BA284F/00/en/08.04
Nr. 52025089
Valid as of software version:
V 01.01.00 (amplifier)
V 01.01.00 (communication)
Micropilot M FMR250 with HART/4...20 mA
Brief overview
For quick and simple commissioning:
Safety Instructions
Explanation of the warning symbols
You can find special instructions at the appropriate position in the chapter in
question. The positions are indicated with the icons Warning #, Caution " and
Note !.
Æ
Installation
The steps for installing the device and installation conditions (e.g. dimensions)
can be found here.
Æ
Wiring
The device is virtually completely wired on delivery.→ Page 25 ff.
Æ
Display and Operating Elements
An overview of the position of the display and operating elements can be found
here.
→ Page 6 ff.
→ Page 11 ff.
→ Page 33 ff.
Æ
Commissioning
In the "Commissioning" section, you learn how to switch on the device and
check the functioning.
Æ
Commissioning via Display VU 331
In the "Operating" section, you become familiar with the operating elements
and the various setting options.
Basic Setup with the VU331.
Æ
Commissioning via Operating Software ToF Tool
Basic Setup with the ToF Tool.
Additional information on the operation of the ToF Tool can be found in the
operating instructions BA224F/00, which can be found on the enclosed
CD-ROM.
Æ
Fault Tracking / Trouble Shooting
If faults occur during operation, use the checklist to localise the cause.
Here you can find measures you can take yourself to take remedial action
against the fault.
→ Page 41 ff.
→ Page 31 ff.
→ Page 44 ff.
→ Page 59 ff.
→ Page 66 ff.
Æ
Index
You can find important terms and keywords on the individual sections here.
Use the keyword index to find quickly and efficiently the information you need.
2Endress + Hauser
→ Page 92 ff.
Micropilot M FMR250 with HART/4...20 mA
Brief operating instructions
KA 235F/00/a2/08.04
52025245
000
measured
value
E
+
-
Group
selection
00
basic
+
setup
01
safety
settings
04
linearisation
05
extended
calibr.
06
output
09
display
0E
envelope
curve
-
0A
diagnostics
0C
system parameter
001
media
type
- liquid
- solid
092
language
0E1
plot settings
- envel. curve
- incl. FAC
- incl. cust. map
0A0
present error
00A
vessel /
silo
- unknown
- metal silo
- concrete
silo
- bin / bunker
…
Micropilot M FMR250 - Brief operating instructions
Contrast:+or +
+
-
002
002
tank
tank
shape
shape
- dome
ceiling
- horizontal
cyl.
- bypass
…
00B
medium
cond.
- unknown
- DC: 1.6...1.9
- DC: 1.9 …2.5
- DC: 2.5 …4
...
… …
0E2
recording
curve
- single curve
- cyclic
0A1
previous error
003
medium
cond.
- unknown
- DC: <1.9
- DC: 1.9 … 4
- DC: 4 … 10
- DC: >10
00C
proscess
cond.
- standard
- fast change
- slow change
- test: no filter
… …
004
process
cond.
…
005
empty
calibr.
input E
(see sketch)
input E
(see sketch)
- standard
- calm
surface
- add.
agitator
0A4
unlock parameter
= 100: unlocked
100: locked≠
005
empty
calibr.
006
full
calibr.
input F
(see sketch)
flange:
referencepoint of
measurement
… …
HART
}
006
full
calibr.
input F
(see sketch)
threaded
connection
1 ½”(R 1
or 1½ NPT
reference point of
measurement
only for
bypass +
stilling well
BSPT½”)
:
007
pipe
diameter
E
008
dist./
meas value
D and L are
displayed
(see sketch)
flange:
referencepoint of
measurement
E
F
051
check
distance
- ok
- too small
- too big
- unknown
- manual
D
L
008
E
dist./
052
range of
mapping
confirm
suggestion
or specify
range
meas value
053
start
mapping
20 mA
100%
4mA
0%
E
52025245
!
L00-FMR250xx-19-00-00-en-020
Note!
This operating manual explains the installation and initial start-up for the level transmitter. All
functions that are required for a typical measuring task are taken into account here. In addition, the
Micropilot M provides many other functions that are not included in this operating manual, such as
optimising the measuring point and converting the measured values.
An overview of all device functions can be found on Page 86.
The operating manual BA291F/00/en "Description of the instrument functions for Micropilot M"
provides an extensive description of all device functions, which can be found on the enclosed
CD-ROM.
Endress + Hauser3
Micropilot M FMR250 with HART/4...20 mA
4Endress + Hauser
Micropilot M FMR250 with HART/4...20 mATable of contents
Safety instructionsMicropilot M FMR250 with HART/4...20 mA
1Safety instructions
1.1Designated use
The Micropilot M FMR250 is a compact level radar for the continuous, contactless measurement of
predominantly solids. The device can also be freely mounted outside closed metal vessels because
of its operating frequency of about 26 GHz and a maximum radiated pulsed energy of 1mW
(average power output 1 µW). Operation is completely harmless to humans and animals.
