This appliance may be installed in an aftermarket,
permanently located, manufactured home (USA
only) or mobile home, where not prohibited by
state or local codes.
This appliance is only for use with the type of gas
indicated on the rating plate. This appliance is
not convertible for use with other gases, unless
a certified kit is used.
WARNING: If not installed, operated and
maintained in accordance with the manufacturer’s instructions, this product could expose you
to substances in fuel or from fuel combustion
which can cause death or serious illness.
EFFECTIVE DATE
JANUARY 2007
WARNING: If the information in these instructions are not followed exactly, a fire or explosion
may result causing property damage, personal
injury or loss of life.
— Do not store or use gasoline or other flamma-
ble vapors and liquids in the vicinity of this or
any other appliance.
— WHAT TO DO IF YOU SMELL GAS
• Do not try to light any appliance.
• Do not touch any electrical switch; do not
use any phone in your building.
• Immediately call your gas supplier from a
neighbor’s phone. Follow the gas supplier’s instructions.
• If you cannot reach your gas supplier, call
the fire department.
— Installation and service must be performed by
a qualified installer, service agency or the gas
supplier.
13119-6-0107 Page 1
TABLE OF CONTENTS
SECTION PAGE
Important Safety Information ......................................................................................................................3
Safety Information for Users of LP Gas ......................................................................................................
Requirements for Massachusetts ..................................................................................................................5
Gas Supply ............................................................................................................................................... 7-8
Service and Maintenance Suggestions .......................................................................................................17
DVC-35IPT Intermittent Pilot Sequence of Operation ..............................................................................
12
13
15-16
18
4
6
DVC-35IPT Intermittent Pilot System Troubleshooting Sequence ...........................................................
How to Order Repair Parts .........................................................................................................................20
Parts List ...................................................................................................................................................20
Parts View ..................................................................................................................................................
Service Notes ....................................................................................................................................... 22-23
19
21
Page 213119-6-0107
IMPORTANT SAFETY INFORMATION
THIS IS A HEATING APPLIANCE
DO NOT OPERATE THIS APPLIANCE WITHOUT FRONT PANEL INSTALLED.
• Due to high temperatures the appliance should be located
out of traffic and away from furniture and draperies.
• Children and adults should be alerted to the hazards of
high surface temperatures and should stay away to avoid
burns or clothing ignition.
• Young children should be carefully supervised when they
are in the same room as the appliance.
• Clothing or other flammable material should not be placed
on or near the appliance.
• Any safety screen or guard removed for servicing an appli
ance must be replaced prior to operating the appliance.
• Keep burner and control compartment clean.
• Vent cap hot while furnace is in operation.
• Installation and repair should be done by a QUALIFIED
SERVICE PERSON. The appliance should be inspected
before use and at least annually by a qualified service
person. More frequent cleaning may be required due to
excessive lint from carpeting, bedding materials, etc. It
is imperative that control compartments, burners and
circulating air passageways of the appliance be kept
clean.
VENT KIT INFORMATION
• DO NOT put anything around the furnace that will ob
struct the flow of combustion and ventilation air.
• DO keep the appliance area clear and free from combus
tible material, gasoline and other flammable vapors and
liquids.
• DO examine venting system periodically and replace
damaged parts.
• DO make a periodic visual check of pilot and burners.
Clean and replace damaged parts.
• CAUTION: Pilot hole cover must be kept tightly closed
during operation.
• DO NOT use this heater if any part has been under water.
Immediately call a qualified service technician to inspect
the heater and to replace any part of the control system
and any gas control which has been under water.
• IMPORTANT: This furnace has a washable permanent
type filter which should be cleaned at least once per
year before the heating season. For dirty or high use
areas more frequent cleaning is required.
-
-
Attention: The DVC-35T and DVC-35IPT direct vent wall furnaces are provided with vent kit, DV4T-59-1 for wall depths of 5” to
9”. For wall depths greater than 9”, refer to Accessories, Page 6. Listed below are the vent kits.
