EMRI LX4 Instruction Manual

LX4
Voltage regulator for generators
Instruction Manual V3.1.1
Manual V3.1.1 Page 2 of 36
Warnings
The manual does not cover all technical details of the product. Specifications may be modified by the manufacturer without notice. For further information, the manufacturer should be contacted.
WARNING
The system should not be installed, operated, serviced or modified except by qualified personnel who understand the danger of electric shock hazards and have read and understood the user instructions
.
ELECTRICAL HAZARDOUS VOLTAGES DANGEROUS DO NOT OPERATE WHEN NOT FAMILIAR WITH GENERATORS
WARNING
Dangerous voltages are present at the voltage regulator board. Accidental contact with live conductors could result in serious electrical shock or electrocution. Disconnect the power source before making repairs, connecting test instruments, or removing or making connections to the voltage regulator or generator.
WARNING
Never work on a LIVE generator. Unless there is another person present who can switch off the power supply or stop the engine
WARNING
Due to liability reasons, EMRI products may not be used, applied or commissioned in equipment residing under law of the United States of America or Canada. Neither may EMRI products be applied or commissioned by any person residing under law of the United States of America or Canada.
Manual V3.1.1 Page 3 of 36
Table of contents
Part 1/2
1. Introduction
1.0 General description 5
1.1 AVR Layout 5
1.2 Absolute maximum ratings 6
1.3 Commissioning information 6
2. Installation
2.0
Interfaces overview 7
2.1 Adjustments overview 8
2.2 Terminals overview 9
2.3 Electrical characteristics 10
3. Operation and maintenance
3.0 AVR status 11
3.1 Modes of control 11
3.1.0 Idle
11
3.1.1 Build-up
11
3.1.2 Voltage control
12
3.2 Setpoint limiting 13
3.2.0 Introduction
13
3.2.1 Excitation current limiting
14
3.2.2 Generator over temperature limiting
15
3.2.3 Underspeed limiting
16
3.3 Special functions 17
3.3.0 Self Excitation
17
3.4 CAN bus 18
3.4.1 Introduction
18
3.4.2 CAN status LED
18
3.4.3 CAN heartbeat
18
3.4.4 CAN AVR measurements & status
19
3.4.5 CAN control
20
4 Protections and diagnose
4.1 LED error codes 21
4.2 Protections 21
4.2.0
Over excitation protection
22
4.2.1 Generator over temperature protection
23
4.2.2 AVR over temperature protection
24
4.2.3 Phase loss / phase sequence protection
25
4.2.4 Over voltage protection 110%
26
4.2.5 Over voltage protection 125%
27
Manual V3.1.1 Page 4 of 36
Table of contents
Part 2/2
5 Settings and adjustments
5.1 Generator voltage 28
5.2 P & I stability 28
5.3 Underspeed frequency 28
5.4 Dipswitch settings 29
5.5 T.Disable header 30
5.6 SE header 30
5.7 EXT.POT. header 30
5.8 CAN Termination header 30
5.9 Factory settings 31
6 Wiring diagrams
6.1 Wiring diagram single auxiliary supply winding 32
6.2 Wiring diagram double auxiliary supply winding 33
6.3 Wiring diagram transformer supply 34
Appendix
General Installation information 35
Manual V3.1.1 Page 5 of 36
1. INTRODUCTION
1.0 General description
This manual contains instructions for installing, operating and maintaining the LX4 Automatic Voltage Regulator (AVR).
1.1 AVR Layout
The AVR is protected against environmental influences by a PUR coating. Prefabricated links are provided for T.Disable, EXT.POT and CAN termination
WVUS2S1T1 T2LH1 LH2- +
F
on
dip
1
2 3 4
Status
LED
V P I D
JTAG
Interface
EME RD200.1
Firmware: V1.x
Nr: 1234
Hardware: V1.x
Prod: 0106
Ede NL
CAN Interface
CAN LED
T.Disable
CAN Termination
FUSE
LHGND NC
LH3 LH4
SE
EXT.
POT.
28 23130,00
9,00
115,00
9,00
Fig 1. AVR layout
Max AVR height: 60 mm Dimensions in mm
Manual V3.1.1 Page 6 of 36
1.2 Absolute maximum ratings
Symbol
Parameter
Condition
Min.
Max.
Unit
U,
V,
W Voltage sensing input
< 30 s.
-
500 VAC
+, -
AVR field current
Continuous
< 10 s.
-
- 3
6 A
DC
ADC
LH1-LH2,
LH3-LH4
Supply input
1 phase connected (dc
-
400Hz)
3 phases connected (dc-400Hz)
20
15
100
100
V
V
R
field
Field resistance
@ 100 V
LH1-2 LH3-4
(rms)
@ 60 V
LH1-2 LH3-4
(rms)
10
6 -
-
Ω Ω
T
AMB
Operating temperature
95 % RHD non condensing
-20 +70
°C
T
STG
Storage temperature
95 % RHD non condensing
-20 +85
°C
S1,S2
Unused terminals
EXT. POT.
