EMS ZITON RADIO LOOP MODULE Programming Manual

ZITON RADIO LOOP MODULE
PROGRAMMING
MANUAL
Table of Contents
Section Page No
1.0 INTRODUCTION .................................................................................... 3
1.1 System Design...................................................................................... 3
1.2 Handling Precautions ............................................................................. 3
1.3 Packaging: ........................................................................................... 3
2.0 MENU STRUCTURE ................................................................................ 4
2.1 Menu Structure Layout........................................................................... 4
3.0 MENU EXPLANATION ............................................................................. 5
3.1 Device Status ....................................................................................... 5
3.2 Add New device .................................................................................. 12
3.3 Remove device ................................................................................... 13
3.4 Interface Status ................................................................................. 13
3.5 Radio Channels .................................................................................. 14
4.0 FRONT DISPLAY OF RADIO LOOP MODULE ............................................ 14
5.0 ACCESSING THE RADIO LOOP MODULES MENUS ................................... 14
5.1 Viewing the Device Status ................................................................... 15
5.2 Output Test ........................................................................................ 19
5.3 Adding New Devices to the System....................................................... 20
5.4 Removing Device from the System ....................................................... 21
5.5 Viewing the Radio Loop Module Status .................................................. 22
5.6 Radio Channels .................................................................................. 23
Tel: +44 (0) 1227 369570 Fax: +44 (0) 1227 369679 Email: enquiries@emsgroup.co.uk Website: www.emsgroup.co.uk
Ziton Radio Loop Module Programming Manual (Issue 7d) TSD022
EMS Group Head Office, Technology House, Sea Street, Herne Bay, Kent CT6 8JZ, England
2
1.0 INTRODUCTION
This manual provides a programming guide for the Ziton Radio Loop Module.
The Ziton Radio Loop Module comprises of a radio transceiver capable of receiving 31 radio devices. An LCD display is provided along with function buttons to allow programming and diagnostics to be carried out for associated devices.
The Ziton Radio Loop Module is capable of connection to a ZP Protocol Fire Alarm Control Panels Loop via its Loop in and out connection terminals. The Radio Loop Module is addressed on the loop via its onboard 8 way DIP switch. A total of 2 Radio Loop Modules can be fitted onto a Fire Alarm Control Panels Loop.
Compatible products for use with the Ziton Radio Loop Module are as follows;
Part Number – ZR485-3 Radio manual call point Part Number – ZR432-2 Radio multisensor detector Part Number – ZR455-3R Red radio sounder Part Number – ZR455-3W White radio sounder
Part Number – ZR455V-3RC Red radio sounder with clear beacon Part Number – ZR455V-3RR Red radio sounder and red beacon Part Number – ZR455V-3RA Red radio sounder with amber beacon Part Number – ZR451-3 Single input output unit
1.1 System Design
All installation work should be carried out in accordance with the survey and system design.
It is recommended that the Ziton Radio Loop Module and peripheral devices are located in accordance with the radio survey and system design. This should be established before installation work commences.
1.2 Handling Precautions
General; Care should be taken when handling Ziton Radio Loop Module. Avoid dropping any of the parts onto hard surfaces, as damage may occur to the case and internal circuitry.
ESD Precautions; Ziton Radio Loop Module includes components that are susceptible to damage from Electro-Static Discharge (ESD). Permanent damage may be caused to these components through routine handling if precautions are not observed. To reduce the risk of damage from ESD, the following precautions should be observed.
Minimise the handling of PCB’s which contain static sensitive devices. Where handling is unavoidable, always ensure that you have taken adequate earthing precautions. An earthed wrist strap is recommended.
When storing or transporting a “loose” PCB, always use a container, which has been designed and manufactured with ESD protective properties.
Avoid placing static sensitive devices on plastic surfaces, which may increase the risk of a static discharge.
1.3 Packaging:
All products should be kept in their packaging until they are due to be installed, to minimise the risk of damage. Retain all packaging until the installation activities have been completed. Should any product be found to be surplus to requirements, or require returning, the original packaging should be used.
Tel: +44 (0) 1227 369570 Fax: +44 (0) 1227 369679 Email: enquiries@emsgroup.co.uk Website: www.emsgroup.co.uk
Ziton Radio Loop Module Programming Manual (Issue 7d) TSD022
EMS Group Head Office, Technology House, Sea Street, Herne Bay, Kent CT6 8JZ, England
3
2.0 MENU STRUCTURE
The menu structure is shown below and is entered by pressing the Rotary Control button. Further menu options are entered by also pressing the Rotary Control button. To exit the menus the back button can be pressed or the menus will automatically exit one step at a time at 30 second time intervals.
2.1 Menu Structure Layout
Front Screen
Device Status
Add New Device
Remove Device
Interface Status
Radio Channel
Device Address
Fault Status
Alarm Status*
Battery Level
Signal Level
Manual Update
Ident
Software Version
Loop Address
Output Test**
Fault Status
Background Level
Ident
Software Version
Node Number **
Audio Detect **
Batt Smooth **
Serial Data **
Currently Used
Auto Select ***
Manual Select ***
Scan Time
First Channel
Second Channel
* Alarm Status shown as I/O Status for Input/Output Device types.
** Highlighted menu options are only available when switch 8 is ‘ON’. *** Menu Options only available when Radio Loop Module does not have any devices allocated to it.
Scan Time
First Channel
Second Channel
Tel: +44 (0) 1227 369570 Fax: +44 (0) 1227 369679 Email: enquiries@emsgroup.co.uk Website: www.emsgroup.co.uk
Ziton Radio Loop Module Programming Manual (Issue 7d) TSD022
EMS Group Head Office, Technology House, Sea Street, Herne Bay, Kent CT6 8JZ, England
4
3.0 MENU EXPLANATION
3.1 Device Status
This function allows the current status of the allocated devices on the Radio Loop Module to be viewed (Maximum of 31 devices). The devices are shown in the menu indicating their loop address number, its logged on status and the device type. Further information on the device can be obtained by pressing the Rotary Control button. This enables the following details to be viewed:- Fault status, Alarm Status, Battery Level, Signal Level, unique 5 digit ident number, software version and also allows a manual signal level update to take place.
