Empire Comfort Systems FAW-40-1SPP, FAW-40-1IP User Manual

INSTALLATION INSTRUCTIONS
AND
OWNER'S MANUAL
FAN TYPE
VENTED
WALL FURNACE
MODEL
FAW-40-1IP
Installer: Leave this manual with the appli-
ance.
Consumer: Retain this manual for future refer-
ence.
WARNING: If not installed, operated and maintained in accordance with the manu­facturer's instructions, this product could expose you to substances in fuel or from fuel combustion which can cause death or serious illness.
WARNING: If the information in these in­structions are not followed exactly, a fire or explosion may result causing property dam­age, personal injury or loss of life.
— Do not store or use gasoline or other flam-
mable vapors and liquids in the vicinity of this or any other appliance.
— WHAT TO DO IF YOU SMELL GAS
Do not try to light any appliance.
Do not touch any electrical switch; do not use any phone in your building.
Immediately call your gas supplier from a neighbor’s phone. Follow the gas sup­plier’s instructions.
If you cannot reach your gas supplier, call the fire department.
— Installation and service must be performed
by a qualified installer, service agency or the gas supplier.
Page 1
Introduction
Always consult your local Building Department regarding regulations, codes or ordinances which apply to the installation of a vented wall furnace.
Instructions to Installer
1. Insta ller must le ave inst ruction ma nual with ow ner afte r installation.
2. Installer must have owner fill out and mail warranty card supplied with furnace.
3. Installer should show owner how to start and operate furnace and thermostat.
Warning: Any change to this furnace or its control can be dangerous. This is a heating appliance and any panel, door or guard removed for servicing an appliance must be replaced prior to operating the appliance.
General Information
This series is design certified in accordance with American National Standard / CSA Standard Z21.86 and CSA 2.32 by the Canadian Standards Association, as a Fan Type Vented Wall Furnace and must be installed according to these instructions.
Any alteration of the original design, installed other than as shown in these instructions or use with a type of gas not shown on the rating plate is the responsibility of the person and company making the change.
Important
All correspondence should refer to complete Model No., Serial No. and type of gas.
Notice: During initial firing of this unit, its paint will bake out and smoke will occur. To prevent triggering of smoke alarms, ventilate the room in which the unit is installed.
Installation on Rugs and Tile
If this appliance is installed directly on carpeting, tile or other combustible material other than wood flooring the appliance shall be installed on a metal or wood panel extending the full width and depth of the appliance.
The base referred to above does not mean the fire-proof base as used on wood stoves. The protection is for rugs that are extremely thick and light colored tile.
Installation in Residential Garages
Gas utilization equipment in residential garages shall be installed so that all burners and burner ignition devices are located not less than 18" (457mm) above the floor.
Such equipment shall be located, or protected, so it is not subject to physical damage by a moving vehicle.
Specifications
Model FAW-40SPP FAW-40IP Input BTU/HR (KW/H) 40,000 (11.7) 40,000 (11.7) Height 72 1/2" (84.1mm) 72 1/2" (184.1mm) Width 14 1/8" (35.9mm) 14 1/8" (35.9mm) Depth 10 3/8" (26.4mm) 10 3/8" (26.4mm) Gas Inlet Pipe 1/2" (12.7mm) 1/2" (12.7mm) Vent Collar Type B Oval 4" (101mm) 4" (101mm)
CFM 275 275 Accessories
Register, side outlet, fixed register Side outlet, 10" (254mm)
maximum extension, fixed register Rear outlet, 10" (254mm)
maximum extension, adjustable register Vent enclosure, 24" (609mm)
[for rooms up to 96 1/2" 2451mm) in height] Vent enclosure, 34" (86cm)
[for rooms up to 106 1/2" (2705mm) in height] Vent enclosure, 46" (1168mm)
[for rooms up to 118 1/2" (3009mm) in height] Oval-to-Round flue adapter kit 4" (102mm) DV-648
SOR-1 SOK-1
ROK-1
FVE-24
FVE-34
FVE-46
THIS IS A HEATING APPLIANCE
DO NOT OPERATE THIS APPLIANCE WITHOUT FRONT PANELS INSTALLED.