External Volt adjust
- 10 kΩ
FUSE
Fuse rating
Time delay
4 AT
Table 1. Absolute maximum ratings
1.3 Commissioning information
The system should not be installed, operated, serviced or modified except by qualified personnel who understand the danger of electric shock hazards and have read and understood the user instructions.
Defects in the generator or AVR may cause consequential loss. Precautions must be taken to prevent this from occurring.
Never work on a LIVE generator. Unless there is another person present who can switch off the power supply or stop the prime mover.
Dangerous voltages are present at the voltage regulator board. Accidental contact with live conductors could result in serious electrical shock or electrocution. Disconnect the power source before making repairs, connecting test instruments or removing or making connections to the voltage regulator.
The unit should be installed with respect to the environmental specifications as well as the rules mentioned in the General installation information. For safety reasons the Voltage level potentiometer is best turned completely counter clockwise in order to start at the lowest possible voltage.
Manual V3.1.1 Page 7 of 36
2. INSTALLATION
For a complete wiring diagram refer to chapter 6: Wiring diagrams.
2.0 Interfaces overview
Status
LED
JTAG
Interface
CAN Interface
CAN LED
LHGND NC
Fig 2. Interfaces overview
Symbol
Description
Notes
Status LED AVR control mode & Error diagnostics See Table 6 and 11 CAN LED CAN bus control mode & Error diagnostics See Table 7 CAN Interface.L CAN bus low wire CAN Interface.H CAN bus high wire CAN Interface.GND CAN bus ground CAN Interface.NC Not connected JTAG Interface Maintenance port
Table 2. Interfaces
Manual V3.1.1 Page 8 of 36
2.1 Adjustments overview
F
on
dip
1
2 3 4
V P I D
Fig 3. Adjustments overview
Symbol
Description
Notes
V Generator voltage setpoint P Proportional gain setpoint I Integral time setpoint D Unused Should be in CCW position F Underspeed setpoint Dipswitch 1 Sensing voltage selection Off = 400Vac On = 230V
ac
Dipswitch 2 Phaseloss protection Off = disabled On = enabled Dipswitch 3 Control mode selection Off = Constant voltage On = VPH Dipswitch 4 Overexcitation threshold Off = 2A On = 4A
Table 3. Adjustments
DO NOT CHANGE DIPSWITCH SETTINGS DURING OPERATION
Manual V3.1.1 Page 9 of 36
2.2 Terminals overview
WVUS2S1T1 T2LH1 LH2- +
T.Disable
CAN Termination
LH3 LH4
SE
EXT.
POT.
Fig 4. Terminals overview
Symbol
Description
Notes
U, V, W Voltage sensing input phase sequence UVW S1, S2 Unused terminals T1, T2 Temperature sensor input KTY84-130, PTC or Clixon sensor LH1, LH2 LH3, LH4
Supply inputs For self excitation, the auxiliary supply
winding must be connected to LH3-LH4 +, - Field excitation output SE Self Excitation link
(Caution: High voltage)
Never fit or remove link while generator is in
operation
Shorting SE enables self excitation. EXT. POT. External voltage adjust input
10
k
Ω potentiometer
T.Disable Disables T1 – T2 sensing Shorting T.Disable disables temperature
protection CAN Termination CAN bus termination link Shorting enables 120 Ohm bus termination
Table 4. Terminals
Manual V3.1.1 Page 10 of 36
2.3 Electrical characteristics
Symbol
Parameter
Condition
Min.
Max.
Unit
U, V, W
Voltage sensi
ng input
50-60 Hz 20 480 VAC
+, - AVR field current
- 3 ADC
LH1
– LH2,
LH3 – LH4
Supply input
dc -
400 Hertz
20 100
VAC
R
field
Field resistance
10 -
T
AMB
Operating temperature
95 % RHD non condensing
0
+70
°C
T
STG
Storage temperature
95 % RHD
non condensing
-20 +85
°C
S1 – S2
Unused terminals
EXT. POT.
External Volt adjust
10k
Ω potentiometer
0 10 kΩ
FUSE
Fuse rating
Ceramic,
Time delay
4 AT
Table 5. Electrical characteristics
Stresses above those listed under “Absolute Maximum Ratings” may cause permanent damage to the device. This is a stress rating only and functional operation of the device at those or any other conditions above those indicated in the operation listings of this specification is not implied. Exposure to maximum rating conditions for extended periods may affect device reliability and lifetime.
Manual V3.1.1 Page 11 of 36
3. Operation and maintenance
3.0 AVR Status LED
The AVR’s mode of control is indicated by the status LED. The options are depicted in table 6.
