Enda EI7412-230VAC-AS24, EI7412-24VAC-AS24, EI7412-SM-AS24, EI7412-230VAC-AS12, EI7412-24VAC-AS12 User guide

...
english
Read this document carefully before using this device. The guarantee will be expired by damaging of the device if you don't attend to the directions in the user manual. Also we don't accept any compensations for personal injury, material damage or capital disadvantages.
ENDA EI7412 PROGRAMMABLE INDICATOR WITH RELAY
Thank you for choosing ENDA EI7412 INDICATOR.
* 72x72mm sized. * 4 digits display. * On-offcontrol. * Relays for Out and Alarm control. * Up and low limits of Set values can be configured. * Decimal point can be adjusted between 1. and 3. digits. * Display scale can be adjusted between -1999 and 4000. * Measurement unit can be displayed. * Selectable four different standart input types (0-20mA, 4-20mA, 0-1V, 0-10V). * User can calibrate the device according to his/her own specified input type. * Sampling time can be adjusted in four steps. * Selectable control option below and above the set value. * Selectable independent, deviation or band alarms. * Maximum and minimum values are registered and can be hold on the display. * Current and voltage calibration can be made. * Selectable parameter access protection. * CE marked according to European Norms.
Order code : EI7412--
1 2
1 - Supply Voltage
230VAC...230V AC
24VAC.....24V AC
SM...........9-30V DC / 7-24V AC
2 - Auxilary Supply OUT
AS24.....24V DC 50mA
AS12.....12V DC 50mA
AS08.....8V DC 50mA
AS05.....5V DC 50mA
None.......No auxilary supply out
TECHNICAL SPECIFICATIONS
ENVIRONMENTAL CONDITIONS
Ambient/storage temperature Max. relative humidity
Rated pollution degree
Height
Do not use the device in locations subject to corrosive and flammable gases.
ELECTRICAL CHARACTERISTICS
Supply
Power consumption Wiring Date retention EMC Safety requirements
Input type
0-1V DC voltage 0-10V DC voltage 0-20mA DC current 4-20mA DC current
In the current measurement mode input impedance is 5W. Therefore, in the current measurement mode, any voltage input should not be connected to the input terminals. Otherwise, the device will be broken down. To change the input type from voltage to a current measurement mode while the device is operating, first, leave out the voltage inputs. Then, change input type to one of the current measurement modes.
OUTPUTS
Auxilary power supply Out Alarm
Life expectancy for relay
CONTROL
Control type Control algorithm Hysteresis
HOUSING
Housing type
Weight
Enclosure material
up to date: 01092009, modification reserved and can be change any time previous notice !
While cleaning the device, solvents (thinner, benzine, acid etc.) or corrosive materials must not be used.
0 ... +50°C/-25 ... +70°C (with no icing) 80% up to 31°C decreasing linearly 50% at 40°C. According to EN 60529 Front panel : IP65
Rear panel : IP20
Max. 2000m
230VAC +10%/-20%, 50/60Hz, 24VAC±10%,50/60Hz or 24Vac/dc (9-30Vdc or 7-24Vac)
Max. 7VA
2.5mm² screw-terminal connections
EEPROM (Min. 10 years) EN 61326-1: 1997, A1: 1998, A2: 2001 (Performance criterion B for the EMC standard) EN 61010-1: 2001 (pollution degree 2, overvoltage category II, measurement category I)
EI7412 must not be used in location where measurement category is II, III or IV.
Measurement range
Min.
0V 0V 0mA 0mA
Max.
1.1V 14V 25mA 25mA
All auxilary power supplies supply maximum 50mA (Regulated and isolated) Relay: 250V AC, 8A (for resistive load), NO; 1/2 HP 240V AC CosF = 0.4 (for inductive load)
Relay: 250V AC, 8A (for resistive load), NO; 1/2 HP 240V AC CosF = 0.4 (for inductive load) Mechanical 30.000.000 operation; 100.000 operation at 250V AC, 8A resistive load.
Single set-point and alarm control On-Off control
Adjustable between 1 ... 200
Suitable for flush-panel mounting according to DIN 43 700. W72xH72xD97mm
Approx. 350g (after packaging) Self extinguishing plastics.
