7.8 Line Fuse ........................................................................................................................................... 24
8.2 Factory Service .................................................................................................................................. 27
9. ORDERING INFORMATION & ACCESSORIES...................................................................................... 29
9.1 OASIS Part Numbers ......................................................................................................................... 29
9.2 Model 400 Series Accessories............................................................................................................ 29
i
1. INTRODUCTION
ENDEVCO®, a leader in the vibration measurement field since 1951, has contributed many firsts
in vibration sensor design. These include: the first piezoelectric accelerometer capable of
continuous operation from cryogenic temperatures up to +750°F, the first shear design
accelerometer and the world's smallest piezoelectric accelerometer. To support a broad family of
vibration transducers, ENDEVCO has provided a wide variety of signal conditioners, including the
first transistorized charge amplifier, the first computer-programmable charge amplifier and the
first airborne vibration monitoring system that is based on a true digital tracking filter.
Other support systems includes the introduction of the first Laser Interferometer absolute
calibration system. Endevco is a pioneer in the science of Micro-Electro-Mechanical Systems
(MEMS) design and manufacturing various sensor technologies to include Gyro, Variable
Capacitance and silicone Pressure Transducers.
1.1 SIGNAL CONDITIONERS
To support the use of its sensors in large scale testing, ENDEVCO has developed several
generations of signal conditioner systems. Until recently, a state-of-the-art vibration laboratory
set up consisted of a rack of manually controlled signal conditioners. These signal conditioners
have manually controlled switches and knobs, to set full scale ranges, sensitivity and filter
corners and the set up information is recorded by hand.
ENDEVCO MODEL 4990A RACK
INSTRUCTION MANUAL
1.2 COMPUTER CONTROLLED SIGNAL CONDITIONERS
To support the use of its sensors in large scale testing, and to eliminate the risk of incorrect
amplifier settings, ENDEVCO has developed several generations of computer controlled signal
conditioning systems. The first generation was the Multi-channel Amplifier Control system
(MAC). The second generation was the Computer Controlled Amplifier Systems (CCAS). The
CCAS family consists of five different systems that use the same rack and digital interface
assemblies with different analog boards. These units receive their setup commands over an
IEEE-488 interface bus from a computer/controller so that tests can be pre-programmed. In
addition, these units provide comprehensive self-test and self-calibration capabilities, which
greatly improves the reliability of the test data. User feedback indicates these units pay for
themselves by shortening test cycles, preventing re-tests and eliminating over-testing.
ENDEVCO is pleased to announce the third generation of computer controlled signal
conditioners: the OASIS 2000 (Optimal Architecture Sensor Interface System). Utilizing Ethernet
or EIA232 bus control, SMART Transducer technology, and a wide variety of signal conditioning
modules, the OASIS 2000 will meet all the requirements of multi-channel testing.
1.3 OASIS 2000 Hardware
The OASIS 2000 allows for configuration of a flexible modular multi-channel measurement
system that can interface to multiple sensor types (charge, voltage, full, half, quarter bridge PR,
VC, Isotron, IEEE 1451.4 compatible Smart Isotron) by using any combination of the 400 family
of signal conditioner cards housed in a 16 slot, 19” rack (ENDEVCO part No. 4990A).
The OASIS 2000 system can be customized to meet most requirements and is adaptable to the
developing needs of the user.
1
Acceleration
Velocity
Pressure
Force
Str ain
Temperature
Charge
PE
Isotron
Quarter
Bri dge
PR
Half
Bridge
PR
Full
Bridge
PR
AC
DC
Smart
Isotron
Smart
Sensors
ENDEVCO MODEL 4990A RACK
INSTRUCTION MANUAL
B a r C o d e L a b e l s
Measurement Position
Sensor Ser ial No.
Up to 48 Analog Outputs
Combined in 4 connectors
Ethernet
Up to 16 Racks
RS-232
Up to 128 Channels per Rack
16 4XX Cards
System Configuration Information
Am pl i fier Channel No.
Se nsor Serial Number
Measu re ment Po siti on
Cable ID
Ca ble ID
e 2 0 0 0 S o f t w a r e
System C onfiguration Control
Meas urement Posi tion
Ca b le ID
Sensor Serial No.
Sensor Sensitivity
Am p lifier C hannel No.
Full Sca le Inpu t Range
Outp ut Sc aling
Am p lifier' s Gain
Customizable Reports
Electronic or Paper
Sensor Database
Electr onic File
Created Manually
or Automatically by
Endevco Calibration System
1.4 OASIS 2000Software
The OASIS 2000 Configuration Editor software (SW2000 or SW400) was developed to configure
Model 400 series signal conditioners and amplifiers installed in a Model 4990A rack.
The SW2000 software is a full featured software package designed to simplify system
configuration and amplifier setup.
• Intuitive, simple to use, graphical interface provides both table view and matrix view windows
for quick configuration for up to 2048 channels.
• Ethernet (one or more 4990A racks) or serial (single 4990A rack) communications.
• Reads 1451.4 Transducer Electronic Data Sheet (TEDS) information from sensors with a
TEDS capability. Writes 1451.4 ‘User Data’ (up to 8 characters) to TEDS capable sensors.
