EMS FireCell FC-555-024, FireCell FC-555-324 Installation Manual

1 Pre Installation
All five circled fixing positions are available for use.
The key hole can also be used for locating and fixing where required.
2 Components
Part No Product Description
!
Installation must conform to applicable local installation codes and
should only be installed by a fully trained
competent person.
Ensure the RCC is installed as per the site survey.
Refer to step 3 to ensure optimised wireless performance.
If using remote aerials with this product, refer to the Remote Aerial Installation guide for more information.
6 Fix to the Wall
4 Optional PCB Removal
5 Remove Cable Entry Points
Drill the cable entry points as necessary.
Radio Cluster Communicator
POWER
FAULT
1
2
3
4
5
= Do Not Use
= Available Cable Entry Points
3 Mounting Location Guidelines
POWER FAULT
0.6m
2m
Power
Supply
RCC
24Vdc Radio Cluster Communicator (RCC) Installation Guide
RADIO CLUSTER COMMUNICATOR
POWER
FAULT
FC-555-024 FC-555-324
24Vdc Powered RCC 24Vdc RCC c/w remote aerial facility
Ensure the RCC is not installed within 2m of other wireless or electrical equipment.
The RCC must not be installed within 0.6m of any metal work.
Note: the above points exclude the power supply, provided it is mounted below the RCC as shown.
Remove the three circled retaining screws, before unclipping the PCB.
RESET
LOGONBACK
HEALTHY
FAULT
SYS FAULT
RF1 RF2
ATTENTION
OBSERVE PRECAUTIONS
FOR HANDLING
ELECTROSTATIC
SENSITIVE
For optimum wireless performance,the following must be observed:
4x Corner Covers 4x Lid Screws 1x RCC Lid
1x RCC PCB
1x RCC Box
1
2
3
4
5
©2018 EMS Ltd. All rights reserved Page 1 of 2 TSD054 Iss 8 05/09/2018 AJM
RADIO CLUSTER COMMUNICATOR
POWER
FAULT
LOGONBACK
Figure 9
POWER 1 POWER 2
+ - + -
OK
OK
DO NOT ADJUST VR1
L N
BATTERY FUSE
3.15AF F2
CONN4 FAULT RELAY
CONN3
CONN1
+v
Battery
0v
+v
Output
0v
PLK1
NO NCC
PLK2
PL2 Temp
PL1
Display
off
Charg
e
0v
CONN5
PRIMARY FUSE F1
1ATH 250V HRC
0V
+V
0V
+V
Output
CONN3
CN/CN/O
CONN4
Fault
RESET
LOGONBACK
HEALTHY
FAULT
SYS FAULT
RF1 RF2
Figure 9
POWER 1 POWER 2
+ - + -
OK
OK
9 Configuration
The RCC’s programming and loop address are configured within the menu structure of the Radio Hub.
TX
RESET
RX
HEALTHY
FAU LT
SYS
FAU LT
RF1 RF2
8 Applying Power
Apply power to the power supply. The normal LED states for the RCC are as below:
10 Close RCC
Ensure that the RCC PCB is correctly inserted and the PCB retaining screws are refitted.
Refit the RCC lid, ensuring LEDs are not damaged by the light pipe when refitting.
Healthy LED - Green LED will be on.
Fault LED - Yellow LED will be off.
Sys Fault LED - Yellow LED will be off.
Power 1 LED - Green LED will be on.
Power 2 LED - Green LED will be on.
7 Connection Wiring
Power cables should only be passed via the access points available.
Flame retardant cable glands should be used.
DO NOT leave excess cable in the RCC.
RADIO CLUSTER COMMUNICATOR
POWER
FAULT
Operating Temperature -10°C to 55°C
Storage Temperature 5°C to 30°C
Humidity Up to 95% non-condensing
IP Rating IP54
Operating Voltage 17 to 28Vdc
Power Requirements 17mA @ 24Vdc
Operating Frequency 868MHz
Output Transmitter Power Auto adjusting 0 - 14 dBm (0 - 25 mW)
Dimensions 270mm (W) 205mm (H) 75mm (D)
Weight 0.95kg
Application Indoor use only
2012/19/EU (WEEE directive): Products marked with this symbol cannot be disposed of as unsorted municipal waste in the European Union. For proper recycling, return this product to your local supplier upon purchase of equivalent new equipment, or dispose of it at designated collection points. For more information see www.recyclethis.info
Certification
Certification body
CPR Certificate DOP 0359-CPR-0046
Approved to
EN54-18:2005. Fire detection and fire alarm
systems. Part 18: Input/output devices.
EN54-25:2008. Incorporating corrigenda September 2010 and March 2012. Fire detection and fire alarm systems. Part 25: Components using radio links.
European Union directives
Refer to the programming manual (Doc Ref: MK98) for full programming information.
0359
Free to download from www.emsgroup.co.uk
12
Regulatory InformationSpecification
Manufacturer EMS Ltd. Technology House, Herne Bay, Kent,
CT6 8JZ, United Kingdom
Year of manufacture See devices serial number label
EMS declares that the radio equipment type FireCell 24Vdc RCC is in compliance with Directive 2014/53/EU. The full text of the EU declaration of conformity is available at the following internet address: www.emsgroup.co.uk
©2018 EMS Ltd. All rights reserved Page 2 of 2 TSD054 Iss 8 05/09/2018 AJM