltage floating, Insulation voltage 1 350 VDC to power supply aund 500 VAC to ground
Switch point freely programmable, separately for switch-on and switch-off point
Switching delay freely programmable from 0 to 100 s, separately for switch-on and switch-off
Number of switching cycles corresponds to the measuring cycle
Signal source device variables
Number of switching cycles unlimited
PROFIBUS PA and FOUNDATION Fieldbus always have a switch output.
point is reached
U = 16 to 35 VDC, I = 0
The voltage drop at this internal resistance has to be taken into account on planning the configuration. For example, the resulting voltage at a connected relay must be sufficient to switch the relay.
point
• Level linearized Distance
• Terminal voltage
• Electronic temperature
• Relative echo amplitude
• Diagnostic values, Advanced diagnostics
to 40 mA

Signal on alarm

Depending on the interface, failure information is displayed as follows:
Current output (for HART devices)
• – Failsafe mode selectable (in accordance with NAMUR Recommendation NE 43):
Minimum alarm: 3.6 mA Maximum alarm (= factory setting): 22 mA
– Failsafe mode with user-selectable value: 3.59 to 22.5 mA
• Local display – Status signal (in accordance with NAMUR Recommendation NE 107) – Plain text display
• Operating tool via digital communication (HART, PROFIBUS PA, FOUNDATION Fieldbus) or service interface (CDI) – Status signal (in accordance with NAMUR Recommendation NE 107) – Plain text display

Linearization

The linearization function of the device allows the conversion of the measured value into any unit of length or volume. Linearization tables for calculating the volume in cylindrical tanks are pre­programmed. Other linearization tables of up to 32 value pairs can be entered manually or semi­automatically.
10 V. 1, Rev. 3, 11-04-2017 Endress+Hauser
Micropilot FMR67

Galvanic isolation

All circuits for the outputs are galvanically isolated from each other.

Protocol-specific data HART

Manufacturer ID 17 (0x11)
Device type ID 0x112B
HART specification 7.0
Device description files (DTM, DD) Information and files under:
HART load min. 250 Ω
HART device variables The measured values can be freely assigned to the device variables.
Supported functions • Burst mode
www.endress.com
www.fieldcommgroup.org
Measured values for PV (primary variable)
Level linearized
• Distance
• Electronic temperature
• Relative echo amplitude
• Area of incoupling
• Analog output adv. diagnostics 1
• Analog output adv. diagnostics 2
Measured values for SV, TV, FV (second, third and fourth variable)
• Level linearized
• Distance
• Electronic temperature
• Terminal voltage
• Relative echo amplitude
• Absolute echo amplitude
• Area of incoupling
• Analog output adv. diagnostics 1
• Analog output adv. diagnostics 2
• Additional transmitter status
Wireless HART data
Minimum start-up voltage 16 V
Start-up current 3.6 mA
Start-up time 65 s
Minimum operating voltage 14.0 V
Multidrop current 4.0 mA
Set-up time 15 s
Endress+Hauser V. 1, Rev. 3, 11-04-2017 11

Power supply

8
9
1
+
2
4...20mA HART
10 mm
Spare part
71108xxx
2- wire level
4-20 mA 4-20 mA
HART
[21
]
open
-
1
+
2
4-20mA
1-channel overvoltage protection
-
[16]
A
7
B
!
4...20 mA
5
4
1
2
3
+ –
+
#
+
4...20 mA
5
4
1
2
3
+ –
6
#
Micropilot FMR67

