EMS FireCell Radio Hub, FireCell Radio Cluster Communicator Quick Start Manual

POWER FAULT
SYSTEM
FAULT
POWER FAULT
FIRE
Radio Hub
Control Panel
Radio Cluster
Communicator (RCC)
230V AC
230V AC
Wireless Diagnostics Quick Start Guide Iss 3 - MK252 AJM
www.emsgroup.co.uk
WIRELESS DIAGNOSTICS
QUICK START GUIDE
How to resolve a disconnect fault
A device disconnect fault is shown on the Control Panel display, if the communication path between the individual device and it’s associated Radio Cluster Communicator is not present. The majority of device disconnect faults can be investigated and resolved by following these 10 simple steps:
Step 1 Is the device in it’s location?
www.emsgroup.co.uk
Radio Detector Base
PRESS HERE TO
LOG ON
IDENT
Step 2 Is the device powered?
Combined Sounder Detectors are powered by Switch 1 as shown:
www.emsgroup.co.uk
Combined Sounder and Detector Base
PRESS HERE TO
LOG ON
IDENT
!
ON
1
234
ON
OFF
0359
12
0359-CPR-00XX
3.5 - 4.5V DC
0.2 - 300mA 1W Max
Type A: for indoor use
Technical Data see Installation Guide
Part No: FCX-XXX-XXX
EN54-3: 2001 EN54-25: 2008
ON
1
2
3
4
Step 3 Is the associated RCC powered?
If not, all devices reporting to the RCC will be disconnected.
POWER FAULT
Disconnected
230Vac
POWER FAULT
Connected
230Vac
Other wireless devices have power jumpers as shown:-
SIZE AA
SIZE AA
SIZE AA
SIZE AA
SIZE AA
SIZE AA
(Link pins to power device)
Step 4 Is the ident programmed correctly?
(Switch 1 On = Power ON)
Check the device’s ident located on the side of the device under the barcode and cross reference it with the ident programmed into the Radio Hub.
0C03B Rev:5 01/08/17
0C03B Rev:5 01/08/17
RCC01 ID 1C03B
RCC01 ID 0C03B
©2018 EMS Ltd. All rights reserved Page 2 of 4 MK252 Iss 3 15/08/2018 AJM