Due to high temperatures the appliance should be located out
of traffic and away from furniture and draperies.
• Children and adults should be alerted to the hazards of high surface temperatures and should stay away to avoid burns or clothing ignition.
• Young children should be carefully supervised when they are in the same room as the appliance.
• Clothing or other flammable material should not be placed on or near the appliance.
• Any safety screen or guard removed for servicing an appliance must be replaced prior to operating the appliance.
• Keep burner and control compartment clean.
• Installation and repair should be done by a QUALIFIED SER­VICE PERSON. The appliance should be inspected before use and at least annually by a qualified service person. More frequent cleaning may be required due to excessive lint from carpeting, bedding materials, etc. It is imperative that control compartments, burners and circulating air passageways of the appliance be kept clean.
• DO NOT put anything around the furnace that will obstruct
Page 2
the flow of combustion and ventilation air.
• DO keep the appliance area clear and free from combustible material, gasoline and other flammable vapors and liquids.
• DO examine venting system periodically and replace damaged parts.
• DO make a periodic visual check of pilot and burners. Clean and replace damaged parts.
• CAUTION: Pilot hole cover must be kept tightly closed during operation.
• DO NOT use this heater if any part has been under water. Immediately call a qualified service technician to inspect the heater and to replace any part of the control system and any gas control which has been under water.
• This furnace must not be connected to a chimney flue serving a separate solid-fuel burning appliance.
IMPORTANT: This furnace has a washable permanent type
filter in the door which should be cleaned at least once per year before the heating season. For dirty or high use areas more frequent cleaning is required.
12427-6-0707
SAFETY INFORMATION FOR USERS OF LP-GAS
Propane (LP-Gas) is a flammable gas which can cause fires and explosions. In its natural state, propane is odorless and colorless. You may not know all the following safety precau­tions which can protect both you and your family from an accident. Read them carefully now, then review them point
LP-GAS WARNING ODOR
If a gas leak happens, you should be able to smell the gas because of the odorant put in the LP-Gas.
That's your signal to go into immediate action!
by point with the members of your household. Someday when there may not be a minute to lose, everyone's safety will depend on knowing exactly what to do. If, after read­ing the following information, you feel you still need more information, please contact your gas supplier.
Do not operate electric switches, light matches, use your phone. Do not do anything that could ignite the gas.
• Get everyone out of the building, vehicle, trailer, or area. Do that IMMEDIATELY.
• Close all gas tank or cylinder supply valves.
• LP-Gas is heavier than air and may settle in low areas such as basements. When you have reason to suspect a gas leak, keep out of basements and other low areas. Stay out until
NO ODOR DETECTED - ODOR FADE
Some people cannot smell well. Some people cannot smell the odor of the chemical stench put into the gas. You must find out if you can smell the odorant in propane. Smoking
can decrease your ability to smell. Being around an odor for a time can affect your sensitivity or ability to detect that odor. Sometimes other odors in the area mask the gas odor. People may not smell the gas odor or their minds are on something else. Thinking about smelling a gas odor can make it easier to smell.
The odorant in LP-gas is colorless, and it can fade under some circumstances. For example, if there is an underground
leak, the movement of the gas through soil can filter the odor
firefighters declare them to be safe.
• Use your neighbor's phone and call a trained LP-Gas service person and the fire department. Even though you may not continue to smell gas, do not turn on the gas again. Do not re-enter the building, vehicle, trailer, or area.
Finally, let the service man and firefighters check for escaped gas. Have them air out the area before you return. Properly trained LP-Gas service people should repair the leak, then check and relight the gas appliance for you.
ant. Odorants in LP-Gas also are subject to oxidation. This fading can occur if there is rust inside the storage tank or in iron gas pipes.
The odorant in escaped gas can adsorb or absorb onto or into walls, masonry and other materials and fabrics in a room. That will take some of the odorant out of the gas, reducing its odor intensity.
LP-Gas may stratify in a closed area, and the odor intensity could vary at different levels. Since it is heavier than air, there may be more odor at lower levels. Always be sensitive to the
-
slightest gas odor. If you detect any odor, treat it as a serious leak. Immediately go into action as instructed earlier.