Terminal assignment

2-wire: 4-20mA HART
3 Terminal assignment 2-wire; 4-20mA HART
12 V. 1, Rev. 3, 11-04-2017 Endress+Hauser
A Without integrated overvoltage protection B With integrated overvoltage protection 1 Active barrier with power supply (e.g. RN221N): Observe terminal voltage 2 HART communication resistor (≥ 250 Ω): Observe maximum load 3 Connection for Commubox FXA195 or FieldXpert SFX350/SFX370 (via VIATOR Bluetooth modem) 4 Analog display device: Observe maximum load 5 Cable screen; observe cable specification 6 4-20mA HART (passive): Terminals 1 and 2 7 Overvoltage protection module 8 Terminal for potential equalization line 9 Cable entry
A0011294
Micropilot FMR67
1
+
2
4...20 mA HART
10 mm
Spare part
71108xxx
2- wire
4-20 mA PFS
HART
[02
/03]
open
-
A
1
+
2
-
3
+
4
-
1
3
+
+
2
4
4-20mA/
FIELDBUS
4-20mA/
2-channel overvoltage protection
-
-
[17]
B
10
9 8
7
11
+
+
-
-
2
2
3
3
4
4
6
5
5
1
1
4...20 mA
≥250 Ω
3+
3+
4-
4-
+
+
$
$
%
4...20 mA
≥250 Ω
2-wire: 4-20mA HART, switch output
A0013759
4 Terminal assignment 2-wire; 4-20mA HART, switch output
A Without integrated overvoltage protection B With integrated overvoltage protection 1 Active barrier with power supply (e.g. RN221N): Observe terminal voltage 2 HART communication resistor (≥ 250 Ω): Observe maximum load 3 Connection for Commubox FXA195 or FieldXpert SFX350/SFX370 (via VIATOR Bluetooth modem) 4 Analog display device: Observe maximum load 5 Cable screen; observe cable specification 6 4-20mA HART (passive): Terminals 1 and 2 7 Switch output (open collector): Terminals 3 and 4 8 Terminal for potential equalization line 9 Cable entry for 4-20mA HART line 10 Cable entry for switch output line 11 Overvoltage protection module
Endress+Hauser V. 1, Rev. 3, 11-04-2017 13
2-wire: 4-20mA HART, 4-20mA
1
3
+
+
2
4
4...20mA HART
4...20mA
10 mm
Spare part
71108xxx
2- wire level
4-20 mA 4-20 mA
HART
[04
/05]
open
-
-
11
A
1
3
+
+
2
4
4-20mA/
FIELDBUS
4-20mA/
2-channel overvoltage protection
-
-
[17]
14 13 12
+
+
+
+
-
-
-
-
1
1
2
2
3
3
9
9
5
5
8
8
6
6
7
7
4
4
4
4
+
+
+
+
4...20 mA
4...20 mA
10
B
4...20 mA
4...20 mA
"
"
"
"
#
Micropilot FMR67
5 Terminal assignment 2-wire, 4-20 mA HART, 4...20mA
14 V. 1, Rev. 3, 11-04-2017 Endress+Hauser
A Without integrated overvoltage protection B With integrated overvoltage protection 1 Connection current output 2 2 Connection current output 1 3 Supply voltage for current output 1 (e.g. RN221N); Observe terminal voltage 4 Cable screen; observe cable specification 5 HART communication resistor (≥ 250 Ω): Observe maximum load 6 Connection for Commubox FXA195 or FieldXpert SFX350/SFX370 (via VIATOR Bluetooth modem) 7 Analog display device ; observe maximum load 8 Analog display device ; observe maximum load 9 Supply voltage for current output 2 (e.g. RN221N); Obeserve terminal voltage 10 Overvoltage protection module 11 Current output 2: Terminals 3 and 4 12 Terminal for the potential equalization line 13 Cable entry for current output 1 14 Cable entry for current output 2
This version is also suited for single-channel operation. In this case, current output 1 (terminals 1 and 2) must be used.
A0013923
Micropilot FMR67
3
1
+
L+
4
2
4...20 mA HART
10.4...48 V=
10 mm
Spare part
71108xxx
2- wire
4-20 mA
HART
[08
]
open
-
L-
A
13 12 11
9
10
2
3
4
7
8
5
1
!
!
+
-
6
!
4...20 mA
≥250 Ω
4-wire: 4-20mA HART (10.4 to 48 VDC)
A0011340
 6 Terminal assignment 4-wire; 4-20mA HART (10.4 to 48 VDC)
1 Evaluation unit, e.g. PLC 2 HART communication resistor (≥ 250 Ω): Observe maximum load 3 Connection for Commubox FXA195 or FieldXpert SFX350/SFX370 (via VIATOR Bluetooth modem) 4 Analog display device: Observe maximum load 5 Signal cable including screening (if required), observe cable specification 6 Protective connection; do not disconnect! 7 Protective earth, observe cable specification 8 4...20mA HART (active): Terminals 3 and 4 9 Supply voltage: Terminals 1 and 2 10 Supply voltage: Observe terminal voltage, observe cable specification 11 Terminal for potential equalization 12 Cable entry for signal line 13 Cable entry for power supply
Endress+Hauser V. 1, Rev. 3, 11-04-2017 15
Micropilot FMR67
3
1
+
L
4
2
4...20 mA HART
90...253 V~
10 mm
Spare part
71108xxx
2- wire
4-20 mA
HART
[09
]
open
-
N
A
13 12 11
910
6
7
8
!
!
2
3
4
5
1
+
-
4...20 mA
≥250 Ω
4-wire: 4-20mA HART (90 to 253 VAC)
 7 Terminal assignment 4-wire; 4-20mA HART (90 to 253 VAC)
1 Evaluation unit, e.g. PLC 2 HART communication resistor (≥ 250 Ω): Observe maximum load 3 Connection for Commubox FXA195 or FieldXpert SFX350/SFX370 (via VIATOR Bluetooth modem) 4 Analog display device: Observe maximum load 5 Signal cable including screening (if required), observe cable specification 6 Protective connection; do not disconnect! 7 Protective earth, observe cable specification 8 4...20mA HART (active): Terminals 3 and 4 9 Supply voltage: Terminals 1 and 2 10 Supply voltage: Observe terminal voltage, observe cable specification 11 Terminal for potential equalization 12 Cable entry for signal line 13 Cable entry for power supply
A0018965
CAUTION
L
To ensure electrical safety:
Do not disconnect the protective connection (6).
Disconnect the supply voltage before disconnecting the protective earth (7).
Connect protective earth to the internal ground terminal (7) before connecting the supply voltage. If necessary, connect the potential matching line to the external ground terminal (11).
In order to ensure electromagnetic compatibility (EMC): Do not only ground the device via the protective earth conductor of the supply cable. Instead, the functional grounding must also be connected to the process connection (flange or threaded connection) or to the external ground terminal.
An easily accessible power switch must be installed in the proximity of the device. The power switch must be marked as a disconnector for the device (
IEC/EN61010).
16 V. 1, Rev. 3, 11-04-2017 Endress+Hauser
Micropilot FMR67
3+
+
-
4-
3+
2
1
+
4-
Connection examples for the switch output
For HART devices, the switch output is available as an option. See product structure, feature 20: "Power Supply, Output", option B: "2-wire; 4-20mA HART, switch output"
Devices with
8 Connection of a relay
Suitable relays (examples):
• Solid-state relay: Phoenix Contact OV-24DC/480AC/5 with mounting rail connector UMK-1 OM-R/AMS
• Electromechanical relay: Phoenix Contact PLC-RSC-12DC/21
PROFIBUS PA and FOUNDATION Fieldbus always have a switch output.
A0015909
9 Connection of a digital input
1 Pull-up resistor 2 Digital input
For optimum interference immunity we recommend to connect an external resistor (internal resistance of the relay or Pull-up resistor) of <
1 000 Ω.
A0015910
Endress+Hauser V. 1, Rev. 3, 11-04-2017 17
Micropilot FMR67
2
1
3
4
4
2
3
1

