WARNING: If the information in these instructions are not followed exactly, a fire or explosion
may result causing property damage, personal
injury or loss of life.
— Do not store or use gasoline or other flamma-
ble vapors and liquids in the vicinity of this or
any other appliance.
— WHAT TO DO IF YOU SMELL GAS
• Do not try to light any appliance.
• Do not touch any electrical switch; do not
use any phone in your building.
• Immediately call your gas supplier from a
neighbor’s phone. Follow the gas supplier’s instructions.
• If you cannot reach your gas supplier, call
the fire department.
— Installation and service must be performed by
a qualified installer, service agency or the gas
supplier.
This is an unvented gas-fired heater. It uses air
(oxygen) from the room in which it is installed.
Provisions for adequate combustion and ventilation
air must be provided. Refer to page 6.
WARNING: If not installed, operated and maintained in accordance with the manufacturer’s
instructions, this product could expose you to
substances in fuel or from fuel combustion which
can cause death or serious illness.
WATE R VAPOR : A BY- P RO DUCT O F
UNVENTED ROOM HEATERS
Water vapor is a by-product of gas combustion. An
unvented room heater produces approximately one
(1) ounce (30ml) of water for every 1,000 BTU’s
(.3KW’s) of gas input per hour. Refer to page 6.
Page 1
Page 2
TABLE OF CONTENTS
SECTION PAGE
Important Safety Information .....................................................................................3
Safety Information for Users of LP Gas .....................................................................
Service Notes ...........................................................................................................23
16941-5-0907Page 2
Page 3
IMPORTANT SAFETY INFORMATION
THIS IS A HEATING APPLIANCE
DO NOT OPERATE THIS APPLIANCE WITHOUT FRONT PANEL INSTALLED.
• An unvented room heater having an input rating of
more than 6,000 Btu per hour shall not be installed in a
bathroom.
• An unvented room heater having an input rating of more
than 10,000 Btu per hour shall not be installed in a bedroom
or bathroom.
• Due to high temperatures, the appliance should be located
out of traffic and away from furniture and draperies.
• Children and adults should be alerted to the hazard of
high surface temperature and should stay away to avoid
burns or clothing ignition.
• Young children should be carefully supervised when they
are in the same room with the appliance.
• Do not place clothing or other flammable material on or
near the appliance.
• Due to high surface temperatures, keep children, clothing
and furniture away.
• Installation and repair should be done by a QUALIFIED
SERVICE PERSON. The appliance should be inspected
before use and at least annually by a professional service
person. More frequent cleaning may be required due to
excessive lint from carpeting, bedding materials, etc. It
is imperative that control compartments, burners and
circulating air passageways of the appliance be kept
clean.
• DO NOT use this room heater if any part has been under
water. Immediately call a qualified service technician to
inspect the room heater and to replace any part of the
control system and any gas control which has been under
water.
• WARNING: ANY CHANGE TO THIS HEATER OR ITS
CONTROLS CAN BE DANGEROUS.
Any safety screen or guard removed for servicing an
appliance must be replaced prior to operating the
heater.
• Keep appliance area clear and free from combustible
materials, gasoline and other flammable vapors and
liquids
• WARNING: Failure to keep the primary air opening(s)
of the burner(s) clean may result in sooting and property
damage.
WARNING
When used without adequate combustion and ventilation air,
heater may give off CARBON MONOXIDE, an odorless,
poisonous gas.
Do not install heater until all necessary provisions are
made for combustion and ventilation air. Consult the writ
ten instructions provided with the heater for information
concerning combustion and ventilation air. In the absence
of instructions, refer to the National Fuel Gas Code, ANSI
Z223.1/NFPA 54, Air for Combustion and Ventilation, or
applicable local codes.
This heater is equipped with a PILOT LIGHT SAFETY
SYSTEM designed to turn off the heater if not enough fresh
air is available.
DO NOT TAMPER WITH PILOT LIGHT SAFETY
SYSTEM!
If heater shuts off, do not relight until you provide fresh air.
If heater keeps shutting off, have it serviced. Keep burner and
control compartment clean.
-
CARBON MONOXIDE POISONING MAY LEAD TO
DEATH.
Early signs of carbon monoxide poisoning resemble the flu,
with headache, dizziness and/or nausea. If you have these
signs, heater may not be working properly. Get fresh air at
once! Have heater serviced.
Some people — pregnant women, persons with heart or lung
disease, anemia, those under the influence of alcohol, those
at high altitudes — are more affected by carbon monoxide
than others.
The pilot light safety system senses the depletion of oxygen at
its location. If this heater is installed in a structure having a
high vertical dimension, the possibility exists that the oxygen
supply at the higher levels will be less than that at the heater.
In this type of application, a fan to circulate the structure
air will minimize this effect. The use of this fan will also im
prove the comfort level in the structure. When a fan is used
to circulate air, it should be located so that the air flow is not
directed at the burner.
-
16941-5-0907Page 3
Page 4
SAFETY INFORMATION FOR USERS OF LP-GAS
Propane (LP-Gas) is a flammable gas which can cause fires
and explosions. In its natural state, propane is odorless and
colorless. You may not know all the following safety precau
tions which can protect both you and your family from an
accident. Read them carefully now, then review them point
LP-GAS WARNING ODOR
If a gas leak happens, you should be able to smell the gas because of the odorant put in the LP-Gas.
That’s your signal to go into immediate action!
• Do not operate electric switches, light matches, use your
phone. Do not do anything that could ignite the gas.
• Get everyone out of the building, vehicle, trailer, or area. Do
that IMMEDIATELY.
• Close all gas tank or cylinder supply valves.
• LP-Gas is heavier than air and may settle in low areas such
as basements. When you have reason to suspect a gas leak,
keep out of basements and other low areas. Stay out until
firefighters declare them to be safe.
NO ODOR DETECTED - ODOR FADE
Some people cannot smell well. Some people cannot smell the
odor of the chemical put into the gas. You must find out if you
can smell the odorant in propane. Smoking can decrease your
ability to smell. Being around an odor for a time can affect your
sensitivity or ability to detect that odor. Sometimes other odors
in the area mask the gas odor. People may not smell the gas odor
or their minds are on something else. Thinking about smelling a
gas odor can make it easier to smell.