SOME POINTS TO REMEMBER
Learn to recognize the odor of LP-gas. Your local LP-Gas Dealer can give you a "Scratch and Sniff" pamphlet. Use it to find out what the propane odor smells like. If you suspect that your LP-Gas has a weak or abnormal odor, call your LP-Gas Dealer.
• If you are not qualified, do not light pilot lights, perform service, or make adjustments to appliances on the LP-Gas system. If you are qualified, consciously think about the odor of LP-Gas prior to and while lighting pilot lights or performing service or making adjustments.
• Sometimes a basement or a closed-up house has a musty smell that can cover up the LP-Gas odor. Do not try to light pilot lights, perform service, or make adjustments in an area where the conditions are such that you may not detect the odor if there has been a leak of LP-Gas.
• Odor fade, due to oxidation by rust or adsorption on walls of new cylinders and tanks, is possible. Therefore, people should be particularly alert and careful when new tanks or cylinders are placed in service. Odor fade can occur in new tanks, or reinstalled old tanks, if they are filled and allowed
12427-6-0707
to set too long before refilling. Cylinders and tanks which have been out of service for a time may develop internal rust which will cause odor fade. If such conditions are suspected to exist, a periodic sniff test of the gas is advisable. If you
have any question about the gas odor, call your LP-gas dealer. measure under any condition.
• If, at any time, you do not smell the LP-Gas odorant and you think you should, assume you have a leak. Then take the same immediate action recommended above for the occasion when you do detect the odorized LP-Gas.
• If you experience a complete "gas out," (the container is un der no vapor pressure), turn the tank valve off immediately. If the container valve is left on, the container may draw in some air through openings such as pilot light orifices. If this occurs, some new internal rusting could occur. If the valve is left open, then treat the container as a new tank. Always be sure your container is under vapor pressure by turning it off at the container before it goes completely empty or having it refilled before it is completely empty.
A periodic sniff test of the LP-gas is a good safety
Page 3
-
furnace
opening
confined� space
furna ce
out le t air
inlet a ir
a ttic ve ntila tion louve rs
crawl sp ace ventila tion lou vers
furnace
outlet air
inlet air ends one foot above floor
vertical
furnace
inlet air duct
outlet air duct
horizontal
Ventilation and Combustion Air
WARNING: Danger of property damage, bodily injury or death, this furnace and any other fuel burning appliance must be provided with enough fresh air for proper combustion and ventilation of flue gases. Most homes will require that outside air be supplied. Do not draw air from a corrosive environment such as a workshop or laundry room.
The requirements for providing air for combustion and ventilation are listed in the National Fuel Gas Codes NFPA 54/ANSI Z223.1 (in Canada
- CAN/CGA B149). Note: Air requirements for operation of exhaust fans, kitchen ventilation systems, clothes dryers, fireplace and any other fuel burning or ventilating equipment used in the space must be considered in determining combustion air requirements.
Ventilation Air Openings and Ducts
In determining the free area needed consideration must be given to the blocking effect of louvers, grills or screens protecting openings. — If a screen is used to cover openings it must not be smaller than 1/4"
mesh.
— Use the free area of a louver or grill to determine the size opening
required to provide the free area specified. If the free area is not known assume a 20% free area for wood and a 60% free area for a metal louver or grill.
— Ducts must have the same cross sectional area as the free area of the
openings to which they connect.
— The minimum dimension of air ducts must not be less than 3
inches.
Installation in an Unconfined Space
An unconfined space is an area including all rooms not separated by doors with a volume greater than 50 cubic feet per 1,000 Btuh of the combined total input rates of all appliances which draw combustion air from that space. For example, a space including a water heater rated at 40,000 Btuh input and a furnace rated at 40,000 Btuh requires a volume of 4,000 cubic feet (50 x (40 + 40) = 4,000) to be considered as unconfined. If the space has an 8 ft. ceiling, the floor area of the space must be 500 sq. ft. In general, particularly in older homes, a furnace installed in an unconfined space will not require outside air for combustion. However in a "tight" newly constructed home, outside air may be necessary to insure adequate combustion.
