Empire Comfort Systems DVX36DP31, DVX36DP91, DVX36DP71, DVX42DP71, DVX42DP91, DVX42DP31 User Manual
Specifications and Main Features
Frequently Asked Questions
User Manual
INSTALLATION INSTRUCTIONS
GAS-FIRED
AND
OWNER’S MANUAL
The Studio Series Direct Vent Zero
Clearance Gas Fireplace Heater
Installer: Leave this manual with the appli-
ance.
Consumer: Retain this manual for future refer-
ence.
LUXURY DIRECT VENT
GAS FIREPLACE HEATER
MODEL SERIES
MILLIVOLT STANDING PILOT
DVX36DP31(N,P)-1
DVX42DP31(N,P)-1
INTERMITTENT PILOT
DVX36DP71(N,P)-1
DVX42DP71(N,P)-1
REMOTE RF
DVX36DP91(N,P)-1
DVX42DP91(N,P)-1
UL FILE NO. MH30033
WARNING: If the information in these instruc-
tions are not followed exactly, a re or explosion
may result causing property damage, personal
injury or loss of life.
— Do not store or use gasoline or other amma-
ble vapors and liquids in the vicinity of this or
any other appliance.
— WHAT TO DO IF YOU SMELL GAS
• Do not try to light any appliance.
• Do not touch any electrical switch; do not
use any phone in your building.
• Immediately call your gas supplier from
a neighbor’s phone. Follow the gas supplier’s instructions.
• If you cannot reach your gas supplier, call
the re department.
— Installation and service must be performed by
a qualied installer, service agency or the gas
supplier.
This appliance may be installed in an aftermarket,
permanently located, manufactured home (USA only)
or mobile home, where not prohibited by state or local
codes.
This appliance is only for use with the type of gas
indicated on the rating plate. This appliance is not
convertible for use with other gases, unless a certied
kit is used.
WARNING: If not installed, operated and maintained
in accordance with the manufacturer’s instructions,
this product could expose you to substances in fuel or
from fuel combustion which can cause death or serious illness.
Page 1
TABLE OF CONTENTS
Section Page
Important Safety Information .....................................................................................................................................3
Safety Information for Users of LP Gas .....................................................................................................................4
Requirements for Massachusetts ................................................................................................................................5
Gas Supply ..................................................................................................................................................................9
Venting Fireplace - Top ....................................................................................................................................... 14-17
Examples - Top Vent Run .........................................................................................................................................18
DVVK-4FV Direct Vent Termination Kit ........................................................................................................... 19-25
Vent System Identication ........................................................................................................................................32
Framing and Finishing ........................................................................................................................................ 33-34
Standing Pilot Wiring Diagram.................................................................................................................................46
Standing Pilot Lighting Instructions .........................................................................................................................47
Standing Pilot Troubleshooting ................................................................................................................................48
Intermittent Pilot Operating Instructions ..................................................................................................................49
Intermittent Pilot Wiring Diagram ............................................................................................................................49
Intermittent Pilot Lighting Instructions ....................................................................................................................50
Intermittent Pilot Troubleshooting ...................................................................................................................... 51-55
RF Standing Pilot Operating Instructions .................................................................................................................56
RF Standing Pilot Lighting Instructions ...................................................................................................................59
Maintenance and Service .................................................................................................................................... 60-61
Parts View .................................................................................................................................................................62
Parts List ............................................................................................................................................................. 63-64
Master Parts Distributor List.....................................................................................................................................69
How To Order Repair Parts.......................................................................................................................................69
Before enclosing the vent pipe assembly, operate the appliance to ensure it is venting properly.
DO NOT OPERATE THIS APPLIANCE WITHOUT GLASS FRONT PANEL INSTALLED
• If this appliance is installed directly on carpeting, tile
or other combustible material other than wood ooring
the appliance shall be installed on a metal or wood panel
extending the full width and depth of the appliance.
The base referred to above does not mean the reproof
base as used on wood stoves. The protection is for rugs
that are extremely thick and light colored tile.
• Children and adults should be alerted to the hazards of
high surface temperatures and should stay away to avoid
burns or clothing ignition.
• Young children should be carefully supervised when they
are in the same room as the appliance.
• Clothing or other ammable material should not be placed
on or near the appliance.
• Due to high temperatures the appliance should be located out
of trafc and away from furniture and draperies.
• The glass front or any part removed for servicing the appliance
must be replaced prior to operating the appliance. Work should
be done by a qualied service person.
• Keep burner and control compartment clean.
• Adequate accessibility clearances for servicing and proper
operation.
• This appliance must not share or be connected to a ue
serving a separate solid-fuel burning appliance.
• Keep the area around your appliance clear of combustible
materials, gasoline and other flammable vapor and
liquids.
• Under no circumstances should any solid fuels (wood, coal,
paper or cardboard etc.) be used in this appliance.
• The ow of combustion and ventilation air must not be
obstructed in any way.
• Do keep the appliance area clear and free from combustible
material, gasoline and other ammable vapors and liquids.
• Do examine venting system periodically and replace damaged
parts.
• Do make a periodic visual check of pilot and burners. Clean
and replace damaged parts.
• Vent cap is hot while replace is in operation.
• Installation and repair should be done by a qualied service
person. The appliance should be inspected before use
and at least annually by a qualied service person. More
frequent cleaning may be required due to excessive lint from
carpeting, bedding materials, etc. It is imperative that control
compartments, burners and circulating air passageways of the
appliance be kept clean.
• Do not put anything around the replace that will obstruct
the ow of ventilation air.
• Clearance in accordance with local installation codes and the
requirements of the gas supplier.
25613-0-0309Page 3
• CAUTION: The glass used in your replace is ceramic glass.
If the glass is cracked or damaged in any way, it should be
replaced only with a complete glass frame assembly from
Empire. See parts list on Pages 63 and 64 for ordering.
• Do not use this replace if any part has been under water.
Immediately call a qualied service technician to inspect the
heater and to replace any part of the control system and any
gas control which has been under water.
• Any safety screen or guard removed for servicing an appliance
must be replaced prior to operating the appliance.
