EMR LX10.2 Instruction Manual

LX10.2
Voltage regulator for generators
Instruction Manual V1.2
Manual V1.2 Page 2 of 20
Warnings And Commissioning information
Revision history
The manual does not cover all technical details of the product. Specifications may be modified by the manufacturer without notice. For further information, the manufacturer should be contacted.
Manual V1.2 Page 3 of 20
Table of contents
General description
The LX10.2 is designed for use in brushless generators and can be used as a cost effective universal replacement for a great variety original manufacturers AVR’s.
The LX10.2 can be used for parallel operation with other generators that also control voltage droop by means of Quadrature Droop Compensation (QDC). Parallel operation is possible with an additional droop CT, which can be 0.5 or 1A secondary.
Installation, maintenance and adjustment don’t require special application software.
The AVR is protected from the environment by a PUR coating
.
Manual V1.2 Page 4 of 20
Absolute maximum rating
Manual V1.2 Page 5 of 20
Protections
Manual V1.2 Page 6 of 20
Modes of control I
Sensing voltage
Sensing voltage
Generator voltage
Generator voltage
Manual V1.2 Page 7 of 20
Modes of control II
Sensing voltage
Sensing voltage
Sensing voltage
+
Sensing voltage
+
Manual V1.2 Page 8 of 20
Modes of control III
Sensing voltage
Sensing voltage
Max. excitation voltage
(AVR supply voltage x √2 )
Max. excitation voltage
(AVR supply voltage x √2 )
AVR supply
Manual V1.2 Page 9 of 20
Commissioning set up
Commissioning set up
Start
(AVR Active / Generator running ! )
Underspeed protection
Done
Threshold underspeed
Underspeed
Slowly
Until led on
Setpoint underspeed
Underspeed
Very slowly
Until led off
Led not red flickering!
Nominal speed
GM
Note:
It is recommended to turn
the potentiometer a little
further clockwise,
to allow for short
frequency dips.
Indication setpoints
Manual V1.2 Page 10 of 20
Quick reference I
AFD ModeMinimum Rfield
Formula
Minimum field resistance
Factory settings
Sensing voltage Underspeed frequency Underspeed slope Droop Stability P-action Stability I-action Max. out Dipswitch 1 Dipswitch 2 Dipswitch 3 Dipswitch 4 Dipswitch 5 Dipswitch 6 Dipswitch 7 Dipswitch 8
: 400V : 45Hz : Trip slope : 100% : 50% : 50 % : 100 % : On : Off : Off : On : Off : Off : Off : Off
Link: J3-J4, EX-EX
AVR field current.
Max. rating: Intermitted 12A < 10s.
Max. rating: Field forcing 20A < 1s.
Max. out Droop Underspeed Stability Voltage
(Page 6)(Page 6)(Page 6)(Page 8)
Underspeed
Coarse
Fine
- +
- +
Range 230V sensing
+/- 185 .. 290V
Range 400V sensing
+/- 315 .. 505V
+ -0% 100%0% 100% - + - +
I-action
(Integral time)
P-action
(Proportional gain)
Dipswitch
ON
1234
dip
5678
400V sensing voltage.
Phase loss protection disabled.
Remote adjust enabled.
DIP Off On
S-T internally shorted.1
2
3
4
5
6
7
8
Underspeed trip disabled. Underspeed F/V curve disabled. Buildup speed 2 sec. Normal Integral time. Underspeed trip voltage +/- 27.5% of Unom.
Phase loss protection enabled. 230V sensing voltage. Underspeed trip enabled.
Buildup speed 5 sec. Increased Integral time.
Do not place or remove link!
Inputs are for EMRI AFD.
AFD is an option unit
for dual AVR applications.
For more information
see manual AFD.
Underspeed F/V curve enabled.
Underspeed trip voltage +/- 17.5% of Unom.
(Page 5..8)
Trip @
Higher – RPM - Lower
+/- 62Hz +/- 27Hz
Manual V1.2 Page 11 of 20
Quick reference II
Exciter
0 .. 10Adc
Check
Formula
Minimum
Field Resistance
(Page 4, 10)
Max. rating: Intermitted 12A < 10s.