Measurement accuracy
±0,5% (of full scale) ±0,5% (of full scale) ±0,5% (of full scale) ±0,5% (of full scale)
Input empedance
Approx. 11kW (terminal voltage limits: min. = -2V, max. = 30V) Approx. 11kW (terminal voltage limits: min. = -2V, max. = 30V) Approx. 5W (applicable terminal voltage is max. 50mA.) Approx. 5W (applicable terminal voltage is max. 50mA.)
EI 7412
OUT
SET
OSET
ENDA
ALR
MAX
ASET
PROGRAMMABLE INDICATOR
MIN
SURAN Industrieelektronik
Dettinger Str. 9 / D-72160 Horb a.N
Tel.: +49 (0)7451 / 625 617 Fax: +49 (0)7451 / 625 0650
E-mail : info@suran-elektronik.de Internet : www.suran-elektronik.de
1./4 EI7412-E
Run mode
1000
SET
&
ASET
OSET
Measured value
SET
SET
If first and then keys are pressed together programming mode is entered
OSET
OSET
SET
OSET
While holding key out set value flashes and by using keys the value can be adjusted.
Out set value changes fastly if increase or decrease key is pressed for 0.6 second.
500
Out set value
ASET
ASET
SET
OSET
OSET
SET
MIN
499
Out set value Out set value
Programming mode
out.
MIN
o.HYS. = Out hysteresis value.
o.Hys.
MAX
o.StA.
MAX
o.UP.L.
MAX
o.lo.L.
Can be adjusted between 1 and 200. See NOTE 1 for programming.
MIN
o.StA. = State of out. If H1 is selected then out output is energized above the out setpoint . If Lo is selected then out output is energized below the out setpoint . See NOTE 1 for programming.
MIN
o.UP.L = Out value upper limit. Can be adjusted between out value lower limit (o.lo.l.) and upper limit for scale (H.SCL.). See NOTE1 for programming.
MIN
o.lo.L. = Out value lower limit. Can be adjusted between lower limit for scale (L.SCL.) and out value upper limit (o.UP.l.) See NOTE1 for programming.
NOTE 1
L.SCL.
While holding key out set value flashes and by using keys the value can be adjusted.
If increment key is pressed and held 0.6 seconds, the value of the selected parameter changes rapidly.
If waited enough, the value increases 100 at each step. After 1 second following the release of the key, initial condition is returned. The same procedure is valid for the decrement key.
OSET
ASET
Parameter adjustment method
SET
1000
OSET
SET
MAX
SET
OSET
Alr.
MIN
a.HYS.
MAX
A.typ.
MAX
a.sta.
MAX
A.UP.L.
MAX
A.Lo.L.
MIN
ASET
A.HYS. = Alarm hysteresis value. Can be adjusted between 1 and 200. See NOTE 1 for programming.
MIN
A.tyP. = Function of alarm output. Three kinds of functions can be selected.
IndE = Independent. De = Deviation. band = Band.
See NOTE 1 for programming.
MIN
A.Sta. = State of alarm output. If independent or deviation alarm is selected the alarm output can be Lo and HI. For Lo, alarm output is energized below the alarm setpoint. For HI, alarm output is energized above the alarm setpoint. If band alarm is selected this parameter can be bI.HI and bo.HI. For bI.HI, alarm output is energized between the band. For bo.HI, alarm output is energized out of the band. See NOTE1 for programming.
MIN
a.UP.L. = Alarm value upper limit. Can be adjusted between higher limit for scale (H.SCL.) and alarm value lower limit (a.Lo.L.). See NOTE1 for programming.
MIN
a.Lo.L. = Alarm value lower limit. Can be adjusted between lower limit for scale (L.SCL.) and alarm value upper limit (a.UP.L.).
SET
999
MAX
OSET
MIN
MAX
1000
SET
MAX
OSET
MAX
MIN
500
Page 3/4
Page 3/4
SET
OSET
d.Cnf.
MIN
i.typ.
MAX
dsp.C.
MAX
rate
MAX
Hold
MAX
Unit
i.typ. = Input type.
Input type can be selected as 0-20mA, 4-20mA, 0-1V or 0-10V. See NOTE 1 for programming.