Table 6. AVR status
3.1 Modes of control
3.2.0 Idle
When a supply is connected to the AVR but the generator frequency is below 25Hz, the AVR enters idle mode. During idle mode field excitation is inhibited however all protections remain functional.
3.1.1 Build-up
When the generator frequency rises above 25Hz, the AVR enters the build up mode. The generator voltage is ramped up to the voltage setpoint. When the generator voltage is close to the desired nominal value, the status led signals continuous green. Diagram 1 shows the sequence of events.
Diagram 1. Build up
Manual V3.1.1 Page 12 of 36
3.1.2 Voltage control
When dipswitch 3 is in off position, the AVR performs constant voltage control after finishing the build up mode. The voltage/ frequency characteristic is depicted in diagram 2.
Below the underspeed frequency, set by potentiometer F, the generator voltage is controlled according a Volt per Hertz ramp. Below 25Hz the AVR control mode returns to idle and excitation is stopped. As a consequence the generator voltage will then drop to the residual voltage level. For a detailed description of potentiometer F see chapter 5.4.
Diagram 2. Constant Voltage control
When dipswitch 3 is in on position, the AVR performs Volt per Hertz control after finishing the build up mode. The voltage/ frequency characteristic is depicted in diagram 3.
Diagram 3. Volt per Hertz Control
Manual V3.1.1 Page 13 of 36
3.2 Setpoint limiting
3.2.0 Introduction
The AVR is equipped with both limiting functions and protections.
The limiting functionality lowers the voltage- or excitation setpoint if a certain threshold is exceeded. When the measured quantity no longer exceeds the threshold, the setpoint is increased again. This enables the AVR to recover from the situation.
The protections also lower the voltage setpoint, upon exceeding a certain threshold. However Recovery is only possible by resetting the AVR. This is accomplished by interrupting the AVR supply (LH1-LH2 and LH3-LH4) for at least 5 seconds. In case an auxiliary supply winding is used this may be accomplished by stopping the generator.
When a protection is triggered the voltage setpoint is decreased to a fixed level of 95V. Keep in mind that the actual generator voltage may larger than 95V due to the generator’s residual magnetism.
For a detailed description of all protections refer to chapter 4.
Manual V3.1.1 Page 14 of 36
3.2.1 Excitation current limiting
When the excitation current level, selected by dipswitch 4, is exceeded for more than 5 second, the AVR controls the excitation current to the selected level.
Excitation current control is visualized by the status LED signalling continuous orange.
When the excitation current decreases below the selected threshold again, for more than 5 second, voltage control is resumed. The AVR ramps back to the voltage setpoint, while signalling a orange blinking status LED. When the generator voltage is close to the desired nominal value, the status led becomes continuous green.
Diagrams 5 shows a sequence of events for diagnosis purposes in case of excitation limiting.
Diagram 5. Excitation limiting
Manual V3.1.1 Page 15 of 36
3.2.2 Generator over temperature limiting
The generator temperature may be sensed either by a clixon, PTC or KTY84-130 sensor connected to terminals T1-T2. The over temperature limiting and protection can be disabled by omitting the temperature sensor and shorting link T.Disable
If a clixon or PTC is connected no absolute temperature can be measured, only the exceeding of a threshold. In this case the generator over temperature protection is triggered simultaneously with the over temperature limiting function. This causes the AVR to decrease the voltage setpoint to 95V. The generator over temperature protection is described in 4.2.1.
If a KTY84-130 sensor is connected and the generator temperature exceeds 160ºC for more than 5 seconds, the AVR decreases the voltage level. The voltage level is decreased linear, inverse proportional to the temperature transgression by 1.5V/ºC.
Active voltage limiting is visualized by the status LED signalling continuous orange.
When the generator temperature decreases, voltage is increased again until the nominal voltage. When the generator voltage is close to the desired nominal voltage, the status led becomes continuous green again.
Diagram 6 shows a sequence of events for diagnosis purposes in case of generator over temperature limiting.
Diagram 6. Over temperature limiting
Manual V3.1.1 Page 16 of 36
3.2.3 Underspeed limiting
The goal of the underspeed limiting is to prevent damage to the generator caused by overexcitation. When the generator frequency drops below the underspeed setpoint, F
underspeed
, the generator voltage is decreased linear, proportional to the generator frequency.
The underspeed setpoint is set by potentiometer F, as is described in 5.4.
Active underspeed limiting is visualized by the status LED signalling continuous orange, however only when the constant voltage control mode is selected (dipswitch 3 = ‘ on’).
In case the generator frequency drops below 25Hz excitation is stopped completely and the AVR control mode becomes idle. This is visualized by a green blinking status LED.
Diagrams 7 shows a sequence of events for diagnosis purposes in case of underspeed limiting during constant voltage control.