Attention: The minimum wall depth for installation of a DVC-35T and DVC-35IPT MUST BE 5”. If the wall depth is less than 5”
you can order DV-822, refer to Accessories, Page 6 or refer to Figure 10 and Figure 11 with accompanying text, Page 11.
Vent Kits
No. PartDV4T-59-1 DV4T-812-1 DV4T-1219-1
1Outlet Tube - Inner130571305713058
2Gasket - Outer CollarM-177M-177M-177
3Outlet Tube - Inner131041310413105
4Inlet Tube - Inner130621306213063
5Gasket - Inlet CollarM-178M-178M-178
6Inlet Tube - Inner131061310613107
7Inlet Tube - Outer130641306513066
8Outlet Tube - Outer130591306013061
9Vent Cap130531305313053
Hardware Kit130781307813078
13119-6-0107 Page 3
SAFETY INFORMATION FOR USERS OF LP-GAS
Propane (LP-Gas) is a flammable gas which can cause fires
and explosions. In its natural state, propane is odorless and
colorless. You may not know all the following safety precau
tions which can protect both you and your family from an
accident. Read them carefully now, then review them point
LP-GAS WARNING ODOR
If a gas leak happens, you should be able to smell the gas because of the odorant put in the LP-Gas.
That’s your signal to go into immediate action!
• Do not operate electric switches, light matches, use your
phone. Do not do anything that could ignite the gas.
• Get everyone out of the building, vehicle, trailer, or area. Do
that IMMEDIATELY.
• Close all gas tank or cylinder supply valves.
• LP-Gas is heavier than air and may settle in low areas such
as basements. When you have reason to suspect a gas leak,
keep out of basements and other low areas. Stay out until
firefighters declare them to be safe.
NO ODOR DETECTED - ODOR FADE
Some people cannot smell well. Some people cannot smell the
odor of the chemical put into the gas. You must find out if you
can smell the odorant in propane. Smoking can decrease your
ability to smell. Being around an odor for a time can affect your
sensitivity or ability to detect that odor. Sometimes other odors
in the area mask the gas odor. People may not smell the gas odor
or their minds are on something else. Thinking about smelling a
gas odor can make it easier to smell.
The odorant in LP-gas is colorless, and it can fade under some
circumstances. For example, if there is an underground leak, the
movement of the gas through soil can filter the odorant. Odorants
by point with the members of your household. Someday when
there may not be a minute to lose, everyone’s safety will depend
on knowing exactly what to do. If, after reading the following
information, you feel you still need more information, please
contact your gas supplier.
• Use your neighbor’s phone and call a trained LP-Gas service
person and the fire department. Even though you may not
continue to smell gas, do not turn on the gas again. Do not
re-enter the building, vehicle, trailer, or area.
• Finally, let the service man and firefighters check for escaped
gas. Have them air out the area before you return. Properly
trained LP-Gas service people should repair the leak, then
check and relight the gas appliance for you.
in LP-Gas also are subject to oxidation. This fading can occur if
there is rust inside the storage tank or in iron gas pipes.
The odorant in escaped gas can adsorb or absorb onto or into walls,
masonry and other materials and fabrics in a room. That will take
some of the odorant out of the gas, reducing its odor intensity.
LP-Gas may stratify in a closed area, and the odor intensity could
vary at different levels. Since it is heavier than air, there may be
more odor at lower levels. Always be sensitive to the slightest gas
odor. If you detect any odor, treat it as a serious leak. Immediately
go into action as instructed earlier.
SOME POINTS TO REMEMBER
• Learn to recognize the odor of LP-gas. Your local LP-Gas
Dealer can give you a “Scratch and Sniff” pamphlet. Use it
to find out what the propane odor smells like. If you suspect
that your LP-Gas has a weak or abnormal odor, call your
LP-Gas Dealer.
• If you are not qualified, do not light pilot lights, perform
service, or make adjustments to appliances on the LP-Gas
system. If you are qualified, consciously think about the odor
of LP-Gas prior to and while lighting pilot lights or perform
ing service or making adjustments.
