Empire Comfort Systems BF28BMN-3, BI28BMN-3, BP28BMN-3, BF28CMN-3, BI28CMN-3 Installation Instructions And Owner's Manual

...
INSTALLATION INSTRUCTIONS
EMPIRE
EMPIRE
Comfor t Systems
WARNING
HOT GLASS
DO NOT TOUCH
NEVER
WILL
CAUSE BURNS.
GLASS
UNTIL COOLED.
ALLOW CHILDREN
TO TOUCH GLASS.
WARNING: If not installed, operated and maintained in accordance with the manufacturer’s instructions, this product could expose you to substances in fuel or from fuel combustion which can cause death or serious illness.
Attention: Check local codes for venting requirements.
Attention: This appliance may be installed in the U.S. and Canada.
Installer: Leave this manual with the appliance. Consumer: Retain this manual for future reference.
AND
OWNER’S MANUAL
POWER-VENT
HIGH-EFFICIENCY
FIREPLACE WITH
BAY WINDOW MODELS
BI28(B,C,G)M(N,P)-3
FLAT FRONT MODELS
FF28BM(N,P)-1
FI28BM(N,P)-1
WARNING: If the information in these instructions arenotfollowed exactly,a re orexplosionmay result causing property damage, personal injury or loss of life.
— Donotstoreorusegasolineorotherammablevapors
and liquids in the vicinity of this or any other appli­ance.
— WHAT TO DO IF YOU SMELL GAS
• Donottrytolightanyappliance.  • Donottouchanyelectricalswitch;donotuseany
phone in your building.
• Immediatelycall your gas supplier fromaneigh-
bor’s phone. Follow the gas supplier’s instruc­tions.
• Ifyoucannotreachyourgassupplier,callthere
— Installation and service must be performed by a quali-
edinstaller,serviceagencyorthegassupplier.
department.
FW28BM(N,P)-1
Young children should be carefully supervised when they are in the same room as the appliance. Toddlers, young children and others may be susceptible to accidental con­tact burns. A physical barrier is recommended if there are atriskindividualsinthehouse.Torestrictaccesstoare­place or stove, install an adjustable safety gate to keep tod­dlers, young children and other at risk individuals out of the room and away from hot surfaces.
This appliance may be installed in an aftermarket, permanently located, manufactured home (USA only) or mobile home, where not prohibited by state or local codes.
This appliance is only for use with the type of gas indicated on the rating plate. This appliance is not convertible for use
withothergases,unlessacertiedkitisused.
Page 1
TABLE OF CONTENTS
SECTION PAGE
Important Safety Information ....................................................................................................................................................................... 3
Safety Information for Users of LP-Gas ....................................................................................................................................................... 4
Requirements for Massachusetts ................................................................................................................................................................... 5
Gas Supply .................................................................................................................................................................................................... 6
Introduction ................................................................................................................................................................................................... 7
Installation Instructions – General Safety Information ................................................................................................................................. 8
Specications ................................................................................................................................................................................................ 8
Clearances for Single Flue ............................................................................................................................................................................. 9
Heater Installation for Single Flue ................................................................................................................................................................. 9
Clearances for Direct Vent ........................................................................................................................................................................... 10
Heater Installation for Direct Vent ............................................................................................................................................................... 10
Bay Window Specications .................................................................................................................................................................. 11 - 12
Flat Front Specications .............................................................................................................................................................................. 13
Bay Window Clearance to Combustibles .................................................................................................................................................... 14
Flat Front Clearance to Combustibles .......................................................................................................................................................... 15
Rough Framing Dimensions ........................................................................................................................................................................ 16
Insert Into Masonry Fireplace ...................................................................................................................................................................... 16
Bay Window Wall Clearances ...................................................................................................................................................................... 17
Flat Front Wall Clearances ........................................................................................................................................................................... 17
Bay Window Log Set Installation Instructions ............................................................................................................................................ 18
Flat Front Log Set Installation Instructions .......................................................................................................................................... 19 - 20
Vent Examples for Single Flue ............................................................................................................................................................. 20 - 22
Flex Vent Kit ................................................................................................................................................................................................ 23
Horizontal Vent Adaptor Kit ........................................................................................................................................................................ 24
Horizontal Examples for Colinear Direct Vent ............................................................................................................................................ 25
Vertical Examples for Colinear Direct Vent .......................................................................................................................................... 26 - 27
Horizontal Colinear Direct Vent Adaptor..................................................................................................................................................... 28
Termination Cap Vent .................................................................................................................................................................................. 29
Colinear Transition Vent Kit ........................................................................................................................................................................ 30
Direct Vent Installation Instructions ............................................................................................................................................................ 31
Vent Kit ................................................................................................................................................................................................. 32 - 33
Bay Window Gas Connection Installation Instructions ............................................................................................................................... 34
Flat Front Gas Connection Installation Instructions .................................................................................................................................... 35
F(F,I,W)K28(BL, CM, HP, SS)Surround Installation Instructions .............................................................................................................. 36
FGK Surround Installation Instructions ................................................................................................................................................ 36 - 37
Operating Instructions Checklist .................................................................................................................................................................. 38
Lighting Instructions ............................................................................................................................................................................... 39-40
Fan Operation ............................................................................................................................................................................................... 41
Automatic Humidier Operation ................................................................................................................................................................. 41
Optional Controllers .............................................................................................................................................................................. 42 - 43
Wiring .......................................................................................................................................................................................................... 44
General Information ..................................................................................................................................................................................... 45
Bay Window Maintenance .................................................................................................................................................................... 45 - 46
Flat Front Maintenance ......................................................................................................................................................................... 47 - 49
Unit Operating Faults ................................................................................................................................................................................... 50
Resetting the Heater ..................................................................................................................................................................................... 50
Log Placement ............................................................................................................................................................................................. 50
Main Convection Fan ................................................................................................................................................................................... 51
Heat Exchanger ............................................................................................................................................................................................ 51
Bay Window Surround Installation Instructions .......................................................................................................................................... 51
Pedestal Installation Instructions - Bay Window Only ................................................................................................................................ 52
Master Parts Distributor List ........................................................................................................................................................................ 53
How To Order Repair Parts .......................................................................................................................................................................... 53
Bay Window Parts List ......................................................................................................................................................................... 54 - 55
Bay Window Exploded View ................................................................................................................................................................ 56 - 57
Flat Front Parts List ..................................................................................................................................................................................... 58
Flat Front Parts View ................................................................................................................................................................................... 59
Warranty Terms ............................................................................................................................................................................................ 60
Appliance Service History .................................................................................................................................................................... 61- 63
27020-3-0410Page 2
IMPORTANT SAFETY INFORMATION
THIS IS A HEATING APPLIANCE
DO NOT OPERATE THIS APPLIANCE WITHOUT FRONT PANEL INSTALLED.