MIN
dSP.C. = Display configuration. Selectable as PrcS. or Pr.Un. . If PrcS. is selected, process value appears. If Pr.Un. is selected, process value and then measurement unit are displayed 4 and 2 seconds successively. See NOTE 1 for programming.
MIN
RAtE = Sampling rate. Measurement is performed at each 200ms. However, for FASt rate, each measurement is displayed. for SLo.1 rate, the average of 4 successive measurements is displayed. for SLo.2 rate, the average of 8 successive measurements is displayed. for SLo.3 rate, the average of 16 successive measurements is displayed. See NOTE 1 for programming.
MIN
Hold = Display holding parameter. Selecting NonE , this parameter becomes inactive. Selecting Lo. , always the minimum measured value is displayed. Selecting Hi. , always the maximum measured value is displayed.
MIN
Unit = Measurement unit. A constant, a message etc. to be displayed can be entered. If a decimal point is desired, it should be included before entering the character.
For including decimal point first, then,
keys are pressed and held together. And
MAX
then, by using key decimal point can be adjusted.
ASET
SET
OSET
MIN
NOTE 2
CAL.
CAL okey?
C.end
s.err.
C.err.
NOTE 3
The message on the left flashes approximately 5 seconds and calibration is completed.
No
Yes
s.err.
If calibration is error free, the message
C.End appears for 1 seconds. However,
if it is wrong, the message S.Err. appears for 1 seconds and the program is shifted to the next step.
CAL.
CAL okey?
C.end
The message on the left flashes approximately 5 seconds and calibration is completed.
No
Yes
C.err.
If calibration is error free, the message
C.End appears for 1 seconds. However,
if it is wrong, the message C.Err. appears for 1 seconds and the program is shifted to the next step.
ERROR MESSAGES
If the difference between the reference voltages or currents applied for the calibration of H.inP. and L.inP. is lower than one half of the full scale, this error message appears on the display. For example: Assume that the selected input type is 0-1V. In this case, if the difference between the reference voltages applied for calibration of H.inP.and L.inP. is lower than 0.5V, this error message appears.
If the reference voltage or current applied to the input for calibration is too high or too low, this error message appears.
2./4 EI7412-E
Page 2/4
Run mode
1000
ASET
Alarm set value
While holding key alarm set value flashes and by using keys the value can be adjusted.
Alarm set value changes fastly if increase or decrease key is pressed for 0.6 second.
SET
OSET
ASET
MIN
999
Alarm set value
ASET
MAX
MAX
MIN
1000
Alarm set value
MAX
Res.
If first and then keys
&
MIN
MAX
are pressed together, the maximum and the minimum measurement values become equal to the measured value at that time and the message Res. appears on the display.
MIN
Page 2/4
No
U.opt.
MIN
Cal.t.
MAX
d.pnt.
MAX
l.sCl.
MAX
H.sCl.
MIN
CAL.t.=U.ýnP.
Yes
l.inp.
MAX
H.inp.
ASET
CAL.t. = Calibration type. Selectable as S.inP. or U.inP. If S.inp. is selected, input type is one the four standard input types. If U.inP is selected, input types can be modified. See NOTE 1 for modification.
MIN
d.Pnt. = Decimal point. Decimal point can be adjusted between
1. and 3. digits. See NOTE 1 for programming.
MIN
L.SCL. = Lower limit for the scale. It can be adjusted between -1999 and (H.SCL. -100). See NOTE 1 for programming.
MIN
H.SCL. = Upper limit for scale. It can be adjusted between (L.SCL. +100) and 4000. See NOTE 1 for programming.
At this state, the reference voltage or current that corresponds to L.SCL. parameter is applied to the input. To initialize calibration, first then
keys are pressed together and held until ‘CAL' message appears. See NOTE 2.
MIN
At this state, the reference voltage or current that corresponds to H.SCL. parameter is applied to the input. To initialize calibration, first then
keys are pressed together and held until ‘CAL' message appears. See NOTE 2.
SET
OSET
SET
OSET
Programming mode
d.Cal. SeCU.
MIN
s.Cod. = Access code for calibration
S.Cod.
MAX
a.CAL.
MAX
1.CA.
MAX
10.CA.
MAX
MAX
menu. This parameter should be 222. See NOTE 1 for programming.