• Sometimes a basement or a closed-up house has a musty
smell that can cover up the LP-Gas odor. Do not try to light
pilot lights, perform service, or make adjustments in an area
where the conditions are such that you may not detect the
odor if there has been a leak of LP-Gas.
• Odor fade, due to oxidation by rust or adsorption on walls
of new cylinders and tanks, is possible. Therefore, people
should be particularly alert and careful when new tanks or
cylinders are placed in service. Odor fade can occur in new
tanks, or reinstalled old tanks, if they are filled and allowed
Page 413119-6-0107
-
to set too long before refilling. Cylinders and tanks which
have been out of service for a time may develop internal rust
which will cause odor fade. If such conditions are suspected
to exist, a periodic sniff test of the gas is advisable. If you
have any question about the gas odor, call your LP-gas
dealer. A periodic sniff test of the LP-gas is a good safety
measure under any condition.
• If, at any time, you do not smell the LP-Gas odorant and you
think you should, assume you have a leak. Then take the same
immediate action recommended above for the occasion when
you do detect the odorized LP-Gas.
• If you experience a complete “gas out,” (the container is
under no vapor pressure), turn the tank valve off immediately.
If the container valve is left on, the container may draw in
some air through openings such as pilot light orifices. If this
occurs, some new internal rusting could occur. If the valve is
left open, then treat the container as a new tank. Always be
sure your container is under vapor pressure by turning it off
at the container before it goes completely empty or having
it refilled before it is completely empty.
REQUIREMENTS FOR MASSACHUSETTS
For all side wall horizontally vented gas fueled equipment
installed in every dwelling, building or structure used in
whole or in part for residential purposes, including those
owned or operated by the Commonwealth and where the
side wall exhaust vent termination is less than seven (7) feet
above finished grade in the area of the venting, including but
not limited to decks and porches, the following requirements
shall be satisfied:
1. INSTALLATION OF CARBON MONOXIDE DETEC
TORS. At the time of installation of the side wall horizontal
vented gas fueled equipment, the installing plumber or
gasfitter shall observe that a hard wired carbon monoxide
detector with an alarm and battery back-up is installed on
the floor level where the gas equipment is to be installed.
In addition, the installing plumber or gasfitter shall observe
that a battery operated or hard wired carbon monoxide
detector with an alarm is installed on each additional
level of the dwelling, building or structure served by
the side wall horizontal vented gas fueled equipment. It
shall be the responsibility of the property owner to secure
the services of qualified licensed professionals for the
installation of hard wired carbon monoxide detectors
a. In the event that the side wall horizontally vented gas
fueled equipment is installed in a crawl space or an
attic, the hard wired carbon monoxide detector with
alarm and battery back-up may be installed on the
next adjacent floor level.
b. In the event that the requirements of this subdivision
can not be met at the time of completion of installa
tion, the owner shall have a period of thirty (30) days
to comply with the above requirements; provided,
however, that during said thirty (30) day period, a
battery operated carbon monoxide detector with an
alarm shall be installed.
3. SIGNAGE. A metal or plastic identification plate shall be
permanently mounted to the exterior of the building at a
minimum height of eight (8) feet above grade directly in
line with the exhaust vent terminal for the horizontally
vented gas fueled heating appliance or equipment. The
sign shall read, in print size no less than one-half (1/2)
inch in size, “GAS VENT DIRECTLY BELOW. KEEP
CLEAR OF ALL OBSTRUCTIONS”.
-
4. INSPECTION. The state or local gas inspector of the
side wall horizontally vented gas fueled equipment shall
not approve the installation unless, upon inspection, the
inspector observes carbon monoxide detectors and signage
installed in accordance with the provisions of 248 CMR
5.08(2)(a) 1 through 4.