A typical display is shown below;
Addr 067 L Multi
The descriptions for the shown display are as follows;
Addr 067 – In this example this indicates the devices loop address number which has been selected. Available options are between 1 and 127.
L – In this example this field indicates the devices logged on or fault status.
Available options are;
L= Logged On and in a normal condition. ! = Logged On with fault(s) present.
= Logged On with a fire alarm present.
= Logged On with a pre alarm present.
Multi – This field indicates the device type. Available options are:
Radio = Ziton Radio Loop Module Multi = Multisensor Detector Optic = Optical Detector Heat = Heat Detector HTemp = Heat Detector MCP = Manual Callpoint Sound = Sounder Device I/O = Input/Output Device ??? = Unknown Device
Further Device Status Information on the displayed device is available by pressing the Rotary Control button. This allows the following menus to be viewed;
Fault Status – this menu when entered, shows detailed information on the fault status of the device.
Note; If multiple faults are applicable to a device the rotary control can be turned to view the total fault listing and a down arrow will be present to indicate that there is more than one fault present
The available fault descriptions are described below;
Tel: +44 (0) 1227 369570 Fax: +44 (0) 1227 369679 Email: enquiries@emsgroup.co.uk Website: www.emsgroup.co.uk
Ziton Radio Loop Module Programming Manual (Issue 7d) TSD022
EMS Group Head Office, Technology House, Sea Street, Herne Bay, Kent CT6 8JZ, England
5
No Fault Present – this description indicates that the device is not in any fault condition and is operating correctly.
The analogue value seen on the Fire Alarm Control Panel in their normal status will vary depended upon the signal strength readings. The range of values is shown below:
Analogue
Value
Signal
Strength
GOOD
(Slot 5)
Analogue
Value
Signal
Strength
MEDIUM
(Slot 5)
Analogue
Value
Signal
Strength
LOW
(Slot 5)
Analogue
Value
Signal
Strength
CAUTION
(Slot 5) Detector 090 085 080 075 Manual Call Point 090 085 080 075 Sounder 090 085 080 075 Input/Output 090 085 080 075
In Tamper – this indicates that the devices tamper switch is not currently making contact against the ceiling or wall mounted base plate.
The analogue value seen on the Fire Alarm Control Panel for devices in this state is;
Analogue Value
(Slot 5) (Slot 6)
Detector N/A 181 Manual Call Point N/A 181 Sounder N/A 181 Input/Output N/A 181
Head Missing – this indicates that the detectors head is not currently fitted on the detector base.
The analogue value seen on the Fire Alarm Control Panel for devices in this state is;
Analogue Value
(Slot 3) (Slot 6)
Detector 244 118 Manual Call Point N/A N/A Sounder N/A N/A Input/Output N/A N/A
Sounder Missing – this indicates that the sounder, strobe only or sounder/strobe head is not currently fitted on the sounder base.
The analogue value seen on the Fire Alarm Control Panel for devices in this state is;
Analogue Value
(Slot 3) (Slot 6) Detector N/A N/A Manual Call Point N/A N/A Sounder 244 118 Input/Output N/A N/A
Tel: +44 (0) 1227 369570 Fax: +44 (0) 1227 369679 Email: enquiries@emsgroup.co.uk Website: www.emsgroup.co.uk
Ziton Radio Loop Module Programming Manual (Issue 7d) TSD022
EMS Group Head Office, Technology House, Sea Street, Herne Bay, Kent CT6 8JZ, England
6
Signal Fault – this indicates that there has currently not been any communication between the device and the Radio Loop Module for 300 seconds. This is indicated as an analogue value of 020 on the fire alarm control panel.
This will be shown on the Fire Alarm Control Panel as if the device had been removed from the system as it does not respond to polls on the loop i.e Disconnect fault.
The analogue value seen on the Fire Alarm Control Panel for devices in this state is;
Analogue Value
Slot 5 Slot 6
Detector 020 N/A Manual Call Point 020 N/A Sounder 020 N/A Input/Output 020 N/A
Battery Fault – this shows that the device has either a low battery and has a minimum operational life of 7- 30 days or has a battery missing.
The analogue value seen on the Fire Alarm Control Panel for devices with low batteries is;
Analogue Value
Slot 5 Slot 6
Detector N/A 213 Manual Call Point N/A 213 Sounder N/A 213 Input/Output N/A 213
The analogue value seen on the Fire Alarm Control Panel for devices with a battery missing is;
Analogue Value
Slot 5 Slot 6
Detector N/A 020 Manual Call Point N/A 020 Sounder N/A 020 Input/Output N/A 020
This will be shown as Idle High on the Fire Alarm Control Panel as if the device has a fault.
No Sndr Audio – this indicates that a sounder device has given no audio output or a low audio output when sounding. This is selectable via a DIP switch on the sounder head and must be disabled when using strobe only devices.
The analogue value seen on the Fire Alarm Control Panel for devices in this state is;
Analogue Value
Slot 3 Slot 6
Detector N/A N/A Manual Call Point N/A N/A Sounder 244 152 Input/Output N/A N/A
Tel: +44 (0) 1227 369570 Fax: +44 (0) 1227 369679 Email: enquiries@emsgroup.co.uk Website: www.emsgroup.co.uk
Ziton Radio Loop Module Programming Manual (Issue 7d) TSD022
EMS Group Head Office, Technology House, Sea Street, Herne Bay, Kent CT6 8JZ, England
7
Head Fault – this indicates that a detectors head has a fault i.e no communication between the head and the radio base.
The analogue value seen on the Fire Alarm Control Panel for devices in this state is;
Analogue Value
Slot 3 Slot 6
Detector 244 152 Manual Call Point N/A N/A Sounder N/A N/A Input/Output N/A N/A
Short Circuit – this indicates that an input has a short circuit wiring fault.
The analogue value seen on the Fire Alarm Control Panel for devices in this state is;
Analogue Value
Slot 5 Slot 6
Detector N/A N/A Manual Call Point N/A N/A Sounder N/A N/A Input/Output N/A 118
Open Circuit – this indicates that an input has a short circuit wiring fault.