1.2Installation, commissioning and operation
The Micropilot M has been designed to operate safely in accordance with current technical, safety
and EU standards. If installed incorrectly or used for applications for which it is not intended,
however, it is possible that application-related dangers may arise, e.g. product overflow due to
incorrect installation or calibration. For this reason, the instrument must be installed, connected,
operated and maintained according to the instructions in this manual: personnel must be authorised
and suitably qualified. The manual must have been read and understood, and the instructions
followed. Modifications and repairs to the device are permissible only when they are expressly
approved in the manual.
1.3Operational safety
1.3.1Hazardous areas
Measuring systems for use in hazardous environments are accompanied by separate "Ex
documentation", which is an integral part of this Operating Manual. Strict compliance with the
installation instructions and ratings as stated in this supplementary documentation is mandatory.
• Ensure that all personnel are suitably qualified.
• Observe the specifications in the certificate as well as national and local standards and regulations.
1.3.2FCC approval
This device complies with part 15 of the FCC Rules. Operation is subject to the following two
conditions: (1) This device may not cause harmful interference, and (2) this device must accept any
interference received, including interference that may cause
undesired operation.
Caution!
"
Changes or modifications not expressly approved by the part responsible for
compliance could void the user’s authority to operate the equipment.
6Endress + Hauser
Micropilot M FMR250 with HART/4...20 mASafety instructions
1.4Notes on safety conventions and symbols
In order to highlight safety-relevant or alternative operating procedures in the manual, the following
conventions have been used, each indicated by a corresponding symbol in the margin.
Safety conventions
Warning!
#
"
!
Explosion protection
0
A warning highlights actions or procedures which, if not performed correctly, will lead to personal
injury, a safety hazard or destruction of the instrument
Caution!
Caution highlights actions or procedures which, if not performed correctly, may lead to personal
injury or incorrect functioning of the instrument
Note!
A note highlights actions or procedures which, if not performed correctly, may indirectly affect
operation or may lead to an instrument response which is not planned
Device certified for use in explosion hazardous area
If the device has this symbol embossed on its name plate it can be installed in an explosion hazardous
area
-
.
Electrical symbols
%
&
)
*
+
Explosion hazardous area
Symbol used in drawings to indicate explosion hazardous areas. Devices located in and wiring
entering areas with the designation “explosion hazardous areas” must conform with the stated type
of protection.
Safe area (non-explosion hazardous area)
Symbol used in drawings to indicate, if necessary, non-explosion hazardous areas. Devices located in
safe areas still require a certificate if their outputs run into explosion hazardous areas
Direct voltage
A terminal to which or from which a direct current or voltage may be applied or supplied
Alternating voltage
A terminal to which or from which an alternating (sine-wave) current or voltage may be applied or
supplied
Grounded terminal
A grounded terminal, which as far as the operator is concerned, is already grounded by means of an
earth grounding system
Protective grounding (earth) terminal
A terminal which must be connected to earth ground prior to making any other connection to the
equipment
Equipotential connection (earth bonding)
A connection made to the plant grounding system which may be of type e.g. neutral star or
equipotential line according to national or company practice
t >85°C
Endress + Hauser7
Temperature resistance of the connection cables
States, that the connection calbes must be resistant to a temperature of at least 85 °C.