(b) EXEMPTIONS: The following equipment is exempt
from 248 CMR 5.08(2)(a)1 through 4:
1. The equipment listed in Chapter 10 entitled
“Equipment Not Required To Be Vented” in the
most current edition of NFPA 54 as adopted by
the Board; and
2. Product Approved side wall horizontally vented
gas fueled equipment installed in a room or
structure separate from the dwelling, building or
structure used in whole or in part for residential
purposes.
(c) MANUFACTURER REQUIREMENTS - GAS
EQUIPMENT VENTING SYSTEM PROVIDED.
-
When the manufacturer of Product Approved side
wall horizontally vented gas equipment provides a
venting system design or venting system components
with the equipment, the instructions provided by the
manufacturer for installation of the equipment and
the venting system shall include:
1. Detailed instructions for the installation of the
2. APPROVED CARBON MONOXIDE DETECTORS.
Each carbon monoxide detector as required in accordance
with the above provisions shall comply with NFPA 720
and be ANSI/UL 2034 listed and IAS certified.
13119-6-0107 Page 5
2. A complete parts list for the venting system design
(e) A copy of all installation instructions for all Product
venting system design or the venting system
components; and
or venting system.
Approved side wall horizontally vented gas fueled
equipment, all venting instructions, all parts lists for
venting instructions, and/or all venting design instruc
tions shall remain with the appliance or equipment
at the completion of the installation.
-
INTRODUCTION
Introduction
Always consult your local Building Department regarding regulations,
codes or ordinances which apply to the installation of a direct vent wall
furnace.
Instructions to Installer
1. In sta lle r must leav e i nstruction manual with owne r a fter
installation.
2. Installer must have owner fill out and mail warranty card supplied
with furnace.
3. Installer should show owner how to start and operate furnace and
thermostat.
Warning:
Any change to this furnace or its control can be dangerous. This
is a heating appliance and any panel, door or guard removed for
servicing an appliance must be replaced prior to operating the
appliance.
General Information
This furnace is design certified in accordance with American National
Standard/CSA Standard Z21.86 and CSA 2.32 by the Canadian Standards
Association, as a fan type direct vent wall furnace to be installed according
to these instructions.
Any alteration of the original design, installed other than as shown in
these instructions or use with a type of gas not shown on the rating plate
is the responsibility of the person and company making the change.
Important
All correspondence should refer to complete Model No., Serial No. and
type of gas.
Notice: During initial firing of this unit, its paint will bake out and smoke
will occur. To prevent triggering of smoke alarms, ventilate the room in
which the unit is installed.
Installation on Rugs and Tile
If this appliance is installed directly on carpeting, tile or other combustible
material other than wood flooring the appliance shall be installed on a metal
or wood panel extending the full width and depth of the appliance.
The base referred to above does not mean the fire-proof base as used on
wood stoves. The protection is for rugs that are extremely thick and light
colored tile.
Installation in Residential Garages
Gas utilization equipment in residential garages shall be installed so that
all burners and burner ignition devices are located not less than 18” above
the floor.
Such equipment shall be located, or protected, so it is not subject to physical
damage by a moving vehicle.
Qualified Installing Agency
Installation and replacement of gas piping, gas utilization equipment or
accessories and repair and servicing of equipment shall be performed
only by a qualified agency. The term “qualified agency” means any
individual, firm, corporation or company which either in person or through
a representative is engaged in and is responsible for (a) the installation
or replacement of gas piping or (b) the connection, installation, repair or
servicing of equipment, who is experienced in such work, familiar with
all precautions required and has complied with all the requirements of the
authority having jurisdiction.
State of Massachusetts: The installation must be made by a licensed
plumber or gas fitter in the Commonwealth of Massachusetts.
The installation must conform with local codes or, in the absence of local
codes, with the National Fuel Gas Code ANSI Z223.1/NFPA 54* Natural
Gas and Propane Installation Code, CSA B149.1.
*Available from the American National Standards Institute, Inc., 11 West
42nd St., New York, N.Y. 10036.