The odorant in LP-gas is colorless, and it can fade under some
circumstances. For example, if there is an underground leak, the
movement of the gas through soil can filter the odorant. Odorants
by point with the members of your household. Someday when
there may not be a minute to lose, everyone’s safety will depend
on knowing exactly what to do. If, after reading the following
information, you feel you still need more information, please
contact your gas supplier.
• Use your neighbor’s phone and call a trained LP-Gas service
person and the fire department. Even though you may not
continue to smell gas, do not turn on the gas again. Do not
re-enter the building, vehicle, trailer, or area.
• Finally, let the service man and firefighters check for escaped
gas. Have them air out the area before you return. Properly
trained LP-Gas service people should repair the leak, then
check and relight the gas appliance for you.
in LP-Gas also are subject to oxidation. This fading can occur if
there is rust inside the storage tank or in iron gas pipes.
The odorant in escaped gas can adsorb or absorb onto or into walls,
masonry and other materials and fabrics in a room. That will take
some of the odorant out of the gas, reducing its odor intensity.
LP-Gas may stratify in a closed area, and the odor intensity could
vary at different levels. Since it is heavier than air, there may be
more odor at lower levels. Always be sensitive to the slightest gas
odor. If you detect any odor, treat it as a serious leak. Immediately
go into action as instructed earlier.
SOME POINTS TO REMEMBER
• Learn to recognize the odor of LP-gas. Your local LP-Gas
Dealer can give you a “Scratch and Sniff” pamphlet. Use it
to find out what the propane odor smells like. If you suspect
that your LP-Gas has a weak or abnormal odor, call your
LP-Gas Dealer.
• If you are not qualified, do not light pilot lights, perform
service, or make adjustments to appliances on the LP-Gas
system. If you are qualified, consciously think about the odor
of LP-Gas prior to and while lighting pilot lights or perform
ing service or making adjustments.
• Sometimes a basement or a closed-up house has a musty
smell that can cover up the LP-Gas odor. Do not try to light
pilot lights, perform service, or make adjustments in an area
where the conditions are such that you may not detect the
odor if there has been a leak of LP-Gas.
• Odor fade, due to oxidation by rust or adsorption on walls of
new cylinders and tanks, is possible. Therefore, people should
be particularly alert and careful when new tanks or cylinders
are placed in service. Odor fade can occur in new tanks, or
reinstalled old tanks, if they are filled and allowed to set too
long before refilling. Cylinders and tanks which have been
out of service for a time may develop internal rust which will
cause odor fade. If such conditions are suspected to exist, a
periodic sniff test of the gas is advisable. If you have any
question about the gas odor, call your LP-gas dealer. A
periodic sniff test of the LP-gas is a good safety measure
under any condition.
• If, at any time, you do not smell the LP-Gas odorant and you
-
think you should, assume you have a leak. Then take the same
immediate action recommended above for the occasion when
you do detect the odorized LP-Gas.
• If you experience a complete “gas out,” (the container is un
der no vapor pressure), turn the tank valve off immediately.
If the container valve is left on, the container may draw in
some air through openings such as pilot light orifices. If this
occurs, some new internal rusting could occur. If the valve is
left open, then treat the container as a new tank. Always be
sure your container is under vapor pressure by turning it off
at the container before it goes completely empty or having it
refilled before it is completely empty.
-
16941-5-0907Page 4
Page 5
INTRODUCTION
Instructions to Installer
1. Installer must leave instruction manual with owner after
installation.
2. Installer must have owner fill out and mail warranty card supplied
with unvented room heater.
3. Installer should show owner how to start and operate unvented
room heater.
Always consult your local Building Department regarding
regulations, codes or ordinances which apply to the installation of
an unvented room heater.
This appliance may be installed in an aftermarket* permanently
located, manufactured (mobile) home, where not prohibited by
state or local codes.
*Aftermarket: Completion of sale, not for purpose of resale, from
the manufacturer.
This appliance is only for use with the type of gas indicated on the
rating plate. This appliance is not convertible for use with other
gases.
General Information
This appliance is design certified in accordance with American
National Standards Institute Z21.11.2 by the Canadian Standards
Association Laboratories as an Unvented Room Heater and shall
be installed according to these instructions.
Any alteration of the original design, installed other than as
shown in these instructions or use with a type of gas not shown on
the rating plate is the responsibility of the person and company
making the change.
Important
All correspondence should refer to complete Model Number, Serial
Number and type of gas.
Well Head Gas Installations
Some natural gas utilities use “well head” gas. This may affect the
Btu output of the unit. Contact the gas company for the heating
value. Contact the manufacturer or your gas company before
changing spud/orifice size.
Qualified Installing Agency
Installation and replacement of gas piping, gas utilization equipment
or accessories and repair and servicing of equipment shall be
performed only by a qualified agency. The term “qualified agency”
means any individual, firm, corporation, or company that either in
person or through a representative is engaged in and is responsible
for (a) the installation, testing, or replacement of gas piping or (b) the
connection, installation, testing, repair, or servicing of equipment;
that is experienced in such work; that is familiar with all precautions
required, and that has complied with all the requirements of the
authority having jurisdiction.
State of Massachusetts: The installation must be made by
a licensed plumber or gas fitter in the Commonwealth of
Massachusetts.
Sellers of unvented propane or natural gas-fired supplemental
room heaters shall provide to each purchaser a copy of 527 CMR
30 upon sale of the unit.
In the State of Massachusetts, unvented propane and natural
gas-fired space heaters shall be prohibited in bedrooms and
bathrooms.
The installation must conform with local codes or, in the absence
of local codes, with the National Fuel Gas Code, ANSI Z223.1
(latest edition).*
*Available from the American National Standards Institute, Inc.,
11 West 42nd St., New York, N.Y. 10036.
High Altitudes
For altitudes/elevations above 2,000 feet (610m) ratings should be
reduced at the rate of 4 percent for each 1,000 feet (305m) above
sea level. Contact the manufacturer or your gas company before
changing spud/orifice size.
SPECIFICATIONS
ModelSR-10TSR-18TSR-30T
Input BTU/HR (KW/H) Five Plaques--30,000 (8.8)
BTU/HR (KW/H) Three Plaques
BTU/HR (KW/H) One Plaque10,000 (2.9)--
Height22” (559mm)22” (559mm)22” (559mm)
Width11 7/8” (302mm)
Depth6 1/2” (165mm)6 1/2” (165mm)6 1/2” (165mm)
Gas Inlet3/8” (10mm)3/8” (10mm)3/8” (10mm)
Accessories
Blower-SRB-18TSRB-30T
Floor StandSRS-10*SRS-18SRS-30
*Floor stand can not be used in a bedroom installation. SR-10T must be wall mounted in a bedroom installation.