The analogue value seen on the Fire Alarm Control Panel for devices in this state is;
Analogue Value
Slot 5 Slot 6
Detector N/A N/A Manual Call Point N/A N/A Sounder N/A N/A Input/Output N/A 118
Alarm Status – this menu when entered shows information on the current alarm status of the device. The available alarm descriptions are described below;
No Alarm Present – this indicates the device is currently not in an alarm or pre-alarm
condition.
In Fire – this indicates the device is currently in a fire alarm condition.
The analogue value seen on the Fire Alarm Control Panel for devices in this state is;
Analogue Value
Slot 5 Slot 6
Detector 181 N/A Manual Call Point 181 N/A Sounder N/A N/A Input/Output 213 N/A
Tel: +44 (0) 1227 369570 Fax: +44 (0) 1227 369679 Email: enquiries@emsgroup.co.uk Website: www.emsgroup.co.uk
Ziton Radio Loop Module Programming Manual (Issue 7d) TSD022
EMS Group Head Office, Technology House, Sea Street, Herne Bay, Kent CT6 8JZ, England
8
In Pre-Alarm – this indicates the device is currently in a Pre-alarm condition.
The analogue value seen on the Fire Alarm Control Panel for devices in this state is;
Analogue Value
Slot 5 Slot 6
Detector 152 N/A Manual Call Point N/A N/A Sounder N/A N/A Input/Output N/A N/A
I/O Status – this menu replaces the Alarm Status menu for Input/Output devices. When entered this shows information on the current status of the two inputs for the device. The available status descriptions are described below;
IN1: 0 – this indicates that input 1 is in the open (normal) state.
IN1: 1 – this indicates that input 1 is in the closed (activated) state.
IN2: 0 – this indicates that input 2 is in the open (normal) state.
IN2: 1 – this indicates that input 2 is in the closed (activated) state.
The analogue value seen on the Fire Alarm Control Panel for devices with inputs in the normal state is;
Analogue Value Slot 5 Slot 6
Detector N/A N/A Manual Call Point N/A N/A Sounder N/A N/A Input/Output 090 244
The analogue value seen on the Fire Alarm Control Panel for devices with inputs in the closed state is;
Analogue Value
Slot 5 Slot 6 Detector N/A N/A Manual Call Point N/A N/A Sounder N/A N/A Input/Output 213 N/A
Battery Level – this menu when entered shows information on the battery pack status for a device. A device has 2 packs, the status of each of these can be viewed from this menu. The status of the pack is updated whenever there is a status change or automatically updated every 6 hours. The available battery descriptions are described below;
Pack 1 OK – this indicates a good battery voltage is present in Pack 1. This is represented by displaying a full battery icon.
Pack 1 Warning – this indicates the battery voltage is low in Pack 1 and is a 30 day warning indication. The batteries must be changed on the device within 30 days for continued reliable operation. This is represented by displaying a half full battery icon.
Pack 1 Low – this indicates the battery voltage is low in Pack 1 and is a 7 day warning indication. The batteries must be changed on the device within 7 days for continued reliable operation. This is represented by displaying an empty battery icon.
Tel: +44 (0) 1227 369570 Fax: +44 (0) 1227 369679 Email: enquiries@emsgroup.co.uk Website: www.emsgroup.co.uk
Ziton Radio Loop Module Programming Manual (Issue 7d) TSD022
EMS Group Head Office, Technology House, Sea Street, Herne Bay, Kent CT6 8JZ, England
9
Pack 1 Missing – this indicates a battery from Pack 1 is missing. The battery must be inserted on the device for continued reliable operation. This is represented by displaying an X symbol.
Pack 2 OK – this indicates a good battery voltage is present in Pack 2. This is represented by displaying a full battery icon.
Pack 2 Warning – this indicates the battery voltage is low in Pack 2 and is a 30 day warning indication. The batteries must be changed on the device within 30 days for continued reliable operation. This is represented by displaying a half full battery icon.
Pack 2 Low – this indicates the battery voltage is low in Pack 2 and is a 7 day warning indication. The batteries must be changed on the device within 7 days for continued reliable operation. This is represented by displaying an empty battery icon.
Pack 2 Missing – this indicates a battery from Pack 2 is missing. The battery must be inserted on the device for continued reliable operation. This is represented by displaying an X symbol.
Signal Level – this menu when entered shows information on the two signalling channels used by the Radio Loop Module in both directions, as the devices are bi-directional. The received signal strength at the Radio Loop Module from the device is shown as an LI Dev level, therefore indicating the signal that has been sent from the device to the Radio Loop Module. The LI Dev level is updated on every poll response (123 seconds). The forward signal strength received at a device from the Radio Loop Module is shown as an LI  Dev level, therefore indicating the signal that has been sent from the Radio Loop Module to the device. The LI  Dev level is updated every 6 hours or when requested manually by selecting the Manual Update Option from the menu.
Ch 1 LI  Dev – this indicates the received signal strength at the Radio Loop Module from the device on the first frequency channel used by the system. A level from 100 -0 is shown to indicate the levels, a table of which is shown at the end of this section.
Ch 2 LI  Dev – this indicates the received signal strength at the Radio Loop Module from the device on the second frequency channel used by the system. A level from 100 -0 is shown to indicate the levels, a table of which is shown at the end of this section.
Ch 1 LI

Dev – this indicates the forward signal strength received at the device from the Radio Loop Module on the first frequency channel used by the system. A level from 100 -0 is shown to indicate the levels, a table of which is shown at the end of this section.
Ch 2 LI

Dev – this indicates the forward signal strength received at the device from the Radio Loop Module on the second frequency channel used by the system. A level from 100 -0 is shown to indicate the levels, a table of which is shown at the end of this section.