IdentificationMicropilot M FMR250 with HART/4...20 mA
2Identification
2.1Device designation
2.1.1Nameplate
The following technical data are given on the instrument nameplate:
Fig. 1: Information on the nameplate of the Micropilot M (example)
2.1.2Ordering structure
Ordering structure Micropilot M FMR250
10Approval:
A Non-hazardous area
1 ATEX II 1/2G EEx ia IIC T6
4 ATEX II 1/2G EEx d [ia] IIC T6
G ATEX II 3G EEx nA II T6
B ATEX II 1/2GD EEx ia IIC T6, Alu blind cover
C ATEX II 1/2G EEx ia IIC T6, ATEX II 1/3D
D ATEX II 1/2D, Alu blind cover
E ATEX II 1/3D
S FM IS-Cl.I/II/III Div.1 Gr.A-G
T FM XP-Cl.I/II/III Div.1 Gr.A-G
N CSA General Purpose
U CSA IS-Cl.I/II/III Div.1 Gr.A-G
V CSA XP-Cl.I/II/III Div.1 Gr.A-G
YSpecial version
20Antenna:
4 Horn 80mm/3"
5 Horn 100mm/4"
6 Parabolic 200mm/8"
9 Special version
L00-FMR2xxxx-18-00-00-en-001
FMR250-Product designation (part 1)
8Endress + Hauser
Micropilot M FMR250 with HART/4...20 mAIdentification
Ordering structure Micropilot M FMR250 (continued)
30Antenna seal; Temperature:
E FKM Viton GLT; -40...200°C/-40...392 °F
Y Special version
40Antenna extension:
1Not selected
2 250mm/10"
3 450mm/18"
9Special version
50Process connection:
– Threaded boss –
GGJThread DIN2999 R1-1/2, 316L
GNJThread ANSI NPT1-1/2, 316L
– Universal-Flanges –
X3JUNI flange DN200/8"/200A, 316L
max PN1/14.5LBS/1K, compatible DN200 PN10/16, 8" 150LBS, 10K 200A
XCJTop target pos., UNI DN100/4"/100A, 316L
max PN1/14.5LBS/1K, compatible DN100 PN10/16, 4" 150LBS, 10K 100A
XEJTop target pos., UNI DN200/8"/200A, 316L
max PN1/14.5LBS/1K, compatible DN200 PN10/16, 8" 150LBS, 10K 200A
– EN-Flanges –
CMJDN80 PN10/16 B1, 316L
CQJDN100 PN10/16 B1, 316L
– ANSI-Flanges –
ALJ3" 150LBS RF, 316/316L
APJ4" 150LBS RF, 316/316L
– JIS-Flanges –
KLJ10K 80A RF, 316L
KPJ10K 100A RF, 316L
YY9Special version
60Output; Operation:
A 4-20mA HART; 4-line display VU331, envelope curve display on site
B 4-20mA HART; w/o display, via communication
K 4-20mA HART; prepared for FHX40, remote display (Accessory)
Y Special version
70Housing:
A F12 Alu, coated IP65 NEMA4X
B F23 316L IP65 NEMA4X
C T12 Alu, coated IP65 NEMA4X, separate connection compartment
D T12 Alu, coated IP65 NEMA4X + OVP, separate connection compartment,
OVP = overvoltage protection
Y Special version
80Cable entry:
2Gland M20
3Thread G1/2
4Thread NPT1/2
9Special version
90Additional option:
K Air purge connection G1/4
M Air purge connection NPT1/4
YSpecial version
FMR250-Complete product designation
Endress + Hauser9
IdentificationMicropilot M FMR250 with HART/4...20 mA
2.2Scope of delivery
Caution!
"
It is essential to follow the instructions concerning the unpacking, transport and storage of
measuring instruments given in the chapter "Incoming acceptance, transport, storage" on Page 11!
Program including Device Descriptions (device drivers) and documentation for all
Endress+Hauser devices wich are operable using ToF Tool
– CD 2: ToF Tool - FieldTool
Utility program (e.g. Adobe Acrobat Reader, MS Internet Explorer)
• Accessories (→ Chap. 8)
Accompanying documentation:
• Short manual (basic setup/troubleshooting): housed in the instrument
• Operating manual (this manual)
• Approval documentation: if this is not included in the operating manual.
Note!
The operating manual "Description of Instrument Functions" you can be found on the enclosed CRROM.
®
Package CD-ROMs
®
Program
®
Utilities
2.3Certificates and approvals
CE mark, declaration of conformity
The instrument is designed to meet state-of-the-art safety requirements, has been tested and left the
factory in a condition in which it is safe to operate. The instrument complies with the applicable
standards and regulations and thus complies with the statutory requirements of the EG directives.
Endress+Hauser confirms the successful testing of the instrument by affixing to it the CE mark.
2.4Registered trademarks
KALREZ®, VITON®, TEFLON
Registered trademark of the company, E.I. Du Pont de Nemours & Co., Wilmington, USA
TRI-CLAMP
Registered trademark of the company, Ladish & Co., Inc., Kenosha, USA
HART
Registered trademark of HART Communication Foundation, Austin, USA
®
ToF
Registered trademark of the company Endress+Hauser GmbH+Co. KG, Maulburg, Germany
PulseMaster
Registered trademark of the company Endress+Hauser GmbH+Co. KG, Maulburg, Germany
PhaseMaster
Registered trademark of the company Endress+Hauser GmbH+Co. KG, Maulburg, Germany
®
®
®
®
®
10Endress + Hauser
Micropilot M FMR250 with HART/4...20 mAInstallation
90°
90°
90°
90°
9
3Installation
3.1Quick installation guide
At mounting adjust the marking at the instrument flange!
#
Installation in vessel (free space):
Mark on process connector facing the nearest vessel wall!
The housing can be turned 350° in order to simplify access to the
Turn housing
display and the terminal compartment
mark at instrument flange
or threaded boss
90°90
°
90°
Note!