The bathroom or bedroom must be an unconfined space. ANSI Z223.1/NFPA54 defines an unconfined space as “a space whose volume is
not less than 50 cubic feet per 1,000 Btu per hour (4.8m3 per kw) of the aggregate input rating of all appliances installed in that space.”
16941-5-0907Page 5
-18,000 (5.3)-
18” (457mm)24 1/8” (613mm)
Page 6
WATER VAPOR: A BY-PRODUCT OF UNVENTED ROOM HEATERS
Water vapor is a by-product of gas combustion. An unvented room
heater produces approximately one (1) ounce (30ml) of water for
every 1,000 BTU’s (.3KW’s) of gas input per hour.
Unvented room heaters must be used as supplemental heat (a
room) rather than a primary heat source (an entire house). In most
supplemental heat applications, the water vapor does not create a
problem. In most applications, the water vapor enhances the low
humidity atmosphere experienced during cold weather.
The following steps will help insure that water vapor does not
become a problem.
1. Be sure the heater is sized properly for the application, including
ample combustion air and circulation air.
2. If high humidity is experienced, a dehumidifier may be used to
help lower the water vapor content of the air.
3. Do not use an unvented room heater as the primary heat source
(an entire house).
PROVISIONS FOR ADEQUATE COMBUSTION & VENTILATION AIR
This heater shall not be installed in a confined space or unusually
tight construction unless provisions are provided for adequate
combustion and ventilation air.
The National Fuel Gas Code, ANSI Z223.1 defines a confined space
as a space whose volume is less than 50 cubic feet per 1,000 Btu per
hour (4.8m
installed in that space and an unconfined space as a space whose
volume is not less than 50 cubic feet per 1,000 Btu per hour (4.8m3
per kw) of the aggregate input rating of all appliances installed in
that space. Rooms communicating directly with the space in which
the appliances are installed, through openings not furnished with
doors, are considered a part of the unconfined space.
The following example is for determining the volume of a typical
area in which the SR-30T may be located and for determining if
this area fits the definition of an unconfined space.
The input of the SR-30T is 30,000 Btu per hour. Based on the 50
cubic feet per 1,000 Btu per hour formula, the
is an unconfined space for installation of the SR-30T is 1,500 cubic
feet, 50 cubic feet x 30 = 1,500 cubic feet. To determine the cubic
feet of the area in which the SR-30T is to be installed, measure the
length, width and height of the area. Example: The area measures
16 feet in length, 12 feet in width and 8 feet in height, the area is
1,536 cubic feet. The SR-30T can be installed in this unconfined
space with no requirement to provide additional combustion and
ventilation air.
3
per kw) of the aggregate input rating of all appliances
minimum area that
Warning: If the area in which the heater may be operated is smaller
than that defined as an unconfined space or if the building is of
unusually tight construction, provide adequate combustion and
ventilation air by one of the methods described in the
Fuel Gas Code, ANSI Z223.1/NFPA 54, Air for Combustion and
Ventilation, or applicable local codes.
Unusually Tight Construction
The air that leaks around doors and windows may provide enough
fresh air for combustion and ventilation. However, in buildings of
unusually tight construction, you must provide additional fresh
air.
Unusually tight construction is defined as construction
where:
a. Walls and ceilings exposed to the outside atmosphere have
a continuous water vapor retarder with a rating of one perm
or less with openings gasketed or sealed, and
b. Weatherstripping has been added on openable windows and
doors, and
c. Caulking or sealants are applied to areas such as joints
around window and door frames, between sole plates and
floors, between wall-ceiling joints, between wall panels, at
penetrations for plumbing, electrical, and gas lines, and at
other openings.
If the SR-30T heater is installed in a building of unusually tight
construction, adequate air for combustion, ventilation and dilution
of flue gases shall be provided in accordance with ANSI Z223.1/
National
16941-5-0907Page 6
Page 7
GAS SUPPLY
The gas line can be routed either through the floor or wall. The gas
line opening should be made at this time. Location of the opening
will be determined by the position of floor joists and the valve and
union used for servicing.
Gas Supply
Check all local codes for requirements, especially for the size and
type of gas supply line required.
Recommended Gas Pipe Diameter
Pipe LengthSchedule 40 Pipe
Inside Diameter
Nat.L.P.Nat.L.P.
0-10 feet
0-3 meters
10-40 feet
4-12 meters
40-100 feet
13-30 meters
100-150 feet
31-46 meters
Note: Never use plastic pipe. Check to confirm whether your local
codes allow copper tubing or galvanized.
Note: Since some municipalities have additional local codes, it is
always best to consult your local authority and installation code.
Dimensions Apply to SR-10T, SR-18T and SR-30T
Installing a New Main Gas Cock
Each appliance should have its own manual gas cock.
A manual main gas cock should be located in the vicinity of the
unit. Where none exists, or where its size or location is not ad
equate, contact your local authorized installer for installation or
relocation.
Compounds used on threaded joints of gas piping shall be resistant
to the action of liquefied petroleum gases. The gas lines must be
checked for leaks by the installer. This should be done with a soap
solution watching for bubbles on all exposed connections, and if
unexposed, a pressure test should be made.
Never use an exposed flame to check for leaks. Appliance must
be disconnected from piping at inlet of control valve and pipe
capped or plugged for pressure test. Never pressure test with
appliance connected; control valve will sustain damage!
A gas valve and ground joint union should be installed in the gas
line upstream of the gas control to aid in servicing. It is required
1/2”
12.7mm
1/2”
12.7mm
1/2”
12.7mm
3/4”
19mm
3/8”
9.5mm
1/2”
12.7mm
1/2”
12.7mm
1/2”
12.7mm
Figure 1
Tubing, Type L
Outside Diameter
1/2”
12.7mm
5/8”
15.9mm
3/4”
19mm
7/8”
22.2mm
3/8”
9.5mm
1/2”
12.7mm
1/2”
12.7mm
3/4”
19mm
by the National Fuel Gas Code that a drip line be installed near
the gas inlet. This should consist of a vertical length of pipe tee
connected into the gas line that is capped on the bottom in which
condensation and foreign particles may collect.