Diagram 7. VPH underspeed limiting
Manual V3.1.1 Page 17 of 36
3.3 Special functions
3.3.0 Self Excitation
When the AVR supply voltage, connected to LH1-2 and LH3-4, is insufficient to supply the AVR, self excitation can be used. Self excitation is enabled by shorting the SE terminal. The self excitation circuit redirects the AVR supply voltage to the generator’s exciter field uncontrolled, bypassing the internal controller. This field flashing causes the generators flux to increase, amplifying the supply voltage. When the supply voltage has increased to a level sufficient to supply the AVR, the self excitation circuit is disabled again. Hereafter, the AVR’s internal controller builds up the generator voltage.
Diagram 8 shows a sequence of events with enabled self excitation, for diagnosis purposes.
Caution:
Never fit or remove the SE link when the generator is operation.
This is a live conductor, contact can result in serious electrical shock.
Diagram 8. Self Excitation
Manual V3.1.1 Page 18 of 36
3.4
CAN-bus
3.4.1 Introduction
The AVR is equipped with a CAN bus interface. The CAN interface enables the user to obtain detailed information about the AVR status, measured quantities and to adjust AVR control setpoints.
The interface complies with CAN specification 2.0B. The AVR communication operates at a transfer rate of 250kBit/s and uses standard frame (11-bit) message identifiers.
3.4.2 CAN status LED
The CAN bus status is indicated by the CAN status LED. The options are depicted in table 7.
Table 7. CAN status
3.4.3 CAN heartbeat
The AVR sends a heartbeat signal when the AVR is powered. This signal may be used to assess the proper functioning of the CAN bus communication. The heartbeat consists of a message with ID 0x70A and is sent every 500ms. The message content is 1 byte long and alternating 0x05 or 0x85 .
Heartbeat
ID:0x70A
Byte
Description
Value
Remarks
0 Alternating heartbeat
0x05 ~ 0x85
Table 8. CAN heartbeat
Manual V3.1.1 Page 19 of 36
3.4.4 CAN AVR measurements & status
When the AVR is powered a message containing AVR measurements and the present AVR status is sent. The message with ID 0x18A is sent every 500ms. The definition of the 8 byte content is described in table 9
AVR measurements & status
ID:0x18A
Byte
Description
Value
Unit
Remarks
0 Gener
ator voltage
0-
255 V Phase
- Neutral
1 Excitation current ratio
0-
100 % (Byte 5 / Byte 3) * 100%
2 Generator temperature
0-
255 ºC
3 Excitation current
0-
255 0.01A
4 Generator frequency
0-
255 0.5Hz
5 Excitation current setpoint
0-
255 0.01A
6 Statu
s AVR
Bitwise AVR statusregister
bit 0
Generator current limiting
1 - 0 bit 1 = active
bit 1
Excitation current limiting
1 - 0 bit 1 = active
bit 2
Over temperature generator limiting
1 – 0 bit 1 = active
bit 3
Over temperature AVR limiting
1 – 0 bit 1 = active
bit 4
Underspeed limiting
1 – 0 bit 1 = active
bit 5
Overvoltage 440V protection
1 – 0 bit 1 = triggered
bit 6
Overvoltage 500V protection
1 – 0 bit 1 = triggered
bit 7
Phaseloss protection
1 – 0 bit 1 = triggered
7 AVR temperature
0-
255 ºC Measured at MCU
Table 9. CAN measurements & status
Manual V3.1.1 Page 20 of 36
3.4.5 CAN control
When the AVR is powered it is possible to obtain remote control over the AVR voltage setpoint and excitation limit setpoint.
To realize CAN control a message with ID 0x20A must be sent at least every 1 seconds complying with the content definition described in table 10. When CAN control is activated, but the AVR has not received a valid control message for the last 1 seconds, CAN control is automatically disabled and normal AVR control is resumed.
Active CAN control is visualized by the CAN status LED signalling continuous orange.
Be aware that when the user enables CAN control over the voltage and/or excitation setpoints, adjustments to the respective potentiometers on the AVR will have no immediate effect. The adjustments will only then be effective when CAN control is disabled and AVR control is resumed again.
CAN control
ID:0x20A
Byte
Description
Value
Unit
Remarks
0 Generator voltage setpoint
0-
255 V Phase
- Neutr
al
1 Excitation current ratio setpoint
0-
100 % Derived from
dipswitch 4 setting
2 - - - not used
3 - - - not used
4 CAN control
Bitwise
CAN commandregister
bit 0
Activate CAN voltage setpoint
1 - 0 bit 1 = active
bit 1
- 0
bit not used
bit 2
- 0
bit not used
bit 3
- 0
bit not used
bit 4
Activate CAN excitation ratio setpoint
1 – 0 bit 1 = active
bit 5
- 0
bit not used
bit 6
- 0
bit not used
bit 7
- 0
bit not used
5 - - - not used
6 - - - not used
7 - -
not used
Table 10. CAN control
Manual V3.1.1 Page 21 of 36
4. Protections and Diagnose
4.1 Led error Codes
Every triggered protection is indicated by an error code signalled by the status LED.