SAFETY INFORMATION FOR USERS OF LP GAS
Propane (LP-Gas) is a ammable gas which can cause res
and explosions. In its natural state, propane is odorless and
colorless. You may not know all the following safety precautions which can protect both you and your family from an
accident. Read them carefully now, then review them point
LP-GAS WARNING ODOR
If a gas leak happens, you should be able to smell the gas because of the odorant put in the LP-Gas.
That’s your signal to go into immediate action!
• Do not operate electric switches, light matches, use your
phone. Do not do anything that could ignite the gas.
• Get everyone out of the building, vehicle, trailer, or area. Do
that IMMEDIATELY.
• Close all gas tank or cylinder supply valves.
• LP-Gas is heavier than air and may settle in low areas such
as basements. When you have reason to suspect a gas leak,
keep out of basements and other low areas. Stay out until
reghters declare them to be safe.
NO ODOR DETECTED - ODOR FADE
Some people cannot smell well. Some people cannot smell the
odor of the chemical put into the gas. You must nd out if you
can smell the odorant in propane. Smoking can decrease your
ability to smell. Being around an odor for a time can affect your
sensitivity or ability to detect that odor. Sometimes other odors
in the area mask the gas odor. People may not smell the gas odor
or their minds are on something else. Thinking about smelling a
gas odor can make it easier to smell.
The odorant in LP-Gas is colorless, and it can fade under some
circumstances. For example, if there is an underground leak, the
movement of the gas through soil can lter the odorant. Odorants
by point with the members of your household. Someday when
there may not be a minute to lose, everyone’s safety will depend
on knowing exactly what to do. If, after reading the following
information, you feel you still need more information, please
contact your gas supplier.
• Use your neighbor’s phone and call a trained LP-Gas service
person and the re department. Even though you may not
continue to smell gas, do not turn on the gas again. Do not
re-enter the building, vehicle, trailer, or area.
• Finally, let the service man and reghters check for escaped
gas. Have them air out the area before you return. Properly
trained LP-Gas service people should repair the leak, then
check and relight the gas appliance for you.
in LP-Gas also are subject to oxidation. This fading can occur if
there is rust inside the storage tank or in iron gas pipes.
The odorant in escaped gas can adsorb or absorb onto or into walls,
masonry and other materials and fabrics in a room. That will take
some of the odorant out of the gas, reducing its odor intensity.
LP-Gas may stratify in a closed area, and the odor intensity could
vary at different levels. Since it is heavier than air, there may be
more odor at lower levels. Always be sensitive to the slightest gas
odor. If you detect any odor, treat it as a serious leak. Immediately
go into action as instructed earlier.
SOME POINTS TO REMEMBER
• Learn to recognize the odor of LP-Gas. Your local LP-Gas
Dealer can give you a “Scratch and Sniff” pamphlet. Use it
to nd out what the propane odor smells like. If you suspect
that your LP-Gas has a weak or abnormal odor, call your
LP-Gas Dealer.
• If you are not qualied, do not light pilot lights, perform
service, or make adjustments to appliances on the LP-Gas
system. If you are qualied, consciously think about the odor
of LP-Gas prior to and while lighting pilot lights or performing service or making adjustments.
• Sometimes a basement or a closed-up house has a musty
smell that can cover up the LP-Gas odor. Do not try to light
pilot lights, perform service, or make adjustments in an area
where the conditions are such that you may not detect the
odor if there has been a leak of LP-Gas.
• Odor fade, due to oxidation by rust or adsorption on walls of
new cylinders and tanks, is possible. Therefore, people should
be particularly alert and careful when new tanks or cylinders
are placed in service. Odor fade can occur in new tanks, or
reinstalled old tanks, if they are lled and allowed to set too
long before relling. Cylinders and tanks which have been
out of service for a time may develop internal rust which will
cause odor fade. If such conditions are suspected to exist, a
periodic sniff test of the gas is advisable. If you have any
question about the gas odor, call your LP-Gas dealer. A
periodic sniff test of the LP-Gas is a good safety measure
under any condition.
• If, at any time, you do not smell the LP-Gas odorant and you
think you should, assume you have a leak. Then take the same
immediate action recommended above for the occasion when
you do detect the odorized LP-Gas.
• If you experience a complete “gas out,” (the container is under no vapor pressure), turn the tank valve off immediately.
If the container valve is left on, the container may draw in
some air through openings such as pilot light orices. If this
occurs, some new internal rusting could occur. If the valve is
left open, then treat the container as a new tank. Always be
sure your container is under vapor pressure by turning it off
at the container before it goes completely empty or having it
relled before it is completely empty.
25613-0-0309Page 4
REQUIREMENTS FOR MASSACHUSETTS
For all side wall horizontally vented gas fueled equipment installed
in every dwelling, building or structure used in whole or in part
for residential purposes, including those owned or operated by the
Commonwealth and where the side wall exhaust vent termination
is less than seven (7) feet above nished grade in the area of
the venting, including but not limited to decks and porches, the
following requirements shall be satised:
1. INSTALLATION OF CARBON MONOXIDE
DETECTORS.
At the time of installation of the side wall horizontal vented
gas fueled equipment, the installing plumber or gastter shall
observe that a hard wired carbon monoxide detector with an
alarm and battery back-up is installed on the oor level where
the gas equipment is to be installed. In addition, the installing
plumber or gastter shall observe that a battery operated
or hard wired carbon monoxide detector with an alarm is
installed on each additional level of the dwelling, building or
structure served by the side wall horizontal vented gas fueled
equipment. It shall be the responsibility of the property owner
to secure the services of qualied licensed professionals for
the installation of hard wired carbon monoxide detectors
a. In the event that the side wall horizontally vented gas
fueled equipment is installed in a crawl space or an attic,
the hard wired carbon monoxide detector with alarm and
battery back-up may be installed on the next adjacent
oor level.
b. In the event that the requirements of this subdivision can
not be met at the time of completion of installation, the
owner shall have a period of thirty (30) days to comply
with the above requirements; provided, however, that
during said thirty (30) day period, a battery operated
carbon monoxide detector with an alarm shall be
installed.
2. APPROVED CARBON MONOXIDE DETECTORS. Each
carbon monoxide detector as required in accordance with the
above provisions shall comply with NFPA 720 and be ANSI/
UL 2034 listed and IAS certied.