Figure 2
Method of Installing a Tee Fitting Sediment Trap (Figure 2)
The use of the following gas connectors is recommended:
— ANS Z21.24 Appliance Connectors of Corrugated Metal Tub
ing and Fittings
— ANS Z21.45 Assembled Flexible Appliance Connectors of
Other Than All-Metal Construction
The above connectors may be used if acceptable by the authority
having jurisdiction.The state of Massachusetts requires that a flex
ible appliance connector cannot exceed three feet in length.
Pressure Testing of the Gas Supply System
1. To check the inlet pressure to the gas valve, a 1/8” (3mm) N.P.T.
plugged tapping, accessible for test gauge connection, must be
placed immediately upstream of the gas supply connection to
the appliance.
2. The appliance and its appliance main gas valve must be discon
nected from the gas supply piping system during any pressure
testing of that system at test pressures in excess of 1/2 psig (3.5
kPa).
3. The appliance must be isolated from the gas supply piping sys
tem by closing its equipment shutoff valve during any pressure
testing of the gas supply piping system at test pressures equal
to or less than 1/2 psig (3.5 kPa).
Attention! If one of the above procedures results in pressures in
excess of 1/2 psig (14” w.c.) (3.5 kPa) on the appliance gas valve,
it will result in a hazardous condition.
Checking Manifold Pressure
Natural gas will have a manifold pressure of approximately 6.0”
w.c. (1.49kPa) at the pressure regulator outlet with the inlet pressure
to the pressure regulator from a minimum of 7.0” w.c. (1.743kPa)
for the purpose of input adjustment to a maximum of 10.5” w.c.
(2.615kPa). Propane/LP gas will have a manifold pressure ap
proximately 10.0” w.c. (2.49kPa) at the pressure regulator outlet
with the inlet pressure to the pressure regulator from a minimum
of 11.0” w.c. (2.739kPa) for the purpose of input adjustment to a
maximum of 13.0” w.c. (3.237kPa).
A test gage connection is located downstream of the gas appliance
pressure regulator for measuring gas pressure. The connection is
a 1/8 inch (3mm) N.P.T. plugged tapping.
-
-
-
-
-
16941-5-0907Page 7
Page 8
(610mm)
(356mm)
(51mm)
6”
(152mm)
(152mm)
SR-10T CLEARANCES
When facing the front of the appliance the following minimum
clearances to combustible construction must be maintained.
Left side 6 inches (152mm). Right side 6 inches (152mm).
Do not install in alcove or closet.
Rear wall 0 inches (0mm). Ceiling 24 inches (610mm).
Minimum vertical clearance from a projection above the
appliance (shelves, window sills, etc.) 14 inches (356mm).
Maximum horizontal extension of projection above the
appliance 12 inches (305mm).
Floor (top surface of carpeting, tile, etc.) 2 inches (51mm).
Provide adequate clearances around air openings.
Adequate accessibility clearances for purposes of servicing and
proper operation must be provided.
Figure 4 (SR-10T)
Figure 3 (SR-10T)
16941-5-0907Page 8
Page 9
(203mm)
(203mm)
36” (914mm)
(152mm)
(914mm)
(152mm)
(51mm)
SR-18T CLEARANCES
When facing the front of the appliance the following minimum
clearances to combustible construction must be maintained.
Left side 6 inches (152mm). Right side 6 inches (152mm).
Do not install in alcove or closet.
Rear wall 0 inches (0mm). Ceiling 36 inches (914mm).
Minimum vertical clearance from a projection above the
appliance (shelves, window sills, etc.) 36 inches (914mm).
Floor (top surface of carpeting, tile, etc.) 2 inches (51mm).
Provide adequate clearances around air openings.
Adequate accessibility clearances for purposes of servicing and
proper operation must be provided.
Figure 5 (SR-18T)
SR-30T CLEARANCES
When facing the front of the appliance the following minimum
clearances to combustible construction must be maintained.
Left side 8 inches (203mm). Right side 8 inches (203mm).
Do not install in alcove or closet.
Rear wall 0 inches (0mm). Ceiling 36 inches (914mm).
Minimum vertical clearance from a projection above the
appliance (shelves, window sills, etc.) 36 inches (914mm).
Floor (top surface of carpeting, tile, etc.) 2 inches (51mm).
Provide adequate clearances around air openings.
Adequate accessibility clearances for purposes of servicing and
proper operation must be provided.
Figure 6 (SR-30T)
16941-5-0907Page 9
Page 10
(28 mm)
(300 mm)
(51)
(51)
(479 mm)
(102 mm)
(51 mm)
(559 mm)
(198 mm)
(28mm)
(613mm)
(511mm)
(51)
(51)
(559 mm)
2” (51 mm)
(479 mm)
(102 mm)
MIN
(457mm)
(356mm)
(28mm)
(479mm)
(559mm)
(102mm)
(52mm)
(51mm)
WALL MOUNT INSTALLATION
Refer to Figures 7, 8 and 9 for measurements in order to locate
(4) mounting holes on wall. Figures 7, 8 and 9 are the front views
of the heaters.
1. Remove lower louver from casing assembly (2 screws).
2. Remove reflector from casing assembly (2 screws).
3. Remove upper louver from casing assembly (2 screws).
Figure 7 (SR-10T)
Figure 9 (SR-30T)
On Solid Wall
1. After locating mounting holes, attach (4) #10 x 1” (25mm)
screws provided into the wall. Do not completely tighten
screwheads to the wall, leave a 1/8” (3mm) gap between
screwheads and wall.
2. Mount heater onto the (4) screwheads and complete tightening
screwheads into the wall.
Attention! Use the following steps to properly align the upper
louver and the reflector with the heat shield.
a. When replacing upper louver, be sure the bottom lip of
upper louver goes behind the heat shield.
b. When replacing reflector, be sure the top lip of reflector
goes in front of the heat shield.
3. Connect the gas line.
On Sheet Rock Wall
1. After locating mounting holes, drill (4) 5/16” (8mm) diameter
holes into the wall.
2. Insert (4) plastic expansion anchors provided into the holes.
3. Tighten (4) #10 x 1” (25mm) screws provided into the plastic
expansion anchors. Do not completely tighten screwheads to
the plastic expansion anchors, leave a 1/8” (3mm) gap between
screwheads and plastic expansion anchors.
Figure 8 (SR-18T)
16941-5-0907Page 10
Page 11
4. Mount heater onto the (4) screwheads and complete tightening
the screwheads to the plastic expansion anchors.