At version with top target positioner, the marker is at the housing adapter
(opposite the air purge connection).
90°
90°
90°
DN80…200
ANSI 3…8”
1½” BSPT (R 1½”),
or
1½ NPT
3.2Incoming acceptance, transport, storage
3.2.1Incoming acceptance
Check the packing and contents for any signs of damage.
Check the shipment, make sure nothing is missing and that the scope of supply matches your order.
F12/F23 housing
2
3
1
T12 housing
2
3
1
Allen key 4 mm / 0.1"
L00-FMR250xx-17-00-00-en-011
3.2.2Transport
Caution!
"
Follow the safety instructions and transport conditions for instruments of more than
18 kg.
Do not lift the measuring instrument by its housing in order to transport it.
3.2.3Storage
Pack the measuring instrument so that is protected against impacts for storage and transport. The
original packing material provides the optimum protection for this.
The permissible storage temperature is -40 °C…+80 °C.
Endress + Hauser11
InstallationMicropilot M FMR250 with HART/4...20 mA
3.3Installation conditions
3.3.1Dimensions
Housing dimensions
max. 110
max. 10094
F12 housing
(Aluminium)
65
ENDRESS+HAUSER
65
ENDRESS+HAUSER
78
Ø 129
150
85
L00-F12xxxx-06-00- 00-en-001
78
T12 housing
(Aluminium)
40
F23 housing
(316L)
max. 94
104
162
Ø 129
85
L00-T12xxxx-06-00-0 0-en-001
Ø 129
150
L00-F23xxxx-06-00- 00-en-001
12Endress + Hauser
Micropilot M FMR250 with HART/4...20 mAInstallation
Micropilot M FMR250 - process connection, type of antenna
F12 / T12 / F23 housing
Threaded connection
BSPT (R 1 ½”)
1 ½”
or 1 ½ NPT
Ø 60
43
23
50
L
135
Ø 60
b
Flange DN80…100
or equivalent
135
Ø DØ 340
250/450
E+H UNI flange DN 200Alignment unit with
8
250/450
Ø 60
135
Parabolic antennaHorn antenna
E+H UNI flange DN 100/200
Ø 60
8
Ø 225 (DN100)
340 (DN200)Ø
50
L
135
40
50
Ø d
Ø dØ d
Horn antennaParabolic antenna
Antenna sizeAntenna size
L [mm]L [mm]
d [mm]d [mm]
Flange to EN 1092-1 (agreeable to DIN 2527)
Flange
b [mm]b [mm]b [mm]
D [mm]D [mm]D [mm]
for PN10/16
80mm/3”200mm/8”
211
DN 80DN 803”
201823.9
200
100mm/4”
75
DN 100DN 1004”
201823.9
220210228.6
L
282195
95197
Flange to ANSI B16.5
Flange
for 150 lbs
50
L
Ø d
Flange to JIS B2210
Flange
185190.5
for 10K
L00-FMR250xx-06-00-00-en-005
Endress + Hauser13
InstallationMicropilot M FMR250 with HART/4...20 mA
E+H UNI flange
The number of bolts has sometimes been reduced. The bolt-holes have been enlarged for adaption
of dimensions, therefore, the flange needs to be properly aligned to the counterflange before the
bolts are tightened.
A-A
E+H UNI flange DN100
compatible with:
- DN100 PN10/16,
- ANSI 4" 150 lbs,
- JIS 10K 100A
Ø 19
A
M80x1.5
4x90
175
185.5
225
°
Ø 23
4x90°
A
8
material: 316L
E+H UNI flange DN200
compatible with:
- DN200 PN10/16,
- ANSI 8" 150 lbs,
- JIS 10K 200A
°
6x60
A
Ø 26
4x90°
Ø 26
A
294.5
340
Top target positioner with E+H UNI flange
A
A
8
A-A
Ø 85
Viton seal
L00-FMR250xx-06-00- 00-en-006
clamping screw
3 x M8 shifty at 120°
40
E+H UNI flange
DN100/DN200
±15°
L00-FMR250xx-06-00- 00-en-007
14Endress + Hauser
Micropilot M FMR250 with HART/4...20 mAInstallation
3.3.2Engineering hints
Orientation
• Recommended distance (1) wall – outer
edge of nozzle: ~1/6 of vessel diameter.
However, the device should not, under any
circumstances, be mounted less than 20 cm/
8“ from the vessel wall.
• Not in the centre (3), interference can cause
signal loss.
• Not above the fill stream (4).
• It is recommended to use a weather
protection cover (2) in order to protect the
transmitter from direct sun or rain. Assembly
and disassembly is simply done by means of a
tension clamp (→ Chap. 8 on Page 64).
