EMS FireCell FCX-170-001, FireCell FCX-175-001, FireCell FCX-176-001, FireCell FCX-177-001 Installation Manual

www.emsgroup.co.uk
Radio Detector Base
PRESS HERE TO
LOG ON
IDENT
www.emsgroup.co.uk
Radio Detector Base
LOG ON
IDENT
63mm
1 Pre Installation
4 Power Device
3 Fix Mounting Plate
2 Components
device
unpowered
(pins unlinked)
device
powered
(both pins linked)
!
Installation must conform to applicable local installation codes and
should only be installed by a fully trained
competent person.
Ensure that the device is installed as per the site survey.
The use of a non-metallic spacer should be considered if mounting the device on to a metal surface.
Do NOT Press the Log On button on a pre-programmed device, as this will cause communication with the Control Panel to be lost. Should this happen, delete the device from the system and add it back on.
Detector Wireless Module
Mounting Plate
2
3
Remove the mounting plate from the wireless module by turning it anticlockwise.
4
Use both mounting holes to ensure a firm fixing.
Use suitable fasteners and fixings.
Once powered, reassemble the device.
Wireless Detector Installation Guide
FCX-170-001 Wireless Detector Base Only [3] FCX-175-001 Heat A1R Detector Only [1] FCX-176-001 Heat CS Detector Only [1] FCX-177-001 Optical Smoke Detector Only [2]
Example shown:
FCX-177-001
FCX-170-001
Part No Product Description
See the Specification section for compliance information.
CPR
SIZE AA
SIZE AA
SIZE AA
SIZE AA
SIZE AA
SIZE AA
ATTENTION
OBSERVE PRECAUTIONS
FOR HANDLING
ELECTROSTATIC
SENSITIVE
2
43
1
Dust Cover
1
When fitting / replacing batteries; observe correct polarity, using only specified batteries.
Connect the power jumper across the PIN header.
The detector can also be locked into the wireless module. To do so, prior to refitting the detector,
remove the cut out (shaded) section as shown.
5 Optional Device Locking
To lock the wireless module into the mounting plate,
insert a 1.5mm Allen key into the allen key slot and turn clockwise as shown
.
To unlock the wireless module from the mounting plate, insert a 1.5mm Allen key and turn anticlockwise to release as shown.
6 Device Unlocking
To unlock the detector from the wireless module, insert a
1.5mm Allen key and lever the Allen key towards the outside of the device whilst turning the detector anticlockwise to release as shown.
©2018 EMS Ltd. All rights reserved Page 1 of 2 TSD044 Iss 12 05/09/2018 AJM
www.emsgroup.co.uk
Radio Detector Base
PRESS HERE TO
LOG ON
IDENT
Operating Temperature -10°C to 55°C
Storage Temperature 5°C to 30°C
Humidity Up to 95% non-condensing
Supply 6x AA Alkaline (Panasonic LR6AD Powerline /
Varta 4006 Industrial)
CAUTION! Fitting of an incorrect battery type invalidates the product certification and may result in poor performance.
IP Rating IP23
Operating Frequency 868MHz
Output Transmitter Power Auto adjusting 0 - 14 dBm (0 - 25 mW)
Dimensions 113mm (Ø) 40mm (D) (No detector)
113mm (Ø) 81mm (D) (With detector)
Weight 0.40kg (with detector)
Location Type A: For indoor use
2012/19/EU (WEEE directive): Products marked with this symbol cannot be disposed of as unsorted municipal waste in the European Union. For proper recycling, return this product to your local supplier upon purchase of equivalent new equipment, or dispose of it at designated collection points. For more information see www.recyclethis.info Dispose of your batteries in an environmentally friendly manner according to your local regulations.
European Union directives
EMS declares that the radio equipment type FireCell Detector is in compliance with Directive 2014/53/EU. The full text of the EU declaration of conformity is available at the following internet address: www.emsgroup.co.uk
Certification
Certification body
CPR Certificate See part listing for associated products: DOP [1]0359-CPR-0015, [2]0359-CPR-0017 &
[3]0359-CPR-0041
0359
10
7 Configuration
The device’s loop address is configured within the menu structure of the Radio Hub.
Refer to the programming manual (Doc Ref: MK98) for full programming information.
Free to download from
www.emsgroup.co.uk
IMPORTANT
Remove dust cover before use.
The device should be tested upon installation and in accordance with local requirements.
Testing should only be carried out by a fully trained competent person.
The Manufacturer recommends regular functional testing of at least once per annum or in accordance with local codes of practice.
Cleaning and repairs must be undertaken by the Manufacturers authorised representative.
Do not open the case to clean inside the detector.
!
Specification
See part listing for associated products: EN54-5:2001. Incorporating Amendment No. 1. Fire detection and fire alarm systems. Part 5: Heat detectors - Point Detectors. [1]
EN54-7:2001. Incorporating Amendment No. 1. Fire detection and fire alarm systems. Part 7: Smoke detectors - Point detectors using scattered light, transmitted light or ionization. [2]
E
N54-25:2008.Incorporating corrigenda September 2010 and March 2012. Fire detection and fire alarm systems. Part 25: Components using radio links. [3]
Approved to
Regulatory Information
Manufacturer EMS Ltd. Technology House, Herne Bay, Kent,
CT6 8JZ, United Kingdom
Year of manufacture See devices serial number label
©2018 EMS Ltd. All rights reserved Page 2 of 2 TSD044 Iss 12 05/09/2018 AJM