Attention! Use the following steps to properly align the upper
louver and the reflector with the heat shield.
a. When replacing upper louver, be sure the bottom lip of
upper louver goes behind the heat shield.
b. When replacing reflector, be sure the top lip of reflector
goes in front of the heat shield.
5. Connect the gas line.
Figure 10
OPTIONAL FLOOR STAND INSTALLATION
1. Align clearance holes on floor stand with screw holes on bot
tom of heater, as shown in Figure 11.
2. Attach floor stand to heater with (4) screws provided with floor
stand.
3. Connect the gas line.
*Floor stand can not be used in a bedroom installation. SR-10T
must be wall mounted in a bedroom installation.
Installation on Rugs and Tile
If this appliance is installed directly on carpeting, tile or other
combustible material, other than wood flooring, the appliance shall
be installed on a metal or wood panel extending the full width and
depth of the appliance.
Attention: Optional Floor Stand meets requirement.
The base referred to above does not mean the fire-proof base as
used on wood stoves. The protection is for rugs that are extremely
thick and light colored tile.
SR-30T SHOWN
Figure 11
16941-5-0907Page 11
Page 12
LIGHTING INSTRUCTIONS
FOR YOUR SAFETY READ BEFORE LIGHTING
WARNING: If you do not follow these instructions exactly, a fire or explosion may result caus-
ing property damage, personal injury or loss of life.
A. This appliance has a pilot which must be lighted by hand.
When lighting the pilot, follow these instructions exactly.
B. BEFORE LIGHTING smell all around the appliance area
for gas. Be sure to smell next to the floor because some gas
is heavier than air and will settle on the floor.
WHAT TO DO IF YOU SMELL GAS
• Do not try to light any appliance.
• Do not touch any electrical switch;
do not use any phone in your building.
• Immediately call your gas supplier from a neighbor’s
phone. Follow the gas supplier’s instructions.
• If you cannot reach your gas supplier, call the fire depart-
LIGHTING INSTRUCTIONS
1. STOP! Read the safety information above.
2. Set thermostat (gas control knob) to lowest setting.
3. Turn off all electric power to the appliance (if applicable).
4. Push in gas control knob slightly and turn clockwise
to “OFF”. Do not force.
5. Wait ten (10) minutes to clear out any gas. Then smell for
gas, including near the floor. If you smell gas, STOP! Follow
“B” in the safety information above. If you don’t smell gas,
go to the next step.
6. Find pilot - the pilot is
attached at the bottom of
the burner assembly .
7. Turn gas control knob
counterclockwise to “PILOT.”
8. Push in gas control knob all the way and hold in. Repeatedly
ment.
C. Use only your hand to push in or turn the gas control knob.
Never use tools. If the knob will not push in or turn by hand,
don’t try to repair it; call a qualified service technician. Force
or attempted repair may result in a fire or explosion.
D. Do not use this appliance if any part has been under water.
Immediately call a qualified service technician to inspect the
appliance and to replace any part of the control system and
any gas control which has been under water.
push the piezo ignitor button until pilot is lit (or use a match
to light pilot). Continue to hold the control knob in for about
one (1) minute after the pilot is lit. Release knob and it will
pop back up. Pilot should remain lit. If it goes out, repeat
steps 4 through 8.
• If knob does not pop up when released, stop and immediately call your service technician or gas supplier.
• If the pilot will not stay lit after several tries, turn the gas
control knob to “OFF” and call your service technician
or gas supplier.
9. Attention! Gas control has an INTERLOCK latching device.
When the pilot is initially lit and the safety magnet is energized (pilot stays “ON”) the INTERLOCK latching device
becomes operative. If the gas control is turned to the “OFF”
position or gas flow to the appliance is shut off, the pilot
cannot be relighted until the safety magnet is de-energized
(approximately 60 seconds). There will be an audible “click”
when the safety magnet in the gas control is de-energized.
Pilot can now be relighted. Repeat steps 4 through 8.
10. Turn gas control knob counterclockwise to “HI”.
11. Turn on all electric power to appliance (if applicable).
12. Set thermostat (gas control knob) to desired setting from “HI”
to “LO”.
TO TURN OFF GAS TO APPLIANCE
1. Set thermostat (gas control knob) to lowest setting.
2. Turn off all electric power to appliance if service is to be
performed (if applicable).
3. Push in gas control knob slightly and turn clockwise
to “OFF”. Do not force.
16941-5-0907Page 12
Page 13
MAIN BURNER FLAME CHARACTERISTICS
SR-10T, SR-18T and SR-30T Main Burner Flame (Figure12)
The main burner flame will have a red-orange glow over the surface
of the ceramic plaques. A few small, hairline cracks may form over
the surface of the ceramic plaques or at the edges of the ceramic
plaques where they have been cemented into position on the burner
assembly frame. These small, hairline cracks will not affect the
operation or performance of the ceramic plaques. Only, when large
cracks develop, with blue flames escaping from the large cracks,
should you contact your QUALIFIED SERVICE PERSON.
A red-orange haze that is visible on the ceramic plaques is acceptable.
A blue flame that rolls out at the top of the ceramic plaques indicates
an accumulation of dust, lint or spider webs inside the casing
assembly and main burner assembly. Use the following procedure
to inspect the casing assembly and main burner assembly.
1. Turn OFF gas supply to the heater.
2. Turn OFF electric supply to the heater if optional blower is
installed in heater.
3. Remove lower louver from casing assembly ( 2 screws).
4. Remove reflector from casing assembly (2 screws).
5. Inspect interior of casing assembly for accumulation of dust, lint
or spider webs. If necessary, clean interior of casing assembly
with a vacuum cleaner or apply air pressure. Do not damage any
components within casing assembly when you are cleaning.
6. Remove pilot bracket from main burner assembly (2
screws).
7. Pivot pilot bracket with attached pilot away from main burner
assembly (do not damage pilot tubing).
8. Inspect main burner orifice(s) through the rectangular opening(s)
in the venturi (throat) of the main burner(s). Dust, lint and spider
webs can accumulate on top of the main burner orifice(s). If
necessary, clean main burner orifice(s) with a vacuum cleaner
or apply air pressure. To thoroughly clean the main burner
orifice(s) proceed to Step 9.
9. Disconnect supply tubing from orifice holder(s).
10. Remove orifice holder from venturi of main burner assembly
(1 screw for each orifice holder).