• In extremely dusty applications, the
integrated air purge connection can prevent
clogging of the antenna.
1
234
L00-FMR250xx-17-00 -00-xx-003
Vessel installations
• Avoid any installations (1), like limit switches,
struts, etc., inside the signal beam (refer to
beam angle see "Beam angle" on Page 16).
• Symmetrical installations (2), i.e. reinforcing
rings, heating coils, etc., can also interfere
with the measurement.
Optimization options
• Antenna size: the bigger the antenna, the
smaller the beam angle, the less interference
echoes.
1
• Mapping: the measurement can be optimized
by means of electronic suppression of
interference echoes.
• Antenna alignment: refer to "Optimum
mounting position"
2
• In devices with top target positioner, the
sensor can be optimally aimed within the
vessel and/or interference reflections can be
avoided.
The max. angle β is ±15°.
Please contact Endress+Hauser for further
information.
L00-FMR250xx-17-00 -00-xx-002
Endress + Hauser15
InstallationMicropilot M FMR250 with HART/4...20 mA
Beam angle
The beam angle is defined as the angle a where the energy density of the radar waves reaches half
the value of the maximum energy density (3dB-width). Microwaves are also emitted outside the
signal beam and can be reflected off interfering installations. Beam diameter W as function of
antenna type (beam angle α) and measuring distance D:
Antenna size
FMR250
Beam angle α10°8°4°
Measuring
distance (D)
5m / 16 ft
10 m / 32 ft
15 m / 49 ft
20 m / 65 ft
30 m / 98 ft
40 m / 131 ft
50 m / 164 ft
Horn antennaParabolic antenna
80 mm
3"
80 mm
3"
0.87 m /
2.80 ft
1.75 m /
5.60 ft
2.62 m /
8.57 ft
3.50 m /
11.37 ft
5.25 m /
17.15 ft
7.00 m /
22.92 ft
8.75 m /
28.70 ft
100 mm
4"
Beamwidth diameter (W)
100 mm
4"
0.70 m /
2.24 ft
1.40 m /
4.48 ft
2.10 m /
6.85 ft
2.80 m /
9.09 ft
4.20 m /
13.71 ft
5.59 m /
18.32 ft
6.99 m /
22.94 ft
200 mm
200 mm
0.35 m /
1.12 ft
0.70 m /
2.23 ft
1.05 m /
3.42 ft
1.40 m /
4.54 ft
2.10 m /
6.84 ft
2.79 m /
9.15 ft
3.50 m /
11.45 ft
8"
D
8"
W
L00-FMR2xxxx-14-00 -06-de-027
16Endress + Hauser
Micropilot M FMR250 with HART/4...20 mAInstallation
Measuring conditions
• The measuring range begins, where the beam hits the vessel bottom. Particularly with dish
bottoms or conical outlets the level cannot be detected below this point.
• In case of media with a low dielectric constant (groups A and B), the vessel bottom can be visible
through the medium at low levels. In order to guarantee the required accuracy in these cases, it
is recommended to position the zero-point at a distance C =50...150 mm above the vessel bottom
(see Fig.).
• In principle it is possible to measure up to the tip of the antenna with FMR250. However, due to
considerations regarding abrasion and build-up, the end of the measuring range should not be
chosen any closer than A=400 mm (see Fig.) to the tip of the antenna.
• The smallest possible measuring range B=500 mm (see Fig.).
100%
0%
A
B
C
L00-FMR250xx-17-00-00-en-001
Endress + Hauser17
InstallationMicropilot M FMR250 with HART/4...20 mA
Measuring range
The usable measuring range depends on the size of the antenna, the reflectivity of the medium, the
mounting location and eventual interference reflections. The maximum configurable range is 70 m
(229 ft) for Micropilot M FMR250.
To achieve an optimised Signal strength it is recommended to use an antenna with as large as
possible diameter (DN200/8" parabolic antenna, DN100/4" horn).
Reduction of the max. possible measuring range through:
• Media with poor reflection properties (= small DC). For examples refer to table 1.
• Angle of repose.
• Extremely loose surfaces of bulk solids, e.g. bulk solids with low bulk weight for pneumatic filling.
• Build-up, above all of moist products.
Table 1:
The following table describes the media groups and the dielectric constant
Media groupDC (εr)ExamplesSignal attenuation
A1.6...1.9
B1.9...2.5– Portland cement, plaster16...13 dB
C2.5...4
D4...7
E>7
– Plastic granulate
– White lime, special cement
–Sugar
–Grain, seeds
–Ground stones
–Sand
– Naturally moist (ground) stones, ores
–Salt
– Metallic powder
– Carbon black
–Coal
εr.
19...16 dB
13...10 dB
10...7 dB
< 7 dB
The respective lower group applies for very loose or loosened bulk solids.