• Due to high temperatures the appliance should be located out of trafc and away from furniture and
draperies.
• Children and adults should be alerted to the hazards
of high surface temperatures and should stay away to avoid burns or clothing ignition.
• Young children should be carefully supervised when
they are in the same room as the appliance. Toddlers, young children and others may be susceptible to acci­dental contact burns. A physical barrier is recommend­ed if there are at risk individuals in the house. To restrict
accesstoareplaceorstove,installanadjustablesafety
gate to keep away toddlers, young children and other at risk individuals out of the room and away from hot surfaces.
• Clothing or other ammable material should not be
placed on or near the appliance.
• Any safety screen or guard removed for servicing an appliance must be replaced prior to operating the appliance.
• Keepburnerandcontrolcompartmentclean.
• Ventcaphotwhilefurnaceisinoperation.
• For manufactured home (USA only) or mobile home
or residential installation convertible for use with natural gas and liqueed petroleum gases when provision is made for the simple conversion from one gas to the other.
• Installation and repair should be done by a QUALIFIED SERVICE PERSON. The appliance should be inspected before use and at least annually
by a qualied service person. More frequent cleaning
may be required due to excessive lint from carpeting, bedding materials, etc. It is imperative that control compartments, burners and circulating air passageways of the appliance be kept clean.
• DO NOT put anything around the furnace that will obstructtheowofcombustionandventilationair.
• DO keep the appliance area clear and free from combustible material, gasoline and other ammable
vapors and liquids.
• Do examine venting system periodically and replace
damaged parts.
• Domakea periodic visualcheckof burner.Clean and
replace damaged parts.
• DO NOT use this heater if any part has been under water. Immediately call a qualied service technician
to inspect the heater and to replace any part of the control system and any gas control which has been under water.
27020-3-0410 Page 3
SAFETY INFORMATION FOR USERS OF LP-GAS
Propane (LP-Gas) is a ammable gas which can cause res and
explosions. In its natural state, propane is odorless and colorless. You may not know all the following safety precautions which can protect both you and your family from an accident. Read them carefully now, then review them point by point with the mem-
LP-GAS WARNING ODOR
If a gas leak happens, you should be able to smell the gas because of the odorant put in the LP-Gas.
That’s your signal to go into immediate action!
Do not operate electric switches, light matches, use your
phone. Do not do anything that could ignite the gas.
Get everyone out of the building, vehicle, trailer, or area. Do
that IMMEDIATELY.
Close all gas tank or cylinder supply valves.
LP-Gas is heavier than air and may settle in low areas such
as basements. When you have reason to suspect a gas leak, keep out of basements and other low areas. Stay out until
reghters declare them to be safe.
NO ODOR DETECTED - ODOR FADE
Some people cannot smell well. Some people cannot smell the
odor of the chemical put into the gas. You must nd out if you
can smell the odorant in propane. Smoking can decrease your ability to smell. Being around an odor for a time can affect your sensitivity or ability to detect that odor. Sometimes other odors in the area mask the gas odor. People may not smell the gas odor or their minds are on something else. Thinking about smelling a gas odor can make it easier to smell.
The odorant in LP-gas is colorless, and it can fade under some circumstances. For example, if there is an underground leak, the
movement of the gas through soil can lter the odorant. Odorants
bers of your household. Someday, there may not be a minute to lose, everyone’s safety will depend on knowing exactly what to do. If, after reading the following information, you feel you still need more information, please contact your gas supplier.
Use your neighbor’s phone and call a trained LP-Gas service person and the re department. Even though you
may not continue to smell gas, do not turn on the gas again. Do not re-enter the building, vehicle, trailer, or area.
Finally, let the service man and reghters check for escaped gas. Have them air out the area before you return. Properly trained LP-Gas service people should repair the leak, then check and relight the gas appliance for you.
in LP-Gas also are subject to oxidation. This fading can occur if there is rust inside the storage tank or in iron gas pipes.
The odorant in escaped gas can adsorb or absorb onto or into walls, masonry and other materials and fabrics in a room. That will take some of the odorant out of the gas, reducing its odor intensity.
LP-Gas may stratify in a closed area, and the odor intensity could vary at different levels. Since it is heavier than air, there may be more odor at lower levels. Always be sensitive to the slightest gas odor. If you detect any odor, treat it as a serious leak. Immediately go into action as instructed earlier.
Learn to recognize the odor of LP-gas. Your local LP-Gas
Dealer can give you a “Scratch and Sniff” pamphlet. Use it
to nd out what the propane odor smells like. If you suspect
that your LP-Gas has a weak or abnormal odor, call your LP-Gas Dealer.
If you are not qualied, do not light pilot lights, perform
service, or make adjustments to appliances on the LP-Gas
system. If you are qualied, consciously think about the
odor of LP-Gas prior to and while lighting pilot lights or performing service or making adjustments.
Sometimes a basement or a closed-up house has a musty
smell that can cover up the LP-Gas odor. Do not try to light pilot lights, perform service, or make adjustments in an area where the conditions are such that you may not detect the odor if there has been a leak of LP-Gas.