Table 11 shows the relation between the number of red blinks and the error condition.
Table 11. Error codes
4.2 Protections
When an error condition triggers the AVR’s protections, field excitation is limited, decreasing the voltage setpoint to 95V. Nevertheless, the generator voltage could be higher than 95V due to the generator’s remanent voltage.
The AVR may be reset from the error condition by interrupting the AVR supply (LH1-LH2 and LH3-LH4) for at least 5 seconds. In case an auxiliary supply winding is used this can be accomplished by stopping the generator. After a successful reset the AVR restarts from idle mode and any information concerning the previous error is lost.
Manual V3.1.1 Page 22 of 36
4.2.0 Over excitation protection
The over excitation protection validates the generator field excitation measured on terminals + and -.
If the field excitation current exceeds the threshold of 6A for longer than 5s, the over excitation protection is triggered, decreasing the generator voltage setpoint to 95V.
An over excitation error is visualized by the status LED blinking red two times. The AVR may be reset from the error condition by interrupting the AVR supply (LH1-LH2 and LH3-LH4) for at least 5 seconds. In case an auxiliary supply winding is used this can be accomplished by stopping the generator.
Diagram 11 shows a sequence of events for diagnosis purposes in case of an over excitation error.
Diagram 11. Over excitation protection
Manual V3.1.1 Page 23 of 36
4.2.1 Generator over temperature protection
The generator over temperature protection validates the generator temperature, sensed by either a clixon, PTC or KTY84-130 sensor, connected to terminals T1-T2. The over temperature limiting and protection can be disabled by omitting the temperature sensor and shorting terminals T.Disable.
In case a KTY84-130 sensor is connected, the over temperature protection is triggered upon exceeding a generator temperature of 200ºC for 2 seconds. In case a clixon or PTC is connected, the over temperature protection is triggered upon exceeding the specific sensor temperature threshold for 2 seconds. As is described in 3.2.2, fitting a clixon or PTC, instead of a KTY84-130 sensor, effectively disables the generator over temperature limiting.
If the generator over temperature protection is triggered, the generator voltage setpoint is decreased to 95V.
A generator over temperature error is visualized by the status LED blinking red three times. The AVR may be reset from the error condition by interrupting the AVR supply (LH1-LH2 and LH3-LH4) for at least 5 seconds. In case an auxiliary supply winding is used this can be accomplished by stopping the generator.
Diagram 12 shows a sequence of events for diagnosis purposes in case of a generator over temperature error.
Diagram 12. Generator over temperature
Manual V3.1.1 Page 24 of 36
4.2.2 AVR over temperature protection
The AVR over temperature protection validates the AVR temperature, measured by an internal sensor. If the over temperature limit of 85°C is exceeded for 20 seconds, the generator voltage setpoint is decreased to 95V.
An AVR over temperature error is visualized by the status LED blinking red four times.
The AVR may be reset from the error condition by interrupting the AVR supply (LH1-LH2 and LH3-LH4) for at least 5 seconds. In case an auxiliary supply winding is used this can be accomplished by stopping the generator.
Diagram 13 shows a sequence of events for diagnosis purposes in case of an AVR over temperature error.
Diagram 13. AVR over temperature
Manual V3.1.1 Page 25 of 36
4.2.3 Phase loss / phase sequence protection
The functionality of the protection is twofold.
First; The phase sequence protection validates the order of the phase sequence connected to terminals U, V and W to be clockwise (U
VW). Second, the phase loss protection validates the presence of all three generator phases on the terminals U, V and W.
In case an incorrect phase sequence is measured, the protection is usually triggered during the build up mode of the AVR. The protection decreases the generator voltage to 95V and visualizes the error by blinking the status LED red five times.
Second; In case one of the phases U, V or W is not sensed for at least 500ms, the phaseloss protection is triggered.
If the phaseloss protection is triggered, the generator voltage setpoint is decreased to 95V and the error is visualized by the status LED blinking red five times.
The AVR may be reset from the error condition by interrupting the AVR supply (LH1-LH2 and LH3-LH4) for at least 5 seconds. In case an auxiliary supply winding is used this can be accomplished by stopping the generator.
Diagram 14 shows a sequence of events for diagnosis purposes in case of a phaseloss error.
Diagram 14. Phaseloss
Manual V3.1.1 Page 26 of 36
4.2.4 Over voltage protection 110%
The 20% over voltage protection validates the generator voltage on terminals U,V and W. If an over voltage condition is detected but relieved within two seconds, the protection is not triggered and normal control proceeds.