• Automatic Sensor Calibration due warnings.
• Customizes easily to user defined row definitions allowing for consolidation of all relevant
information in a single file.
• Configuration table data imports easily into MS Excel spreadsheets.
• Convenient ‘Online’, ‘Offline’ modes to facilitate setup prior to hardware installation or to
configure different setups without affecting the hardware.
• GoTo and Find operations for quickly accessing specific table view data.
The SW400 software is a subset of the SW2000 software that provides a basic set of tools for
controlling the amplifiers. This version provides only the matrix view window and it’s
associated amplifier functions.
2
2. DESCRIPTION
The Endevco Model 4990A is a 19 inch rack that houses up to 16 of the Endevco Model 400
series signal conditioning modules in any combination. Signal conditioning modules supported by
the Model 4990A are:
• 3-channel PE/Isotron Signal Conditioner Model 433
• 3-channel DC Differential Voltage Amplifier Model 436
• 2-channel PE/Isotron High Performance Signal Conditioner Model 428
• 8-Channel Smart Transducer/Isotron® Signal Conditioner Model 482
The Model 4990A provides power, input and output connections, and computer interface for the
signal conditioning modules. Any combination of the 400 family of signal conditioning cards may
be used. The address of each signal conditioning module is automatically determined by the
position of the module in the rack.
The Model 4990A has four 25-pin “D” connectors on the front panel for access to the signal
conditioner outputs. Each connector contains the outputs of 4 modules for a maximum of 12
outputs. The outputs of the 8-Channel Smart Transducer Signal Conditioner Model 482 are
accessible only on its front panel, or through the optional Model 36020 output breakout panel.
The connection of the 4990A-1 rack to the controlling PC is a standard TCP/IP Ethernet Network
bus RJ-45 connector.
ENDEVCO MODEL 4990A RACK
INSTRUCTION MANUAL
The connection of the 4990A-2 rack to the controlling PC is a standard EIA-232 bus through a 9
pin “D” connector.
Both computer interface connectors, 9 pin “D” connector and RJ-45 connector, are available on
the Model 4990A-1 and Model 4990A-2.
The Model 4990A-1 rack contains an Ethernet to EIA-232 bus converter (EDAS) that can be
accessed through the TCP/IP Ethernet Network bus. This allows for multiple rack applications
where up to sixteen (16) 4990A-1 racks (total of up to 256 signal conditioning modules) can be
interconnected and controlled by a single computer. Each Model 4990A-1 rack contains an RJ45 Ethernet connector and is assigned a unique IP address. The address of each individual card
is automatically determined by the rack address and the position of the card in the rack.
SW2000 configuration editor software and SW400 matrix view software is available to control the
Model 4990A rack and Model 400 series modules.
2.1 KEY FEATURES
• 19 inch rack to support up to 16 Endevco Series 400 Signal conditioning modules in cabinet
installations or stand alone operation.
• Computer interface via TCP/IP Ethernet or serial EIA-232.
• Flexible design to accommodate any combination of the 400 family of signal conditioning
modules.
• Signal conditioner outputs easily accessible through four 25 pin “D” connectors.
• External Calibration input
3
ENDEVCO MODEL 4990A RACK
3. FUNCTIONAL CHARACTERISTICS
3.1 General
The Endevco Model 4990A-1 performs bi-directional communication with a computer through a
10 Mbps Ethernet bus. Each rack and module is assigned a unique address. The 4990A-2 rack
communicates with the 400 family of signal conditioning cards through a half-duplex multi-drop
EIA-232 bus running at 9.6 or 19.2 kbps in a Master/Slave mode.
The Model 4990A only activates the communication bus as required by software polling or fault
reporting. This feature insures low noise operation.
3.2 Mechanical Characteristics
The Model 4990A consists of:
• CE certified 19” rack per IEC-297
• Power supply
• Power entry module with on/off switch
• Fuse
INSTRUCTION MANUAL
• Fan
• Computer interface port
• Module interconnect/power distribution PCB
• Four 25 pin “D” signal output connectors
• Calibration input BNC
• Card guides for installation of 16 signal conditioning cards
• Two 8 position DIP switches to set computer interface parameters.
The front side of the rack provides access to the front panels of the signal conditioning modules,
the signal output connectors, the computer interface port, and the calibration input BNC
connector. The rear side has the power entry module with on/off switch, fuse and fan.
The brackets for mounting the rack into a standard 19” cabinet and the handles are mounted on
the front side. The handles and brackets can be mounted on the rear side at the factory if
required.
The rack is designed to be used in 19” cabinets or stand-alone on the bench top. For bench top
applications the unit can be mounted in an optional Endevco Model EHM1616 powder-coated
shell. This option offers the following features:
• Light gray powder coat finish (RAL 7035).
• Tilt feet in the front, static feet in the rear.
• Integrated folding carrying handles on the sides.
3.3 Model 4990A-1: Ethernet Option
In the Model 4990A-1 the EDAS monitors 32 discrete hardware lines that provide status on the
presence, absence and fault condition of each card, speeding up all control operations issued via
the Ethernet.