Odor fade, due to oxidation by rust or adsorption on walls
of new cylinders and tanks, is possible. Therefore, people should be particularly alert and careful when new tanks or cylinders are placed in service. Odor fade can occur in new
tanks, or reinstalled old tanks, if they are lled and allowed to set too long before relling. Cylinders and tanks which
SOME POINTS TO REMEMBER
have been out of service for a time may develop internal rust which will cause odor fade. If such conditions are suspected to exist, a periodic sniff test of the gas is advisable. If you have any question about the gas odor, call your LP-gas dealer. A periodic sniff test of the LP-gas is a good safety measure under any condition.
If, at any time, you do not smell the LP-Gas odorant and
you think you should, assume you have a leak. Then take the same immediate action recommended above for the occasion when you do detect the odorized LP-Gas.
If you experience a complete “gas out,” (the container is under no vapor pressure), turn the tank valve off immediately. If the container valve is left on, the container may draw in some air through openings such as pilot light orices. If this occurs, some new internal rusting could occur. If the valve is left open, then treat the container as a new tank. Always be sure your container is under vapor pressure by turning it off at the container before it goes com-
pletely empty or having it relled before it is completely
empty.
27020-3-0410Page 4
REQUIREMENTS FOR MASSACHUSETTS
For all side wall horizontally vented gas fueled equipment installed in every dwelling, building or structure used in whole or in part for residential purposes, including those owned or operated by the Commonwealth and where the side wall exhaust vent termination
is less than seven (7) feet above nished grade in the area of
the venting, including but not limited to decks and porches, the
following requirements shall be satised:
1. INSTALLATION OF CARBON MONOXIDE DETECTORS. At the time of installation of the side wall horizontal vented
gas fueled equipment, the installing plumber or gastter shall
observe that a hard wired carbon monoxide detector with an
alarm and battery back-up is installed on the oor level where
the gas equipment is to be installed. In addition, the installing
plumber or gastter shall observe that a battery operated
or hard wired carbon monoxide detector with an alarm is installed on each additional level of the dwelling, building or structure served by the side wall horizontal vented gas fueled equipment. It shall be the responsibility of the property owner
to secure the services of qualied licensed professionals for
the installation of hard wired carbon monoxide detectors
a. In the event that the side wall horizontally vented gas
fueled equipment is installed in a crawl space or an attic, the hard wired carbon monoxide detector with alarm and battery back-up may be installed on the next adjacent
oor level.
b. In the event that the requirements of this subdivision can
not be met at the time of completion of installation, the owner shall have a period of thirty (30) days to comply with the above requirements; provided, however, that during said thirty (30) day period, a battery operated carbon monoxide detector with an alarm shall be installed.
2. APPROVED CARBON MONOXIDE DETECTORS. Each carbon monoxide detector as required in accordance with the above provisions shall comply with NFPA 720 and be ANSI/
UL 2034 listed and IAS certied.
3. SIGNAGE. A metal or plastic identication plate shall be
permanently mounted to the exterior of the building at a minimum height of eight (8) feet above grade directly in line with the exhaust vent terminal for the horizontally vented gas fueled heating appliance or equipment. The sign shall read, in print size no less than one-half (1/2) inch in size, “GAS
VENT DIRECTLY BELOW. KEEP CLEAR OF ALL
OBSTRUCTIONS”.
4. INSPECTION. The state or local gas inspector of the side wall horizontally vented gas fueled equipment shall not approve the installation unless, upon inspection, the inspector observes carbon monoxide detectors and signage installed in accordance with the provisions of 248 CMR 5.08(2)(a) 1 through 4.
(b) EXEMPTIONS: The following equipment is exempt
from 248 CMR 5.08(2)(a)1 through 4:
1. The equipment listed in Chapter 10 entitled
“Equipment Not Required To Be Vented” in the most current edition of NFPA 54 as adopted by the Board; and
2. Product Approved side wall horizontally vented gas
fueled equipment installed in a room or structure separate from the dwelling, building or structure used in whole or in part for residential purposes.
(d) MANUFACTURER REQUIREMENTS - GAS
EQUIPMENT VENTING SYSTEM NOT PROVIDED. When the manufacturer of a Product Approved side wall horizontally vented gas fueled equipment does not
provide the parts for venting the ue gases, but identies
“special venting systems”, the following requirements
shall be satised by the manufacturer:
1. The referenced “special venting system” instructions
shall be included with the appliance or equipment installation instructions; and
2. The “special venting systems” shall be Product
Approved by the Board, and the instructions for that system shal include a parts list and detailed installation instruction.
(e) A copy of all installation instructions for all Product
Approved side wall horizontally vented gas fueled equipment, all venting instructions, all parts lists for venting instructions, and/or all venting design instructions shall remain with the appliance or equipment at the completion of the installation.
27020-3-0410 Page 5
GAS SUPPLY
FLEX TUBING
3/8 NPT NIPPLE
FLARE FITTING
GAS VA L V E
SOLENOID
FLARE SHUT OFF VA LV E
Consult the current National Fuel Gas Code, ANSI Z223.1 CAN/ CGA-B149 (.1 or .2) installation code.
Recommended Gas Pipe Diameter
Pipe Length Schedule 40 Pipe
Inside Diameter
Tubing, Type L
Outside Diameter
Nat. L.P. Nat. L.P.
0-10 feet
0-3 meters
10-40 feet
4-12 meters
40-100 feet
13-30 meters
100-150 feet
31-46 meters
1/2”
12.7mm
1/2”
12.7mm
1/2”
12.7mm
3/4”
19mm
3/8”
9.5 mm
1/2”
12.7mm
1/2”
12.7mm
1/2”
12.7mm
1/2”
12.7mm
5/8”
15.9 mm
3/4”
19mm
7/8”
22.2 mm
3/8”
9.5 mm
1/2”
12.7mm
1/2”
12.7mm
3/4”
19mm
Note: Never use plastic pipe. Check to conrm whether your local
codes allow copper tubing or galvanized.
Note: Since some municipalities have additional local codes, it is always best to consult your local authority and installation code.