3. SIGNAGE. A metal or plastic identication plate shall be
permanently mounted to the exterior of the building at a
minimum height of eight (8) feet above grade directly in line
with the exhaust vent terminal for the horizontally vented gas
fueled heating appliance or equipment. The sign shall read,
in print size no less than one-half (1/2) inch in size, “GAS
VENT DIRECTLY BELOW. KEEP CLEAR OF ALL
OBSTRUCTIONS”.
4. INSPECTION. The state or local gas inspector of the side
wall horizontally vented gas fueled equipment shall not
approve the installation unless, upon inspection, the inspector
observes carbon monoxide detectors and signage installed in
accordance with the provisions of 248 CMR 5.08(2)(a) 1
through 4.
(b) EXEMPTIONS: The following equipment is exempt
from 248 CMR 5.08(2)(a)1 through 4:
1. The equipment listed in Chapter 10 entitled
“Equipment Not Required To Be Vented” in the
most current edition of NFPA 54 as adopted by the
Board; and
2. Product Approved side wall horizontally vented gas
fueled equipment installed in a room or structure
separate from the dwelling, building or structure
used in whole or in part for residential purposes.
(d) MANUFACTURER REQUIREMENTS - GAS
EQUIPMENT VENTING SYSTEM NOT PROVIDED.
When the manufacturer of a Product Approved side
wall horizontally vented gas fueled equipment does not
provide the parts for venting the ue gases, but identies
“special venting systems”, the following requirements
shall be satised by the manufacturer:
1. The referenced “special venting system” instructions
shall be included with the appliance or equipment
installation instructions; and
2. The “special venting systems” shall be Product
Approved by the Board, and the instructions for
that system shall include a parts list and detailed
installation instruction.
(e) A copy of all installation instructions for all Product
Approved side wall horizontally vented gas fueled
equipment, all venting instructions, all parts lists for
venting instructions, and/or all venting design instructions
shall remain with the appliance or equipment at the
completion of the installation.
25613-0-0309Page 5
INTRODUCTION
Instructions to Installer
1. Installer must leave instruction manual with owner after
installation.
2. Installer must have owner ll out and mail warranty card supplied
with the replace.
3. Installer should show owner how to start and operate the
replace.
This direct vent gas replace heater is designed to operate with all
combustion air being siphoned from the outside of the building
and all exhaust gases expelled to the outside of the building. The
information contained in this manual pertains to all models and gas
control systems unless otherwise noted.
Warning: This unit is not for use with solid fuels.
Appliance Certication
This replace is design certied in accordance with American
National Standard/CSA Standard ANSI Z.21-88/CSA 2.33 and by
Underwriters Laboratories as a Direct Vent Gas Fireplace Heater
and shall be installed according to these instructions.
Consult your local building code agency, prior to installation,
to ensure compliance with local codes-including permits and
inspections.
The replace, when installed, must be electrically grounded in
accordance with local codes or, in absence of local codes, with the
National Electric Code ANSI/NFPA 70 or Canadian Electric code,
CSA C22.1, if an external electrical source is utilized.
These models may be installed in a bedroom or bed-sitting room
in the U.S.A. and Canada.
Qualied Installing Agency
Installation and replacement of gas piping, gas utilization equipment
or accessories and repair and servicing of equipment shall be
performed only by a qualied agency. The term “qualied agency”
means any individual, rm, corporation or company which either in
person or through a representative is engaged in and is responsible
for (a) the installation or replacement of gas piping or (b) the
connection, installation, repair or servicing of equipment, who is
experienced in such work, familiar with all precautions required
and has complied with all the requirements of the authority having
jurisdiction.
State of Massachusetts: The installation must be made by
a licensed plumber or gas tter in the Commonwealth of
Massachusetts.
Any alteration of the original design, installed other than as
shown in these instructions or use with a type of gas not shown on
the rating plate is the responsibility of the person and company
making the change.
Important
All correspondence should refer to complete Model Number, Serial
Number and type of gas.
High Altitude
When installing this unit at an elevation above 2000 feet (in the
United States) it may be necessary to decrease the input rating by
changing the existing burner orice to a smaller size. Generally,
input should be reduced 4 percent for each 1000 feet above sea
level. However, if the heating value of the gas has been reduced,
this general rule may not apply. Check with local gas utility for
proper orice size identication.
Canadian High Altitude
Altitude: 0-4500 feet (0-1370 m)
When installing this unit at an elevation above 4500 feet (in Canada),
check with local authorities.
Consult your local gas utility for assistance in determining the
proper orice for location.
Preparation
This direct vent gas replace and its components are tested and safe
when installed in accordance with this Installation Manual. Report
to your dealer any parts damaged in shipment, specically check
glass condition. Do not install unit with damaged, incomplete, or
substitute parts. Read all instructions before starting installation
and follow these instructions carefully during installation to insure
maximum benet and safety. Failure to follow them will void your
warranty and may present a re hazard.
The warranty will be voided by, and the warranter disclaims any
responsibility for the following actions:
• Installation of any damaged fireplace or vent system
component.
• Modication of the replace or direct vent system.
• Installation other than as instructed by Empire Comfort Systems,
Inc.
• Improper positioning of the logs, glass door or decorative
rock.
• Installation and/or use of any component part not manufactured
or approved by manufacturer.
The installation must conform with local codes or, in the absence
of local codes, with the National Fuel Gas Code ANSI Z223.1/
NFPA 54* Natural Gas and Propane Installation Code, or CSA
B149.1 in Canada. *Available from the American National Standards Institute, Inc.
11 West 42nd St., New York, N.Y. 10036.
Warning: ANY CHANGE TO THIS FIREPLACE OR ITS
CONTROLS CAN BE DANGEROUS.
Improper installation or use of the replace can cause serious
injury or death from re, burns, explosions, or carbon
monoxide poisoning.