The individual devices have signal levels available for both of their operating channels (Ch1 and Ch2) and also for both directions (Radio Loop Module to Device (LI Dev) and Device to Radio Loop Module (LI Dev)) as the devices are bi-directional. The signal levels shown range from 100 - 0 with 100 being the highest signal to 0 where no signal is being seen, as shown below;
100 Shown indicates Good Signal Level 90 Shown indicates Good Signal Level 80 Shown indicates Good Signal Level 70 Shown indicates Good Signal Level 60 Shown indicates Good Signal Level 50 Shown indicates Good Signal Level 40 Shown indicates Medium Signal Level 30 Shown indicates Low Signal Level 20 Shown indicates Caution Signal Level 10 Shown indicates Caution Signal Level 0 Shown indicates No Signal Level Received
Tel: +44 (0) 1227 369570 Fax: +44 (0) 1227 369679 Email: enquiries@emsgroup.co.uk Website: www.emsgroup.co.uk
Ziton Radio Loop Module Programming Manual (Issue 7d) TSD022
EMS Group Head Office, Technology House, Sea Street, Herne Bay, Kent CT6 8JZ, England
10
An algorithm incorporating both channels and the channels background is employed to indicate the analogue values displayed at the associated control panel and therefore determining the devices signal strength. This is shown in the table below.
Analogue
Value
Displayed at
Radio Device
Type
Device Signal Strength Level
Control Panel
Slot 5 Slot 6
020 N/A All Device Types No Radio Signal received. Device Missing 075 N/A All Device Types Radio Signal strength caution. 080 N/A All Device Types Radio Signal strength low. 085 N/A Detector Radio Signal strength medium. 090 N/A Detector Radio Signal strength good.
The device to Radio Loop Module information is updated every time the device responds to a poll which is every 123 seconds. The Radio Loop Module to device information is automatically updated every 6 hours or if a manual update is requested.
The minimum recommend level is 50 points or above on each channel.
Manual Update – This menu when entered will automatically send signals from the Radio Loop Module to the individual device and ask for its current signal level status to be transmitted back to the Radio Loop Module. This will then automatically update the Signal level fields for the device. If a signal level field is still awaiting an update from a channel 0 will be shown in the field.
Ident – This menu shows the unique 5 digit identification number for the device.
Software Version – This menu shows the software version currently installed in the device.
Node Number – This menu should only be used when two Radio Loop Modules are connected to
one of the Control Panels loops. The first Radio Loop Modules Node Number should be set as 1 whilst the second Radio Loop Modules Node Number should be set as 2.
Loop Address - This menu allows you to view the device’s current loop address. A new device loop address can be selected by pressing the rotary control, thus choosing an alternative address.
Output Test – This menu allows you to turn device LED’s on.
Tel: +44 (0) 1227 369570 Fax: +44 (0) 1227 369679 Email: enquiries@emsgroup.co.uk Website: www.emsgroup.co.uk
Ziton Radio Loop Module Programming Manual (Issue 7d) TSD022
EMS Group Head Office, Technology House, Sea Street, Herne Bay, Kent CT6 8JZ, England
11
3.2 Add New device
Radio Callpoint
Radio Multis
ensor
Radio Sounder
Radio
Input Output Unit
This menu allows the adding of new radio devices to the Radio Loop Module. A maximum of 31 devices are allowed. When this menu is entered the log on button must be pressed on the new device. A confirmation of the device ident number is requested and when accepted will add the device to the Radio Loop Module. The log on button can be found on the devices in the following locations;
Callpoint Log On Button
Detector Log On Button
Sounder Log On Button
Sounder Log On Button
Tel: +44 (0) 1227 369570 Fax: +44 (0) 1227 369679 Email: enquiries@emsgroup.co.uk Website: www.emsgroup.co.uk
Ziton Radio Loop Module Programming Manual (Issue 7d) TSD022
EMS Group Head Office, Technology House, Sea Street, Herne Bay, Kent CT6 8JZ, England
12
3.3 Remove device
This menu allows removal of devices from the Radio Loop Module. A list of devices on the Radio Loop Module are shown and the applicable device to be removed can be selected. A confirmation of the device to be removed is required prior to removal.
3.4 Interface Status
This function allows the current status of the Radio Loop Module to be viewed. Available options are: - Fault status, Background Level, Unique ident number and Software version. Additional more detailed options are available by pressing the Navigation button on the required item. This allows the following menus to be viewed;
Fault Status – this menu when entered shows detailed information on the fault status of the Radio Loop Module. If multiple faults are outstanding for the Radio Loop Module then by turning the rotary control they can be individually viewed. The available fault descriptions are described below;
No Fault Present – this description indicates that the Radio Loop Module is not in any fault and is operating normally.
The analogue value seen on the Fire Alarm Control Panel for this state is;
Analogue Value
Slot 5 Slot 6
Radio Loop
090 244
Module
Ch1RFI Det – this description indicates that a radio frequency interference signal has been detected on radio channel 1 that the system is operating on.
Ch2 RFI Det– this description indicates that a radio frequency interference signal has been detected on radio channel 2 that the system is operating on.
The analogue value seen on the Fire Alarm Control Panel for when both Ch 1 and Ch 2 are in this state is;
Analogue Value
Slot 5 Slot 6
Ziton Radio Loop
181 118
Module
Background Level – this menu when entered shows the background radio signal level on the two signalling channels used by the Ziton Radio Loop Module. The available background level descriptions are described below;
Ch 1 – this indicates the background level at the Radio Loop Module on the first frequency channel used by the system. A range from 100 – 0 is shown to indicate the levels, a table of which is shown at the end of this section.
Ch 2 – this indicates the background level at the Radio Loop Module on the second frequency channel used by the system. A range from 100 – 0 is shown to indicate the levels, a table of which is shown at the end of this section.
100 shown indicates VERY HIGH 75 shown indicates HIGH 50 shown indicates MEDIUM 25 shown indicates LOW 0 shown indicates GOOD.
Tel: +44 (0) 1227 369570 Fax: +44 (0) 1227 369679 Email: enquiries@emsgroup.co.uk Website: www.emsgroup.co.uk
Ziton Radio Loop Module Programming Manual (Issue 7d) TSD022
EMS Group Head Office, Technology House, Sea Street, Herne Bay, Kent CT6 8JZ, England
13
Ident – this menu shows the unique identification number for the device.
Software Version – This menu details the software version of the Radio Loop Module.
Legacy Mode – To ensure correct operation of devices reporting to the Control Panel, Legacy
Mode must be correctly selected.
Legacy Mode ‘ON’ is to be selected when the Ziton Radio Loop Module is connected to a ZP3 Panel.
Legacy Mode ‘OFF’ is to be selected when the Ziton Radio Loop Module is connected to a ZP2 (2010) Panel.