Installation in a Confined Space
A confined space is an area with volume less than 50 cubic feet per 1,000 Btuh of the combined input rates of all appliances drawing combustion air from that space. Small areas such as equipment rooms are confined spaces. Furnaces installed in a confined space which supply heated air to areas outside the space must draw return air from outside the space through tightly sealed return air ducts. A confined space must have 2 openings into the space for combustion air. One opening must be within 12 inches of the ceiling and the other must be within 12 inches of the floor. The required sizing of these openings is determined by whether inside or outside air is used to support combustion, the method by which the air is brought to the space (vertical or horizontal duct) and by the total input rate of all appliances in the space. See Figure 1.
All Air From Inside — Confined Space
If combustion air is taken from the heated space the 2 openings must each have a free area of at least one square inch per 1,000 Btuh of total input of all appliances in the confined space but not less than 100 square inches (645cm2) of free area.
For example: for a 40,000 Btuh furnace only in the confined space each opening must be 100 square inches (645cm2) each of free area.
Figure 1
Outdoor Air
Outlet and inlet air can be brought into the confined space via openings into a ventilated attic and ventilated crawl space.
Figure 2
Confined Space Outdoor Air Using Vertical or Horizontal Ducts
If combustion air is taken from outdoors through vertical ducts, the openings and ducts must have a minimum free area of one square inch (6.5cm2) per 4,000 Btuh of total appliance input. In installations drawing combustion air from a ventilated attic both air ducts must extend above the attic insulation.
WARNING: Combustion air must not be drawn from a heated space which includes exhaust fans, fireplaces or other devices that may produce a negative pressure in the space.
Page 4
Figure 3
If combustion air is taken from outdoors through horizontal ducts the openings and ducts must have a minimum free area of one square inch (6.5cm2) per 2,000 Btuh of total appliance input.
12427-6-0707
4” ROUND
VENT ENCLOSURE
ADAPTER
BASEPLA
TE
WALL
SIDE
FRONT
A.
4” B-1 OVAL
BRACKET
BASEPLA
TE
B.
4” B-1 OVAL
4” B-1 OVAL
SPACER
BASEPLA
TE
BASEPLA
TE
C.
SPACER
C.
4” 45 DEG. OVAL ELBOW
S
Qualified Installing Agency
Installation and replacement of gas piping, gas utilization equipment or accessories and repair and servicing of equipment shall be performed only by a qualified agency. The term "qualified agency" means any individual, firm, corporation or company which either in person or through a representative is engaged in and is responsible for (a) the installation or replacement of gas piping or (b) the connection, installation, repair or servicing of equipment, who is experienced in such work, familiar with all precautions required and has complied with all the requirements of the authority having jurisdiction.
The installation must conform with local codes or, in the absence of local codes, with the National Fuel Gas Code, ANSI Z223.1/NFPA 54* Natural
and Propane Installation Code, CSA B149.1.
*Available from the American National Standards Institute, Inc., 11 West 42nd St., New York, N.Y. 10036.
Clearances
1. In selecting a location for installation, it is necessary to provide adequate accessibility clearances for servicing and proper installation.
2. The FAW-40 can be attached to the wall or recessed into the wall up to 9 1/2 inches (24.1cm) in depth.
header or material on top of unit when installed in wall. Maintain 3/4" minimum spacing above heater.
3. The wall in which the furnace is recessed has (0) zero (0mm) clearance to the furnace sides.
Note:
Do not place combustible
4. When using side discharge registers, SOR-1 or SOK-1, the furnace cannot be recessed into the wall.
5. Clearance to sidewall or combustible material is 4 inches (10.2cm).
6. Ceiling clearance is 4 inches (10.2cm).
7. Floor and rear wall clearance is (0) zero inches (0mm).
8. Clearance of 18 inches (46cm) is required to adjacent wall or combustible material when flush mounted SOR-1, side outlet register is used.