The use of the following gas connectors is recommended:
— ANS Z21.24 Appliance Connectors of Corrugated Metal Tubing
and Fittings
— ANS Z21.45 Assembled Flexible Appliance Connectors of
Other Than All-Metal Construction
The above connectors may be used if acceptable by the authority
having jurisdiction. The state of Massachusetts requires that a exible
appliance connector cannot exceed three feet in length.
Figure 1
Installing a New Main Gas Cock
Each appliance should have its own manual gas cock.
A manual main gas cock should be located in the vicinity of the unit. Where none exists, or where its size or location is not adequate, contact your local authorized installer for installation or relocation.
Compounds used on threaded joints of gas piping shall be resistant
to the action of liqueed petroleum gases. The gas lines must be
checked for leaks by the installer. This should be done with a soap solution watching for bubbles on all exposed connections, and if unexposed, a pressure test should be made.
Neveruseanexposedametocheckforleaks.Appliancemust
be disconnected from piping at inlet of control valve and pipe capped or plugged for pressure test. Never pressure test with
applianceconnected;controlvalvewillsustaindamage!
A gas valve and ground joint union should be installed in the gas line upstream of the gas control to aid in servicing. It is required by the National Fuel Gas Code that a drip line be installed near the gas inlet. This should consist of a vertical length of pipe tee connected into the gas line that is capped on the bottom in which condensation and foreign particles may collect.
Pressure Testing of the Gas Supply System
1. To check the inlet pressure to the gas valve, a 1/8" (3 mm) N.P.T. plugged tapping, accessible for test gauge connection, must be placed immediately upstream of the gas supply connection to the appliance.
2. The appliance and its individual shutoff valve must be disconnected from the gas supply piping system during any pressure testing of that system at test pressures in excess of 1/2 psig (3.5 kPa).
3. The appliance must be isolated from the gas supply piping system by closing its individual manual shutoff valve during any pressure testing of the gas supply piping system at test pressures equal to or less than 1/2 psig (3.5 kPa).
Attention! If one of the procedures results in pressures in excess
of1/2psig(14"w.c.)(3.5kPa)onthereplacegasvalve,itwill resultinahazardouscondition.
Checking Manifold Pressure
Both Propane and Natural gas valves have a built-in pressure regulator in the gas valve. Natural gas models will have a manifold pressure of approximately 3.5" w.c. (.872 kPa) at the valve outlet with the inlet pressure to the valve from a minimum of 5.0" w.c. (1.245 kPa) for the purpose of input adjustment to a maximum of
10.5" w.c. (2.614 kPa) Propane gas models will have a manifold
pressure approximately 7.0" w.c. (2.49 kPa) at the valve outlet with the inlet pressure to the valve from a minimum of 11.0" w.c. (2.739 kPa) for the purpose of input adjustment to a maximum of
13.0" w.c. (3.237 kPa).
A 1/8" (3 mm) N.P.T. plugged tapping, accessible for test gauge connection, is located on the outlet side of the gas control.
27020-3-0410Page 6
INTRODUCTION
Introduction
Always consult your local Building Department regarding regulations, codes or ordinances which apply to the installation of a direct vent wall furnace.
Instructions to Installer
1. Installer must leave instruction manual with owner after installation.
2. Installer must have owner ll out and mail warranty card supplied with furnace.
3. Installer should show owner how to start and operate furnace and thermostat.
4. Installer must locate unit near a grounded wall receptacle for 115VAC power and must provide gas supply and vent the unit properly for safe operation.
Warning: Any change to this furnace or its control can be dangerous. This is a heating appliance and any panel, door or guard removed for servicing an appliance must be replaced prior to operating the appliance.
General Information
This series is designed certied in accordance with American
National Standard/CSA Standard Z21.88 and CSA 2.33 by the Canadian Standards Association as a Gas Fireplace Heater to be installed according to these instructions.
Any alteration of the original design, installed other than as shown in these instructions or use with a type of gas not shown on the rating plate is the responsibility of the person and company making the change.
Important
All Correspondence should refer to complete Model Number, Serial Number and type of gas.
Notice: During initial ring of this unit, oil from the heat exchanger may bake out and smoke may occur. To prevent trig­gering of smoke alarms, ventilate the room in which the unit is installed.
Installation in Residential Garages
Gas utilization equipment in residential garages shall be installed so that all burners and burner ignition devices are located not less
than 18” (457 mm) above the oor.
Such equipment shall be located, or protected, so it is not subject to physical damage by a moving vehicle.
QualiedInstallingAgency
Installation and replacement of gas piping, gas utilization equipment or accessories and repair and servicing of equipment
shall be performed only by a qualied agency. The term “quali­ed agency” mean any individual, rm, corporation or company
which either in person or through a representative is engaged in and is responsible for (a) the installation or replacement of gas piping or (b) the connection, installation, repair or servicing of equipment, who is experienced in such work, familiar with all precautions required and has complied with all the requirements of the authority having jurisdiction. The installation must conform with local codes, or in the absence of local codes, the National Fuel Gas Code, ANSI Z223.1/NFPA 54 or Natural Gas and Propane Installation Code, CSA B149.1. * Available from the American National Standards Institute, Inc., 11 West 42nd St., New York, NY 10036.
A manufactured home (USA only) or mobile home OEM installation must conform with the Manufactured Home Construction and Safety Standard, Title 24 CFR, Part 3280, or, when such a standard is not applicable, the Standard for Manu­factured Home Installations, ANSIZ225.1, or Standard for Gas Equipped Recreational Vehicles and Mobile Housing, CSA Z240.0.
Sate of Massachusetts: The installation must be made by a licensed plumber or gas tter in the Commonwealth of Mas­sachusetts.