MIN
A.CAL. = Current calibration. At this state, 20.000 mA current is applied to the input of the device.
For initializing calibration, first then
keys are pressed together and held until ‘CAL' message appears. See NOTE 3.
MIN
1.CA. = 1V input calibration. At this state, 1.0000V is applied to the input of the device.
To initialize calibration, first then
keys are pressed together and held until ‘CAL' message appears. See NOTE 3.
MIN
10.CA. = 10V input calibration. At this state, 10.000V is applied to the input of the device.
To initialize calibration, first then
keys are pressed together and held until ‘CAL' message appears. See NOTE 3.
ASET
SET
OSET
MAX
SET
OSET
MAX
SET
MAX
OSET
MIN
S.Cod.
MAX
MIN
ou.sC.
MAX
MIN
AL.sC.
MAX
MIN
D.C.sC.
MAX
MIN
Uo.sC.
MAX
MIN
D.Ca.s.
ASET
s.Cod. = Access code for safety menu.
This parameter should be 333. See NOTE 1 for programming.
ou.SC. = out. menu protection level parameter.
nonE = No menu is seen. P. no = Menu is seen but can not be
programmed. P.yES. = Menu is seen and programming is possible. See NOTE 1 for programming.
AL.SC. = ALr. menu protection level param.eter.
nonE = No menu is seen. P. no = Menu is seen but can not be
programmed. P.yES. = Menu is seen and programming is possible. See NOTE 1 for programming.
d.C.SC. = ConF. menu protection level parameter.
nonE = No menu is seen. P. no = Menu is seen but can not be
programmed. P.yES. = Menu is seen and programming is possible. See NOTE 1 for programming.
Uo.SC. = U.oPt. menu protection level parameter.
nonE = No menu is seen. P. no = Menu is seen but can not be
programmed. P.yES. = Menu is seen and programming is possible. See NOTE 1 for programming.
d.CA.S. = d.CAL. menu protection level parameter.
nonE = No menu is seen. P. no = Menu is seen but can not be
programmed. P.yES. = Menu is seen and programming is possible. See NOTE 1 for programming.
Independent alarm A.tyP.=indE
ON
OFF
ON
OFF
HyS.A.
ASV
OSV = Out set value ASV = Alarm set valuei
Deviation alarm A.tyP.= dE.
OSV
HyS.A.
OSV+ASV
ON
A.StA.= Hi
OFF
ON
OFF
A.StA.= Lo
Band alarm A.tyP.= bAnd
HyS.A.
OSV-ASV
OSV
HyS.A.
OSV+ASV
ON
OFF
ON
OFF
A.StA.= Bo.Hi.
A.StA.= Bi.Hi.
Run mode Error messages
- - - -
Measured value is below scale
L.inp.
L.inp.
Input voltage or input current is below zero
H.inp. H.inp.
Input voltage is above 14V or input voltage is above 25mA
3./4 EI7412-E
TERMS
EI 7412
OUT
SET
OSET
ENDA
( 1 ),( 2 ) Out and Alarm LED ( 3 ) Digital display
Character height
( 4 ),( 5 ),( 6 ),( 7 ) Key pad
DIMENSIONS
EI 7412
OUT
72mm
78mm
ENDA
SET
OSET
ASET
ALR
MAX
ASET
PROGRAMMABLE INDICATOR
MIN
3mm bright red LED 4 digits 7 segment red LED display
14.2mm
Mikro switch
ALR
MAX
PROGRAMMABLE INDICATOR
MIN
1) Shows out status.
2) Shows alarm status.
3) Shows measurement value, measurement unit and maximum and minimum measured values. (Run mode) Shows name, value and unit of parameters. (Programming mode)
4) Shows maximum measured value. (Run mode) Increases value or adjusts parameter. (Programming mode)
5) Shows minimum measured value. (Run mode) Decreases value or adjusts parameter. (Programlama modu)
6) Shows alarm set value. (Run mode) Menu selection key. (Programming mode)
7) Shows out set value. (Run mode) Parameter adjustment key. (Programming mode)
Depth
Panel cut-out
97mm
2
+0.7
+0.7
68 mm
68 mm
75mm
Flush mounting
clamp
Panel
Rubber packing
CONNECTION DIAGRAM
1
2
3
+
GND
4
5
6
ENDA
EI7412-230VAC-AS24 INDICATOR
ALARM AC 250V 8A RESISTIVE LOAD
AUXILIARY SUPPLY OUT 24V 50mA
OUT AC 250V 8A RESISTIVE LOAD
INDUSTRIAL ELECTRONICS
230V AC +10% -20% 50/60Hz 7VA
84mm
Connection cables
For removing mounting clamps:
- Push the flush-mounting clamp in direction 1 as shown in the figure left.