25613-0-0309Page 6
LEFT SIDE VIEW
FRONT VIEW
RIGHT SIDE VIEW
ELECTRICAL
ACCESS
VENT COLLAR
TOP VIEW
GAS LINE ACCESS
A
C
J
G
I
GAS LINE
ACCESS
H
D
E
B
VENT COLLAR
STANDOFFS
NAILING
FLANGES
GLASS
FRAME
ASSEMBLY
GAS LINE
ACCESS
RATING PLATE
AND LABELS
GAS CONTROLS
AND SWITCHES
SPECIFICATIONS
DVX36 NATDVX36 LPDVX42 NATDVX42 LP
Input Btu/hr Maximum35,00030,00037,50035,000
Btu/hr Minimum24,00021,00026,00024,000
KWH (Maximum)10.38.811.010.3
(Minimum)7.26.27.67.2
Orice#32 (P-211)1.65 mm (P-250)#31 (P-209)#50 (P-245)
Air Shutter Opening1/4"(6.4 mm)FULL OPEN1/4" (6.4 mm)FULL OPEN
SEE MANTLE CHART
FOR MINIMUM HEIGHT
OF MANTLE ABOVE UNIT
CLEARANCES
MANTEL
19”
18 3/4”
17”
16”
15”
14”
13”
12”
11”
10”
2 1/4”
1 1/2”
3/4”
8”
6”
4 1/2”
3 3/4”
3”
12” (305mm)
10” (254mm)
TOP EDGEOF FIREPLACE
COMBUSTIBLE TRIM AND
MANTELS ALLOWED IN
SHADED AREA
Clearance to Combustibles
Back0" (0 mm)
Side0" (0 mm)
Floor0" (0 mm)
Top Stand-off0" (0 mm)
Top Framing Edge6" (152 mm)
Mantel Chart (Figure 3)
Figure 3
Clearances (Figure 4)
Clearance from top front edge of replace to ceiling is 36"
Clearance from side of replace to adjacent sidewall is 6".
Combustible Material
No greeting cards, stockings or ornamentation of any type should
be placed on or attached to the replace. The ow of heat can
ignite combustibles.
Note: Island (C) and Room Divider (F)
installation is possible as long as the
horizontal portion of the vent system
(H) does not exceed 20 feet with a
minimum vertical run of 8 feet. See
details in Venting Section.
When you install your Direct Vent
Fireplace in (F) Room divider or (A) Flat
on wall corner positions, a minimum of
6 inches clearance must be maintained
from the perpendicular wall and the
front edge of the appliance.
Figure 2
LOCATING FIREPLACE
Figure 5
Figure 4
25613-0-0309Page 8
GAS SUPPLY
The gas pipeline can be brought in through the right or left side of
the appliance. Consult the current National Fuel Gas Code, ANSI
Z223.1 CAN/CGA-B149 (.1 or .2) installation code.
Recommended Gas Pipe Diameter
Pipe LengthSchedule 40 Pipe
Inside Diameter
Nat.L.P.Nat.L.P.
0-10ft
0-3m
11-40ft
4-12m
41-100ft
13-30m
101-150ft
31-46m
Note: Never use plastic pipe. Check to conrm whether your local
codes allow copper tubing or galvanized.
Note: Since some municipalities have additional local codes, it is
always best to consult your local authority and installation code.
The use of the following gas connectors is recommended:
— ANS Z21.24 Appliance Connectors of Corrugated Metal Tubing
and Fittings.
— ANS Z21.45 Assembled Flexible Appliance Connectors of
Other Than All-Metal Construction
The above connectors may be used if acceptable by the authority
having jurisdiction. The state of Massachusetts requires that a exible
appliance connector cannot exceed three feet in length.
1/2"
12.7 mm
1/2"
12.7 mm
1/2"
12.7 mm
3/4"
19 mm
Gas Supply Pressure (inches w.c.)
3/8"
9.5 mm
1/2"
12.7 mm
1/2"
12.7 mm
1/2"
12.7 mm
Figure 6
Tubing, Type L
Outside Diameter
1/2"
12.7 mm
5/8"
15.9 mm
3/4"
19 mm
7/8"
22.2 mm
3/8"
9.5 mm
1/2"
12.7 mm
1/2"
12.7 mm
3/4"
1.9 mm
Installing a New Main Gas Cock
Each appliance should have its own manual gas cock.
A manual main gas cock should be located in the vicinity of the
unit. Where none exists, or where its size or location is not adequate, contact your local authorized installer for installation or
relocation.
Compounds used on threaded joints of gas piping shall be resistant
to the action of liqueed petroleum gases. The gas lines must be
checked for leaks by the installer. This should be done with a soap
solution watching for bubbles on all exposed connections, and if
unexposed, a pressure test should be made.
Never use an exposed ame to check for leaks. Appliance must
be disconnected from piping at inlet of control valve and pipe
capped or plugged for pressure test. Never pressure test with
appliance connected; control valve will sustain damage!
NOTE: The millivolt gas controls are equipped with a captured
screw type pressure test point, therefore it is not necessary to provide
a 1/8" test point up stream of the control.
When using copper or ex connector use only approved ttings.
The appliance and it’s individual shut off valve must be disconnected
from supply piping system during any pressure testing of that system
at test pressures in excess of 1/2 psig (3.5kPa).
The appliance must be isolated from the gas supply piping system
by closing its individual manual shut off valve during any pressure
testing of the gas supply piping system at test pressures equal to or
less than 1/2 psig (3.5kPa).
Attention! If one of the procedures results in pressures in excess
of 1/2 psig (14" w.c.) (3.5 kPa) on the replace gas valve, it will
result in a hazardous condition.
Checking Manifold Pressures
Both Propane and Natural gas valves have a built-in pressure
regulator in the gas valve. Natural gas models will have a manifold
pressure of approximately 3.5" w.c. (.871kPa) at the valve outlet
with the inlet pressure to the valve from a minimum of 4.5" w.c.
(1.120kPa) for the purpose of input adjustment to a maximum of
14.0" w.c. (3.484kPa). Propane gas models will have a manifold
pressure approximately 10.0" w.c. (2.49kPa) at the valve outlet
with the inlet pressure to the valve from a minimum of 10.8" w.c.
(2.68kPa) for the purpose of input adjustment to a maximum of
14.0" w.c. (3.484kPa).