4
3.4 Model 4990A-2: RS-232 Option
The Model 4990A-2 uses the EIA-232 interface with a baud rate of 9.6 or 19.2 kbps to
communicate with the controlling PC. The communication function in the rack is simply an
extension of the EIA-232 connection between the controlling PC and the rack.
Card faults are detected in the Model 4990A-2 by polling the addresses corresponding to each
slot.
ENDEVCO MODEL 4990A RACK
INSTRUCTION MANUAL
5
ENDEVCO MODEL 4990A RACK
INSTRUCTION MANUAL
4. INSTALLATION AND COMMUNICATION
To help you get started using your OASIS 2000 with the fewest manuals in front of you as
possible, we’ve put all the basic information needed in this section. Once the system is
unpacked, setup, and running, refer to the following instruction manuals for detailed information
and specifications:
IMSW2000 Instruction Manual for the OASIS configuration software
IM428 Instruction Manual for the two channel PE/ISOTRON amplifier
IM433 Instruction Manual for the three channel PE/ISOTRON amplifier
IM436 Instruction Manual for the three channel DC amplifier
IM482 Instruction Manual for the eight channel SMART MODAL/ISOTRON amplifier
You will only receive the Instruction Manuals for the units you purchased. If you do not have
these documents contact Endevco before proceeding
4.1 Unpacking
CAUTION
OBSERVE SOUND ESD PRACTICES WHEN HANDLING THE SIGNAL
The Endevco Model 4990A rack is shipped with its instruction manual, accessories and power
cord in one package. The Model 400 series signal conditioning modules are shipped together
with their instruction manual and accessories, and the OASIS 2000 software is shipped
individually with its instruction manual. Carefully unpack and check all items for shipping
damage. Report any damage to the carrier immediately. If the shipping container or cushioning
material is damaged, it should be kept until the contents of the shipment have been checked
mechanically and electrically. Save the original packing materials for future shipments of the
hardware. Check each item of the shipment against the packing list. Verify that all ordered
optional accessories are included. Notify Endevco of any discrepancy.
4.2 Installation
Set the Model 4990A on a level, firmly supported surface. The weight of an empty 4990A is
approximately 24 pounds (35 pounds with the optional powder coated shell assembly). Add 12
ounces (340 grams) per amplifier card.
Insure sufficient clearance of the top and rear of the rack for proper operation of the ventilation
system. Insure the fan and chassis vents are not blocked. The internal temperature should not
exceed 28° C. Observe the environmental limitations of temperature and humidity when
installing the rack.
• Operating Temperature: 32° F to 122° F (0° C to 28° C)
CONDITIONING MODULES TO PREVENT DAMAGE.
• Storage Temperature: -40° F to 185° F (-40° C to 85° C)
• Operating Humidity: 0 % to 90 % non condensing
With no cards installed, look inside the 4990A rack from the front. On the backplane, above and
to the right of card slot 16 you will see two 8 position DIP switches. Verify the DIP switches are
set for the type of Model 4990A you have. Refer to the model number label on the rear of the
6
ENDEVCO MODEL 4990A RACK
INSTRUCTION MANUAL
unit and the default switch settings shown in paragraphs 4.3 and 4.4. You either have a Model
4990A-1 (Ethernet and RS232 control) or a Model 4990A-2 (RS232 control only).
Once the DIP switches are set to the appropriate position, install the Model 400 series signal
conditioning modules into the front side of the 4990A. Carefully align the modules with the card
guides, push the modules into the rack and secure them with the attached mounting screws.
Install the narrow blank panel to the right of slot 16. If your rack has less than 16 cards, install
the optional blank panels. Check that all modules and blank panels are secure in the rack.
S1
J1J2J3J4J5J6J7J8J9J10J11J1 2J13J14J15J16
S2
DIP Switches S1 and S2
7
ENDEVCO MODEL 4990A RACK
INSTRUCTION MANUAL
S1
S2
ON
1
2
3
4
5
6
7
8
1
2
3
4
S1
S2
1
2
3
4
5
6
7
8
1
2
3
4
ON
5
6
7
8
4990-14990-2
5
6
7
8
8
ENDEVCO MODEL 4990A RACK
INSTRUCTION MANUAL
4.3 Default Jumper Settings for Ethernet Rack (4990A-1):
POS S1
SWITCH
SETTING
1 OFF (ON for snoop mode) OFF
2 ON EDAS RX ßà back plane RX OFF
3 OFF OFF (ON for snoop mode)
4 OFF (ON for snoop mode) OFF (ON for snoop mode)
5 ON EDAS TX ßà back plane TX X
6 OFF X
7 X X
8 X OFF baud rate = 19.2 kbd
4.4 Default Jumper Settings for RS-232 Rack (4990A-2):
POS S1
SWITCH
SETTING
1 ON front panel RX ßà
REMARK S2
REMARK S2
SWITCH
SETTING
OFF (use POS1 ON for reversed
back plane RX
REMARK
SWITCH
SETTING
REMARK
cable, TX <- -> RX)
2 OFF OFF (use POS2 ON for reversed
cable, RX <- -> TX)
3 OFF ON straight cable (TX ßà TX)
4 ON front panel TX ßà
back plane TX
5 OFF X
6 OFF X
7 X X
8 X ON baud rate = 9.6 kbd (OFF for
ON straight cable (RX ßà RX)
19.2kbd)
9
ENDEVCO MODEL 4990A RACK
INSTRUCTION MANUAL
5. POWERING UP OF THE RACK ASSEMBLY AND ESTABLISHING COMMUNICATION
CAUTION:
PRIOR TO INSERTING THE POWER CORD INTO THE POWER ENTRY MODULE, VERIFY
THE FOLLOWING:
5.1 Apply Power
Power source is between 90 and 264 VAC, 47 to 440 Hz.
