ENDA EDT1411P User Manual

Technical Specifications
Supply voltage
230V AC +10% -20% or 12/24V AC/DC ±10%, 50/60Hz or 9-30V DC / 7-24V AC ±10%.
Power consumption
Max. 4VA
2.5mm² screw-terminal connections.
(±1%-15sec) for hour unit, (±1%-1sec) for minute unit 4 digits, 12.5mm, 7 segment yellow LED
Time Accuracy Indicator EMC
Safety requirements
The device is designed to operate in controlled electromagnetic environment)
EN 61326-1: 1997, A1: 1998, A2: 2001 (Performance criterion B is satisfied for EMC tests.
EN 61010-1: 2001 (Pollution degree 2, overvoltage category II)
CONTROL
Control type
Single-setpoint control On-Off control
Control algorithm Hysteresis
Adjustable between 0.1 ... 20.0°C.
ELECTRICAL CHARACTERISTICS
ENVIRONMENTAL CONDITIONS
Height
Max. 2000m
80 , up to 40% 31°C decreasing linearly 50% at °C
Ambient/storage temperature Max. relative humidity
0 ... +50°C/-25 ... 70°C (with no icing)
-50.0 ... +110.0°C (-58.0 ... +230.0°F)
0.1°C / ±1°C
Rated pollution degree
According to EN 60529 Front panel : IP65
Rear panel : IP20
Do not use the device in locations subject to corrosive and flammable gasses.
HOUSING
Housing type
Suitable for flush-panel mounting.
Dimensions
W77xH35xD71mm
Weight
Approx. 250g (Equipment and prob a ) fter packing
Enclosure material
Self extinguishing plastics
ENDA EDT1411P TEMPERATURE CONTROLLER
Thank you for choosing ENDA EDT1411 temperature controller.
Connection Diagram
ENDA EDT1411 is intended for installation in control panels. Make sure that the device is used only for intended purpose. The electrical connections must be carried out by a qualified staff and must be according to the relevant locally applicable regulations. During an installation, all of the cables that are connected to the device must be free of electrical power. The device must be protected against inadmissible humidity, vibrations, severe soiling and make sure that the operation temperature is not exceeded. The cables should not be close to the power cables or components.
1/3
SÝSEL MÜHENDÝSLÝK ELEKTRONÝK SAN. VE TÝC. A.Þ. Yukarý Dudullu Barbaros Cad. Kutup Sok. No:20 34775 - ÜMRANÝYE/ÝSTANBUL/TURKEY Tel : +90 216 499 46 64 Pbx. Fax : +90 216 365 74 01 url : www.enda.com.tr
Panel cut-out
Dimensions
Note :
1) Panel thickness
should be maximum 7 mm.
2) If there is no 60mm
free space at the back side of the device, it would be difficult to remove it from the Panel.
EDT1411P-E-01-R
Holding screw
0.4-0.5Nm.
Equipment is protected throughout by DOUBLE INSULATION
71mm
29mm
Flush mounting
clamp
For removing mounting clamps:
Push the flush-mounting clamp in direction 1 as shown in the figure below. Then, pull out the clamp in direction 2.
1
While cleaning the device, solvents (thinner, benzine, acid etc.) or corrosive materials must not be used.
4 5
SUPPLY:
NOTE:
184-253V AC 50/60Hz 4VA
Line
Neutral
230V AC Supply
Switch
Note:
Cable size: 1,5mm²
Fuse
F 100 mA
250V AC
Fuse should be connected
1) Mains supply cords shall meet the requirements of IEC 60227 or IEC 60245.
2) In accordance with the safety regulations, the power
supply switch shall bring the identification of the relevant instrument and it should be easily accessible by the operator.
Ple
a
s
e re
ad
th
is
d
oc
u
me
nt
c
ar
e
f
u
ll
y be
fo
re
us
in
g
th
is
p
rod
uc
t
.
T
h
e g
ua
ran
te
e w
ill be
in
va
li
da
te
d
if
the
d
e
vi
ce
is
da
mag
ed
by
no
t fo
ll
ow
in
g
in
s
t
ruc
tio
n
s
de
ta
il
ed in
t
he
man
ua
l. Th
e c
omp
a
ny
s
h
a
ll
n
ot
b
e
r
es
po
n
sib
le
f
or
an
y
da
m
ag
e
or
lo
ss
e
s
ho
we
v
e
r
cau
se
d,
w
h
ic
h
may
b
e
e
xpe
ri
e
n
ce
d
as
a
re
su
lt
of th
e
in
st
al
la
ti
on
or use
of t
h
is
p
ro
du
ct.
Flush mounting
clamp
Depth
Panel
2
71mm
5mm
Rubber packing
35mm
77mm
SET
SET
EDT1411
ENDA
°F
°C
Order Code
Output
Supply Voltage
EDT1411-NTC-230P
Röle -16A
230V AC +%10 -%20 24V AC %10±
EDT1411-NTC-24P
9-24V AC/DC %10±
EDT1411-NTC-12P
* 35 x 77mm sized. * On-Off control. * Single contact output for cooling control. * Single NTC probe input. * Offset value can be entered for NTC probe. * Compressor protection parameters can be entered. * In the case of probe failure, output state can be selected on, off or periodical running. * Upper and lower limits of the setpoint can be adjusted. * Defrosting duration and interval can be adjusted. * Temperature unit can be selected °C or °F. * Upper and lower limits of the alarm value can be adjusted depending on the setpoint value. * CE marked according to European Norms.