MinimumNormalMaximum
Natural Gas4.5"7.0"*14.0"
LP (Propane)10.8"11.0"14.0"
Manifold Pressure (inches w.c.)
Normal (HI)
Natural Gas3.5"
LP (Propane)10.0"
*NOTE: Remote "RF" Models - 10.5" w.c. maximum
Figure 7
25613-0-0309Page 9
VENT PIPE
1" MINIMUM CLEARANCE AROUND VENT PIPE
USE OUTER
(4) FLANGES
FOR 1/2”
DRYWALL
INSTALLATION
2” X4” STUD
2” X4” BOTTOM
PLATE
FINISHED WALL
FINISHED SURFACE
(TILE, ETC.)
TOPSTANDOFF
Framing and Finishing
1. Choose unit location.
2. Frame in replace with a header across the top. It is important to
allow for nished face when setting the depth of the frame.
3. Attach replace to frame using adjustable nailing ange. Preset
depth to suit facing material (adjustable to 3/8", 1/2" or 3/4" depths).
Note: Fireplace must mount ush to facing material. If facing
material requires more depth than 3/4" mark and drill two
(2) 1/8" holes into replace side at appropriate depth. See
Figure 10.
4. Use (8) 1/2" hex-head screws supplied in hardware package,
to screw through slotted holes in drywall strip and then screw
into pre-drilled holes on replace side. Measure from face of
replace to face of drywall strip to determine nal depth.
Vent Pipe Clearance
Note: Maintain one inch (1") of clearance around vertical vent
pipe. See Figure 9A. For horizontal vent, maintain a minimum 1"
clearance to the bottom and sides of the vent, and 3" clearance to
combustibles above the vent pipe. See Figure 9B.
Figure 9A
Figure 8A
Figure 8B
Figure 9B
25613-0-0309Page 10
NAIL OR OTHER
SUITABLE FASTENER
INSTALLATION (continued)
Figure 10
Framing (Figure 11)
Fireplace framing can be built before or after the replace is set in
place. Framing should be positioned to accommodate wall covering
and replace facing material. The replace framing should be
constructed of 2 x 4 lumber or heavier. The framing headers may
rest on the replace standoffs. Refer to Figure 11 for minimum
framing dimensions.
CAUTION: MEASURE FIREPLACE DIMENSIONS AND
VERIFY FRAMING METHODS, AND WALL COVERING
DETAI L S B E FORE F R A M I NG CON S T R UCTIO N
BEGINS.
Framing dimension "A" includes a six inch clearance
for standoffs on replace. After installing replace into
framing, the nished non-combustible wall surface must
cover the six inch opening above the replace.
Attention: Appliance must not be recessed below any ooring,
including carpeting, for proper front mounting. A metal or wood
panel extending the full width and depth of the appliance may
be required to raise the unit to the same level, or above existing
ooring. The vertical dimension in Figure 11 must be adjusted
when a panel is placed beneath the appliance.
DVX36DVX42
"A"40 7/8"40 7/8"
"B"40 3/8"43 3/8"
"C"19 7/8"19 7/8"
Figure 11
Attention: If a base is not used and the appliance is installed directly
on tile or other combustible material other than wood ooring, it
shall be installed on a metal or wood panel extending the full width
and depth of the appliance. The vertical dimension in Figure 11
must be adjusted when a metal or wood panel is placed beneath
the appliance.
Finishing (Figures 12 and 13)
Finish the walls with the material of your choice. Figure 3 on
page 8 shows the minimum vertical and corresponding maximum
horizontal dimensions of mantels or other combustible projections
above the top front edge of the replace.
The black replace front must not be covered. It must be ush
to the nished wall.
Warning: When nishing the replace never obstruct or
modify the air inlet/outlet louvers in any manner. Provide
adequate clearances around air openings into the combustion
chamber.
Caution: If the joints between the nished wall and the replace
surround (top and sides) are sealed, a 300°F minimum sealant
material must be used. These joints are not required to be sealed.
Only non-combustible material (using 300°F minimum adhesive
if needed), can be applied as facing to the replace.
25613-0-0309Page 11
Flush Wall Installation
FINISHED WA LL
JOINT BETWEEN FINISHED
WALL AND UNIT SEALED
WITH 300° F, 149°CSEALANT
MATERIAL (SEALANTISOPTIONAL)
6” OF NON-COMBUSTIBLE MATERIAL
NON-COMBUSTIBLE MATERIAL
(INSTALLATION IS OPTIONAL
FINISHED WALL
COMBUSTIBLE SURROUND
MANTELSHELF
2X4
HEADER
STAND OFF
6” OF NON-COMBUSTIBLE
MATERIAL
FRONT TRIM OR
NON-COMBUSTIBLE
MATERIAL (INSTALLATION
IS OPTIONAL)
JOINT BETWEEN FINISHED
WALL AND UNIT SEALED WITH
300°F (149°C) SEALANT MATERIAL
(SEALANT IS OPTIONAL)
3” (76mm)
MINIMUM CLEARANCE
TO COMBUSTIBLES
VENT CAP/
THIMBLE
WALL FIRESTOP
DVX36,42
50 1/2” (1283mm)
TO BOTTOM
OF UNIT
Attention: Cold climate installation recommendation:
When installing this unit against a non-insulated exterior
wall, it is recommended that the outer walls be insulated to
conform to applicable insulation codes.
Vent Runs (Figures 14, 15, and 16)
In planning the installation for the replace, it is necessary to install
certain components before the appliance is completely positioned
and installed. These include the direct vent system, gas piping for
the appliance and the electrical wiring.
The appliance can be mounted on any of the following surfaces:
1. A at, hard combustible (burnable) surface.
2. A raised wooden platform.
3. Four (4) corner supports. (Example: Four (4) concrete masonry
blocks.) These supports must be positioned so they contact all
four (4) perimeter edges on the bottom of the unit.