11. Remove main burner orifice from orifice holder.
12. Apply air pressure through main burner orifice and orifice
holder to remove dust, lint or spider webs.
13. Apply air pressure into ceramic plaque(s) to remove dust, lint
or spider webs.
14. As parts are being replaced in reverse order, check for gas
leaks at all gas connections before lower louver is replaced
onto casing assembly.
SR-30T SHOWN
Figure 12
16941-5-0907Page 13
Page 14
PILOT FLAME CHARACTERISTICS
The correct flame will be blue and will extend beyond the thermocouple. The flame will surround the thermocouple just below
the tip. A slight yellow flame may occur where the pilot flame and
main burner flame meet.
Figure 13
Oxygen Depletion Sensor Pilot (Figure 14)
When the pilot has a large yellow tip flame, clean the Oxygen
Depletion Sensor as follows:
1. Clean the ODS pilot by loosening nut B from the pilot tubing.
When this procedure is required, grasp nut A with an open end
wrench.
2. Blow air pressure through the holes indicated by the arrows
This will blow our foreign materials such as dust, lint and
spider webs. Tighten nut B also by grasping nut A.
Figure 14
Never use needles, wires, or similar cylindrical objects to
clean the pilot to avoid damaging the calibrated ruby that
controls the gas flow.
.
THERMOSTAT OPERATION
To ignite main burner, turn gas control knob counterclockwise to
ward HI setting. To shut down main burner, turn gas control knob
clockwise toward LO setting.
The SR-10T has an input of 10,000 BTUH (2.9KW/H). The hydraulic thermostat bulb is located at the casing assembly bottom.
When the hydraulic thermostat bulb senses the need for heat, the
unit cycles “ON” at a full input rate of 10,000 BTUH (2.9KW/H).
The unit remains at this full input rate until the hydraulic thermostat
bulb is “satisfied.” When the hydraulic thermostat bulb is “satisfied”
the burner will shut “OFF” with the pilot flame remaining “ON.”
The SR-18T has an input of 18,000 BTUH (5.3KW/H). The hy
draulic thermostat bulb is located at the casing assembly bottom.
When the hydraulic thermostat bulb senses the need for heat, the
unit cycles “ON” at a full input rate of 18,000 BTUH (5.3KW/H).
The unit remains at this full input rate until the hydraulic thermostat
bulb is “satisfied.” When the hydraulic thermostat bulb is “satisfied”
the burner will shut “OFF” with the pilot flame remaining “ON.”
Note: The burner does not modulate between “ON” and the pilot
flame. When the SR-18T is “ON,” all three ceramic plaques will
“glow.” There will never be a time when only one or two ceramic
plaques are “glowing.”
The SR-30T has an input of 30,000 BTUH (8.8KW/H). The hy
draulic thermostat bulb is located at the casing assembly bottom.
When the hydraulic thermostat bulb senses the need for heat, the
unit cycles “ON” at a full input rate of 30,000 BTUH (8.8KW/H).
The unit remains at this full input rate until the hydraulic thermostat
bulb is “satisfied.” When the hydraulic thermostat bulb is “satisfied”
the burner will shut “OFF” with the pilot flame remaining “ON.”
-
Note: The burner does not modulate between “ON” and the pilot
flame. When the SR-30T is “ON,” all five ceramic plaques will
“glow.” There will never be a time when only one or three ceramic
plaques are “glowing.”
The LO and HI setting has temperature range of approximately 55°F
(12.78°C) to 90°F (32.22°C), respectively. This is the temperature at
the hydraulic thermostat bulb not the room temperature. The owner
is advised to determine the particular heat setting that is desired for
comfort, as heating requirements are different for every owner.
Attention: If the owner does not want the main burner to ignite
and turns the gas control knob to the LO setting, the main burner
will still ignite if the temperature at the hydraulic thermostat bulb
drops to 55°F (12.78°C).
If no heat is desired, turn the gas control knob to the PILOT posi
tion.
Main Burner Operation
Description of Gas Control Knob:
OFF position.
PILOT position.
-
LO/HI will allow the hydraulic thermostat bulb to cycle the heater
ON and OFF.
-
16941-5-0907Page 14
Page 15
APPLIANCE MAINTENANCE
Removing Pilot/Thermocouple From Main Burner Assembly
Attention: The thermocouple CAN NOT be replaced as an individual
item. You must order a new pilot when replacing thermocouple.
1. Turn OFF gas supply to the heater.
2. Turn OFF electrical supply to the heater if optional blower is
installed in heater.
3. Remove lower louver from casing assembly (2 screws).
4. Remove reflector from casing assembly (2 screws).
5. Disconnect pilot tubing from pilot (see Figure 14, Page 14).
Grasp nut A with a wrench when removing nut B with a second
wrench.
6. Remove pilot from pilot bracket (2 screws).
7. Remove thermocouple lead from gas valve.
8. As parts are being replaced in reverse order, check for gas leaks
at all gas connections before lower louver is replaced onto casing
assembly.
Removing Main Burner Orifice(s) From Main Burner
Assembly
1. Turn OFF gas supply to the heater.
2. Turn OFF electrical supply to the heater if optional blower is
installed in heater.
3. Remove lower louver from casing assembly (2 screws).
4. Remove reflector from casing assembly (2 screws).
5. Remove pilot bracket from main burner assembly (2 screws).
6. Pivot pilot bracket with attached pilot away from main burner
assembly (do not damage pilot tubing).
7. Disconnect supply tubing from orifice holder(s).
8. Remove orifice holder from venturi of main burner assembly
(1 screw for each orifice holder).
9. Remove main burner orifice from orifice holder. Attention: The
number stamped on the main burner orifice is a millimeter
diameter.
10. As parts are being replaced in reverse order, check for gas leaks
at all gas connections before lower louver is replaced onto casing
assembly.
Removing Gas Valve From Casing Assembly
1. Turn OFF gas supply to the heater.
2. Turn OFF electrical supply to the heater if optional blower is
installed in heater.
3. Remove lower louver from casing assembly (2 screws).
4. Remove reflector from casing assembly (2 screws).
5. Remove upper louver from casing assembly (2 screws).
6. If installed, remove optional blower assembly (4 screws).
7. Disconnect inlet supply tubing, outlet supply tubing, pilot
supply tubing and thermocouple lead from gas valve.
8. If heater is attached to wall, disconnect gas supply line from
inlet regulator.