Device plug connectors

For the versions with fieldbus plug connector (M12 or 7/8"), the signal line can be connected without opening the housing.
Pin assignment of the M12 plug connector
Pin Meaning
1 Signal +
2 not connected
3 Signal -
4 Ground
A0011175
Pin assignment of the 7/8" plug connector
Pin Meaning
1 Signal -
2 Signal +
3 Not connected
4 Screen
A0011176
18 V. 1, Rev. 3, 11-04-2017 Endress+Hauser
Micropilot FMR67
R [ ]W
U0[V]
10
14
25
20 30 35
0
500
R [ ]W
U0[V]
10
16
27
20 30 35
0
500

Supply voltage

An external power supply is necessary.
Various power supply units can be ordered as an accessory from Endress+Hauser.
2-wire, 4-20mA HART, passive
"Power supply, output"
A:
2-wire; 4-20mA HART
1) Feature 020 in the product structure
2)
3) At ambient temperatures Ta≤ -20 °C, a terminal voltage U ≥ 16 V is required to start the device with the
"Approval"
1)
• Non­hazardous Ex nA
• Ex ic
• CSA GP
Ex ia / IS 14 to 30 V
• Ex d(ia) / XP Ex ic(ia)
• Ex nA(ia)
• Ex ta / DIP
Ex ia + Ex d(ia) / IS + XP
Feature 010 in the product structure
min. error current (3.6 mA).
2)
Terminal voltage U at device
14 to 35 V
14 to
3)
35 V
14 to 30 V
Maximum load R, depending on the supply voltage U0 of the power supply unit
A0031745
"Power supply, output"
B:
2-wire; 4-20 mA HART, switch outpu
1) Feature 020 in the product structure
2)
"Approval"
1)
• Non-
• Ex nA(ia)
• Ex ic
• Ex ic(ia)
• Ex d(ia) / XP
• Ex ta / DIP
• CSA GP
• Ex ia / IS
Feature 010 in the product structure
2)
hazardous Ex nA
Ex ia + Ex d(ia) / IS + XP
Terminal voltage U at device
16 to 35 V
16 to 30 V
Maximum load R, depending on the supply voltage U0 of the power supply unit
A0031746
Endress+Hauser V. 1, Rev. 3, 11-04-2017 19
Micropilot FMR67
R [ ]W
U0[V]
10
16
27
20 30 35
0
500
"Power supply, output"
C:
2-wire; 4-20mA HART, 4-20mA
1) Feature 020 in the product structure Feature 010 in the product structure
2)
Integrated polarity reversal protection Yes
Permitted residual ripple with f = 0 to 100 Hz USS < 1 V
Permitted residual ripple with f = 100 to 10000 Hz USS < 10 mV
"Approval"
1)
All 16 to 30 V
2)
Terminal voltage U at device
Maximum load R, depending on the supply voltage U0 of the power supply unit
A0031746