High Altitudes
For altitudes/elevations above 2,000 feet, input ratings should be reduced
at the rate of 4 percent for each 1,000 feet above sea level. For Canadian
high altitude applications, this appliance is suitable for installation at
elevations between 0 feet and 4,500 feet without change.
Piezo Pilot Ignitor Instructions
Depressing the red button completely causes a spark to occur at the pilot. This
is a substitute for a match which requires opening the pilot hole cover.
To light the pilot, it is important that the electrode be 1/8” from the
thermocouple. The spark must occur at the point the burner flame hits the
thermocouple. The end of the electrode will be red hot with the pilot on.
On a new installation with air in the gas line, it is suggested that a match
be used. The match will light the pilot faster than the piezo under this
condition.
SPECIFICATIONS
ModelDVC-35TDVC-35IPT
Input BTU/HR35,00035,000
Height72 1/2”72 1/2”
Width
Depth10 3/8”10 3/8”
Gas Inlet1/2” Pipe1/2” Pipe
CFM275275
Accessories
SOR-1Register, Side Outlet
SOK-1Side Outlet Kit, 10” (25.4cm) Boot Assembly with Register
*DV-822Vinyl Siding Vent Kit
* DV-822, Vinyl siding vent kit, adds 3” to wall depth. You must include the three (3) additional inches for TOTAL
vent kit.
Page 613119-6-0107
14 1/8”14 1/8”
wall depth when ordering a
GAS SUPPLY
Locating Gas Supply
The gas line can enter the unit either through the floor or outside
wall. The gas line opening should be made at this time. Location
of the opening will be determined by the position of floor joists
and the valve and union used for servicing.
Recommended Gas Pipe Diameter
Pipe LengthSchedule 40 Pipe
Inside Diameter
Nat.L.P.Nat.L.P.
0-10 feet
0-3 meters
10-40 feet
4-12 meters
40-100 feet
13-30 meters
100-150 feet
31-46 meters
Note: Never use plastic pipe. Check to confirm whether your local
codes allow copper tubing or galvanized.
Note: Since some municipalities have additional local codes, it is
always best to consult your local authority and installation code.
The use of the following gas connectors is recommended:
— ANS Z21.24 Appliance Connectors of Corrugated Metal Tubing
and Fittings
— ANS Z21.45 Assembled Flexible Appliance Connectors of
Other Than All-Metal Construction
The above connectors may be used if acceptable by the authority
having jurisdiction. The state of Massachusetts requires that a flexible
appliance connector cannot exceed three feet in length.
1/2”
12.7mm
1/2”
12.7mm
1/2”
12.7mm
3/4”
19mm
3/8”
9.5mm
1/2”
12.7mm
1/2”
12.7mm
1/2”
12.7mm
Tubing, Type L
Outside Diameter
1/2”
12.7mm
5/8”
15.9mm
3/4”
19mm
7/8”
22.2mm
3/8”
9.5mm
1/2”
12.7mm
1/2”
12.7mm
3/4”
19mm
Installing a New Main Gas Cock
Each appliance should have its own manual gas cock.
A manual main gas cock should be located in the vicinity of
the unit. Where none exists, or where its size or location is not
adequate, contact your local authorized installer for installation
or relocation.
Compounds used on threaded joints of gas piping shall be resistant
to the action of liquefied petroleum gases. The gas lines must be
checked for leaks by the installer. This should be done with a soap
solution watching for bubbles on all exposed connections, and if
unexposed, a pressure test should be made.
Never use an exposed flame to check for leaks. Appliance must
be disconnected from piping at inlet of control valve and pipe
capped or plugged for pressure test. Never pressure test with
appliance connected; control valve will sustain damage!
A gas valve and ground joint union should be installed in the gas
line upstream of the gas control to aid in servicing. It is required
by the National Fuel Gas Code that a drip line be installed near
the gas inlet. This should consist of a vertical length of pipe tee
connected into the gas line that is capped on the bottom in which
condensation and foreign particles may collect.
