EMS FireCell FCX-500-444, FireCell FCX-500-004 Installation Manual

Radio Hub Installation Guide
1 Pre Installation
FCX-500-004 FCX-500-444
4 Loop Radio Hub 4 Loop Radio Hub c/w Remote Aerial Facility
2 Components
Part No Product Description
!
Installation must conform to applicable local installation codes and
should only be installed by a fully trained
competent person.
Ensure the
Radio Hub is located as per the site survey.
Refer to step 3 to ensure optimised wireless performance.
I
f using remote aerials with this product, refer to the Remote
Aerial Installation manual for more information.
6 Fix to the Wall
4 Optional PCB Removal
5 Remove Cable Entry Points
Drill the cable entry points as necessary.
1
2
3
4
5
4x Corner Covers
4x Lid Screws
1x Radio Hub Lid
1x Radio Hub PCB 1x Radio Hub Back Box
= Do Not Use
= Available cable entry points
FIRE
Fire Alarm Control
3 Mounting Location Guidelines
Ensure the Radio Hub is not installed within 2m of other wireless or electrical equipment (not including the Control Panel).
Ensure the Radio Hub is not installed within 0.6m of any metal work.
POWER FAULT
0.6m
2m
Control
Panel
Radio
Hub
Remove the three circled retaining screws, before unclipping the PCB.
TX
RESET
LOGONRXBACK
HEALTHY
FAULT
SYS FAULT
LOOP 1
+
-
IN OUT IN OUT
+
-
LOOP 2
+
-
IN OUT IN OUT
+
-
LOOP 3
+
-
IN OUT IN OUT
+
-
LOOP 4
+
-
IN OUT IN OUT
+
-
RF1 RF2
TX
RX
ATTENTION
OBSERVE PRECAUTIONS
FOR HANDLING
ELECTROSTATIC
SENSITIVE
1
2 3
4 5
For optimum wireless performance,the following must be observed:
All five circled fixing positions are available for use.
The key hole can also be used for locating and fixing where required.
RADIO HUB
POWER
FAULT
SYSTEM
FAULT
©2018 EMS Ltd. All rights reserved Page 1 of 2 TSD052 Iss 17 05/09/2018 AJM
TX
RESET
RX
BACK
HEALTHY
FAU LT
SYS FAULT
RF1 RF2
TX
RX
TX
RESET
LOGON
RX
BACK
HEALTHY
FAULT
SYS FAULT
LOOP 1
+
-
IN OUT IN OUT
+
-
LOOP 2
+
-
IN OUT IN OUT
+
-
LOOP 3
+
-
IN OUT IN OUT
+
-
LOOP 4
+
-
IN OUT IN OUT
+
-
RF1 RF2
TX
RX
Operating Temperature -10°C to 55°C
Storage Temperature 5°C to 30°C
Humidity Up to 95% non-condensing
Operating Voltage 17 to 28Vdc
Typical Operating Current 24mA@24Vdc loop powered (1st loop)
+7mA per each connected loop
IP Rating IP54
Operating Frequency 868MHz
Output Transmitter Power 0 - 14 dBm (0 - 25 mW)
Dimensions 270mm (W) 205mm (H) 75mm (D)
Weight 0.95kg
2012/19/EU (WEEE directive): Products marked with this symbol cannot be disposed of as unsorted municipal waste in the European Union. For proper recycling, return this product to your local supplier upon purchase of equivalent new equipment, or dispose of it at designated collection points. For more information see www.recyclethis.info
European Union directives
EMS declares that the radio equipment type FireCell Radio Hub is in compliance with Directive 2014/53/EU. The full text of the EU declaration of conformity is available at the following internet address: www.emsgroup.co.uk
Approved to
EN54-18:2005. Fire detection and fire alarm systems. Part 18: Input/output devices.
EN54-25:2008. Incorporating corrigenda September 2010 and March 2012. Fire detection and fire alarm systems. Part 25: Components using radio links.
Certification
Certification body
CPR Certificate DOP 0359-CPR-0028
9 Configuration
The Radio Hub’s programming and loop address are configured within the menu structure of the Radio Hub.
8 Applying Power
Apply power to the Control Panel. The normal LED states for the Radio Hub are as below:
10 Close Radio Hub
Ensure that the Radio Hub PCB is correctly inserted and that the PCB retaining screws are refitted.
Refit the Radio Hub lid, ensuring the LEDs are not damaged by the light pipe when refitting.
POWER
FAULT
SYSTEM FAULT
RADIO HUB
Healthy LED - Green LED will be on.
Fault LED - Yellow LED will be off.
Sys Fault LED - Yellow LED will be off.
7 Connection Wiring
Loop cables should only be passed via the access points available.
Flame retardant cable glands must be used.
DO NOT leave excess cable in the Radio Hub.
Repeat for Loops 2, 3 and 4 if used.
Radio Hub Loop 1 connection
+
-
Control Panel
Loop 1
LOOP 1
+
-
IN OUT
+
-
LOOP 2
+
-
IN OUT IN OUT
+
-
+
-
OUT
IN
Refer to the programming manual (Doc Ref: MK98) for details of compatible FireCell devices and full programming information.
Free to download from www.emsgroup.co.uk
0359
10
Manufacturer EMS Ltd. Technology House, Herne Bay, Kent, CT6 8JZ, United Kingdom
Year of manufacture See devices serial number label
Regulatory InformationSpecification
©2018 EMS Ltd. All rights reserved Page 2 of 2 TSD052 Iss 17 05/09/2018 AJM