VERTICAL, 90° ELBOW WITH HORIZONTAL
TERMINATION
Figure 12
Combustible Surround Installation
Figure 14
Figure 13
25613-0-0309Page 12
90º ELBOW
“A”
PIPE
LENGTH
VENT CAP
WALL FIRESTOP/
THIMBLE
“C”
“B”
“A”
“B”
“D”
9” (229mm)
MINIMUM
VENT
CAP
6” (152mm)
MINIMUM
WALL FIRESTOP/
THIMBLE
“C”
INSTALLATION (continued)
VERTICAL, 90° ELBOW TO
HORIZONTAL OUT THE WALL
"A""B""C"
6"(152 mm)11 1/4"(286 mm) to
12 3/4"(324 mm)
9"(229 mm)14 1/4"(362 mm) to
15 3/4"(400 mm)
12"(305 mm)17 1/4"(438 mm) to
18 3/4"(476 mm)
4 3/4"(121 mm) to
6 1/4"(159 mm)
7 3/4"(197 mm) to
9 1/4"(235 mm)
10 3/4"(273 mm) to
12 1/4"(311 mm)
CORNER INSTALLATION VERTICAL, 90° ELBOW TO
HORIZONTAL OUT THE WALL
Dim.DVX36DVX42
45 3/8" (1152 mm)49 5/8" (1260 mm)
A
32 1/8" (816 mm)35 1/8" (892 mm)
B
13 3/8" (34 mm)15 1/2" (39 mm)
C
64 1/8" (1628 mm)70 1/8" (1781 mm)
D
Figure 16
Figure 15
25613-0-0309Page 13
VENTING FIREPLACE - TOP
TOP EXIT-VERTICAL AND HORIZONTAL TERMINATION
(DIMENSIONS IN FEET)
VERTICAL DIMENSION
FROM
THE BOTTOM OF THE UNIT
TO THE CENTER OF
THE FLUE OUTLET
WITH VERTICAL OR HORIZONTAL TERMINATION CAPS
TOP VENT
CONNECTION
HORIZONTAL RUN
FLUE HEAT
SHIELD
REQUIRED
To Use the Vent Graph (Figure 17)
1. Determine the height of the center of the horizontal vent
pipe. Using this dimension on the Sidewall Vent Graph,
locate the point it intersects with the slanted graph
line.
2. From the point of this intersection, draw a vertical line
to the bottom of the graph.
3. Select the indicated dimension, and position the unit in
accordance with same.
EXAMPLE A:
If the vertical dimension from the oor of the unit is 35 feet,
the horizontal run to the outer wall ange must not exceed
6.5 feet.
EXAMPLE B:
If the vertical dimension from the oor of the unit is 6.5
feet, the horizontal run to the outer wall ange must not
exceed 14.5 feet.
Special Note: For each 45 degree elbow installed in the
horizontal run, the length of the horizontal run MUST be
reduced by 18" (45cm). This does not apply if the 45 degree
elbows are installed on the vertical part of the vent system.
Reduce 3' for every 90° elbow.
Example: According to the chart the maximum horizontal
vent length is 20' and if two 45 degree elbows are required
in the horizontal vent it must be reduced to 17'.
The maximum number of 45 degree elbows permitted per
side wall installation is two (2). These elbows can be installed
in either the vertical or horizontal run.
Note: On vertical venting the rst elbow does not get
counted.
Note: Flue heat shield must be installed for venting
applications with less than two feet of vertical pipe off the
top of the replace.
Venting Graph (Dimensions in Feet)
Figure 17
Acceptable vertical and horizontal vent run.
(40' maximum vertical and 20' maximum horizontal)
Unacceptable vertical and horizontal vent run.
25613-0-0309Page 14
VENTING FIREPLACE - TOP (continued)
HOLES FOR 42” MODELS
HOLES FOR 36” MODELS
NOTE: 42” MODEL SHOWN
TAB
Installation of Flue Heat Shield
1. Remove ue insulation.
2. Remo ve (2) screws on outside of inlet vent ada pter.
See Figure 18.
3. Lift top shield placing ue heat shield around ue.
4. Repl ace (2) screws on outside of inlet vent adapte r.
See Figure 19.
5. Bend tab at top front of ue heat shield if necessary to maintain
air gap between ue pipe and ue heat shield.
6. Replace ue insulation.
Figure 18
Figure 19
25613-0-0309Page 15
FIRESTOP AT
CEILING LEVEL
SEE GRAPH FOR PERMISSIBLE “H” AND “V” DIMENSIONS
NOTE: H1 AND H2 MUST BE ADDED TOGETHER TO USE CHART
SEE GRAPH FOR PERMISSIBLE “H” AND “V” DIMENSIONS
FIRESTOP AT
CEILING LEVEL
VENTING FIREPLACE - TOP (continued)
Below Grade Installation
When it is not possible to meet the required vent terminal clearances
of 12" (305mm) above grade level, a snorkel kit is recommended. It
allows installation depth down to 7" (178 mm) below grade level.
The 7" (178 mm) is measured from the center of the horizontal
vent pipe as it penetrates through the wall.
Ensure the sidewall venting clearances are observed. If venting
system is installed below ground, we recommend a window well
with adequate and proper drainage to be installed around the
termination area.
TYPICAL BASEMENT INSTALLATION
Figure 20
Examples of possible venting systems using one (1) 90° elbow.
Eight (8) feet is listed as minimum vertical vent run with 20 feet
of maximum horizontal vent run. Vertical dimensions are based on
centerline to centerline of pipe. Horizontal dimensions are based
on centerline of pipe to end of termination.
Figure 21
Examples of possible venting systems using two (2) 90° elbows.
V is listed as minimum vertical dimensions and H1 + H2 is listed
as total of maximum horizontal dimensions. The maximum vertical
and horizontal distances for two (2) 90° elbows as shown in Figure 22 is 22 feet.
Attention: Refer to Figure 17 for a d d itional v e nting
requirements.