If the over voltage limit of 110% is exceeded for at least 2 second, the over voltage protection is triggered and the generator voltage setpoint is decreased to 95V. The over voltage error is visualized by the status LED blinking six times.
The AVR may be reset from the error condition by interrupting the AVR supply (LH1-LH2 and LH3-LH4) for at least 5 seconds. In case an auxiliary supply winding is used this can be accomplished by stopping the generator.
Diagrams 15 shows a sequence of events for diagnosis purposes in case of an 110% over voltage error.
Diagram 15. 110% Over voltage
Manual V3.1.1 Page 27 of 36
4.2.5 Over voltage protection 125%
The 125% over voltage protection validates the generator voltage on terminals U,V and W. If an over voltage condition is detected but relieved within one second, the protection is not triggered and normal control proceeds.
If the over voltage limit of 125% is exceeded for at least 1 second, the over voltage protection is triggered and the generator voltage setpoint is decreased 95V. The over voltage error is visualized by the status LED blinking seven times. The AVR may be reset from the error condition by interrupting the AVR supply (LH1-LH2 and LH3-LH4) for at least 5 seconds. In case an auxiliary supply winding is used this can be accomplished by stopping the generator.
Diagrams 16 shows a sequence of events for diagnosis purposes in case of an 125% over voltage error.
Diagram 16. 125% Over voltage
Manual V3.1.1 Page 28 of 36
5. Settings and adjustments
5.1 Generator Voltage
The generator voltage setpoint is user adjustable by means of the V potentiometer. The voltage potentiometer range is U
nom
±12.5%. Turning the potentiometer clockwise increases the generator voltage, turning counter clockwise decreases the generator voltage.
5.2 P & I stability
The generator stability and dynamic response are adjustable by means of the P, proportional, and I, integral action, potentiometers. Turning the proportional action potentiometer clockwise increases the proportional gain, turning counterclockwise decreases the proportional gain. Turning the integral action potentiometer clockwise decreases the integral time, turning counterclockwise increases the integral time. Tuning the PI-controller must be performed by a control expert to prevent damage to the AVR and generator.
5.3 Underspeed frequency
Potentiometer F sets the underspeed frequency setpoint. The underspeed frequency setpoint is used to decrease voltage, according a VPH slope, at low rpm. This protects the exciter field against over excitation during constant voltage control. For more information, see diagram 2.
As shown in figure 9, turning the potentiometer completely counter clockwise disables the underspeed protection. Be aware that disabling the underspeed protection is not recommendable. This could lead to over excitation, which will inflict serious damage to the generator.
Turning clockwise increases the frequency setpoint from 40Hz to 65Hz
Fig 5. Voltage adjustment
Fig 6. Stability adjustments
Fig 8. Underspeed adjustment
Manual V3.1.1 Page 29 of 36
5.4 Dipswitch settings
The dipswitches are used for enabling or setting several AVR functions. The layout and positions are depicted in table 12. Dipswitch positions must not be changed during operation. Always interrupt the AVR supply or stop the generator before switching any of the dipswitches.
Dipswitch
Description
OFF
ON
1
Sensing Voltage selection
400Vac
230V
ac
2
Phaseloss protection
Protection disabled
Protection enabled
3
Control mode selection
Constant Voltage
Volt Per Hertz
4
Overexcitation threshold
2A 4A
Table 12. Dipswitch settings
Fig 9. Dipswitch settings
DO NOT CHANGE DIPSWITCH SETTINGS DURING OPERATION
Manual V3.1.1 Page 30 of 36
5.5 T.Disable header
When no generator over temperature limiting or protection is desired, this can be disabled by shorting the T.Disable header with a prefabricated link. In this case it is still allowed, but not required to connect a temperature sensor at terminals T1, T2.
5.6 SE header
Caution: Never fit or remove the SE link when the generator is operation, this could result in serious electrical shock.
Shorting the SE header with a supplied prefabricated link, enables the self excitation function of the AVR. Self excitation can be used if the AVR supply voltage is insufficient to start voltage control. See 3.3.0 for an explanation of this feature.
5.7 EXT.POT. header
The generator voltage setpoint is also user adjustable by means of an external 10 k potentiometer. The external potentiometer range is U
nom
-15%. Increasing the impedance, decreases the generator voltage. When no external potentiometer is fitted, the EXT.POT. terminals must be shorted with one of the supplied links.
5.8 CAN Termination header
Shorting the CAN Termination header, by placing a prefabricated link, enables CAN bus termination. The terminator resistance is 120 Ohm. The header must be shorted if the AVR is connected as a CAN bus endpoint.