Figure 2
Method of Installing a Tee Fitting Sediment Trap
Pressure Testing of the Gas Supply System
1. To check the inlet pressure to the gas valve, a 1/8” N.P.T.
plugged tapping, accessible for test gauge connection, must be
placed immediately upstream of the gas supply connection to
the appliance.
2. The appliance and its individual shutoff valve must be
disconnected from the gas supply piping system during any
pressure testing of that system at test pressures in excess of 1/2
psig (3.5 kPa).
3. The appliance must be isolated from the gas supply piping
system by closing its individual manual shutoff valve during
Figure 1
Consult the current National Fuel Gas Code, ANSI Z223.1 CAN/
CGA-B149 (.1 or .2) installation code.
13119-6-0107 Page 7
any pressure testing of the gas supply piping system at test
pressures equal to or less than 1/2 psig (3.5 kPa).
Attention! If one of the above procedures results in pressures in
excess of 1/2 psig (14” w.c.) (3.5 kPa) on the appliance gas valve,
it will result in a hazardous condition.
Figure 3
Checking Manifold Pressure
Both Propane and Natural gas valves have a built-in pressure
regulator in the gas valve. Natural gas models will have a manifold
CLEARANCES
Clearances
1. In selecting a location for installation, it is necessary to provide
adequate accessibility clearances for servicing and proper
installation. A front clearance of 36” is recommended. Do not
block outlet or inlet air openings on the front grill.
2. The DV4T-59-1, 5” to 9” wall depth is the standard vent kit
provided with the DVC-35T or DVC-35IPT. See Accessories
Page 6 to order vent kits for wall depths of 8” to 12” or 12”
to 19”. The use of tubes not supplied by the manufacturer
results in unsatisfactory performance.
3. The DVC-35T and DVC-35IPT can be attached to the wall or
recessed into the wall up to 9 1/2” in depth but the minimum
5” vent/air intake system wall depth must be maintained.
Example: If furnace is recessed into the wall at a depth of
9 1/2”, the minimum wall depth behind the furnace must be
5”.
4. The wall in which the furnace is recessed has (0) zero clearance
to the furnace sides and top.
5. When using side discharge registers, SOR-1 or SOK-1, the
furnace cannot be recessed into the wall.
6. Clearance to sidewall or combustible material is 4”.
7. Ceiling clearance is 4”.
8. Floor and rear wall clearance is (0) zero inches.
9. Clearance of 18” is required to sidewall or combustible material
when flush mounted SOR-1, side outlet register is used.
10. The minimum distance from the center of the vent cap to the
nearest outside corner or obstruction is 12”.
pressure of approximately 4.0” w.c. (.996kPa) for DVC-35T and
3.5” w.c. (.871kPa) for DVC-35IPT at the valve outlet with the
inlet pressure to the valve from a minimum of 5.0” w.c. (1.245kPa)
for the purpose of input adjustment to a maximum of 7.0” w.c.
(1.743kPa). Propane gas models will have a manifold pressure
approximately 10.0” w.c. (2.49kPa) at the valve outlet with the inlet
pressure to the valve from a minimum of 11.0” w.c. (2.739kPa)
for the purpose of input adjustment to a maximum of 13.0” w.c.
(3.237kPa).
A 1/8” N.P.T. plugged tapping, accessible for test gauge connection,
is located on the outlet side of the gas control.
The built-in regulator comes on at approximately 1/4th pressure
and full on in 10 seconds.
Figure 4
The vent terminal of this direct vent appliance shall be located at
least 9” from any opening through which flue gases could enter a
building. The bottom of the vent terminal and the air intake shall
be located at least 12” above grade. See vent location, Figure 4.
WARNING: The nearest point of the vent cap should be
a minimum horizontal distant of six (6) feet from any
pressure regulator. In case of regulator malfunction, the
six (6) feet distance will reduce the chance of gas entering
the vent cap.
Page 813119-6-0107
Loading...
+ 16 hidden pages
You need points to download manuals.
1 point = 1 manual.
You can buy points or you can get point for every manual you upload.