Power consumption

Current consumption

4-wire, 4-20mA HART, active
"Power supply; output"
K:
4-wire 90-253VAC; 4-20mA HART
L:
4-wire 10.4-48VDC; 4-20mA HART
1) Feature 020 in the product structure
"Power supply; Output"
A: 2-wire; 4-20mA HART < 0.9 W
B: 2-wire; 4-20mA HART, switch output < 0.9 W
C: 2-wire; 4-20mA HART, 4-20mA < 2 x 0.7 W
4-wire 90-253VAC; 4-20mA HART 6 VA
K:
L: 4-wire 10,4-48VDC; 4-20mA HART 1.3 W
1) Feature 020 of the product structure
HART
Nominal current 3.6 to 22 mA the start-up current for multidrop mode can be parametrized
Breakdown signal (NAMUR NE43) adjustable: 3.59 to 22.5 mA
1)
1)
(is set to
Terminal voltage U Maximum load R
90 to 253 VAC (50 overvoltage category II
10.4 to 48 V
3.6 mA on delivery)
DC
Power consumption
to 60 Hz),
500 Ω
max
Configuration is retained in the HistoROM (EEPROM).

Power supply failure

Potential equalization

• Error messages (incl. value of operated hours counter) are stored.
No special measures for potential equalization are required.
If the device is designed for hazardous areas, observe the information in the documentation "Safety Instructions" (XA).
20 V. 1, Rev. 3, 11-04-2017 Endress+Hauser
Micropilot FMR67

Cable entries Connection of power supply and signal line

To be selected in feature 050 "Electrical connection"
Gland M20; Material dependent on the approval:
• – For Non-Ex, ATEX, IECEx, NEPSI Ex ia/ic:
Plastics M20x1.5 for cable ⌀5 to 10 mm (0.2 to 0.39 in)
– For Dust-Ex, FM IS, CSA IS, CSA GP, Ex nA:
Metal M20x1.5 for cable ⌀7 to 10 mm (0.28 to 0.39 in)
– For Ex d:
No gland available
• Thread – ½" NPT – G ½" – M20 × 1.5
• Plug M12 / Plug 7/8" Only available for Non-Ex, Ex ic, Ex ia
Connection of remote display FHX50
Dependent on feature 030: "Display, Operation":
• "Prepared for display FHX50 + M12 connection": M12 socket
• "Prepared for display FHX50 + custom connection": M16 cable gland
1)

Cable specification

Overvoltage protection

Devices without integrated overvoltage protection Pluggable spring-force terminals for wire cross-sections
0.5 to 2.5 mm2 (20 to 14 AWG)
Devices with integrated overvoltage protection Screw terminals for wire cross-sections 0.2 to 2.5 mm2 (24 to 14 AWG)
• For ambient temperature TU≥60 °C (140 °F): use cable for temperature TU +20 K.
HART
• A normal device cable suffices if only the analog signal is used.
• A shielded cable is recommended if using the HART protocol. Observe grounding concept of the plant.
• For 4-wire devices: Standard device cable is sufficient for the power line.
If the measuring device is used for level measurement in flammable liquids which requires the use of overvoltage protection according to
DIN EN 60079-14, standard for test procedures 60060-1 (10 kA, pulse 8/20 μs), overvoltage protection has to be ensured by an integrated or external overvoltage protection module.
Integrated overvoltage protection
An integrated overvoltage protection module is available for 2-wire HART as well as PROFIBUS PA and FOUNDATION Fieldbus devices.
Product structure: Feature 610 "Accessory mounted", option NA "Overvoltage protection".
Technical data
Resistance per channel 2 × 0.5 Ω max.
Threshold DC voltage 400 to 700 V
Threshold impulse voltage < 800 V
Capacitance at 1 MHz < 1.5 pF
Nominal arrest impulse voltage (8/20 μs) 10 kA
1) The material of the gland is dependent on the housing type; GT18 (stainless steel housing): 316L (1.4404); GT19 (plastic housing) and GT20 (aluminum housing): nickel-coated brass (CuZn).
Endress+Hauser V. 1, Rev. 3, 11-04-2017 21
External overvoltage protection
HAW562 or HAW569 from
For detailed information please refer to the following documents:
HAW562: TI01012K
• HAW569: TI01013K
Endress+Hauser are suited as external overvoltage protection.
Micropilot FMR67
22 V. 1, Rev. 3, 11-04-2017 Endress+Hauser
Micropilot FMR67
1.5 (4.92)
20 (0.79)
3 (0.12)
-3 (-0.12)
-20 (-0.79)
D [m (!)]
[mm (in)]
R
0