- Then, pull out the clamp in
2
direction 2.
7
1
230V AC +10% -20% 50/60Hz 7VA
SN: XXXXXXXXX
INPUT
GND
ALARM AC 250V 8A RESISTIVE LOAD
8
2
+
9
3
10
4
5
OUT AC 250V 8A RESISTIVE LOAD
6
INDUSTRIAL ELECTRONICS
ENDA
EI7412-24VAC INDICATOR
24V AC ±10% 50/60Hz 7VA
SN: XXXXXXXXX
Note 1) While panel mounting, additional distance required for connection cables should be considered.
2) Panel thickness should be maximum 10mm.
3) If there is no 90mm free space at back side of the device, it would be difficult to remove it from the panel.
INPUT
GND
SN: XXXXXXXXX
7
1
ALARM AC 250V 8A RESISTIVE LOAD
8
2
+
9
3
+
AUXILIARY SUPPLY OUT 8V 50mA
10
GND
4
5
OUT AC 250V 8A RESISTIVE LOAD
6
INDUSTRIAL ELECTRONICS
ENDA
EI7412-SM-AS08 INDICATOR
7
1
ALARM AC 250V 8A RESISTIVE LOAD
8
2
+
9
INPUT
3
+
AUXILIARY
GND
SUPPLY OUT 24V 50mA
10
GND
4
5
OUT AC 250V 8A RESISTIVE LOAD
6
INDUSTRIAL ELECTRONICS
ENDA
EI7412-24VAC-AS05 INDICATOR
24V AC ±10% 50/60Hz 7VA
SN: XXXXXXXXX
7
ALARM
9-30V DC / 7-24V AC
AC 250V 8A
±10% 7VA
RESISTIVE LOAD
2
8
+
9
3
INPUT
GND
10
4
5
OUT AC 250V 8A RESISTIVE LOAD
6
INDUSTRIAL ELECTRONICS
ENDA
EI7412-SM INDICATOR
1
1
2
3
+
GND
4
5
6
ENDA
EI7412-230VAC-AS12 INDICATOR
1
ALARM AC 250V 8A RESISTIVE LOAD
AUXILIARY SUPPLY OUT 12V 50mA
OUT AC 250V 8A RESISTIVE LOAD
INDUSTRIAL ELECTRONICS
1
ENDA EI7412 is intended for installation in control panels. Make sure that the device is used only for intended purpose. The shielding must be grounded on the instrument side. During an installation, all of the cables that are connected to the device must be free of energy. The device must be protected against inadmissible humidity, vibrations, severe soiling and make sure that the operation temperature is not exceeded. All input and output lines that are not connected to the supply network must be laid out as shielded and twisted cables. These cables should not be close to the power cables or components. The installation and electrical connections must be carried on by a qualified staff and must be according to the relevant locally applicable regulations.
7
8
+
9
INPUT
GND
10
SN: XXXXXXXXX
9-30V DC / 7-24V AC ±10% 7VA
SN: XXXXXXXXX
7
8
+
9
INPUT
GND
10
NOTE :
SUPPLY :
Line
184-253V AC 50/60Hz 7VA
1) Mains supply cords shall meet the requirements of IEC 60227 or IEC 60245.
Note :
2) In accordance with the safety regulations, the power supply switch shall bring the identification of the relevant instrument and it
7
Neutral
8
Fuse
F 100 mA
250V AC
Fuse should be connected
Switch
230V AC Supply
Cable size: 1,5mm²
Holding screw
0.4-0.5Nm
Equipment is protected throughout by DOUBLE INSULATION.
should be easily accessible by the operator.
4./4 EI7412-E
Loading...