3.5 Radio Channels
This menu allows the two frequency channels currently used by the Radio Loop Module to be viewed and also allows the channels used to be selected either manually or automatically. 32 channels are available for use on the system and these are as follows;
Ch1: 868.048 MHz Ch9: 868.248 MHz Ch17: 868.749 MHz Ch25: 868.950 MHz Ch2: 868.073 MHz Ch10 868.273 MHz Ch18: 868.774 MHz Ch26: 868.975 MHz Ch3: 868.098 MHz Ch11: 868.298 MHz Ch19: 868.800 MHz Ch27: 869.000 MHz Ch4: 868.123 MHz Ch12: 868.323 MHz Ch20: 868.825 MHz Ch28: 869.025 MHz Ch5: 868.148 MHz Ch13: 868.349 MHz Ch21: 868.850 MHz Ch29: 869.050 MHz Ch6: 868.173 MHz Ch14: 868.374 MHz Ch22: 868.875 MHz Ch30: 869.075 MHz Ch7: 868.198 MHz Ch15: 868.399 MHz Ch23: 868.900 MHz Ch31: 869.100 MHz Ch8: 868.223 MHz Ch16: 868.424 MHz Ch24: 868.925 MHz Ch32: 869.125 MHz
4.0 FRONT DISPLAY OF RADIO LOOP MODULE
The front display of the Ziton Radio Loop Module will show the number of devices that are
allocated it, along with the total number of current alarm and fault conditions. The DEV field shows the total number of devices allocated between 00-31. The AL field shows the amount of devices currently with outstanding Alarms and Pre-alarms ranging between 00-31. The FT field shows the amount of devices currently with outstanding Faults ranging between 00-31. An example display will show;
5.0 ACCESSING THE RADIO LOOP MODULES MENUS
To access the Users menu’s from the front display screen , follow the steps listed below:
Press the rotary control. The display will change to show;
The Menu structure can be viewed by scrolling through the menu by turning the rotary control.
Entry into the required menu is achieved by locating the required menu on the display and pressing the rotary control. Exiting from a menu option is achieved automatically after 30 seconds or by pressing the Radio Loop Modules back button.
DEV01 AL00 FT00
DEV01 AL00 FT00
Device Status
Tel: +44 (0) 1227 369570 Fax: +44 (0) 1227 369679 Email: enquiries@emsgroup.co.uk Website: www.emsgroup.co.uk
Ziton Radio Loop Module Programming Manual (Issue 7d) TSD022
EMS Group Head Office, Technology House, Sea Street, Herne Bay, Kent CT6 8JZ, England
14
5.1 Viewing the Device Status
Enter the menu structure by pressing the rotary control.
Turn the Rotary control until the display shows;
Device Status
Press the rotary control and the display will change to show the devices allocated onto the
Ziton Radio Loop Module and their current status. The list can be viewed by turning the rotary control. The information is shown in the following format;
Addr 067 L Multi
Addr 067 – In this example this indicates the devices loop address number (067). Available options are between 1 and 127.
L – In this example this field indicates the devices logged on or fault status. Available options are;
L= Logged On and in a normal condition. ! = Logged On with fault(s) present.
= Logged On with a fire alarm present.
= Logged On with a pre alarm present.
Multi – This field indicates the device type. Available options are:
Radio = Radio Loop Module Module Multi = Multisensor Detector Optic = Optical Detector Heat = Heat Detector HTemp = Heat Detector MCP = Manual Callpoint Sound = Sounder Device I/O = Input/Output Device ??? = Unknown Device
For more detailed information on the device displayed press the Rotary control. This
information will always be available regardless of the status identifier of the device. The list of available information is shown in the following format;
Fault Status Alarm Status * Battery Level Signal Level Manual Update Ident xxxxx Software xxxxx Set Loop Address Output
* Alarm Status shown as Input Status for Input/Output Device types.
Tel: +44 (0) 1227 369570 Fax: +44 (0) 1227 369679 Email: enquiries@emsgroup.co.uk Website: www.emsgroup.co.uk
Ziton Radio Loop Module Programming Manual (Issue 7d) TSD022
EMS Group Head Office, Technology House, Sea Street, Herne Bay, Kent CT6 8JZ, England
15
To enter the Fault Status Menu press the rotary control with the Fault Status text displayed.
The display will change to show the current Fault status of the device an example is shown below;
In Tamper 
Available Options are; No Fault Present In Tamper Head Missing Sounder Missing Signal Fault Battery Fault Head Dirty No Sndr Audio Head Fault Short Circuit Open Circuit
Note: If multiple faults are applicable to a device the rotary control can be turned to view the total fault listing and a down arrow will be present to indicate that there is more than one fault present.
The menu will timeout after 30 seconds or alternatively press the Back button to immediately
return to the previous Menu.
To enter the Alarm Status Menu press the rotary control with the Alarm Status text displayed.
The display will change to show the current Alarm status of the device an example is shown below;
In Fire
Available Options are; No Alarm Present In Fire In Pre-Alarm
The menu will timeout after 30 seconds or alternatively press the Back button to immediately
return to the previous Menu.
To enter the Input Status Menu (This is only available for Input/Output device types) press the
rotary control with the Input Status text displayed. The display will change to show the current Input status of the device an example is shown below;
IN: 0 - 0 OUT: 0 - 0
Available Options are; IN: 0-0 (Inputs 1 + 2 normal/open state) IN: 1-0 (Input 1 activated/closed state, Input 2 normal/open state) IN: 0-1 (Input 1 normal/open state, Input 2 activated/closed state) IN: 1-1 (Inputs 1 + 2 activated/closed state) OUT: 0-0 (Output 1 + 2 normal/open state) OUT: 1-0 (Output 1 active closed state, Output 2 normal/open state) OUT: 0-1 (Output 1 normal open state, Output 2 active closed state) OUT: 1-1 (Outputs 1 + 2 active closed state)
The menu will timeout after 30 seconds or alternatively press the Back button to immediately
return to the previous Menu.