9. Remove heater from wall.
10. Remove gas valve bracket from casing assembly (4 screws to
be removed are located on casing assembly back).
11. Remove hydraulic thermostat bulb from thermostat bulb clip
located at casing assembly bottom.
12. Remove gas valve from gas valve bracket.
13. As parts are being replaced in reverse order, check for gas
leaks at all gas connections before upper louver, reflector and
lower louver are replaced onto casing assembly.
Removing Main Burner From Casing Assembly
1. Turn OFF gas supply to the heater.
2. Turn OFF electrical supply to the heater if optional blower is
installed in heater.
3. Remove lower louver from casing assembly (2 screws).
4. Remove reflector from casing assembly (2 screws).
5. Disconnect supply tubing from orifice holder(s).
6. Remove pilot bracket from main burner assembly (2 screws).
7. Remove main burner assembly from casing assembly (4
screws).
8. Remove orifice shield from main burner assembly. Attach orifice
shield to new main burner assembly.
9. As parts are being replaced in reverse order, check for gas leaks
at all gas connections before lower louver is replaced onto casing
assembly.
Piezo Pilot Ignitor Instructions
Depressing the ignitor button completely causes a spark to occur
at the pilot.
To light the pilot, it is important that the electrode be 1/8” (3mm)
from the pilot. The spark must occur at the point the pilot flame
hits the thermocouple.
On a new installation with air in the gas line, it is suggested that a
match be used. The match will light the pilot faster than the piezo
under this condition.
16941-5-0907Page 15
Page 16
TROUBLESHOOTING
1. Spark electrode does not produce spark.
a. Spark electrode broken - replace.
b. Ignitor wire may not be attached to spark electrode -
attach.
c. Ignitor wire damaged - replace.
d. Piezo ignitor defective - replace.
2. Spark electrode produces spark but pilot does not light.
a. No gas to heater - turn on gas.
b. PILOT position not properly aligned - turn gas control knob
to PILOT position and depress.
c. Pilot is blocked from spider web or dirt - clean pilot, see
Page 14.
3. Pilot flame does not stay “ON” when control knob is
released.
a. Control knob in PILOT position not completely depressed
c. Thermocouple not tightened into gas control - tighten
thermocouple.
d. Pilot flame not surrounding thermocouple - clean pilot, see
Page 14.
e. Inlet gas pressure too low, contact gas supplier.
f. Thermocouple defective - replace.
g. Gas control defective - replace.
4. Main burner does not ignite.
a. Main burner orifice is blocked - clean, see “Main Burner Flame
Characteristics,” Page 13. Attention: The number stamped
on the main burner orifice is a millimeter diameter.
b. Inlet gas pressure too low, contact gas supplier.
5. Heater keeps shutting “OFF” during normal operation.
a. Pilot is blocked - clean pilot, see Page 14.
b. Inlet gas pressure too low, contact gas supplier
or held in long enough.
b. INTERLOCK latching device is operative - see “Lighting
Instructions,” Page 12, Step 9.
HOW TO ORDER REPAIR PARTS
Parts can be ordered
the distributor. Parts can be shipped directly to the service person/dealer.
All parts listed in the Parts List have a Part Number. When ordering parts, first obtain the Model Number from the name plate on your
equipment. Then determine the Part Number (
illustration and list. Be sure to give all this information.
Unvented Heater Model Number Part Description
Unvented Heater Serial Number Part Number
Type of Gas (Propane or Natural)
Do not order bolts, screws, washers or nuts. They are standard hardware items and can be purchased at any local hardware store.
Shipments contingent upon strikes, fires and all causes beyond our control.
only through your service person or dealer. For best results, the service person or dealer should order parts through
not the Index Number) and the Description of each part from the following appropriate
PARTS LIST
SR-10T
PLEASE NOTE: When ordering parts, it is very important that part number and description of part coincide.
INDEX PART
NUMBER NUMBER DESCRIPTION
1 13347 CASING SIDE ASSEMBLY - LEFT
2 SR-180 CASING BACK
3 R-2313 PIEZO IGNITOR
4 SR-008 CASING SIDE ASSEMBLY - RIGHT
5 SR-113 VALVE BRACKET
6 R-6563 GAS VALVE -SIT
7 12438 TUBING - GAS VALVE TO BURNER
8 12437 TUBING - INLET REGULATOR TO GAS
VALVE
9 10753 INLET REGULATOR BRACKET
10 R-5097 INLET REGULATOR - NAT
10 R-5098 INLET REGULATOR - LPG
11 SR-158 TUBING - GAS VALVE TO PILOT
12 R-2314 ORIFICE HOLDER
13 R-2317 MAIN BURNER ORIFICE - NAT
13 R-2476 MAIN BURNER ORIFICE - LPG
14 R-2331 BURNER
15 R-6308 PILOT ASSEMBLY (LPG ONLY)
(INCLUDES ITEMS 16 & 17)
Empire Comfort Systems, Inc. Nine Eighteen Freeburg Ave. Belleville, Illinois 62222-0529
(INCLUDES 31 THROUGH 38)
31 R-1454 BRASS BUSHING (4 REQUIRED)
32 R-1499 RUBBER GROMMET (4 REQUIRED)
33 SR-198 BLOWER PAN
34 R-2099 CORD SET ASSEMBLY
35 R-1468 BUSHING - HEYCO #SR5KN4
36 R-2395 WIRE ASSEMBLY
37 R-2503 FAN CONTROL
38 R-2396 BLOWER (INCLUDES MOTOR, FAN,
AND FAN HOUSING)
NS SR-219 BLOWER HARDWARE PACKAGE
NS R-2390 IGNITOR WIRE
NS SR-216 HARDWARE PACKAGE
USE ONLY MANUFACTURED REPLACEMENT PARTS. USE OF ANY OTHER PARTS COULD CAUSE INJURY OR DEATH.
16941-5-0907Page 17
Page 18
PARTS VIEW
SR-10T
16941-5-0907Page 18
Page 19
PARTS VIEW
SR-18T
16941-5-0907Page 19
Page 20
PARTS VIEW
SR-30T
16941-5-0907Page 20
Page 21
REFLECTOR A
ND LOUVERS ARE
REMOVED FROM
CASING ASSEMBL
Y
GROUND
WIRE SCRE
W
FAN CONTROL
HEAT SHIELD
CORD
SET HOLE
IN
CASING
BAC
K
OPTIONAL BLOWER INSTALLATION INSTRUCTIONS
SRB-18T and SRB-30T
for Unvented Room Heaters SR-18T and SR-30T
INSTALLING OPTIONAL BLOWER SRB-18T OR SRB-30T
If heater is installed onto the wall, in order to install the optional blower,
the heater must be removed from the wall. If heater is installed on
optional floor stand there is adequate access area available to install
the optional blower.