Fig 10. T.Disable header
Fig 13. CAN Termination header
Fig 11. Self excitation header
Fig 12. EXT.POT. header
Manual V3.1.1 Page 31 of 36
5.9 Factory settings
All new or AVR’s returned from service are supplied with factory settings as described in table
13. Adjusting the factory settings must only be performed by qualified personnel who understand the danger of electric shock hazards and have read and understood the user instructions
Parameter
Value
Unit
Output Voltage
400 Vac
Overe
xcitation
threshold
2A I
exc
P & I stability
Middle position
D 0 %
Underspeed
setpoint
47 Hz
Phaseloss protection
Disabled
-
Control mode selection
Constant Voltage
T.Disable header
Sho
rted with link
SE header
Open
EXT.POT header
Shorted with link
CAN termination header
Shorted with link
Ceramic
Fuse
5x20mm
4 AT
Table 13. Factory settings
Manual V3.1.1 Page 32 of 36
6. Wiring Diagrams
6.1 Wiring diagram single auxiliary supply winding
Manual V3.1.1 Page 33 of 36
6.2 Wiring diagram double auxiliary supply winding
Manual V3.1.1 Page 34 of 36
6.3 Wiring diagram transformer supply
LX4
Connection Diagram
ing. R. van Beekum
04-04-2014
V1.1
ENG
DATE
VERSION
1/1PAGE
WVUS2S1T1 T2LH3 LH4 LH1 LH2- +
on
dip
1 2 3 4
Status
LED
V P I D
F
FUSE
SE
T.Disable
EXT.POT.
CAN Interface
JTAG
Interface
CAN LED
CAN Termination
LX4 V2.0
Firmware: V0.x
Nr: 1234
Hardware: V0.x
Prod: 0106
Ede NL
Exciter Field Rotor Stator
Breaker
Bus
Manual V3.1.1 Page 35 of 36
General installation information
Absolute Maximum Ratings
- The Absolute Maximum Ratings are those limits for the device that, if exceeded, will likely damage the device. Exceeding the absolute maximum ratings voids any warranty and/or guarantee.
Mounting
Mounting of the product should be done in such a way that:
- the absolute maximum ambient temperature rating of the product will never be exceeded.
- maximum cooling (direction of cooling ribs and direction of airflow) is achieved.
- Mounting no humid air can flow through the product or condensation occurs.
- dust or other materials or residue will not remain in or on the product.
- the maximum vibration is not exceeded.
- personal contact with persons is impossible.
Wiring
- Diameter size of the wiring should be enough to carry the expected current. Wire insulation should be enough to withstand the expected operating voltages and temperatures.
- To improve EMC emission and immunity, care should be taken for the lay out of the wiring. This in respect to all wiring in the installation.
- Keep current carrying wires as short as possible.
- Keep wires carrying a total sum of zero Ampere close to each other, or in one single cable, E.g. U, V, W, or J (+) and K (-
), or Phase and neutral, or S and T.
- Avoid current carrying conductors next to sensing or control wiring. Especially current controlled by SCR’s or PWM controlled transistors.
- If sensitive sensing signal cables need to be laid across distance along other cabling, shielded cable is preferred. Keep the shield as long as possible and the wiring outside the shield as short as possible. Do not solder or shrink the shield to a regular wire. Connect the original shield to ground at one side with an as large as possible contact surface.
Additional installation information
- When the product is supplied by means of a transformer, it should never be an auto-transformer. Auto-transformers react as voltage sweep up coil and may cause high voltage peaks.
- Standard fit capacitors or over-voltage suppressers across X (+) and XX (-), or exciter field terminals inside the generator should be removed.
- When the product is supplied by means of a transformer, it should be able to carry at least the maximum expected current. Advisable is, to have a transformer which can carry twice the maximum expected current. Inductive loads make voltage sacks and peeks into the secondary voltage of a transformer, from which the device may malfunction.
- It is not recommended to apply switches in dc outputs. It is preferred to use switches in the ac supply inputs of devices. In case it is unavoidable to have switches in the dc output of a device, action must be taken to avoid over voltage damage to the device due to contact arcing. Use a voltage suppressor across the output.
- It is not recommended to apply switches or fuses in the sensing lines. Defects can cause high voltage situations due to over-excitation.
- When using a step down transformer in medium or high voltage generators, the transformer should be three phase (if three phase sensing), and the transformer should be suitable for acting as a sensing transformer. If the transformer is unloaded, connect a resistor to avoid voltage waveform distortion.
- The phase relation from the generator to the AVR is important. Also when voltage transformers and/ or current transformers are installed.
- When using a step down or insulation transformer in the droop circuit, phase relation from the generator to the AVR is important.
- CT’s wiring, connected to the AVR should never be grounded.
- Always disconnect electronic products, circuits and people before checking the insulation resistance (Megger check).
- Due to differences in generators impedance’s, EMC behavior is not predictable. Therefore the commissioner / installer
should be aware of proper and correct installation.