Tel: +44 (0) 1227 369570 Fax: +44 (0) 1227 369679 Email: enquiries@emsgroup.co.uk Website: www.emsgroup.co.uk
Ziton Radio Loop Module Programming Manual (Issue 7d) TSD022
EMS Group Head Office, Technology House, Sea Street, Herne Bay, Kent CT6 8JZ, England
16
To enter the Battery Level Menu press the rotary control with the Battery Level text displayed.
The display will change to show the current Battery Level for the individual packs of each device an example is shown below;
Pack 1 OK 
Available Options are; Pack 1 OK (With full battery icon shown) Pack 1 Warning (With half full battery icon shown) Pack 1 Low (With empty battery icon shown) Pack 1 Missing (With X shown) Pack 2 OK (With full battery icon shown) Pack 2 Warning (With half full battery icon shown) Pack 2 Low (With empty battery icon shown) Pack 2 Missing (With X shown)
Note: Turn the rotary control to view the status of all associated battery packs for a particular device.
The menu will timeout after 30 seconds or alternatively press the Back button to immediately
return to the previous Menu.
To enter the Signal Level Menu press the rotary control with the Signal Level text displayed. The display will change to show the last Signal Level for the two channels used. The received signal strength at the Ziton Radio Loop Module from the device is shown as an LI Dev level, therefore indicating the signal that has been sent from the device to the Radio Loop Module. The LI Dev level is updated every poll (123 seconds). The forward signal strength received at a device from the Radio Loop Module is shown as an LI  Dev level, therefore indicating the signal that has been sent from the Radio Loop Module to the device. The LI  Dev level is updated every 6 hours or when requested manually by selecting the Manual Update Option from the menu.
An example display is shown below;
Ch1 LIDev 100
The signal levels shown range from 100 - 0 with 100 being the highest signal to 0 where no signal is being seen, as shown below;
100 Shown indicates Good Signal Level
90 Shown indicates Good Signal Level 40 Shown indicates Low Signal Level 80 Shown indicates Good Signal Level 30 Shown indicates Caution Signal Level 70 Shown indicates Good Signal Level 20 Shown indicates Caution Signal Level 60 Shown indicates Good Signal Level 10 Shown indicates Caution Signal Level 50 Shown indicates Medium Signal Level 0 Shown indicates No Signal Level Received
The minimum recommend level is 50 points or above on each channel.
Note: Turn the rotary control to view the status of all associated signal levels for a particular device.
The menu will timeout after 30 seconds or alternatively press the Back button to immediately
return to the previous Menu.
Available Options are; Ch1 LIDev (With Levels 100 -0 displayed) Ch2 LIDev (With Levels 100 -0 displayed) Ch1 LIDev (With Levels 100 -0 displayed) Ch2 LIDev (With Levels 100 -0 displayed)
Tel: +44 (0) 1227 369570 Fax: +44 (0) 1227 369679 Email: enquiries@emsgroup.co.uk Website: www.emsgroup.co.uk
Ziton Radio Loop Module Programming Manual (Issue 7d) TSD022
EMS Group Head Office, Technology House, Sea Street, Herne Bay, Kent CT6 8JZ, England
17
To view the Devices Unique Ident rotate the rotary control whilst in the Device Status Menu
until the following example display is shown;
Ident: 12345
The menu will timeout after 30 seconds or alternatively press the Back button to immediately
return to the previous Menu.
To view the Devices Software Version installed rotate the rotary control whilst in the Device
Status Menu until the following example display is shown;
Software V 1.77
The menu will timeout after 30 seconds or alternatively press the Back button to immediately
return to the previous Menu.
To select the Manual Update function turn the rotary control whilst in the Device Status Menu
until the following example display is shown;
Manual Update
Press the rotary control button to initiate the manual update function. The display will show
updating for a few seconds and then revert back to the Manual Update Menu.
Note: Following a manual update the Signal Level Menu should be checked for the device. This will indicate the signal levels seen. If 00 is shown then a signal has not been seen from the device in question on that particular channel as yet.
Tel: +44 (0) 1227 369570 Fax: +44 (0) 1227 369679 Email: enquiries@emsgroup.co.uk Website: www.emsgroup.co.uk
Ziton Radio Loop Module Programming Manual (Issue 7d) TSD022
EMS Group Head Office, Technology House, Sea Street, Herne Bay, Kent CT6 8JZ, England
18
5.2 Output Test
Enter the menu structure by pressing the rotary control
Turn the rotary control until the display shows;
Press the rotary control and the display will change to show the devices on the system; e.g;
Turn the rotary control until the display shows the desired device number;
Press the rotary control. The following screen should be displayed;
Turn the rotary control until the display shows;
Press the rotary control and the display will change to show;
To switch on the output, turn the rotary control until the display shows;
The devices LED should activate;
To switch the output off, turn the rotary control until the display shows;
The menu will timeout after 30 seconds or alternatively press the Back button to immediately
return to the previous Menu.
NOTE: If this step is not performed, the output will time out after 30 seconds and the LED will
thus switch off
Device Status
Addr 01 L Radio
Addr 67 L Multi
Fault Status
Output Test
Output OFF
Output ON
Output OFF
Tel: +44 (0) 1227 369570 Fax: +44 (0) 1227 369679 Email: enquiries@emsgroup.co.uk Website: www.emsgroup.co.uk
Ziton Radio Loop Module Programming Manual (Issue 7d) TSD022
EMS Group Head Office, Technology House, Sea Street, Herne Bay, Kent CT6 8JZ, England
19
5.3 Adding New Devices to the System
Enter the menu structure by pressing the rotary control
Turn the rotary control until the display shows;
Add New Device
Press the rotary control and the display will change to show;
Press Dev Log On
Note: If 31 devices are already allocated to the Ziton Radio Loop Module, the display will show ‘Dev Table Full’ instead of the above screen.
Press the log on button on the new device. The display will change to show;
Add Dev xxxxx N?
If the device is not required to be added press the rotary control. If the correct ident is shown
and the device is to be added turn the rotary control until the display shows;
Add Dev xxxxx Y?
To add the device press the rotary control and the display will change to show;
The screen will now display;
Turn the rotary control until the desired device number is shown;
Press the rotary control and the display will change to show;
01 represents the device slot in which the new device has been allocated. Available options are between 01-31. The Det represents the new device allocated being recognised as a Detector type.