Exciter Field
AVR supply
Transformer
Max. rating: 20..300Vac
PMG
Max. rating: 20..300Vac
Stator
Max. rating: 20..300Vac
Auxilary windings
Max. rating: 20..300Vac
LH1 LH2 LH3 LH4 EX EX
Link
Link
Link
- +
Sensing
U-V-W
clockwise
(Page 12..15)
W
V
U
N
230V
Remote adjust
1kΩ
-
+
Max. value : 10K
Max. : -10V..+10V
S T
Isolated supply
(-10V .. +10V)
Rx (10kΩ ..100kΩ)
Dipswitch 1 off Dipswitch 1 off
S T
0..10kΩ
Rx
Current selection
Input X1-X2
CT 0.5A
(Droopkit)
Input X1-X2
CT 1A
(Droopcat)
J1 J2
J1 J2
J1-J2 : Open J1-J2 : Link
Current sensing
J1 J2
J1 J2
J1-J2 : Open
J1-J2 : Link
V phase
0.5A
V phase
1A
X1 X2 X1 X2
400V
Manual V1.2 Page 12 of 20
Wiring diagram I
AVR with PMG
Manual V1.2 Page 13 of 20
Wiring diagram II
AVR with auxilary windings (self excited)
Manual V1.2 Page 14 of 20
Wiring diagram III
AVR with transformer (self excited)
Manual V1.2 Page 15 of 20
Wiring diagram IV
AVR with generator phase supply (self excited)
Manual V1.2 Page 16 of 20
Tips and Suggestions I
Manual V1.2 Page 17 of 20
Tips and Suggestions II
Field flash with isolated battery (AVR)
Manual V1.2 Page 18 of 20
Tips and Suggestions III
Field flash with isolated battery (Exciter field)
Manual V1.2 Page 19 of 20
General installation information
Absolute Maximum Ratings
- The Absolute Maximum Ratings are those limits for the device that, if exceeded, will likely damage the device. Exceeding the absolute maximum ratings voids any warranty and/or guarantee.
Mounting
Mounting of the product should be done in such a way that:
- the absolute maximum ambient temperature rating of the product will never be exceeded.
- maximum cooling (direction of cooling ribs and direction of airflow) is achieved.
- Mounting no humid air can flow through the product or condensation occurs.
- dust or other materials or residue will not remain in or on the product.
- the maximum vibration is not exceeded.
- personal contact with persons is impossible.
Wiring
- Diameter size of the wiring should be enough to carry the expected current. Wire insulation should be enough to withstand the expected operating voltages and temperatures.
- To improve EMC emission and immunity, care should be taken for the lay out of the wiring. This in respect to all wiring in the installation.
- Keep current carrying wires as short as possible.
- Keep wires carrying a total sum of zero Ampere close to each other, or in one single cable, E.g. U, V, W, or X (+) and XX (-),
or Phase and neutral, or S and T.
- Avoid current carrying conductors next to sensing or control wiring. Especially current controlled by SCR’s or PWM controlled transistors.
- If sensitive sensing signal cables need to be laid across distance along other cabling, shielded cable is preferred. Keep the shield as long as possible and the wiring outside the shield as short as possible. Do not solder or shrink the shield to a regular wire. Connect the original shield to ground at one side with an as large as possible contact surface.
Additional installation information
- When the product is supplied by means of a transformer, it should never be an auto-transformer. Auto-transformers react as voltage sweep up coil and may cause high voltage peaks.
- Standard fit capacitors or over-voltage suppressers across X (+) and XX (-), or exciter field terminals inside the generator should be removed.
- When the product is supplied by means of a transformer, it should be able to carry at least the maximum expected current. Advisable is, to have a transformer which can carry twice the maximum expected current. Inductive loads make voltage sacks and peeks into the secondary voltage of a transformer, from which the device may malfunction.
- It is not recommended to apply switches in dc outputs. It is preferred to use switches in the ac supply inputs of devices. In case it is unavoidable to have switches in the dc output of a device, action must be taken to avoid over voltage damage to the device due to contact arcing. Use a voltage suppressor across the output.
- It is not recommended to apply switches or fuses in the sensing lines. Defects can cause high voltage situations due to over- excitation.
- When using a step down transformer in medium or high voltage generators, the transformer should be three phase (if three phase sensing), and the transformer should be suitable for acting as a sensing transformer. If the transformer is unloaded, connect a resistor to avoid voltage waveform distortion.
- The phase relation from the generator to the AVR is important. Also when voltage transformers and/ or current transformers are installed.
- When using a step down or insulation transformer in the droop circuit, phase relation from the generator to the AVR is important.
- CT’s wiring, connected to the AVR should never be grounded.
- Always disconnect electronic products, circuits and people before checking the insulation resistance (Megger check).
- Due to differences in generators impedance’s, EMC behavior is not predictable. Therefore the commissioner / installer should
be aware of proper and correct installation.