Before Installing Consider The Following Venting
1. A chimney for residential-type or low-heat gas utilization equipment shall extend at least 3 feet (914mm) above the highest point where it passes through a roof of a building and at least 2 feet (610mm) higher than any portion of building within a horizontal distance of 10 feet (3m).
2. This furnace must not be connected to a chimney flue serving a separate solid-fuel burning appliance.
3. Uninsulated Single-Wall Metal Pipe shall not be used outdoors in cold climates for venting gas utilization equipment.
4. Attention! This Fan Type Vented Wall Furnace is equipped with a
vent safety switch. In the event of spillage of flue products due to improper venting the vent safety switch will open, which results in the main burners to "shut off".
Model No. FAW-40 may be vented as shown in Figure 4. The vent cap termination must be at least 12 feet (3.7m) above the floor and must exhaust to the outdoors.. Clearance to combustible construction is held by the fixed spacers at 1 inch (25mm) with B-1 or (B-W) vent pipe. Installation must conform to local codes.
A. 4" (102mm) Round
1. Type B-1 round pipe
(all parts purchase locally except Item 2)
2. Part No. DV-648, 4" (102mm) oval-to-round flue adapter kit (see
accessories)
3. Single story type B-1 gas vents require a baseplate and one pair
of ceiling plate spacers.
4. Multi-story type B-1 gas vents require a baseplate, one pair of
ceiling plate spacers at the first floor ceiling and one pair of fire stop spacers at each successive ceiling level.
B. 4" (102mm) Oval
(all parts purchase locally)
1. Type B-1 oval pipe or B-W vent pipe
2. Single story type B-1 or (B-W) gas vents require a baseplate and
one pair of ceiling plate spacers.
3. Multi-story type B-1 or (B-W) gas vents require a baseplate, one
pair of ceiling plate spacers at the first floor ceiling and one pair of fire stop spacers at each successive ceiling level
C. 4" (102mm) Oval In-The-Wall (all parts purchase locally)
1. Type B-1 oval pipe or B-W vent pipe
2. Type B-1 oval elbows or B-W oval elbows
3. Single story type B-1 or (B-W) gas vents require a baseplate and one pair of ceiling plate spacers.
4. Multi-story type B-1 or (B-W) gas vents require a baseplate, one pair of ceiling plate spacers at the first floor ceiling and one pair of fire stop spacers at each successive ceiling level.
Stud space around gas vents must be free of obstructions and building paper.
Figure 4
.
12427-6-0707
Page 5
Use U.L. listed gas vent equipment when installing the FAW-40. For
4" MINIMUM TO COMBUSTIBLE� WALL OR SURFACE
CLEARANCE FOR SIDE OUTLET KITS AND REAR REGISTER� KIT TO ADJACENT WALL
4" MINIMUM TO COMBUSTIBLE� WALL OR SURFACE
18" MIN. CLEARANCE TO WALL OR COMBUSTIBLE SURFACE USING MODEL SOR-1 SIDE REGISTER.
WALL
5 1/2"
5 1/2"
UNIT CANNOT BE RECESSED� WHEN SIDE REGISTERS ARE� USED.
WHEN SIDE REGISTERS ARE� NOT USED UNIT MAY BE RECESSED� UP TO 9 1/2"
6 1/4"
10 1/4"
REAR REGISTER OPENING� IN OUTER CABINET
12"
12"
TYPE B-1 OR B-W OVAL� VENT PIPE
vent pipe running through walls, roof, and within one (1) inch (25mm) of combustible construction, use B-1 or (B-W) [one inch (25mm) clearance to combustibles] vent pipe. Type B-2 x 4 or Type B-2 x 6 are to be used in conjunction with a Listed fire stop spacer.
Be sure baseplate is attached to top of furnace before inserting unit into recessed wall installation.
Installing Optional Side Outlets
Side outlet register,
SOR-1 may be installed on one or both sides of the furnace at the required clearances of 18 inches (457mm) to adjacent wall or combustible material as shown in Figure 6.
1. Turn "OFF" all electric power to the furnace.
2. Remove the front panel from the furnace.
3. Remove the (2) #8 x 3/8" (9mm) screws that attach the inner shield
cover plate to the inner shield.