18Endress + Hauser
Micropilot M FMR250 with HART/4...20 mAInstallation
90°
90
°
90°
90°
9
3.4Installation instructions
3.4.1Mounting kit
For the mounting , you will require the following tool:
• The tool for flange mounting or
• a key AF60 for threaded boss and
• 4 mm/0.1" Allen wrench for turning the housing.
3.4.2Installation in vessel (free space)
Optimum mounting position
marker at instrument
flange or threaded boss
90
°
90°
1)
at version with top target positioner, the marker is at the housing adapter
90°
°
90
90°
(opposite the air purge connection)
DN80…200
ANSI 3…8”
1)
1½” BSPT (R 1½”)
or
1½ NPT
L00-FMR250xx-17-00-00-en-009
Endress + Hauser19
InstallationMicropilot M FMR250 with HART/4...20 mA
Standard installation FMR250 with horn
antenna
• Observe installation instructions on Page 15.
• Marker is aligned towards vessel wall.
• The marker is always exactly in the middle
between two bolt-holes in the flange.
• After mounting, the housing can be turned
350° in order to simplify access to the display
and the terminal compartment.
• The horn antenna should protrude from the
nozzle. If necessary, choose version with
H
antenna extension (see Page 13).
If this is not possible for mechanical reasons,
nozzle heights up to 500 mm can be
accepted.
Note!
Please contact Endress+Hauser for application
with higher nozzle.
Ø D
• Vertical horn antenna.
Ideally, the horn antenna should be installed
vertically.
L00-FMR250xx-17-00- 00-en-004
To avoid interference reflections or for
optimum alignment within the vessel, the
FMR250 with optional top target positioner
can be swiveled by 15° in all directions.
Antenna size80 mm / 3"100 mm / 4"
D [mm / inch]75 / 395 / 3.7
H [mm / inch]
(without antenna extension)
< 260 / < 10.2 < 330 / < 12.9
20Endress + Hauser
Micropilot M FMR250 with HART/4...20 mAInstallation
Standard installation FMR250 with
parabolic antenna
• Observe installation instructions on Page 15.
1
• Marker is aligned towards vessel wall.
• The marker is always exactly in the middle
between two bolt-holes in the flange.
• After mounting, the housing can be turned
H
350° in order to simplify access to the display
and the terminal compartment.
• Ideally the parabolic antenna should protrude
from the nozzle (1). If necessary, choose
version with antenna extension (see Page 13).
Particularly when using the top target
Ø D
positioner, please ensure that the parabolic
reflector is protruding from the nozzle/roof so
as not to inhibit alignment.
2
Note!
For application with higher nozzle install
parabolic antenna completely in the
nozzle (2), including RF-wave guide (3).
• Vertical parabolic antenna.
Ideally, the parabolic antenna should be
installed vertically.
To avoid interference reflections or for
optimum alignment within the vessel, the
3
L00-FMR250xx-17-00-00-en-005
FMR250 with optional top target positioner
can be swiveled by 15° in all directions.
Antenna size200 mm / 8"
D [mm / inch]197 / 7.75
H [mm / inch]
(without antenna extension)
< 50 / < 1.96
Endress + Hauser21
InstallationMicropilot M FMR250 with HART/4...20 mA
Examples for installation with small flange (< parabolic reflector)
standard installation
Antenna size
D [mm]
H [mm]
1)
without antenna extension
200mm/8”
1)
197
< 50
nozzle
D
H
for installation
in nozzle
you can dismantle
the parabolic reflector
4 bolts
Caution!
At hinged flanges, the length of the antenna
must be taken into account!
L00-FMR250xx-17-00- 00-en-007
22Endress + Hauser
Micropilot M FMR250 with HART/4...20 mAInstallation
FMR250 with top target positioner
Using top target positioner it is possible to tilt the antenna axis by up to 15° in all directions. The
top target positioner is used for the optimum alignment of the radar beam with the bulk solids
surface.
±15°
Align antenna axis:
1.Loosen screws.
2.Align antenna axis (here this is possible up to max. ±15° in all directions).
3.Tighten screws.
Integrated air purge connection
In extremely dusty applications, the integrated
air purge connection can prevent clogging of the
antenna.
• Permanent operation:
recommended pressure range of the purge air:
1.2...1.5 bar abs.
• Pulsed operation:
max. pressure of purge air: 6 bar abs.
air purge connection:
NPT
¼
G (max. torque 3.5 Nm)
¼
or
Caution!
Make sure to use dry purge air.