Check that the installed fuse is the same rating as labeled on the rack next to the power entry
module. The fuse is located in the power entry module, on the outside of the rear panel
Check that the common connection (third wire) of the power source is connected to earth ground.
5.2 Computer Interface
Connect the Ethernet interface cable between the RJ45 connector on the 4990A-1 and network
hub or repeater connection. If you connect the host computer’s 10BASE-T network interface
card (NIC) directly to the 4990A-1 you must use a crossover cable. A crossover cable is a
twisted pair patch cable wired in such a way as to route the transmit signals from one piece of
equipment to the receive signals of another piece of equipment, and vice versa. The maximum
length of cable is 100 meters. If you plan on building your own cables see Appendix A
OR
Connect the RS-232 interface cable between the 9 pin “D” connector on the 4990A-1 or 4990A-2
and one of the host computer’s COM ports. The maximum length of cable is 15.2 meters. The
cable is a standard serial interface cable, straight pinning.
Power up the Model 4990A by activating the switch on the power entry module. Verify the fan is
operating.
5.3 Installing the OASIS SW2000 Software. (Windows 95/98)
Insert the OASIS CD in the CD drive and run the SETUP.EXE program. If your CD’s autorun
capability is active the setup program will run automatically.
All files will be installed into C:\”default directory” usually:
C:\Program Files\Endevco\OASIS (for SW2000 software)
C:\Program Files\Endevco\OASIS (for SW400 software)
An OASIS Program Item will be created.
To run OASIS, click on the Windows “Start” button then Programs>>Endevco>>OASIS
10
5.4 Establishing Communication
The OASIS Configuration Editor screen is the main application screen. When the program is run,
this screen is displayed and the mode is defaulted to OFFLINE, as evidenced by the red
HARDWARE OFFLINE indicator visible below the ENDEVCO text
This spreadsheet-like table allows a user to quickly setup channels for an entire system of 400
series units.
ENDEVCO MODEL 4990A RACK
INSTRUCTION MANUAL
11
ENDEVCO MODEL 4990A RACK
INSTRUCTION MANUAL
Click on the red HARDWARE OFFLINE indicator to establish communication between the computer and
hardware. The indicator should turn white and read HARDWARE ONLINE. This screen will immediately
appear:
Make your selection and click OK.
12
ENDEVCO MODEL 4990A RACK
INSTRUCTION MANUAL
The OASIS software can communicate with Model 400 units in a 4990A rack either serially or
through an Ethernet connection. The Options dialog box is provided to set the appropriate
communication parameters for an installation. To access the Options dialog box click on the Edit
drop down menu and select Options. The following screen will appear:
13
ENDEVCO MODEL 4990A RACK
INSTRUCTION MANUAL
5.4.1 RS-232 Serial Communication Control
If RS-232 communications is selected then the following parameters must be specified:
• Comm Port - Select the Comm port that is connected to the 4990A Rack.
• Baud Rate - Select the baud rate that matches the setting of the 4990A Rack. The 4990A
Rack is limited to 9600 or 19200. The options available in this pull down menu will be
determined by the Unit Type setting.
• Unit Type - Select which type of units are in the configuration. This setting not only
determines the appropriate options for the baud rate selection but also informs OASIS of the
unit types when it is in OFFLINE mode so it can provide the appropriate indications where
unit type is displayed.
5.4.2 Ethernet Communication Control
When Ethernet is selected as the communication type, the Ethernet communication controls
become active.
• Ethernet Addresses Table - This tables purpose is to assign a rack number to each physical
rack in the system. Since the Oasis controller software uses rack and slot number locations
to identify amplifier cards in the system, each physical rack needs to be assigned a different
rack number from 1 to 16.
Every device on an Ethernet network must have a unique set of Ethernet addresses. Therefore,
a rack’s set of Ethernet addresses is used to identify which physical rack is assigned to which
rack number in the table.
Below are the steps to assign and store Ethernet addresses for a rack:
1. Select a rack (row) in the table.
2. Enter in the table the desired Ethernet addresses for the selected rack.
3. Click on the “Write Rack” button and follow the displayed instructions for setting up
the selected rack to receive and store Ethernet addresses.
4. Click on the “Test Rack” button and follow the displayed instructions for setting up
the selected rack to verify Ethernet communication.