4. Scribe a line between the four dimples on the outer casing side to form
a square.
5. Drill a pilot hole within the scribed square on the outer casing. Remove
the sheet metal within the scribed square with a tin snips or comparable tool. Attention! Do not cut the electrical wires located between the outer casing and the inner shield.
6. Insert the 5" x 5" (127mm x 127mm) inner boot through the outer cas
ing. Align the clearance holes on the inner boot with the screw holes on the inner shield. Attach inner boot to inner shield with (2) # 8 x 3/8" (9mm) screws removed in Step 3.
7. Place the register over the 5 1/2" (140mm) square opening with the
louvers set for the desired direction and mark the mounting holes using the register as a template.
8. Drill (2) 1/8" diameter holes in cabinet side and attach the register with
(2) #10 x 1" (25mm) provided screws.
9. Installation of SOR-1 is completed.
Side outlet kit,
SOK-1, 10" (254mm) boot assembly with register, for warm air discharge into an adjoining room may be installed on either side of the furnace at the required clearance of 4 inches (102mm) to adjacent wall as shown in Figure 6.
To install SOK-1, please use Steps 1 through 5 in the SOR-1 instructions for FAW-40 furnaces. Now, use the following Steps to complete installa tion of the SOK-1.
1. Using the inner and outer boots as hole templates, mark and drill (4)
1/8" (3mm) diameter holes in the inner shield and (4) 1/8" (3mm) diameter holes in the cabinet side.
2. Locate and cut a 6 3/4" (171mm) square opening through wall.
3. Attach furnace to wall (see Attaching Furnace to Wall
4. With furnace in place, after checking alignment of side outlet opening
in wall and furnace, place the 9 3/8" x 9 3/8" (238mm x 238mm) side outlet wall plate over outer boot, pass the outer boot through the wall
Page 6
Figure 5
and attach side wall plate to furnace side of wall with (2) #10 x 1 1/2"
(38mm) provided screws.
5. Attach outer boot to the cabinet side with (4) #8 x 1/4" (6mm) provided screws.
6. Position and attach inner boot to inner shield with (4) #8 x 1/4" (6mm) provided screws.
7. Place the register over the 6 3/4" (171mm) square opening with the louvers positioned for the desired discharge direction and mark the mounting holes using the register as a template.
8. Drill (2) 1/8" (3mm) diameter holes in the wall and attach the register with (2) #10 x 1 1/2" (38mm) provided screws.
9. Installation of SOK-1 is completed.
Figure 6
Installing Optional Rear Outlet
Rear outlet kit, 10" (254mm) boot assembly with register, ROK-1 for warm air discharge into an adjoining room.
-
Attention: Before furnace is attached to the wall, the wall opening for the rear outlet must be cut, in addition to removal of the outer and inner casing knockouts on furnace.
1. The wall opening measurements for the rear outlet are the following.
A. From floor to bottom of wall opening is 10 11/16" (271mm). B. From bottom of wall opening to top of wall opening is 8 1/2"
(216mm).
C. Wall opening width is 12 1/8" (308mm).
2. Scribe a line between the four dimples on the outer casing back to form
a square. Drill a pilot hole within the scribed square on the outer casing back. Remove the sheet metal within the scribed square with a tin snips or comparable tool.
3. Remove the (4) #8 x 3/8" (9mm) screws that attach the inner casing
close off plate to the inner casing.
4. Insert the privacy shield through the outer casing back and the inner
-
casing back. The privacy shield will be in front of the inner casing back and behind the combustion chamber tubes. Align clearance holes on privacy shield with screw holes on inner casing back. Attach privacy shield to inner casing back with (2) #8 x 3/8" (9mm) provided. Attention:
The (2) #8 x 3/8" (9mm) screws must be inserted from the front of the furnace.
).
5. Attach furnace to wall.
6. Align clearance holes on 8" x 12" (203mm x 305mm) boot with screw
holes on outer casing back and mark boot to be flush with wall surface. Remove boot and cut to proper length.
7. Attach 8" x 12" (203mm x 305mm)boot to outer casing back with (6)
12427-6-0707
Loading...
+ 12 hidden pages