±15°
L00-FMR250xx-17-00 -00-de-008
L00-FMR250xx-17-00-00-en-010
Endress + Hauser23
InstallationMicropilot M FMR250 with HART/4...20 mA
3.4.3Turn housing
After mounting, the housing can be turned 350° in order to simplify access to the display and the
terminal compartment. Proceed as follows to turn the housing to the required position:
• Undo the fixing screws (1)
• Turn the housing (2) in the required direction
• Tighten up the fixing screws (1)
F12 / F23 housingT12 housing
2
2
1
1
allen key
4 mm/0.1”
L00-FMR2xxxx-17-00-00-en-010
3.5Post-installation check
After the measuring instrument has been installed, perform the following checks:
• Is the measuring instrument damaged (visual check)?
• Does the measuring instrument correspond to the measuring point specifications such as process
temperature/pressure, ambient temperature, measuring range, etc.?
• Is the flange marking correctly aligned? (→ Page 11)
• Have the flange screws been tightened up with the respective tightening torque?
• Are the measuring point number and labeling correct (visual check)?
• Is the measuring instrument adequately protected against rain and direct sunlight (→ Page 64)?
24Endress + Hauser
Micropilot M FMR250 with HART/4...20 mAWiring
ENDRESS+HAUSER
4Wiring
4.1Quick wiring guide
Wiring in F12/F23 housing
Before connection please note the following:
"
●
Caution!
The power supply must be identical to the data on the
nameplate (1).
●
Switch off power supply before connecting up the device.
●
Connect Equipotential bonding to transmitter ground terminal
1
before connecting up the device.
●
Tighten the locking screw:
It forms the connection between the antenna and the housing
ground potential.
When you use the measuring system in hazardous areas, make sure you comply with
national standards and the specifications in the safety instructions (XA’s).
Make sure you use the specific cable gland.
On devices supplied with a certificate, the explosion protection
-
is designed as follows:
●
Housing F12/F23 - EEx ia:
Power supply must be intrinsically safe.
●
The electronics and the current output are galvanically
separated from the antenna circuit.
Connect up the Micropilot M as follows:
●
Unscrew housing cover (2).
●
Remove any display (3) if fitted.
●
Remove cover plate from terminal compartment (4).
●
Pull out terminal module slightly using pulling loop.
●
Insert cable (5) through gland (6).
A standard installation cable is sufficient if only the analogue signal is
used. Use a screened cable when working with a superimposed
communications signal (HART).
ENDRESS+HAUSER
MICROPILOT M
Order Code:
xxxxxxxx
Ser.-No.:
PTB 00ATEX
II 1/2 G EEx ia IIC T6
D00882-A
U 16 ... 30 V DC
4...20 mA
t >85°C
T >70°C:
A
Dat./Insp.:
xxxxxxxx
#
1
PN max.
8
T
Antenne
11
IP65
if modification
x=
see sep. label
3
4
max.°C
7
79689 Maulburg
Made in Germany
2
Unplug display connector!
3
R
E
S
U
A
H
+
S
S
E
R
D
N
E
-
communication
resistor
(> 250 )Ω
Only ground screening of the line (7) on sensor side.
●
Make connection (see pin assignment).
●
Re-insert terminal module.
●
Tighten cable gland (6).
●
Tighten screws on cover plate (4).
●
Insert display if fitted.
●
Screw on housing cover (2).
●
Switch on power supply.
power
alternatively
Commubox
FXA 191
DXR 375
7
4...20 mA
test sockets
(output current)
plant
4
2
3
1
L-
L+
I+
ground
I-
6
5
1234
Sealed terminal
compartment
4
L00-FMR2xxxx-04-0 0-00-en-013
Endress + Hauser25
WiringMicropilot M FMR250 with HART/4...20 mA
Wiring in T12 housing
Before connection please note the following:
●
"
Caution!
When you use the measuring system in hazardous areas, make sure you comply with
national standards and the specifications in the safety instructions (XA’s).
Make sure you use the specific cable gland.
-
The power supply must be identical to the data on the
nameplate (1).
●
Switch off power supply before connecting up the device.
●
Connect Equipotential bonding to transmitter ground terminal
1
before connecting up the device.
●
Tighten the locking screw:
It forms the connection between the antenna and the housing
ground potential.
Connect up the Micropilot M as follows:
Before unscrew housing cover (2) at seperate connection room
turn off the power supply!
●
Insert cable (3) through gland (4).
A standard installation cable is sufficient if only the analogue signal is
used. Use a screened cable when working with a superimposed
communications signal (HART).
ENDRESS+HAUSER
MICROPILOT M
Order Code:
Ser.-No.:
PTB 00ATEX
II 1/2 G EEx ia IIC T6
D00882-A
U 16 ... 30 V DC
4...20 mA
t >85°C
T >70°C:
A
Dat./Insp.:
xxxxxxxx
1
xxxxxxxx
8
IP65
if modification
x=
PN max.