• Active Racks Checkboxes - These checkboxes to the left of the Ethernet Addresses Table,
allow a user to make a rack active/inactive (start/stop communication with it) without having
to re-enter/delete its Ethernet address data in the table.
• Read Rack Button - Reads the Ethernet addresses from the actual rack which is setup and
connected for Ethernet addressing into the selected rack in the table. (Instructions are
displayed for setting up and connecting the rack for Ethernet addressing.)
• Write Rack Button - Writes the selected rack’s Ethernet addresses in the table to the actual
rack which is setup and connected for Ethernet addressing. (Instructions are displayed for
setting up and connecting the rack for Ethernet addressing.)
• Test Rack Button - Verifies Ethernet communication with the selected rack in the table.
(Instructions are displayed for setting up and connecting the rack for Ethernet
communication.)
• Move Up Button - This is a table editing aid which moves the table's selected Ethernet
addresses up one row. (It exchanges the selected row's Ethernet addresses with the row
above it.)
14
• Move Down Button - This is a table editing aid which moves the table's selected Ethernet
addresses down one row. (It exchanges the selected row's Ethernet addresses with the row
below it.)
• All Inactive Button - Unchecks all the active racks checkboxes.
• All Active Button - Checks all the active racks checkboxes.
5.4.3 Ethernet Addressing Guidelines
The host computer must have a 10BASE-T Ethernet Network Interface Card installed and you
must know the IP address, subnet mask, and installed gateway of the host computer.
All devices on a given network must have the same Subnet Mask.
Each device on a network must have the same Network ID portion of the IP address. (The
numbers in the IP Address corresponding to the 255s in the Subnet Mask)
Each device on a network must have a different Host ID portion of the IP address. (The numbers
in the IP Address corresponding to the 0s in the Subnet Mask)
All devices on a given network must have the same/valid Gateway Address if they are
communicating across networks.
Configuring the Model 4990A Rack
After entering the IP address, subnet mask and gateway address for all active racks, this
information must be written to the 4990A racks. Prior to writing data to the 4990A, the DIP
switches on the backplane, above and to the right of card slot 16 must be set to the positions in
the following table:
ENDEVCO MODEL 4990A RACK
INSTRUCTION MANUAL
POS S1
SWITCH
SETTING
1 OFF OFF
2 OFF OFF
3 ON EDAS RX ßà front panel RX ON EDAS TX ßà front
4 OFF ON EDAS RX ßà front
5 OFF X
6 ON EDAS TX ßà front panel TX X
7 X X
8 X X baud rate = 9.6 or
REMARK S2
SWITCH
SETTING
REMARK
panel TX
panel RX
19.2 kbd
15
ENDEVCO MODEL 4990A RACK
INSTRUCTION MANUAL
On the Options screen click on Write Rack. The following window will appear:
Follow the instructions and click OK. A write failure will produce the following window:
Correct the problem and click OK.
If you suspect the Ethernet NIC, cable, or hub may be the cause of the failure:
Identify a vacant serial (COM) port on the host computer
Connect a serial (RS-232) cable between this port and the 9 pin “D” connector on the 4990A.
Set the DIP switches for serial communication per paragraph 3.3
If the 4990A responds, check the hardware (NIC, cable, hub) and check for a correct IP address,
subnet mask and gateway address.
16
ENDEVCO MODEL 4990A RACK
INSTRUCTION MANUAL
Once you have the correct IP address, subnet mask and gateway address displayed in the
Options window, set the DIP switches as follows:
POS S1
SWITCH
SETTING
1 OFF (ON for snoop mode) OFF
2 ON EDAS RX ßà back plane RX OFF
3 OFF OFF (ON for snoop mode)
4 OFF (ON for snoop mode) OFF (ON for snoop mode)
5 ON EDAS TX ßà back plane TX X
6 OFF X
7 X X
8 X OFF baud rate = 19.2 kbd
On the Options screen click on Test Rack. The following window will appear:
REMARK S2
SWITCH
SETTING
REMARK
Follow the instructions and click OK. The following window will be displayed while the computer
is establishing communications with the rack:
17
ENDEVCO MODEL 4990A RACK
INSTRUCTION MANUAL
If communication with the rack fails, the following window will be displayed:
Correct the errors and click OK.
If you suspect the Ethernet NIC, cable, or hub may be the cause of the failure:
Identify a vacant serial (COM) port on the host computer
Connect a serial (RS-232) cable between this port and the 9 pin “D” connector on the 4990A.
Set the DIP switches for serial communication per paragraph 4.3
If the 4990A responds, check the hardware (NIC, cable, hub) and check for a correct IP address,
subnet mask and gateway address.
18
ENDEVCO MODEL 4990A RACK
INSTRUCTION MANUAL
6. OPERATION
6.1 Connecting Sensors to OASIS 2000
6.1.1 Model 428 Two Channel PE/ISOTTRON Amplifier
Both channel 1 and channel 2 input connectors are BNC. If the cable termination is 10-32
Microdot, use the BNC to 10-32 Microdot adapter supplied with the Model 428 to make the
connection.