High Altitudes
For altitudes/elevations above 2,000 feet (610 m), input ratings should be reduced at the rate of 4 percent for each 1,000 feet (305 m) above sea level, this may be accomplished by reducing manifold pressure. The maximum allowable reduction in manifold pressure for Natural gas shall be from 3.5” w.c. (.872 kPa) to 2.8” w.c. (.697 kPa). The maximum allowable reduction in manifold pressure for Propane (LP) gas shall be from 10.0” w.c. (2.49 kPa) to 8.0” w.c. (1.99 kPa). For Canadian high altitude applications, this appliance is suitable for installation at elevations between 0 feet (0 m) and 4,500 feet (1,372 m) without change.
Canada:
This appliance may be installed in Canada.
27020-3-0410 Page 7
INSTALLATION INSTRUCTIONS - GENERAL SAFETY INFORMATION
1. This installation must conform with local codes or, in the absence of local codes with NFPA54.
2. Provide adequate clearances around the product for servicing and ensure there are no obstructions to the combustion air intake situated at the back of the heater. Refer to Pages 14 and
15.
3. The appliance must be installed on a at, solid continuous surface (i.e. wood, metal, concrete). Please Note: Rough
or uneven surfaces can cause vibration or humming in the heater.
4. The Mantis Power-Vent High-Effeciency Fireplace can be
installed in a wide variety of ways and will t nearly any
room layout. For installation options refer to Pages 14 and
15.
5. This appliance (Insert and Freestanding Models) needs to be installed in such a way that the heater can be removed at all
times to service the heater exchanger and ue fan located in
the rear section of the heater.
SPECIFICATIONS
Note: Under no circumstances should the appliance be
installed under conditions which would not allow for easy removal of the appliance to carry out routine inspection and service to the appliance, to do so will void the warranty.
Note: On Single Wall ue pipe installations (imitation
zero clearance replace) a minimum of 2” (50.8 cm) clearance must be provided at the rear of the heater to
enable the heater to get sufcient combustion air to the
air inlet located at the rear of heater. Refer to installation instructions on Pages 14 and 15.
Note: Where a mantel surround is being used on insert
installations and zero clearance replace installations,
the combustion air intake slot located in the top mantel surround must have no obstructions to allow combustion air to enter through the slot to the combustion air inlet located at the back of the heater.
Bay Window Models B(F,I,P)28(B,C,G)M
Input BTU/HR (KW/H) 19,000 Rear - 9,000 Front
Height 25 1/8”
Width 28 3/16”
Depth 17 5/8”
Gas Inlet (Pipe) 3/8” Flair
Electrical - Unit has a 5’ (1.5 m) 3 pronged cordset for con-
nection to an approved 115 VAC 60 Hz maximum AMPs - 5A wall receptacle.
Flat Front Models F(F,I,W)28BM(N,P)
Input BTU/HR (KW/H) 15,000 Rear - 13,000 Front
Height 24 9/16”
Width 28”
Depth 17 3/16”
Gas Inlet (Pipe) 3/8” Flair
Electrical - Unit has a 5’ (1.5 m) 3 pronged cordset for con-
nection to an approved 115 VAC 60 Hz maximum AMPs - 5A wall receptacle.
Accessories
Common
Part Number Description
FRBTC Battery Operated Remote with Thermostat
FRBTP
PVCA Colinear Adapter
PVCT Colinear Transition
PVVK24H Direct Vent 24” Vent Kit
PVVK48H Direct Vent 48” Vent Kit
PVVK-CFA Flex Vent Kit
PVVK-SH Single Flue Horizontal Vent Kit
PVVK-SV Single Flue Vertical Vent Kit
PVVTC Vertical Termination Cap - 1.5”
T24V 24 Volt Thermostat
TMV2 Two-Stage Thermostats
TRW Wall Thermostat - Wireless Remote
TDV1 Wall Thermostat - Wireless Remote
CIFPB-1C Corner Floor Pad Kit
CIPFP-1 Floor Pad Kit
PV-2H Top Cover - Slim Assembly
PV-4H Top Cover - Short Assembly
PVE-1 6” Surround Assembly
PVPK Pedestal Kit
PVSH Rear Shroud
TRW Wall Thermostat - Wireless Remote
Battery Operated Remote with Programmable Thermostat
Bay Window
27020-3-0410Page 8
CLEARANCES FOR SINGLE FLUE
1. Pick a location on a wall with a clear space in the room. In selecting a location for installation, it is necessary to provide adequate accessibility clearances for servicing and proper installation. Be sure to locate the unit close enough to a 115 VAC wall receptacle to properly power appliance.
2. When facing the front of the furnace, the minimum clearances from casing to combustible construction are 0” (0 mm) on top, 0” (0 mm) on each side, recommend 4” (102 mm) for servicing
and 0” (0 mm) from the oor and 2” (51 mm) to rear wall for
servicing and installation.
3. The minimum distance from the center of the vent cap to the nearest outside corner or obstruction is 12” (305 mm).
HEATER INSTALLATION FOR SINGLE FLUE
The bottom of the exhaust vent terminal and the air intake shall be located at least 12” (305 mm) above grade and must be vented outside.
WARNING: The nearest point of the vent cap should be a
minimumhorizontaldistanceofsix(6)feet(1.83m)from
any pressure regulator. In case of regulator malfunction,
thesix(6)feet(1.83m)distancewillreducethechanceof
gas entering the vent cap.
Installation on Rugs and Tile
If this appliance is to be installed directly on carpeting, tile, or other
combustible material, other than wood ooring, the appliance shall
be installed on a metal or wood panel extending the full width and depth of the appliance.
The base referred to above does not mean the re-proof base as
used on wood stoves. The protection is primarily for rugs that may be extremely thick and light-color tile that can discolor.
Locating Wall Opening
The recommended location for this heater is on an outside wall (the unit can be located on an inside wall but must not exceed 40’ (12.19 m) in exhaust vent length). Locate wall studs so that wall vent opening will be located between wall studs. The wall opening required for venting is a 1 7/8” (48 mm) minimum diameter opening.
Refer to Pages 11 to 17 for positioning the heater on wall and for locating gas line connection and vent opening. Heater can sit on
the oor.