01 represents the device slot in which the new device has been allocated. Available options are between 01-31. The Mcp represents the new device allocated being recognised as a Callpoint type.
01 represents the device slot in which the new device has been allocated. Available options are between 01-31. The Sounder represents the new device allocated being recognised as a Sounder type.
01 represents the device slot in which the new device has been allocated. Available options are between 01-31. The I/O represents the new device allocated being recognised as a Input/Output type.
Adding
Address 002
Address 007
Detector Added
OR
MCP Added
OR
Sounder Added
OR
I/O Added
Tel: +44 (0) 1227 369570 Fax: +44 (0) 1227 369679 Email: enquiries@emsgroup.co.uk Website: www.emsgroup.co.uk
Ziton Radio Loop Module Programming Manual (Issue 7d) TSD022
EMS Group Head Office, Technology House, Sea Street, Herne Bay, Kent CT6 8JZ, England
20
The menu will automatically show the following display;
XXX represents the next available unused address number ranging from 1-126.
Set Address XXX
Turn the rotary control until the display shows the address number required to be selected.
Press the rotary control to select and the display will change to show;
Selected XXX
The menu will timeout after 30 seconds or alternatively press the Back button to immediately
return to the previous Menu.
If the log on command is not received at any time during this procedure or received
incorrectly the following messages will be displayed;
Please Retry
The Log On button can be pressed with this display shown and the procedure continued or alternatively press the Back button to revert to the Add Device Menu.
5.4 Removing Device from the System
Enter the menu structure by pressing the rotary control
Turn the rotary control until the display shows;
Remove Device
Press the rotary control and the display will change to show the devices allocated onto the
Radio Loop Module. The list can be viewed by turning the rotary control. The information is shown in the following format
Addr 067 L 12345
Note: Pressing the Help button with the above display shown will indicate the device type. E.g. “Multi”.
To remove any devices press the rotary control the display will change to show;
If the device is not required to be removed press the rotary control. If the correct ident is
shown and the device is to be removed turn the rotary control until the display shows;
To remove the device press the rotary control and the display will change to show Removing
Device for 2 seconds and then confirm the removal;
The menu will timeout after 30 seconds or alternatively press the Back button to immediately
return to the previous Menu.
Remove 12345 N?
Remove 12345 Y?
Removing Device
Followed by
Removed Multi
Tel: +44 (0) 1227 369570 Fax: +44 (0) 1227 369679 Email: enquiries@emsgroup.co.uk Website: www.emsgroup.co.uk
Ziton Radio Loop Module Programming Manual (Issue 7d) TSD022
EMS Group Head Office, Technology House, Sea Street, Herne Bay, Kent CT6 8JZ, England
21
5.5 Viewing the Radio Loop Modules Status
Enter the menu structure by pressing the rotary control.
Turn the rotary control until the display shows;
Interface Status
For more detailed information on the device displayed press the rotary control. The list of
available information is shown in the following format;
Fault Status Background Level Ident xxxxx Software Vxx.xx
Serial Data
Note: The Serial Data option is only available when the Ziton Radio Loop Module has switch 8 on. This enables Serial Data to be seen on a terminal programme via the onboard serial port. If either of these options are selected it is important NOT to leave the Radio Loop Module in this diagnostic / operational mode.
To enter the Fault Status Menu press the rotary control with the Fault Status text displayed.
The display will change to show the current Fault status of the Radio Loop Module, an example is shown below;
No Fault Present
Available Options are; No Fault Present Aerial Tamper Ch1 RFI Det Ch2 RFI Det
Note: If multiple faults are applicable to the Radio Loop Module the rotary control can be turned to view the total fault listing and a down arrow will be present to indicate that there is more than one fault present.
The menu will timeout after 30 seconds or alternatively press the Back button to immediately
return to the previous Menu.
To enter the Background Level Menu press the rotary control with the Background Level text
displayed. The display will change to show the current Background Level for the two channels used. The levels are updated in real time. An example display is shown below;
Ch1 0
Available Options are; Ch1 (With Levels 100 -0 displayed) Ch2 (With Levels 100 -0 displayed)
The Levels shown represent 5 levels these are interrupted as follows;
100 shown indicates VERY HIGH 75 shown indicates HIGH 50 shown indicates MEDIUM 25 shown indicates LOW
Note: Turn the rotary control to view the background level of the second channel used.
Ziton Radio Loop Module Programming Manual (Issue 7d) TSD022
0 Bar shown indicates GOOD.
Tel: +44 (0) 1227 369570 Fax: +44 (0) 1227 369679 Email: enquiries@emsgroup.co.uk Website: www.emsgroup.co.uk
EMS Group Head Office, Technology House, Sea Street, Herne Bay, Kent CT6 8JZ, England
22
The menu will timeout after 30 seconds or alternatively press the Back button to immediately
return to the previous Menu.
To view the Radio Loop Modules Unique Ident rotate the rotary control whilst in the Interface
Status Menu until the following example display is shown;
Ident: 12345
The menu will timeout after 30 seconds or alternatively press the Back button to immediately
return to the previous Menu.
To view the Radio Loop Modules current software version rotate the rotary control whilst in
the Interface Status Menu until the following example display is shown;
Software V XX.XX
The menu will timeout after 30 seconds or alternatively press the Back button to immediately
return to the previous Menu.
To change the Serial Data menu rotate the rotary control whilst in the Interface Status Menu
until the following example display is shown;
Serial Data OFF
Press the rotary control button to toggle the option between OFF and ON.
The menu will timeout after 30 seconds or alternatively press the Back button to immediately
return to the previous Menu.
Note: The Serial Data option is only available when the Ziton Radio Loop Module has switch 8 on. This enables Serial Data to be seen on a terminal programme via the onboard serial port. If either of these options are selected it is important NOT to leave the Radio Loop Module in this diagnostic / operational mode.
5.6 Radio Channels
Enter the menu structure by pressing the rotary control.
Turn the rotary control until the display shows;
Press the rotary control and the display will change to show the radio channels sub menu.
Radio Channels
Currently Used
Auto Select Manual Select
Note: The Auto Select and Manual Select options are only available when the Ziton Radio Loop Module does not have any devices allocated to it.