The analog output signals are available at the two BNC output connectors, and also at one of the
four 25-pin “D” connectors on the 4990A rack. Which connector depends on which slot the 428
board resides in. See paragraph 6.2.1 for pin assignments.
6.1.2 Model 433 Three Channel PE/ISOTRON Amplifier
All three input connectors are BNC. If the cable termination is 10-32 Microdot, use the BNC to
10-32 Microdot adapter supplied with the Model 433 to make the connection.
The analog output signals are available at the three BNC output connectors, and also at one of
the four 25-pin “D” connectors on the 4990A rack. Which connector depends on which slot the
433 board resides in. See paragraph 6.2.1 for pin assignments.
6.1.3 Model 436 Three Channel DC Amplifier
The Model 436 should warm up for one hour prior to taking data.
All three input connectors are 9 pin “D”. The input pin assignments are as follows:
• Pin 4: S- Sensor Signal Input (White wire of Endevco bridge)
• Pin 5: S+ Sensor Signal Input (Green wire of Endevco bridge)
• Pin 7: P+ Excitation Voltage (Red wire of Endevco bridge)
• Pin 8: P- Excitation Voltage (Black wire of Endevco bridge)
CAUTION: If remote sensing is NOT used, pin 7 and pin 1 must be shorted together and pin 8
and pin 6 must be shorted together to avoid damage to the sensor.
The analog output signals are available at one of the four 25-pin “D” connectors on the 4990A
rack. Which connector depends on which slot the 436 board resides in. See paragraph 6.2.1 for
pin assignments.
19
ENDEVCO MODEL 4990A RACK
INSTRUCTION MANUAL
6.1.4 Model 482 Eight Channel SMART MODAL/ISOTRON Amplifier
The eight SMART MODAL/ISOTRON inputs are connected to a 26 pin double density “D”
connector on the 482 module front panel.
The optional model 36019 Input Breakout Panel provides a one to one input connection interface
for up to 32 channels of Smart ISOTRON or Non-Smart Sensors connected to a maximum of
four OASIS Model 482 Smart ISOTRON Signal Conditioning Cards. This Input Breakout Panel
provides a quick-interface panel to attach BNC input connectors with minimal effort. The output of
this panel mates to the female double-density 26-pin subminiature input connectors of the Model
482 card.
Pin-assignments are as follows:
Pin Function
2 Signal 1
3 Return 1
5 Signal 2
6 Return 2
8 Signal 3
9 Return 3
11 Signal 4
12 Return 4
14 Signal 5
15 Return 5
17 Signal 6
18 Return 6
20 Signal 7
21 Return 7
23 Signal 8
24 Return 8
20
ENDEVCO MODEL 4990A RACK
INSTRUCTION MANUAL
All analog outputs are accessible via the two 9 pin “D” connectors on the 482 module front panel.
One of the eight ISOTRON outputs is directed, under software control, to the BNC connector on
the front panel for bank switching.
Due to the high number of outputs, the analog output signals are not available at any of the four
25-pin “D” connectors on the 4990A rack.
The optional model 36020 provides a one to one output connection interface panel for up to four
OASIS Model 482 amplifier cards. This output breakout panel provides an interface panel to
quickly attach BNC connectors for DMM’s, Oscilloscopes and follow-on instrumentation. The
input of this panel mates to the output of the female, 9-pin "D" connectors of the Model 482
Smart ISOTRON amplifier card.
6.2 Connecting the Analog Outputs
The analog outputs are available at the front of all the Model 400 series signal conditioning
modules except the Model 436. The analog outputs are available at one of the four 25 pin DB
connectors on the front of the Model 4990A Rack except the Model 482.
The optional model 36021 is a 24-Channel Breakout Panel that connects to the OASIS Rack
Model 4990A DB-25 output connectors, adapting them to convenient BNC connectors. This
Breakout Panel can be used to connect equipment such as oscilloscopes, data acquisition
systems, DMM’s etc., to the Endevco OASIS system rack Model 4990A. This 24-channel
Breakout Panel is an option when OASIS Model 428, 433 and 436 series cards are installed.
Note: Pin 7 of each DB25 connector is connected to CHASSIS GND.
Now that communication has been established between the computer and the rack you are ready
to configure and operate the amplifier cards.
22
ENDEVCO MODEL 4990A RACK
INSTRUCTION MANUAL
7. SAFETY
The following general safety precautions must be observed during all phases of operation,
service, and repair of this instrument. Failure to comply with these precautions or with specific
warnings elsewhere in this manual violates safety standards of design, manufacture, and
intended use of the instrument. ENDEVCO assumes no liability for the customer’s failure to
comply with these requirements.
7.1 Ground The Instrument
To minimize shock hazard, the instrument chassis and cabinet must be connected to an electrical
ground. The instrument is equipped with a three-conductor ac power cable. The power cable
must either be plugged into an approved three-contact electrical outlet or used with a threecontact to two-contact adapter with the grounding wire (green) firmly connected to an electrical
ground (safety ground) at the power outlet. The power jack and mating plug of the power cable
meet International Electrotechnical Commission (IEC) safety standards.
7.2 Do Not Operate In An Explosive Atmosphere
Do not operate the instrument in the presence of flammable gases or fumes. Operation of any
electrical instrument in such an environment constitutes a safety hazard.
