1 Pre Installation
5 Power Device
3 Disassemble Device
2 Components
device
unpowered
(pins unlinked)
device
(both pins linked)
!
Installation must conform to applicable local installation codes and
should only be installed by a fully trained
competent person.
Ensure that the device is installed as per the site survey.
The use of a non-metallic spacer should be considered if mounting the device on to a metal surface.
Do NOT Press the Log On button on a pre-programmed device. This will cause communication with the Control Panel to be lost. Should this happen, delete the device from the system and add it back on.
Wireless Module Mounting Plate
6 Optional Locking
To lock the remote indicator into the wireless module, remove the cut out section as shown.
Disengage the mounting plate by turning the wireless module anticlockwise, whilst pressing down the locking pin.
Once powered, reassemble the device.
Wireless Remote Indicator Module Installation Guide
FCX-178-001 Wireless Remote Indicator Module FCZ-170-111 Remote Indicator Wireless Module Only 117261 Remote Indicator Only
Example shown:
Model FCX-178-001
Part No Product Description
ATTENTION
OBSERVE PRECAUTIONS
FOR HANDLING
ELECTROSTATIC
SENSITIVE
2
3
Remote Indicator
1
When fitting / replacing batteries; observe correct polarity, using only specified batteries.
Connect the power jumper across the PIN header.
31 2
First disengage the remote indicator from the wireless module by turning it anticlockwise. This exposes the wireless module’s locking pin as shown.
www.emsgroup.co.uk
Wireless Detector Base
PRESS HERE TO
LOG ON
Part No: FCZ-170-111
4 Fix Mounting Plate
Use all four mounting holes to ensure a firm fixing.
Use suitable fasteners and fixings.
THIS WAY UP WHEN WALL
MOUNTING
When wall mounting, ensure the mounting plate is fitted in the orientation shown.
www.emsgroup.co.uk
Wireless Detector Base
PRESS HERE TO
LOG ON
Part No: FCZ-170-111
Locking Pin
©2018 EMS Ltd. All rights reserved Page 1 of 2 TSD116 Iss 3 05/09/2018 AJM
7 Configuration
The device’s loop address is configured within the menu structure of the Radio Hub.
Refer to the Wireless Remote Indicator Programming Instructions (Doc Ref: TSD115) for further information.
Free to download from
www.emsgroup.co.uk
Operating Temperature -10°C to 55°C
Storage Temperature 5°C to 30°C
Humidity Up to 95% non-condensing
Supply 6x AA Alkaline (Panasonic LR6AD Powerline /
Varta 4006 Industrial)
CAUTION! Fitting of an incorrect battery type invalidates the product certification and may result in poor performance.
IP Rating IP23
Operating Frequency 868MHz
Output Transmitter Power Auto adjusting 0 - 14 dB (0 - 25 mW)
Dimensions 113mm (Ø) 81mm (D)
Weight 0.40kg
Location Type A: For indoor use
2012/19/EU (WEEE directive): Products marked with this symbol cannot be disposed of as unsorted municipal waste in the European Union. For proper recycling, return this product to your local supplier upon purchase of equivalent new equipment, or dispose of it at designated collection points. For more information see www.recyclethis.info Dispose of your batteries in an environmentally friendly manner according to your local regulations.
European Union directives
EMS declares that the radio equipment type FireCell Wireless RIM is in compliance with Directive 2014/53/EU. The full text of the EU declaration of conformity is available at the following internet address: www.emsgroup.co.uk
Certification
Certification body
CPR Certificate DOP 0359-CPR-00127
0359
10
Specification
E
N54-25:2008. Incorporating corrigenda September 2010 and March 2012. Fire detection and fire alarm systems. Part 25: Components using radio links.
Approved to
Regulatory Information
Manufacturer EMS Ltd. Technology House, Herne Bay, Kent,
CT6 8JZ, United Kingdom
Year of manufacture See devices serial number label
To unlock the device, insert a flat bladed screwdriver into the release slot and turn the remote indicator anticlockwise to release, as shown.
6 Unlocking
©2018 EMS Ltd. All rights reserved Page 2 of 2 TSD116 Iss 3 05/09/2018 AJM