T
max.°C
Antenne
11
see sep. label
3
4
7
79689 Maulburg
Made in Germany
2
-
communication
resistor
(> 250 )Ω
Only ground screening of the line (5) on sensor side.
●
Make connection (see pin assignment).
●
Tighten cable gland (4).
●
Screw on housing cover (2).
●
Switch on power supply.
power
alternatively
Commubox
FXA 191
DXR 375
4...20 mA
5
test sockets
(output current)
plant
4
2
3
1
L-
L+
I+
ground
I-
4
3
1234
L00-FMR2xxxx-04-00-00-en-014
26Endress + Hauser
Micropilot M FMR250 with HART/4...20 mAWiring
4.2Connecting the measuring unit
Terminal compartment
Three housings are available:
• Aluminium housing F12 with additionally sealed terminal compartment for:
–standard,
–EEx ia,
– EEx ia with dust Ex.
• Aluminium housing T12 with separate terminal compartment for:
–standard,
–EEx d,
– EEx ia (with overvoltage protection),
– dust Ex.
• 316L housing F23 for:
–standard,
–EEx ia,
– EEx ia with dust Ex.
The electronics and current output are galvanically isolated from the antenna circuit.
F12 housingF23 housing
11
44
22
33
sealed terminal
compartment
T12 housing
1
2
3
4
The instrument data are given on the nameplate together with important information regarding the
analog output and voltage supply. Housing orientation regarding the wiring, (→ Page 24).
Load HART
Minimum load for Hart communication: 250 Ω
Cable entry
L00-FMR2xxxx-04-0 0-00-en-019
Cable gland: M20x1.5
Cable entry: G ½ or ½ NPT
Endress + Hauser27
WiringMicropilot M FMR250 with HART/4...20 mA
Supply voltage
The following values are the voltages across the terminals directly at the instrument:
Communication
HART
Fixed current, adjustable
e.g. for solar power
operation (measured
value transferred at
HART)
Fixed current for HART
Multidrop mode
1) Start up current 11 mA.
Current
consumption
standard
EEx ia
EEx d
dust Ex
standard11 mA10 V36 V
EExia11mA10V30V
standard4 mA
EEx ia4 mA
4mA16V36V
20 mA7.5 V36 V
4mA16V30V
20 mA7.5 V30 V
4mA16V30V
20 mA11 V30 V
4mA16V30V
20 mA11 V30 V
1)
1)
Terminal voltage
minimalmaximal
16 V36 V
16 V30 V
Power consumption
Normal operation: min. 60 mW, max. 900 mW
Current consumption
CommunicationCurrent consumption
HART3.6...22 mA
28Endress + Hauser
Micropilot M FMR250 with HART/4...20 mAWiring
4.2.1HART connection with E+H RMA422 / RN221N
- ToF Tool FieldTool
Package
FXA193
4...20 mA
ENDRESS + HAUSER
RMA 422
RMA422
1
234
dsdmdm
df das.
asdas fa
asas la.
FMP40:LIC0001
ONLINE
1 GROUP SELECT
2 PV 8.7 m
HELP SAVE
Page
Up
DeleteBksp
Page
On
# % &
A B C
D E F
2
1
3
Copy
Paste
Hot Key
M N O
G H I
J K L
4
5
6
+ Hot Key
Insert
W XY Z
P Q R S
T UV
8
7
9
+ * /
, ( )‘
_ < >
.
0
-
375
FIELD COMMUNICATOR
HART
DXR375
RN221N
- ToF Tool FieldTool
Package
- FieldCare
Commubox
FXA191
L00-FMR2xxxx-04-0 0-00-en-009
4.2.2HART connection with other supplies
- ToF Tool FieldTool
Package
FXA193
4...20 mA
≥Ω250
1
234
FMP40:LIC0001
ONLINE
1 GROUP SELECT
2 PV 8.7 m
HELP SAVE
# % &
1
Copy
G H I
4
P Q R S
7
, ( )‘
FIELD COMMUNICATOR
dsdmdm
df das.
asdas fa
asas la.
Page
Up
DeleteBksp
Page
On
D E F
A B C
3
2
Hot Key
Paste
M N O
J K L
6
5
+ Hot Key
Insert
W XY Z
T UV
8
9
+ * /
_ < >
-
.
0
375
HART
DXR375
Caution!
"
If the HART communication resistor is not built into the supply unit, it is necessary to insert a
communication resistor of 250 Ω into the 2-wire line.
- ToF Tool FieldTool
Package
- FieldCare
Commubox
FXA191
DC power supply
unit
or
PLC
L00-FMR2xxxx-04-0 0-00-en-008
Endress + Hauser29
Loading...
+ 67 hidden pages
You need points to download manuals.
1 point = 1 manual.
You can buy points or you can get point for every manual you upload.