To select the currently used radio channels menu. Turn the rotary control until the display
shows;
Currently Used
Press the rotary control and the display will change to show the first radio channels currently
used by the Radio Loop Module. An example is shown below;
Ch1 19 868.800Mhz
Note: The Ch1 field indicates the first channel used. The next field indicates the channel number along with the frequency used.
Tel: +44 (0) 1227 369570 Fax: +44 (0) 1227 369679 Email: enquiries@emsgroup.co.uk Website: www.emsgroup.co.uk
Ziton Radio Loop Module Programming Manual (Issue 7d) TSD022
EMS Group Head Office, Technology House, Sea Street, Herne Bay, Kent CT6 8JZ, England
23
Available channels are shown below;
Ch1: 868.048 MHz Ch9: 868.248 MHz Ch17: 868.749 MHz Ch25: 868.950 MHz Ch2: 868.073 MHz Ch10 868.273 MHz Ch18: 868.774 MHz Ch26: 868.975 MHz Ch3: 868.098 MHz Ch11: 868.298 MHz Ch19: 868.800 MHz Ch27: 869.000 MHz Ch4: 868.123 MHz Ch12: 868.323 MHz Ch20: 868.825 MHz Ch28: 869.025 MHz Ch5: 868.148 MHz Ch13: 868.349 MHz Ch21: 868.850 MHz Ch29: 869.050 MHz Ch6: 868.173 MHz Ch14: 868.374 MHz Ch22: 868.875 MHz Ch30: 869.075 MHz Ch7: 868.198 MHz Ch15: 868.399 MHz Ch23: 868.900 MHz Ch31: 869.100 MHz Ch8: 868.223 MHz Ch16: 868.424 MHz Ch24: 868.925 MHz Ch32: 869.125 MHz
Turn the rotary control to show the second radio channel currently used by the Ziton Radio
Loop Module. An example is shown below;
Ch2 31 869.100Mhz
The menu will timeout after 30 seconds or alternatively press the Back button to immediately
return to the previous Menu.
To select the auto select option from the radio channels menu. Turn the rotary control until
the display shows;
Auto Select
Press the rotary control and the display will change to show the time duration the scan is to
take place for. An example is shown below;
Scan Time 1min
Available Options are:
1 min 5 min 10 min 20 min 30 min 60 min
Turn the rotary control until the required duration is shown and press the rotary control to
select. The display will change to show the time duration remaining whilst the scan is taking place. An example is shown below;
Once the scan is completed the 2 channels with the least background RSSI seen during the scan will be automatically selected. The display will change to show the following;
00:59secs - - - - - -
Auto Ch xx Ch xx
If the scan is required to be stopped prior to the scan being completed this can be achieved by pressing the rotary control again. The same display will then be shown.
Press the rotary control and the display will show;
View Results N?
If the results are not required to be viewed press the rotary control again and the display will return to the radio channels menu. If the results are required to be viewed turn the rotary control until the display shows,
View Results Y?
Tel: +44 (0) 1227 369570 Fax: +44 (0) 1227 369679 Email: enquiries@emsgroup.co.uk Website: www.emsgroup.co.uk
Ziton Radio Loop Module Programming Manual (Issue 7d) TSD022
EMS Group Head Office, Technology House, Sea Street, Herne Bay, Kent CT6 8JZ, England
24
Press the rotary control to select and the display will change to show;
Turn the rotary control to view all 32 available channels. Each channel will have a bar chart
which denotes the amount of background signal seen on that channel whilst the scan was taking place.
The menu will timeout after 30 seconds or alternatively press the Back button to immediately
return to the previous Menu.
To select the manual select option from the radio channels menu. Turn the rotary control until
the display shows;
Manual Select
Press the rotary control and the display will change to show;
First Channel
Available Options are:
First Channel Second Channel
Turn the rotary control until the required channel is shown and press the rotary control to
select. The display will change to show the 32 available channels in the following format,
Ch1 868.048Mhz
Available channels for selection are shown below;
Ch1: 868.048 MHz Ch9: 868.248 MHz Ch17: 868.749 MHz Ch25: 868.950 MHz Ch2: 868.073 MHz Ch10 868.273 MHz Ch18: 868.774 MHz Ch26: 868.975 MHz Ch3: 868.098 MHz Ch11: 868.298 MHz Ch19: 868.800 MHz Ch27: 869.000 MHz Ch4: 868.123 MHz Ch12: 868.323 MHz Ch20: 868.825 MHz Ch28: 869.025 MHz Ch5: 868.148 MHz Ch13: 868.349 MHz Ch21: 868.850 MHz Ch29: 869.050 MHz Ch6: 868.173 MHz Ch14: 868.374 MHz Ch22: 868.875 MHz Ch30: 869.075 MHz Ch7: 868.198 MHz Ch15: 868.399 MHz Ch23: 868.900 MHz Ch31: 869.100 MHz Ch8: 868.223 MHz Ch16: 868.424 MHz Ch24: 868.925 MHz Ch32: 869.125 MHz
Press the rotary control to select the chosen frequency and the display will confirm the choice
that has been made by displaying this on the screen in the following format;
Ch1 Selected
Repeat the above procedure for selecting the Second Channel.
The menu will timeout after 30 seconds or alternatively press the Back button to immediately
return to the previous Menu.
Tel: +44 (0) 1227 369570 Fax: +44 (0) 1227 369679 Email: enquiries@emsgroup.co.uk Website: www.emsgroup.co.uk
Ziton Radio Loop Module Programming Manual (Issue 7d) TSD022
EMS Group Head Office, Technology House, Sea Street, Herne Bay, Kent CT6 8JZ, England
25
Dealer Information:
ations being written.
EMS Group Head Office Technology House, Sea Street Herne Bay, Kent CT6 8JZ England Tel: +44 (0) 8712 710804 Fax: +44 (0) 1227 369679
enquiries@emsgroup.co.uk
Email:
www.emsgroup.co.uk
The information contained within this literature is correct at time of publishing. The EMS Group reserves the right to change any information regarding products as part of its continual development enhancing new technology and reliability. The EMS Group advises that any product literature issue numbers are checked with its head office prior to any formal specific
Loading...