27020-3-0410 Page 9
CLEARANCES FOR DIRECT VENT
1 9/16”
4 3/32”
1. Pick a location on a wall with a clear space in the room. In selecting a location for installation, it is necessary to provide adequate accessibility clearances for servicing and proper installation. Be sure to locate the unit close enough to a 110 VAC wall receptacle to properly power appliance.
2. When facing the front of the furnace the minimum clearances from casing to combustible construction are 0” (0 mm) on top, 0” (0 mm) on each side, recommend 4” (102 mm) on sides
for servicing and 0” (0 mm) from the oor, 0” (0 mm) to rear
wall and 40” (1,016 mm) from Mantis top to ceiling.
3. The minimum distance from the center of the vent cap to the nearest outside corner or obstruction is 12” (305 mm).
4. The minimum wall depth is 4” (102 mm) and the maximum is 48” (121.92 cm).
The vent terminal of a direct vent appliance, with an input of 50,000 BTU (14.6KW) per hour or less shall be located at least
9” (229 mm) from any opening through which ue gases could
enter a building.
The bottom of the exhaust vent terminal and the air intake shall be located at least 12” (305 mm) above grade and must be vented outside.
WARNING: The nearest point of the vent cap should be
aminimumhorizontaldistantofsix(6)feet(1.83m)from
any pressure regulator. In case of regulator malfunction,
thesix(6)feet(1.83m)distancewillreducethechanceof
gas entering the vent cap.
Installation on Rugs and Tile
If this appliance is to be installed directly on carpeting, tile, or other
combustible material, other than wood ooring, the appliance shall
be installed on a metal or wood panel extending the full width and depth of the appliance.
The base referred to above does not mean the re-proof base as
used on wood stoves. The protection is primarily for rugs that may be extremely thick and light-color tile that can discolor.
HEATER INSTALLATION FOR DIRECT VENT
Locating Wall Opening
The recommended location for this furnace is on an outside wall. Locate wall studs so that wall vent opening will be located between wall studs. The wall opening required for venting is a 3 1/2” (89 mm) minimum diameter opening.
Refer to Pages 11 to 17 for positioning the heater on wall and for locating gas line connection and vent opening. Furnace can sit on
the oor.
Figure 2
27020-3-0410Page 10
BAY WINDOW SPECIFICATIONS
28 3/16”
(71.6cm)
33 3/4”
(85.7cm)
8 5/8”
(21.9cm)
17 5/8”
(44.8cm)
5 - SINGLE FLUE ADAPTOR
12 1/4”
(31.1cm)
1 - FLUE OUTLET
28 3/16”
(71.6cm)
25 1/8”
(63.8cm)
27 3/4”
(70.5cm)
17 5/8”
(44.8cm)
3 9/16” (9.0cm)
16 15/16”
(43.0cm)
1 - FLUE OUTLET
5 - SINGLE FLUE ADAPTOR
Index No. Description
1 Flue Outlet 1 1/2” PVC Pipe
2 Air Inlet
3 Electric Cord
4 3/8” Flare Connection (Inside)
5 Single Flue Adaptor Model (Required)
6 Surround
PVE1-1 Used on openings less than 35” PVE2-1 Used on openings less than 37 1/2” openings
7 Top Cover Kit, Slim Model #PV2H
8 Top Cover Kit, Short
27020-3-0410 Page 11
Heater with Pedestal and Single Flue Adaptor
Heater without pedestal
35 7/16”
(90.0cm)
29 3/4”
(75.6cm)
5 15/16” (15.1cm)
23 13/16”
(60.5cm)
10 1/8”
(25.7cm)
6 3/16”
(15.7cm)
3 9/16” (9.0cm)
16 15/16”
(43.0cm)
8 -TOP COVER KIT,
SHORT
1 - FLUE OUTLET
5 - SINGLE FLUE
ADAPTOR
LOUVER
BAY WINDOW SPECIFICATIONS - (continued)
35 7/16”
(90.0cm)
29 3/4”
(75.6cm)
5 15/16” (15.1cm)
23 13/16”
(60.5cm)
10 1/8”
(25.7cm)
6 3/16”
(15.7cm)
3 9/16” (9.0cm)
16 15/16”
(43.0cm)
6 - SURROUND
ASSEMBLY
1 - FLUE OUTLET
13/16” (2.1cm)
2 - AIR INLET
7 9/16”
(19.2cm)
2 13/16”
(7.1cm)
1 7/16”
(3.7cm)
4 - ½” FLARE
CONNECTION INSIDE
6 1/8”
(15.6cm)
1 ½”
(3.8cm)
3 9/16”
(9.0cm)
1”
(2.5cm)
3 - ELECTRIC
CORD
8 -TOP COVER KIT,
SHORT
1 - FLUE OUTLET
5 - SINGLE FLUE
ADAPTOR
LOUVER
Fireplace Insert with Mantel Surround with Slim Top Panel
Fireplace Insert with Mantel Surround with Short Top Panel
Rear View (Same with or without pedestal and all tops)
27020-3-0410Page 12
FLAT FRONT SPECIFICATIONS
35”
(88.9cm)
33 7/16”
(84.9cm)
35”
(88.9cm)
29 3/8”
(74.6cm)
38”
(96.5cm)
30 7/8”
(78.4cm)
1 - FLUE OUTLET
2 - AIR INLET
3 - ELECTRIC
CORD
4 - FLEX HOSE OPENING
1 1/8” (2.8cm)
7 5/16”
(18.6cm)
4 3/16”
(10.6cm)
2 5/8”
(6.7cm)
6 1/8”
(15.6cm)
3 9/16”
(9.0cm)
13/16”
(2.1cm)
1” (2.5cm)
17”
(43.2cm)
3 9/16” (9.0cm)
1 - FLUE OUTLET
5 - SINGLE FLUE ADAPTOR MODEL #PVVK-SH
6 1/2” (16.5cm) MIN. WITH 90° STREET ELBOW
24 3/4” MIN
(62.8cm)
Heater In Wall - 35” Picture Frame Surround
FWK28(BL,CM,HP,SS) - Contains surround, hood, and lower
front
Heater-35”SurroundKit
FFK28(BL,CM,HP,SS) - Contains surround, hood, & lower front
Heater - 38” Surround
FIK28(BL,CM,HP,SS) - Contains surround, hood, & lower front
27020-3-0410 Page 13
Index
Description
No.