7.3 Keep away from live circuits
Operating personnel must not remove instrument covers. Component replacement and internal
adjustments must be made by qualified maintenance personnel. Do not replace components with
the power cable connected. Under certain conditions, dangerous voltages may exist even with
the power cable removed. To avoid injuries, always disconnect power and discharge circuits
before touching them.
7.4 Do Not Service Or Adjust Alone
Do not attempt internal service or adjustment unless another person, capable of rendering first
aid and resuscitation, is present.
7.5 Do Not Substitute Parts Or Modify Instrument
Because of the danger of introducing additional hazards, do not install substitute parts or perform
any unauthorized modification to the instrument. Return the instrument to ENDEVCO for service
and repair to ensure that safety features are maintained.
7.6 Dangerous Procedure Warnings
Warnings, such as the example below, precede potentially dangerous procedures throughout this
manual. Instructions contained in the warnings must be followed.
23
Dangerous voltages, capable of causing death, are present in this
during normal operation
.
result in injury
or death to personnel.
instrument. Use extreme caution when handling, testing, and adjusting.
7.7 Safety Symbols
General Definitions of Safety Symbols Used On Equipment or In Manuals.
Instruction manual symbol: the product will be marked with this symbol
when it is necessary for the user to refer to the instruction manual in
!
order to protect against damage to the instrument
ENDEVCO MODEL 4990A RACK
INSTRUCTION MANUAL
WARNING
Protective conductor terminal. For protection against electrical shock
in case of a fault. Used wit h field wiring terminals to indicate the terminal
which must be connected to ground before operating the equipment.
DANGER
WARNING
CAUTION
7.8 Line Fuse
Verify that the correct line fuse is installed before connecting the line cord.
The DANGER sign denotes a hazard. It calls attention to an operating procedure,
practice, condition or the like, which could result in injury or death to personnel even
The WARNING sign denotes a hazard. It ca lls attention to an operating procedure,
practice, co ndition or the like, which, if not correctly performed or adhered to, could
The CAUTION sign d enotes a hazard. It calls attention to an operating procedure,
practice, condition or the like, which, if not correctly performed or adhered to, could
result in damage to or destruction of part or all of the product.
24
ENDEVCO MODEL 4990A RACK
INSTRUCTION MANUAL
100/115/230 VAC
50/60 Hz
3/3/1.5 A
CAUTION: For continuous protection
against fire replace with same type of
fuse only!
ACHTUNG: Zur Vermeidung von Brandgefahr darf die
Sicherung nur durch identischen Typ ersetzt werden!
ATTENTION: Afin d'éviter tous risques de feu,
n'utiliser que de fusible du même type!
PRECAUCION: Para proteccion contra fuego remplace
fusible con el mismo tipo de fusible solamente!
7.9 Troubleshooting Tips
To aid in troubleshooting the rack, access to the power supply and module interconnect PCB is
gained with the rear panel dropped down to the open position.
7.9.1 4990A or cards do not respond check:
250 V, 3A, T
Power applied to 4990A rack. Check fuse. Fan must be audible, air flow must be present.
LETHAL VOLTAGES ARE PRESENT AT THE POWER ENTRY MODULE. USE
EXTREME CAUTION WHEN PERFORMING THE NEXT STEPS
Check DC voltages inside on back plane. Jumpers W2/W4/W7/W8/W9 are labeled with their
appropriate voltages.
Serial cable/Ethernet cable connected?
Type of Ethernet cable to RJ-45 connector on front panel. Must be crossover when connecting
computer directly to the 4990A, straight when connecting the 4990A to hub or repeater.
Type of serial cable (straight TX = 2, RX = 3 at 4990A end), if null-modem cable is used, change
DIP switch S1 position 1 to ON. (See paragraph 4.3.)
Baud rate identical for OASIS 2000 software and for 4990A rack?
Check if card is plugged in properly. Connector must latch, LED must be on.
Check card function. When powered on, LED must go from OFF --> red --> green/red
(depending on fault status).
Cards will blink upon receiving serial data in the proper format.
7.9.2 Cards display/report fault status check:
Is a channel fault enabled for an unused channel?
WARNING
Are all inputs of enabled channels connected to a sensor?
Check break-out box connected to input connector!
Check sensor cable
Check voltage across ISOTRON sensor, must be 10VDC to 14VDC. (Models 482, 433, and 428
in ISOTRON mode)
25
Obtain fault status in OASIS 2000 software menu
7.9.3 No signal on output check:
If BNC output is used, check if proper channel is selected in OASIS 2000 menu. (Model 482)
Is the output cable connected to the proper 25 pin “D” output connector?
If card has just been powered on, exposed to extreme signal, or gain has just been switched, or
cable/sensor has just been connected wait 2 minutes for signal to settle down (ISOTRON
sensors)
ENDEVCO MODEL 4990A RACK
INSTRUCTION MANUAL
26
ENDEVCO MODEL 4990A RACK
INSTRUCTION MANUAL
8. ROUTINE MAINTENANCE AND HANDLING
8.1 Introduction
The OASIS 2000 is a self-contained electronic instrument that requires minimal maintenance.