1. Turn “OFF” gas supply to the heater.
2. Remove lower louver from casing assembly (2 screws).
3. Remove reflector from casing assembly (2 screws).
4. Remove upper louver from casing assembly (2 screws).
5. Insert the fan control wires and the upper portion of the fan control
through the 3/4” (19mm) diameter hole on the bottom side of the
top heat shield. The fan control wires will enter into the top portion
of the heater and the fan control disc will be facing the ceramic
plaques. Attach fan control to the bottom side of the top heat shield
with (2) screws provided with the optional blower.
6. Route cord set through 9/16” (14mm) diameter hole on casing as
sembly back. Insert approximately 3” (76mm) of cord set into casing
assembly back.
7. When you are facing the front of the heater, position the optional
blower assembly onto the top heat shield of the heater. The motor wire
harness should be facing into the top, right portion of the heater.
8. Attach (1) pin terminal from black (hot) wire, smooth insulation on
cord set to (1) socket terminal on fan control wire harness.
9. Attach (1) pin terminal from black (neutral) wire, ribbed insulation
on cord set to (1) socket terminal from white (neutral) wire on motor
wire harness.
10. Attach (1) pin terminal on fan control wire harness to (1) socket
terminal from black (hot) wire on motor wire harness.
11. Attach the green ground wire from the motor wire harness and the
green ground wire from the cord set to the bottom right side of the
blower housing with (1) screw provided with the optional blower.
12. With the heater standing upright, position the air discharge opening
of the blower housing downward. Place the bottom flange of the
blower housing over the top edge of the top heat shield. Insert the
blower housing into the top portion of the heater by pivoting the
blower housing upward 90°. Attach the blower housing to the casing
assembly with (4) screws provided with the optional blower.
13. Grasp cord set at casing assembly back and pull excess cord set
through casing assembly back. Secure cord set in casing assembly
back with the strain relief provided with the optional blower.
14. Installation of optional blower is completed.
15. If heater was removed from the wall, in order to install optional
blower, check for gas leaks at all gas connections before lower
louver is replaced onto casing assembly.
Attention! After optional blower has been installed use the following steps
to properly align the upper louver and the reflector with the heat shield.
A. When replacing upper louver, be sure the bottom lip of upper louver
goes behind the heat shield.
B. When replacing reflector, be sure the top lip of reflector goes in front
of the heat shield.
Excessive Blower Wheel Noise
ATTENTION
! If your blower assembly develops a squeal, hum or grinding
noise, it indicates dirt or debris on shaft of blower wheel. Use the following
steps to clean shaft of blower wheel.
1. Remove red rubber grommet with brass bushing or black rubber
grommet with brass bushing from end of blower wheel shaft opposite
motor.
2. Clean blower wheel shaft with cotton cloth.
3. Place 1 or 2 drops of all purpose oil on END of blower wheel
shaft.
4. Replace red rubber grommet with brass bushing or black rubber
grommet with brass bushing onto end of blower wheel shaft.
Attention: The red rubber grommet with brass bushing or the
black rubber grommet with brass bushing must “snap-back” into
position.
The appliance, when installed, must be electrically grounded in accordance
with local codes or, in the absence of local codes, with the National Electri
cal Code, ANSI/NFPA 70, if an external electrical source is utilized
appliance is equipped with a three-prong [grounding] plug for your
protection against shock hazard and should be plugged directly into a
properly grounded three-prong receptacle. Do not cut or remove the
grounding prong from this plug. For an ungrounded receptacle, an adapter,
which has two prongs and a wire for grounding, can be purchased, plugged
into the ungrounded receptacle and its wire connected to the receptacle
mounting screw. With this wire completing the ground, the appliance cord
plug can be plugged into the adapter and be electrically grounded.
CAUTION: Label all wires prior to disconnection when servicing
controls. Wiring errors can cause improper and dangerous operation.
Verify proper operation after servicing.
-
. This
Blower Motor
The blower motor does not have oiling holes. Do not attempt to oil the
blower motor.
Blower Wheel
The blower wheel will collect lint and could require periodic cleaning.
If the air output decreases or the noise level increases, it indicates a dirty
blower wheel.
To clean blower wheel:
1. Turn OFF gas supply to the heater.
2. Turn OFF electrical supply to the heater.
3. Remove lower louver from casing assembly (2 screws).
4. Remove reflector from casing assembly (2 screws).
5. Remove upper louver from casing assembly (2 screws).
6. Clean blower wheel with a vacuum cleaner.
7. As parts are being replaced in reverse order, check for gas leaks at all gas
connections before lower louver is replaced onto casing assembly.
WARNING:
Unplugging of blower accessory will not stop the heater from
cycling. To turn off gas to the unvented heater: Push in gas control
knob slightly and turn clockwise to “OFF.” Do not force.
If any of the original wire as supplied with the appliance must be replaced, it must be replaced
with type 125°C wire or its equivalent.
PARTS LIST
INDEX
NO.
1R-2396BLOWER (INCLUDES MOTOR, FAN, AND
2R-2503FAN CONTROL
3R-2395WIRE ASSEMBLY
48720161BUSHING - HEYCO #SR5KN4
5VF-068CORD SET ASSEMBLY
6SR-196BLOWER PAN (SR-18T)
6SR-198BLOWER PAN (SR-30T)
78520141RUBBER GROMMET (4 REQUIRED)
88520142BRASS BUSHING (4 REQUIRED)
NOT SHOWN SR-219HARDWARE PACKAGE
PART
NO.DESCRIPTION
FAN HOUSING)
16941-5-0907Page 22
Page 23
SERVICE NOTES
16941-5-0907Page 23
Page 24
Empire Comfort Systems, Inc.
918 Freeburg Ave. Belleville, IL 62220
PH: 618-233-7420 or 800-851-3153
FAX: 618-233-7097 or 800-443-8648
info@empirecomfort.com
www.empirecomfort.com
16941-5-0907Page 24
Loading...
+ hidden pages
You need points to download manuals.
1 point = 1 manual.
You can buy points or you can get point for every manual you upload.