1 Flue Outlet 1 1/2” PVC Pipe
2 Air Inlet
3 Electric Cord
4 3/8” Flare Connection (Inside)
5 Single Flue Adaptor Model #PVVK-SH (required)
BAY WINDOW CLEARANCE TO COMBUSTIBLES
C
C
A
BB
33 1/4”
(84.5cm)
29 3/4”
(75.6cm)
12”
(30.5cm)
26 ½”
(67.3cm)
35 7/16”
(90.0cm)
WALL OPENING
D
LOUVER
12”
18”
24”
8”
6”
4”
COMBUSTIBLE TRIM AND MANTELS
ALLOWED IN SHADED AREA
40”
CEILING
Freestanding Models
Figure 3 Figure 4
Freestanding Units
A Rear Wall to Heater 0” (2” Single Flue and 1 1/4” Direct Vent for Serviceability)
B Side Wall to Heater 0” (4” recommended for serviceability)
C Corner Installation 0”
D Mantel Clearance See Figure 7
Fireplace Insert
Requires surround for combustion air.
Single Flue
Do not cover surround louver.
Figure 5
Single Flue requires surround for combustion air.
Direct Vent Installation Shown
Figure6
Note: The Mantis Power-Vent High-Efciency Fireplace has been tested and approved for zero clearance to combustible materials.
Empire Comfort Systems, Inc. recommends that clearances as listed above should be maintained to allow for removal of the product for servicing.
Mantel and Ceiling Clearances
Figure 7
27020-3-0410Page 14
FLAT FRONT CLEARANCE TO COMBUSTIBLES
37”
(93.98 cm)
30 7/8”
(78.4cm)
12”
(30.5cm)
26 ½”
(67.3cm)
38”
(96.5cm)
WALL OPENING
D
A
A
BB
6 1/4”
MIN
C
C
12”
18”
24”
8”
6”
4”
COMBUSTIBLE TRIM AND MANTELS
ALLOWED IN SHADED AREA
44 3/4”
CEILING
4 3/4”
Insert Models
Figure 8 Figure 10
Figure 9
Freestanding Units
A Rear Wall to Heater 0” (2” Single Flue and 1 1/4” Direct Vent for Serviceability)
B Side Wall to Heater 0”
C Corner Installation 0”
D Mantel Clearance See Figure 12
Fireplace Insert
Requires surround for combustion air.
Note: The Mantis Power-Vent High-Efciency Fireplace has been tested and approved for zero clearance to combustible materials.
Empire Comfort Systems, Inc. recommends that clearances as listed above should be maintained to allow for removal of the
27020-3-0410 Page 15
product for servicing.
Do not cover surround louver.
Single Flue
Figure 11
Mantel and Ceiling Clearances
Figure 12
ROUGH FRAMING DIMENSIONS
A
B
C
ACCESS
PANELS
ACCESS PANELS
1.5”
BAY WINDOW
A - 13 /34” MIN. CO-LINEAR
8 1/2” WHEN USING DIRECT VENTING
NOTE: DIMENSIONS FOR USE WITH SHORT TOP.
THIS IS RECOMMENDED FOR UNIT SERVICE­ABILITY.
B - 25 1/8”
C - 28”
NOTE: IF TRIM AROUND HEATER IS NECESSARY, THE
SURROUND KIT PVE1-1 OR PVE2-1 MUST BE USED, AND SUBTRACT 1” FROM (A) DIMEN-
Figure 13
FLAT FRONT
A - 23 1/2” MIN. WITH 90° STREET ELBOW
B - 24 3/4”
C - 28 3/16” MIN., 31” RECOMMENDED FOR
NOTE: HEATER WILL BE 0” CLEARANCE ON RIGHT
D - 4” - 6”
NOTE: ONLY ONE ACCESS PANEL (FIGURE 14) IS NEED-
Figure 14
SION.
27 3/4” IF FGK SURROUND IS USED
SERVICEABILITY.
AND 3” ON LEFT FOR SERVICEABILITY.
ED. INSTALLER TO DETERMINE BEST OPTION.
INSERT INTO MASONRY FIREPLACE
BAY WINDOW
A - 12 3/4” MIN. SHORT TOP
17 13/16” MIN. SLIM TOP USING SURROUND KIT
B - 25 1/8” MIN. DIRECT VENT
26 1/2” MIN. SINGLE FLUE 29” MAX
C - 28” MIN. NO SURROUND
33” MIN. WITH PVE-1 SURROUND 35” MAX. WITH PVE-1 SURROUND 37” MAX. WITH PVE2-1 SURROUND
FLAT FRONT
A - 23 1/2” WHEN USING FI28(BL,CM,HP,SS) SUR-
ROUND
Figure 15
B - 24 3/4” MIN. DIRECT
29” MAX
C - 28 3/16” MIN. WITH SURROUND
37” MAX. WITH 38” SURROUND
D - 4”
27020-3-0410Page 16
BAY WINDOW WALL CLEARANCES
12 23/32”
6”
11 3/32”
17 13/16”
PVVK-CFA
PVVK-SH
PVE-1
6 ½”
6 ½”
23 1/2”
(59.7cm)
6 ½”
(16.5cm)
24 3/4”
(62.8cm)
MIN.
Figure16
FLAT FRONT WALL CLEARANCES
27020-3-0410 Page 17
Figure 17
BAY WINDOW LOG SET INSTALLATION INSTRUCTIONS
A
B
C
D
E
PLATE - LOG SUPPORT
FRONT HOT SURFACE IGNITOR
REAR HOT SURFACE IGNITOR REAR FLAME SENSOR
FRONT FLAME SENSOR
REAR BURNER
FRONT BURNER
F
G
Log Installation
The positioning of the logs is critical to the safe and clean opera­tion of this heater. Sooting and other problems may result if the
logs are not properly and rmly positioned in the appliance.