The OASIS 2000 is designed to require no component-level repair by the user. However,
detailed schematics are available upon request.
The periodic maintenance function performed by the user is quality calibration. Any component
failures simply require the user to return the failed 4990A rack or 400 series amplifier to
ENDEVCO for repair/replacement.
Should a faulty unit be returned to Endevco, it is suggested that the original or equivalent
packaging be used. This will reduce damage to the equipment during shipment.
8.2 Factory Service
ENDEVCO maintains factory service repair for all ENDEVCO instruments. To obtain repair or
replacement of a defective instrument, place a call to ENDEVCO to obtain a return material
authorization number (RMA), then return the instrument to the factory at the following address:
ENDEVCO
30700 Rancho Viejo Road
San Juan Capistrano, CA 92675
TEL: 949-493-8181
FAX: 949-661-7231
Email: applications@endevco.com
Web Site: http://www.endevco.com
To return an instrument, please:
Ensure proper packaging, preferably the original shipping cartons.
Prepay shipping and insurance charges.
Attach the Return Material Authorization (RMA) number from ENDEVCO and include any
information that may be pertinent to the description of the failure/problem.
8.3 WARRANTY
ENDEVCO warrants each new electronic instrument to be free from defects in material and
workmanship. Please refer to the appropriate Warranty Policies for the terms and warranty
period. Instruments returned under warranty will be repaired or replaced at no charge, if the
failure is due to defective material or workmanship; and the unit is returned within the time period
and conditions of Endevco's warranty policy.
8.4 OUT-OF-WARRANTY RETURNS
Enclose a purchase order not to exceed $300.00, authorizing repair/calibration along with a full
explanation of the failure or symptoms observed to help in fixing the problem. The instrument
will be repaired/calibrated, returned and invoiced for the actual repair charges. If the instrument
27
ENDEVCO MODEL 4990A RACK
INSTRUCTION MANUAL
cannot be repaired for $300.00 or less, ENDEVCO will submit a written quotation for the cost of
the repair and/or replacement of the unit.
28
ENDEVCO MODEL 4990A RACK
INSTRUCTION MANUAL
9. ORDERING INFORMATION & ACCESSORIES
ENDEVCO Model 4990A must be specified in the following manner: 4990A-X
• 4990A-1 for Ethernet and RS232
• 4990A-2 for RS-232 only
Description Endevco Part No. Quantity Supplied
IEC 320 AC Power Cord EW599 1
Instruction Manual IM4990A 1
9.2 Model 400 Series Accessories
For a complete list of accessories and options refer to the following documents:
IMSW2000 Instruction Manual for the OASIS configuration software
IM428 Instruction Manual for the two channel PE/ISOTRON amplifier
IM433 Instruction Manual for the three channel PE/ISOTRON amplifier
IM436 Instruction Manual for the three channel DC amplifier
IM482 Instruction Manual for the eight channel SMART MODAL/ISOTRON amplifier
You will only receive the Instruction Manuals for the units you purchased. If you did not receive
these manuals please contact Endevco.
29
ENDEVCO MODEL 4990A RACK
INSTRUCTION MANUAL
APPENDIX A
Making Ethernet Twisted-Pair Patch Cables
The 10BASE-T media system uses two pairs of wires, which are terminated in an eight pin RJ-45
connector. A male RJ-45 plug is mounted on each end of the twisted pair cable. A female RJ-45
jack is integrated into the Ethernet hub or NIC. The transmit and receive data signals on each
pair of a 10BASE-T segment are polarized, with one wire of each signal pair carrying the positive
(+) signal, and the other carrying the negative (-) signal. A common error when connecting the
computer to a Model 4990A is to make the connection with the widely available "silver satin"
patch cable typically used to connect telephones to a telephone jack. The problem is that the
typical silver satin cable used for telephones does not have twisted wire pairs in it. This lack of
twisted pairs results in excessive signal crosstalk and can cause "phantom collisions." This
occurs because collisions are detected in twisted-pair Ethernet by the simultaneous occurrence
of signals on the transmit and receive wire pairs. Excessive crosstalk signals can look like
simultaneous traffic and can falsely trigger the collision detect circuit.
This can result in "late collisions," which are collisions that occur too late in the transmission of an
Ethernet frame. A normal collision results in the immediate retransmission of a frame by the
Ethernet interface. However, a late collision results in a lost frame that must be detected and
retransmitted by the application software. Retransmission by the application is a lot slower and
can lead to a severe loss of application performance over the network. This problem can be
avoided by using only twisted-pair patch cables rated for use in twisted-pair Ethernet systems.
The following table shows the RJ-45 connector pin assignments
Contact 10Base-T Signal
1 TD+ (Transmit Data)
2 TD- (Transmit Data)
3 RD+ (Receive Data)
4 Not used
5 Not used
6 RD- (Receive Data)
7 Not Used
8 Not Used
30
Loading...
+ hidden pages
You need points to download manuals.
1 point = 1 manual.
You can buy points or you can get point for every manual you upload.