- Large, highly inductive, exciter stator windings can cause destructive high voltage peaks. Adding a resistor from 10 to 20 times the exciter stator field resistance reduces voltage spikes. If necessary filter can be fitted additionally. (e.g. snubber, RC-network)
- Upon problems during commissioning, faulty behavior or defects in the generator, consult the fault finding manual at our web site
- Some advises may be overdone or seem extraordinary, but since the electrical rules are the same everywhere, these advises are given.
Manual V3.1.1 Page 36 of 36
Contact
EMRI Electronics B.V.
Manufacturer
Morsestraat 10 6716 AH, Ede, Netherlands Tel: +31 (0)318 620 427 Fax: +31 (0)318 634 615 Website: www.emri.nl E-mail: info@emri.nl
ICELAND,
Hafnarfjordur
Rafeining ehf
Tel: +354 565 3049 Fax: +354 565 3048 Website: www.rafeining.is E-mail: rafeining@rafeining.is
POLAND,
Gdynia
An-Elec Sp. z o.o.
Tel: +48 58 668 44 00 Fax: +48 58 668 44 66 Website: http://an-elec.pl
E-mail:
info@an
-
elec.pl
INDIA,
Faridabad
Power Solutions
Tel: +91 9868907903 Fax:: +91 129 2431216 Website: www.psolindia.com E-mail: ramesh.powersolutions@gmail.com
SOUTH AFRICA,
Roodepoort
Yneldo Electronics
Tel: +27(0)117637053 Fax: +27(0)117634212 Website: www.yneldo.com
E-mail:
yneldo@yneldo.com
POLAND,
Szczecin-Mierzyn
Marel Serwis
Tel: +48 91 48 58 388 Fax: +48 91 48 79 948 Website: www.marel.szczecin.pl E-mail: handel@marel.szczecin.pl
CHILE,
Santiago
Lucio Vicencio y CIA.LTDA
Tel: +1-281-334-2904 Fax:: +1-832-221-5642 Website: www.luciovicencio.cl
E-mail:
luciovincencioltda@gmail.com
NORWAY,
Bergen
Frydenbø Electric A/S
Tel: +47 55 34 91 00 Fax: +47 55 34 91 10 Website: www.frydenbo.no E-mail: firma.fel@frydenboe.no
SINGAPORE,
Singapore
Cyclect Electrical Engineering
Tel: +65 6868 6013 Fax: +65 6863 6260 Website: www.cyclect.com.sg E-mail: heng.p@cyclect.com.sg
THAILAND,
Bang Lamung
Semtec Maritime/Genetech Co.Ltd
Tel: +66 38301262 Fax: +1-832-221-5642 Website: semtecmaritime.com/
Email
:
ron@northstarusa.co
UNITED
ARAB
EMIRATES,
Sharjah
KDU Technical Services
Tel: +971-6-5575480 Fax: +971-6-5575490 Website: www.kdutech.ae
E-mail:
kdutech@kdutech.ae
SWEDEN,
Kungälv
Elektrisk Drivteknik EDT AB
Tel: +46-705-28 20 60 Tel: +46-709-50 47 90 Website: www.edtab.se
E-mail:
info@edtab.se
GREECE,
Piraeus
Stavros Kassidiaris S.A.
Tel: +30 210 4636000 Fax: +30 210 4624471 Website: www.kassidiaris.gr
E-mail: info@kassidiaris.gr
CANARY ISLANDS,
Las Palmas
Zamakona Yards
Tel: +34 928467521 Fax: +34 928461233 Website: www.zamakonayards.com/
E-mail:
jbetancor@zamakonayards.com
UNITED KINGDOM,
Stockton on Tees
MJR Controls
Tel: +44 1642 762 151 Fax: +44 1642 762 502 Website: www.mjrcontrols.com
Email:
chris.milner@mjrcontrols.com
UNITED STATES,
Kemah - Texas
Ramtec Marine Systems LLC
Tel: +1-281-334-2904 Fax: +1-832-221-5642 Website:
www.ramtec-marine.com
Email:
waling@ramtec
-
marine.com
REPUBLIC OF PANAMA,
Panama
PASRAS S.A.
Tel: +507 3140095 Fax: +507 3140094 Website: www.pasras.com E-mail: info@pasras.com
ROMANIA,
Constanta
SAMTEC SRL
Tel: +40 241 517 047 Fax: +40 241 517 047 Website: www.samtec.ro E-mail: samtec_srl@yahoo.com
UNITED KINGDOM,
Cheadle Hulme
TGS Total Generator Solutions Ltd
Tel: +44161 8188720 Fax: +447754677963 Website: http://totalgeneratorsolutions.com
Email:
sales@totalgeneratorsolutions.com
POLAND,
Szczecin
MARCONTREL
Tel: +48 91 4 888 474 Fax: +48 91 4 888 475 Website: www.marcontrel.com
E-mail:
emri@marcontrel.com
Loading...