Figure 22
25613-0-0309Page 16
VENT CAP
9” (229mm) minimum
TO SIDE WALL
Figure 23
MAXIMUM HORIZONTAL
RUN WITH NO VERTICAL
RISE AND 90° ELBOW
3’
(914mm)
MAXIMUM HORIZONTAL
RUN WITH MINIMUM
VERTICAL RISE AND
90° ELBOW
20’ (6.1m)
PIPE STRAPS
EVERY2’ (61cm)
8’ (244cm)
TO BOTTOM
OF UNIT
SEE CHART FOR
PERMISSIBLE
“H” AND “V”
DIMENSIONS
A
CENTER OF ELBOW
STRAIGHT OUT
(MINIMUM)
10”
(254mm)
C
B
V
C
B
H
12”
(305mm)
MINIMUM HOLE LOCATION DIMENSIONS FOR
THROUGH THE WALL HORIZONTAL INSTALLATIONS
WITH 90 DEGREE ELBOW OFF TOP OF FIREPLACE
Figure 24
FIREPLACE
SERIES
DVX36FP43-1/2"
DVX42FP43-1/2"
FIREPLACE
SERIES
DVX36FP46"
DVX42FP46"
HARD ELBOW DIMENSIONS
"A""B""C"
5"
(1105 mm)
(127 mm)
5"
(1105 mm)
(127 mm)
FLEX PIPE 90 DEGREE BEND
"A""B""C"
5"
(1143 mm)
(127 mm)
5"
(1143 mm)
(127 mm)7" (178 mm)
(178 mm)
(178 mm)
Positioning the Fireplace
Determine the exact position of the appliance so the direct vent
termination will be centered (if possible) between two (2) studs. This
will avoid any extra framing. All vent kit pipes should be assembled
on the unit after the unit is moved into the nal position.
Cutting the Hole (Figure 23)
After the replace has been positioned in its permanent location,
the hole through the exterior wall of the house can be cut. This hole
must be 12" (305 mm) high x 10" (254 mm) wide with its center
line determined by the amount of vertical rise and horizontal run of
the termination. See Figure 23. When locating the hole it must be
noted that the bottom of the cap must be 12" (305 mm) above the
ground level, and top of the cap must be no less than 18" (457 mm)
below a combustible projection, and no closer than 9" (229 mm) to
any wall running parallel to vent termination. See Figure 24.
7"
(178 mm)
7"
7"
Figure 25
25613-0-0309Page 17
Example
H2 3ft, H3 1ft=4ft
(90°+90°+90°)=6ft
V1=21ft
H=10ft V=21ft
Example
H1=2ft
V1=20ft
H=2ft V=20ft
EXAMPLES - TOP VENT RUN
Figure 26
Figure 27
Figure 28
25613-0-0309Page 18
DVVK-4FV DIRECT VENT TERMINATION KIT
Installation Instructions
This termination kit can only be used with Empire Comfort Systems direct vent replaces listed for use with
DVVK-4FV Vertical Flex Vent Kit. Please review the instructions packaged with your replace and verify the
replace model number. Check that this ex vent system is listed for use with your replace model prior to
starting the installation.
This vent kit may be installed as an OEM installation in a manufactured home (USA only) or mobile
home and must be installed in accordance with the manufacturer’s instructions and the manufactured
home construction and safety standard, Title 24 CFR, Part 3280 or Standard for Installation in Mobile
Homes, CAN/CSA Z240 MH.
CAUTION
All Fireplaces listed for use with the DVVK-4FV will operate safely when installed in accordance with this instruction manual. Read
all instructions before starting installation, then follow these instructions carefully to maximize replace performance and safety.
Report damaged parts to your dealer.
WARNING
Any common venting of the gas appliance using the DV vent kit with other gas appliances is not allowed. Do not connect this appli-
ance to a chimney ue servicing a separate solid fuel-burning appliance.
WARNING
Failure to follow these instructions may create a possible re hazard and will void the warranty.
WARNING
Always maintain minimum clearances around vent systems. The minimum clearance to combustibles for horizontal runs of vent pipe
is 3 inches from the top, and 1 inch from the sides and bottom of the vent system. Do not pack the open air spaces around the replace
or ue with insulation or other materials. Any horizontal run must have a 1/4” rise for every one (1) foot of run towards the vent ter-
mination. The vent above the roof must terminate vertically.
WARNING
Contact your Local Building and Fire Ofcials about restrictions and installation inspections in your area.
IMPORTANT SAFETY INFORMATION
• The vertical termination cap MUST be vented directly to the
outside. The termination kit MUST NEVER be connected to
a chimney ue(s) servicing a separate solid-fuel burning ap-
pliance or any other appliances.
• Vertical termination cap MUST NOT be mounted horizontally.
• The exible vent pipe cannot be intermingled with any of the
rigid vent pipe section(s). DO NOT connect two sections of
exible vent pipe together to achieve a longer length without
the use of approved connectors.
• The installation must conform with local codes or in the absence of local codes, with the National Fuel Gas Code, ANSI
Z223.1 (in the United States) or with the current installation
code CAN/CGA B149 (in Canada).
• Only Direct Vent replaces approved for use with Empire
Comfort Systems, Inc. DVVK-4FV termination kit shall be
used. See PARTS LIST/ILLUSTRATIONS section for vent
component identication.
• Horizontal vent runs must be supported every 2 feet using
wall straps. Vertical runs must be supported every 3 feet using wall straps. Slip wall straps loosely on to pipe. Attach
installer provided straps to framing members using nails or
screws.
• The replace and venting system should be inspected before
initial use and at least annually by a qualied eld service
person. Inspect the external vent cap on a regular basis to
make sure that no debris is interfering with the airow. Inspect entire venting system to ensure proper function.
• Please refer to the replace instructions for information on
Termination Cap clearances.
25613-0-0309Page 19
DVVK-4FV DIRECT VENT TERMINATION KIT (cont.)
PRE-INSTALLATION INFORMATION:
Items Required For Installation:
ToolsBuilding Supplies
Phillips Screwdriver
Hammer
Saw and/or saber saw
Level
Measuring Tape
Electric Drill and Bits
Pliers
Square
Tin Snips
Before You Start:
Plan your installation. Read these instructions and the replace installation manual before installing unit and vent system. Set unit in
place and survey how best to vent the unit. After the vent conguration has been decided, stretch the ex pipe components out, then trim
off what will not be needed.
Refer to the replace installation manual for information on vertical venting requirements. The maximum length of vent when using ex
venting is 35 feet total. Contact your dealer or distributor for information on ex vent extension kits that may be added to the DVVK4FV kit, in order to terminate up to 35 feet. Available extension kits include the DVEK-10 (10’ Flex) or the DVEK-25 (25’ Flex) exten-
sion kits. The extension kits include connection hardware.