Note: Before you begin: Do not handle these logs with your
bare hands! Always wear gloves to prevent skin irrita­tion. After handling logs, wash your hands gently with soap and water.
1. To access the log set parcel, lift off top panel.
2. Pivot left and right panels open.
3. Unlatch main door latches located on right and left side of the heater, remove door.
4. Connect Rear Left Log (A) and Rear Right Log (B) at pins on sides of each log and place in rear of burner. Logs should be
all the way to the back of the rebox.
5. Place Front Left Log (C) into groove on (A) Log and into left
corner of rebox.
6. Place Middle Log (D) over ame sensors in middle of re-
box.
7. Place Front Right Log (E) into right front corner of rebox.
8. Place Top Left Log (F) onto pin on (A) Log. The “legs” of (F) Log will rest on (D) Log
9. Place Top Right Log (G) onto pin on (B) Log. The “legs” of (G) Log will rest on (E) Log.
10. Place Door Assembly onto front of heater and latch main door latches located on right and left sides of the heater.
11. Close left and right panels.
12. Installation of log set is complete.
Log Placement
Figure 17a
Log Placement
Figure 17b
Firebox Layout
Figure 18
Log Placement
Figure 17c
27020-3-0410Page 18
FLAT FRONT LOG SET INSTALLATION INSTRUCTIONS
REAR LOG SUPPORT
FRONT LOG SUPPORT
FIREBOX BOTTOM
REAR HOT SURFACE IGNITOR
REAR FLAME SENSOR
REAR BURNER
RIGHT REAR LOG SUPPORT SHELF
FRONT BURNER
FRONT FLAME SENSOR
FRONT HOT SURFACE IGNITOR
LEFT REAR LOG SUPPORT SHELF
B
F
D
A
H
C
G
E
Log Installation
The positioning of the logs is critical to the safe and clean operation of this heater. Sooting and other problems may result if
the logs are not properly and rmly positioned in the appliance.
Note: Before you begin: Do not handle these logs with your bare
hands! Always wear gloves to prevent skin irritation. After handling logs, wash your hands gently with soap and water.
Note: See Page 47 for Glass Assembly removal and
replacement.
Log Placement
1. Place Rear Log (A) onto rear log support. The notch in the
Rear Log ts over the rear Hot Surface Ignitor.
2. Place Left Log (B) on left rear log support shelf. The charred portion of the log must face inward.
3. Place Middle Log (D) on front log support between the front and back burners.
4. Place Front Right Log (F) on right side of Firebox bottom.
Notch in bottom of Front Right Log ts over the front Flame
sensor. See Figure 20A.
5. Place Front Left Log (E) on left side of Firebox bottom. Notch in bottom of Front Left Log ts over front Hot Surface Ignitor. See Figure 20B.
6. Place Right Log (C) on right rear log support shelf. Top of log rests on Rear Log (A) and bottom of log rests on Firebox bottom. Charred portion of log must face inward.
7. Place Left Top Long Log (G) on the pin on Left Log (B). The upper left leg of Left Top Log will rest on Rear Log (A). The upper right leg of Left Top Log will rest on Middle Log (D).
8. Place Right Top Long Log (H) on the pin on the Right Log (C). The bottom left leg of the Right Top Log will rest in the indent on the right side of the Middle Log (D). The bottom right leg of the Right Top Log will rest in the indent in the Front Right Log (F).
Figure 20A
Figure 20B
27020-3-0410 Page 19
Figure 21
FLAT FRONT LOG SET INSTALLATION INSTRUCTIONS
A- Rear Log
B-Left Log
C-Right Log
D-Middle Log
E-Front Left Log
F-Front Right Log
G-Left Top Log
H-Right Top Log
EXTERIOR GRADE
12” MIN.
6” MIN.
MIN. 2”
12” MIN.
SINGLE FLUE ADAPTOR
LOG SET DIAGRAM - A
The Gas Log Kit contains the following:
Index Letter Log Description
A Rear Log
B Left Log
C Right Log
D Middle Log
E Front Left Log
F Front Right Log
G Left Top Log
H Right Top Log
Figure 22
VENT EXAMPLES FOR SINGLE FLUE
Max Vent Run - 40 ft. Equivalent With Three (3) 90° Elbows
Special Note: The vent terminal 90° elbow and rst 90° el­bowoffbackoftheheater,whenwithin6” (15.2cm),donot
contribute to the overall vent length measurement. For each
45° elbow installed in the horizontal run, the length of the horizontal run MUST be reduced by 1.5 feet (45 cm). This
does not apply if the 45° elbows are installed on the vertical
partof theventsystem.Reducethe lengthofthehorizontal
run 3 feet (91.4 cm) for every 90° elbow.
Note: On horizontal runs, a P.V.C. support clamp needs to be in-
stalled every 3 feet. No “sags” in horizontal vent runs; water will settle in the pipe.
When installing a single ue horizontal, the minimum vent length
protruding from the outside wall is 6” (15.2 cm). See Figure 23.
Minimum vent from the rear of the unit is 12”.
Note: Horizontal discharge 90° elbow must be pointed down­ward. See Figure 23. All horizontal runs require either a 1/4” per foot rise to run condensation back to the heater, or a 1/4” per foot downward slope to run condensation away from the heater.
Note: All PVC vent run piping can be purchased at a local hard­ware store. Schedule 40 PVC pipe should be used and cemented. Flex Kit and Horizontal Vent Adaptor Kit are available from Em­pire Comfort Systems, Inc.
Figure 23
Single Flue - Straight Out Back
Min6”OutsideWall
Min 2” From Unit to Wall for Intake Air
Min vent length 12”
Figure 24
SingleFlue-VentingwithShroudKitInstalled
27020-3-0410Page 20