- Large, highly inductive, exciter stator windings can cause destructive high voltage peaks. Adding a resistor from 10 to 20 times the exciter stator field resistance reduces voltage spikes. If necessary filter can be fitted additionally. (e.g. snubber, RC­network)
- Upon problems during commissioning, faulty behavior or defects in the generator, consult the fault finding manual at our web site
- Some advises may be overdone or seem extraordinary, but since the electrical rules are the same everywhere, these advises are given.
Manual V1.2 Page 20 of 20
Contact
EMRI Electronics B.V.
Manufacturer
Morsestraat 10 6716 AH, Ede, Netherlands Tel: +31 (0)318 620 427 Fax: +31 (0)318 634 615 Website: www.emri.nl E-mail: info@emri.nl
I
CELAND,
Hafnarfjordur
Rafeining ehf
Tel: +354 565 3049 Fax: +354 565 3048 Website: www.rafeining.is E-mail: rafeining@rafeining.is
POLAND,
Gdynia
An-Elec Sp. z o.o.
Tel: +48 58 668 44 00 Fax: +48 58 668 44 66 Website: http://an-elec.pl
E-mail:
info@an
-
elec.pl
INDIA,
Faridabad
Power Solutions
Tel: +911 29404 1409 Fax:: +911 29404 1410 Website: www.psolindia.com E-mail: ramesh.powersolutions@gmail.com
SOUTH AFRICA,
Roodepoort
Yneldo Electronics
Tel: +27(0)117637053 Fax: +27(0)117634212 Website: www.yneldo.com
E-mail:
yneldo@yneldo.com
POLAND,
Szczezin-Mierzyn
Marel Serwis
Tel: +48 91 48 58 388 Fax: +48 91 48 79 948 Website: www.marel.szczecin.pl E-mail: handel@marel.szczecin.pl
CHILE,
Santiago
Lucio Vicencio y CIA.LTDA
Tel: +1-281-334-2904 Fax:: +1-832-221-5642 Website: www.luciovicencio.cl
E-mail:
lucio
vincencioltda@gmail.com
NORWAY,
Bergen
Frydenbø Electric A/S
Tel: +47 55 34 91 00 Fax: +47 55 34 91 10 Website: www.frydenbo.no E-mail: firma.fel@frydenboe.no
SINGAPORE,
Singapore
Cyclect Electrical Engineering
Tel: +65 6868 6013 Fax: +65 6863 6260 Website: www.cyclect.com.sg E-mail: heng.p@cyclect.com.sg
THAILAND,
Bang Lamung
Semtec Maritime/Genetech Co.Ltd
Tel: +66 38301262 Fax: +1-832-221-5642 Website: semtecmaritime.com/
Email
:
ron@northstarusa.co
UNITED
ARAB
EMIRATES,
Sharjah
KDU Technical Services
Tel: +971-6-5575480 Fax: +971-6-5575490 Website: www.kdutech.ae
E-mail:
kdutech@kdutech.ae
SWEDEN,
Kungälv
Elektrisk Drivteknik EDT AB
Tel: +46-705-28 20 60 Tel: +46-709-50 47 90 Website: www.edtab.se
E-mail:
info@edtab.se
GREECE,
Piraeus
Stavros Kassidiaris S.A.
Tel: +30 210 4636000 Fax: +30 210 4624471 Website: www.kassidiaris.gr
E-mail: info@kassidiaris.gr
CANARY ISLANDS,
Las Palmas
Zamakona Yards
Tel: +34 928467521 Fax: +34 928461233 Website: www.zamakonayards.com/
E-mail:
jbetanco
r@zamakonayards.com
UNITED STATES,
Fort Lauderdale - Florida
North Star USA inc.
Tel: +1 800 571-4453 Fax: +1 3052985727 Website: www.northstarusa.co/
Email:
ron@northstarusa.co
UNITED KINGDOM,
Stockton on Tees
MJR Controls
Tel: +44 1642 762 151 Fax: +44 1642 762 502 Website: www.mjrcontrols.com
Email:
chris.milner@mjrcontrols.com
UNITED STATES,
Kemah - Texas
Ramtec Marine Systems LLC
Tel: +1-281-334-2904 Fax: +1-832-221-5642 Website: www.ramtec-marine.com
Email:
waling@ramtec
-
marine.com
REPUBLIC OF PANAMA,
Panama
PASRAS S.A.
Tel: +507 3140095 Fax: +507 3140094 Website: www.pasras.com E-mail: info@pasras.com
ROMANIA,
Constanta
SAMTEC SRL
Tel: +40 241 517 047 Fax: +40 241 517 047 Website: www.samtec.ro E-mail: samtec_srl@yahoo.com
Loading...