Framing Materials
Wall Finishing Materials
Caulking Material (Noncombustible)
Support Strap supplies
Installation of the Vertical Flex Termination Kit
WARNING
Ensure that the venting system exits the structure through the roof and does not terminate less than 12 inches (305 mm) above the
roof.
WARNING
Refer to your replace homeowner’s manual for the minimum and maximum venting requirement of your replace prior to installation. Failure to do so may cause a re hazard.
WARNING
This exible pipe termination kit is ONLY for vertical terminations.
WARNING
Any horizontal run section must have a 1/4” rise for every one (1) foot of run towards the vent termination. Never allow the vent pipe
to run downward. This could cause high temperatures and may present a re hazard. This vertical kit may incorporate two (2) 90 de-
gree bends, but must terminate vertically.
CAUTION
This ex vent kit can only be installed vertically off of the unit and must terminate vertically.
WARNING
Because of sharp edges, always use gloves when handling the ex vent components.
CAUTION
Vent connections should overlap a minimum of 1” for proper sealing.
CAUTION
Always stretch and secure venting with metal strapping secured with nails (nails and strapping not supplied) to ensure that the ex
vent runs remain true.
25613-0-0309Page 20
FLEX OUTER
AIR INTAKE PIPE
SPACER SPRINGS
FLEX FLUE PIPE
305mm305mm305mm305mm
12”12”12”12”
4” FLEX
VENT PIPE
SPACER SPRINS
DVVK-4FV DIRECT VENT TERMINATION KIT (cont.)
Step-By-Step Installation For Flex DV Kit
1. Unpack vent components and check all items for shipping
damage.
2. For this venting system to operate as designed it is dependent on the use of all parts and procedures detailed in these
instructions. Failure to follow these instructions may potentially affect the performance of this vent system and the attached appliance.
3. As per the replace manufacturer’s instructions, replace the
existing 6 5/8” diameter replace vent adapter with the 7”
diameter ex vent replace adapter included in the vent kit.
Install the adapter collar with the screws removed from the
standard replace collar. Refer to the replace manual for additional information on the vent collar removal and installation.
4. Once the replace location has been determined, mark the
ceiling where the ex vent will pass through. Cut an opening
for installation of the restop thimble assembly. The opening must measure a minimum of 9-1/2” x 9-1/2” square. See
Figure 29.
5. Next, determine the location for the cutout in the roof opening. This opening must be large enough to provide a minimum 1” air space clearance from the vertical vent pipe to any
combustible framing.
6. Install the Firestop/Thimble assembly to the framed opening
in the ceiling using common nails or screws. Note: The thimble assembly is adjustable up or down as
needed within the restop. It is also designed with a pivoting
restop for use with 0 - 3/12 pitch cathedral ceilings.
7. To begin vent system assembly, rst layout all the vent components on the oor in the order in which they will be as-
sembled.
8. Stretch the 4” diameter inner ex ue and 7” diameter outer
ex vent to the maximum length of 6 feet.
9. Install the spring spacers provided around the 4” diameter
ex ue at 1 foot intervals, then slide the ue pipe with spacers into the 7” diameter outer ex vent pipe. Make sure the
springs are spaced evenly starting at 12 inches from the re-
place collar. See Figure 30.
Figure 29
25613-0-0309Page 21
Figure 30
NUT (2)
SCREW (2)
PIPE CLAMP
ROOF BRACKET (2)
WING NUT (2)
H
X
12
VENTCAP
GAS VENT
LOWEST
DISCHARGE
OPENING
ROOF PITCHIS X/12
H(Min.)-Minimum height from
roof to lowest discharge opening
DVVK-4FV DIRECT VENT TERMINATION KIT (cont.)
10. With the ex vent assembly and the 48” long hard pipe components laid out on the oor, begin securing these parts to-
gether. First, apply a generous bead of silicone sealant to the
inside of the 4” diameter ex ue (not the end with the preinstalled connector), then slide the ex ue over the 4” diameter hard pipe ue. Be sure to overlap at least 1-1/4”. Secure
this connection with a 4” diameter band clamp provided. Be
careful not to damage or tear the ex ue when tightening
clamp.
11. Repeat the connection process for the outer 7” diameter ex
vent to hard pipe connection. Use silicone sealant at this joint
also, overlap at least 1-1/4”, then secure the joint with the 7”
diameter band clamp provided. Be careful not to damage or
tear the ex vent pipe when tightening the clamp.
12. While the venting is still on the oor, assemble the roof jack
components as shown in Figure 31 and pre-install the roof
jack assembly to the hard pipe approximately 18” from the
top end of the hard pipe.
13. Now the pre-assembled vent system may be carried to the
roof, then lowered through the roof cutout opening (see step
5). Feed the ex vent end down through the roof opening and
restop/thimble assembly installed in steps 4 through 6.
14. Secure the roof support assembly to the roof sheathing with
at least (4) nails/screws through each support bracket. Check
that the combustible clearances through the roof framing will
maintain at least a 1” clearance from the vent pipe.
15. Determine how high the vent terminal should be located
above the roof line based on the roof pitch information shown
in Figure 33. Adjust the vent system height by loosening the
pre-installed roof support pipe clamp and sliding the vent
pipe up or down as pre-determined, then re-tighten the pipe
clamp. Install a couple of sheet metal screws through the pipe
clamp into the outer hard vent pipe to lock in place.
16. Check to make sure that the bottom end of the ex vent is
long enough to reach the replace adapter collars. If too long,
trim off the extra ex vent not needed.
Figure 31
Figure 32
When terminating the vent cap near an exterior wall or overhang,
maintain minimum clearances as shown in Figure 32.
ROOF PITCHH (Min.)
Flat to 6/1212” (305 mm)
6/12 to 7/1215” (381 mm)
Over 7/12 to 8/1218” (457 mm)
Over 8/12 to 16/1224” (610 mm)
Over 16/12 to 21/1236” (914 mm)
Figure 33
25613-0-0309Page 22
Loading...
+ 50 hidden pages
You need points to download manuals.
1 point = 1 manual.
You can buy points or you can get point for every manual you upload.