Reference operating conditions

Performance characteristics

Temperature = +24 °C (+75 °F) 5 °C (9 °F)
• Pressure = 960 mbar abs. (14 psia) 100 mbar (1.45 psi)
• Humidity = 60 % 15 %
• Reflector: metal plate with diameter ≥ 1 m (40 in)
• No major interference reflections inside the signal beam

Reference accuracy

Typical data under reference operating conditions:
DIN EN IEC 61298-2 / DIN EN IEC 60770-1;
percentage values in relation to the span.
Output: digital analog
Accuracy (Sum of non­linearity, nonrepeatability and hysteresis)
Non-repeatability
1) Add error of the analogous value to the digital value. If the reference conditions are not met, the offset/zero point arising from the mounting conditions may be
2) up to ±4 mm (0.16 in). This additional offset/zero point can be compensated for by entering a correction (parameter "level correction") during commissioning.
3) The non-repeatability is already considered in the accuracy.
2)
3)
Measuring distance up to 1.5 m (4.92 ft): max. 20 mm (0.79 in) 0.02 %
Measuring distance > 1.5 m (4.92 ft): 3 mm (0.12 in) 0.02 %
≤ 1 mm (0.04 in)
Differing values in near-range applications
1)
10 Maximum measured error in near-range applications
Δ Maximum measured error R Reference point of the distance measurement D Distance from reference point of antenna

Measured value resolution

Dead band according to
• Digital: 1 mm
DIN EN IEC 61298-2 / DIN EN IEC 60770-1:
• Analog: 1 µA
Endress+Hauser V. 1, Rev. 3, 11-04-2017 23
A0032637
Micropilot FMR67

Response time

Influence of ambient temperature

The response time can be configured. The following step response times (in accordance with DIN EN IEC 61298-2
Sampling rate
Response time < 3.6 s
/ DIN EN IEC 60770-1)
≥1.3 s–1 at U
2)
are when damping is switched off:
≥ 24 V
The measurements are performed according to DIN EN IEC 61298-3 / DIN EN IEC 60770-1
• Digital (HART, PROFIBUS PA, FOUNDATION Fieldbus): average TK = 3 mm/10 K
• Analog (current output): – Zero point (4 mA): average TK = 0.02 %/10 K – Span (20 mA): average TK = 0.05 %/10 K
2) According to DIN EN IEC 61298-2 / DIN EN IEC 60770-1, the step response time is the time that elapses after an abrupt change in the input signal until the change in the output signal has adopted 90% of the steady-state value for the first time.
24 V. 1, Rev. 3, 11-04-2017 Endress+Hauser
Micropilot FMR67
A
1 2 3

Installation

Installation conditions

Mounting position
A0016883
Recommended distance A wall - nozzle outer edge: ~ 1/6 of the container diameter. However, the
• device must not under any circumstances be mounted closer than 20 cm (7.87 in) to the container wall. If the container wall is not smooth (corrugated iron, welding seams, joints, etc.) it is recommended to maintain the largest possible distance from the wall. Where necessary use an alignment unit to avoid interference reflections from the container wall.→  29
• Not in the center (2) as interference can cause signal loss.
• Not above the filling curtain (3).
• The use of a weather protection cover (1) is recommended to protect the transmitter from direct sunlight or rain.
• In applications with strong dust emissions, the integrated purge air connection can prevent the antenna from becoming clogged .
Endress+Hauser V. 1, Rev. 3, 11-04-2017 25
Internal container fittings
α
β
Micropilot FMR67
A0031814
Avoid the location of internal fittings (limit switches, temperature sensors, struts etc.) inside the signal beam. Pay attention to the beam angle .
26 V. 1, Rev. 3, 11-04-2017 Endress+Hauser
Loading...