SET
SET
EDT1411
ENDA
°F
°C
SN: XXXXXXXXX
1 2 3 4 5 6
7 8 9
10
11 12
EDT1411-NTC-230VAC-P DIGITAL DEFROST THERMOSTAT
ENDA INDUSTRIAL ELECTRONICS
230V AC +10% -20%
50/60Hz 4VA
COMPRESSOR
240V AC 16A
RESISTIVE LOAD
NTC
SENSOR
SN: XXXXXXXXX
1 2 3 4 5 6
7 8 9
10
11 12
EDT1411-NTC-24VAC-P DIGITAL DEFROST THERMOSTAT
ENDA INDUSTRIAL ELECTRONICS
24V AC ±10%
50/60Hz 4VA
COMPRESSOR
240V AC 16A
RESISTIVE LOAD
NTC
SENSOR
SN: XXXXXXXXX
1 2 3 4 5 6
7 8 9
10
11 12
EDT1411-NTC-SM-P DIGITAL DEFROST THERMOSTAT
ENDA INDUSTRIAL ELECTRONICS
COMPRESSOR
240V AC 16A
RESISTIVE LOAD
NTC
SENSOR
9-30V DC / 7-24V AC
10% 4VA±
SN: XXXXXXXXX
1 2 3 4 5 6
7 8 9
10
11 12
EDT1411-NTC-230VAC-P
DIGITAL DEFROST THERMOSTAT
ENDA INDUSTRIAL ELECTRONICS
230V AC +10% -20%
50/60Hz 4VA
COMPRESSOR
240V AC 16A
RESISTIVE LOAD
NTC
SENSOR
OUTPUT
COMPRESSOR
For EDT1411-NTC-XXP ; Relay: 240V AC, 8A (for resistive load), NO; 1 HP 230V AC CosF = 0.5 (for inductive load)
For EDT1411-NTC-XXP ; Mechanical 30.000.000 operation. (None load) 240V AC ,16A in the resistive load 30.000 operation.
Life expectancy for relay
SET
SET
EDT1411
ENDA
°F
°C
While holding key COMPRESSOR setpoint value appears and by using and keys the value can be adjusted.
Running Mode
Process Value
-30.0
-29.9
-30.0
1000
If both keys are pressed and held for 3 seconds, programming mode is entered.
-22.0
If both keys are pressed, run mode is entered.
Used for adjusting the value of the setpoint in the run mode and for adjusting the selected parameter in the programming mode. While holding key, setpoint value of the selected parameter appears and by using and keys the value can be adjusted.
When held down for 3 second in the run mode, manual defrost starts. After the specified time with D.dur parameter manual defrost finishes. When held down for 3 second manual defrost finishes before the specified time ends. Used for selecting menu and increasing setpoint value of the parameters in the programming mode and for increasing the setpoint value in the run mode. When held down for a few seconds, the change rate accelerates.
When held down for 3 second in the run mode continuous mode (*) starts. After the specified time with C.Con parameter this mode finishes. When held down for 3 second continuous mode finishes before the specified time ends. Used for selecting parameters and decreasing the setpoint value in the programming mode and for decreasing the setpoint value in the run mode. When held down for a few seconds, the change rate accelerates.
DEFROST LED
COMPRESSOR LED
FAHRENHEIT LED
Displayed process value in the run mode, parameter name or value in programming mode.
SET
SET
SET
SET
A.lol
A.uPl
A.Set
A.dpo
The lower limit of the setpoint.
Delay time for the compressor after power is on.
Defrosting duration.
Limit for lower alarm level.
Limit for upper alarm level
Alarm configuration.
Energy was given the message of alarm delayed to show.
The upper limit of the setpoint.
Delay time required for compressor to restart following a stop.
Compressor’s on the continuous on mode length of stay.
Refrigeration differential (hysteresis).
In the probe failure,compressor’s output on duration.
Refrigeration offset value.
Display resolution.
In the probe failure,compressor’s output off duration.
D.dur
D.int
C.pon
C.ppn
C.Con
C.Fos
C.ppF
Interval between defrost cycles.
Programming mode
R.lol
R.uPl
R.Hys
R.off
DrES
EDT1411P-E-01-R
Temperature unit.
Unit
During the defrosting display configuration.
D.dsp
D.drE
Delay time for display real temperature after defrost is over.
Defrosting the process of energy and the start of.
D.Pon
D.dPo
Defrosting’s delayed starting after power is on.
A.dFl
Situation of alarm after the were formed alarm message delayed to show.
A.HYS
Alarm diffrerential (hysteresis).
Security parameter for compressor control menu.
Security parameter for defrosting control menu.
Security parameter for alarm control menu.
Security parameter for refrigeration set value.
A.-re
A.-al
A.-de
A.-Cp
A.rE.S.
Security parameter for refrigeration menu.
RE
CP
DE
Al
SE
2/3
S.Cod
Access code for security menu.This parameter should be 321.
On the side on display at sight message,thermostat probe is short circuit or measured temperature value is higher than the scale.
On the side on display at sight message, measured value is higher than the upper alarm value.
Error Messages
On the side on display at sight message,measured value is lower than the lower alarm value.
Alo
Ahi
Pfa
PsC
On the side on display at sight message,thermostat probe is broken or measured temperature value is lower than the scale.
Loading...
+ 1 hidden pages