result causing property damage, personal injury or
loss of life.
— Do not store or use gasoline or other ammable
vapors and liquids in the vicinity of this or any
other appliance.
— WHAT TO DO IF YOU SMELL GAS
• Do not try to light any appliance.
• Do not touch any electrical switch; do not use
any phone in your building.
• Immediately call your gas supplier from a
neighbor’s phone. Follow the gas supplier’s
instructions.
• If you cannot reach your gas supplier, call the
re department.
— Installation and service must be performed by a
qualied installer, service agency or the gas supplier.
Installer: Leave this manual with the appliance.
Consumer: Retain this manual for future reference.
This appliance may be installed in an aftermarket,
permanently located, manufactured home (USA only)
or mobile home, where not prohibited by state or local
codes.
This appliance is only for use with the type of gas
indicated on the rating plate. This appliance is not
convertible for use with other gases, unless a certied
kit is used.
WARNING: If not installed, operated and maintained
in accordance with the manufacturer’s instructions,
this product could expose you to substances in fuel
or from fuel combustion which can cause death or
serious illness.
Page 1
TABLE OF CONTENTS
Section Page
Important Safety Information .................................................................................................................................................... 3
Safety Information for Users of LP Gas .....................................................................................................................................4
Requirements for Massachusetts ..............................................................................................................................................5
Gas Supply ..............................................................................................................................................................................10
Vent Systems ...........................................................................................................................................................................11
Venting Fireplace - Top ...................................................................................................................................................... 16-18
Examples - Top Vent Run ........................................................................................................................................................19
Venting Examples When Using A DVA47 Adaptor ...................................................................................................................20
DVVK-4FV Direct Vent Termination Kit with DVA47 Adaptor ............................................................................................. 21-27
Examples - Rear Vent Run ......................................................................................................................................................29
DVVK-4RE Vent Kit Installation Instructions - Top Vent Only with DVA47 Adaptor ............................................................ 30-32
DVVK-4F Flex Vent Instructions - Top Vent Only with DVA47 Adaptor .....................................................................................33
Vent System Identication ................................................................................................................................................. 36-37
8" Venting Framing and Finishing ...................................................................................................................................... 38-39
6⅝" Venting Framing and Finishing ................................................................................................................................... 40-41
Standing Pilot Wiring Diagram .................................................................................................................................................48
Standing Pilot Lighting Instructions ..........................................................................................................................................49
Standing Pilot Troubleshooting ................................................................................................................................................50
Direct Ignition Wiring Diagram ..................................................................................................................................................51
Optional Remote Control ..........................................................................................................................................................51
Direct Ignition Lighting Instructions ...........................................................................................................................................52
Initial Start Up Gas Line Purge .................................................................................................................................................53
Direct Ignition Troubleshooting .................................................................................................................................................53
Direct Ignition Propane/LP Gas Conversion ....................................................................................................................... 54-55
Intermittent Pilot Operating Instructions ...................................................................................................................................56
Intermittent Pilot Wiring Diagram .............................................................................................................................................56
Intermittent Pilot Lighting Instructions ......................................................................................................................................57
Intermittent Pilot Troubleshooting ...................................................................................................................................... 58-62
Maintenance and Service ........................................................................................................................................................67
DVP42FP(3,5,7,9) Parts List .............................................................................................................................................. 68-69
DVP48FP(3,5,7,9) Parts List .............................................................................................................................................. 70-71
Parts View .................................................................................................................................................................................72
Master Parts Distributor List .....................................................................................................................................................73
How To Order Repair Parts .......................................................................................................................................................73
Before enclosing the vent pipe assembly, operate the appliance to ensure it is venting properly.
DO NOT OPERATE THIS APPLIANCE WITHOUT GLASS FRONT PANEL INSTALLED
• If this appliance is installed directly on carpeting,
tile or other combustible material other than wood
ooring the appliance shall be installed on a metal
or wood panel extending the full width and depth
of the appliance.
The base referred to above does not mean the
fireproof base as used on wood stoves. The
protection is for rugs that are extremely thick and
light colored tile.
• Children and adults should be alerted to the hazards
of high surface temperatures and should stay away
to avoid burns or clothing ignition.
• Young children should be carefully supervised when
they are in the same room as the appliance.
• Clothing or other ammable material should not be
placed on or near the appliance.
• Due to high temperatures the appliance should be located
out of trafc and away from furniture and draperies.
• The glass front or any part removed for servicing the
appliance must be replaced prior to operating the
appliance. Work should be done by a qualied service
person.
• Keep burner and control compartment clean.
• Adequate accessibility clearances for servicing and
proper operation.
• This appliance must not share or be connected
to a ue serving a separate solid-fuel burning
appliance.
• Keep the area around your appliance clear of
combustible materials, gasoline and other ammable
vapor and liquids.
• Under no circumstances should any solid fuels
(wood, coal, paper or cardboard etc.) be used in
this appliance.
• The ow of combustion and ventilation air must not
be obstructed in any way.
• Do keep the appliance area clear and free from
combustible material, gasoline and other ammable
vapors and liquids.
• Do examine venting system periodically and replace
damaged parts.
• Do make a periodic visual check of pilot and burners.
Clean and replace damaged parts.
• Vent cap is hot while replace is in operation.
• Installation and repair should be done by a qualied
service person. The appliance should be inspected
before use and at least annually by a qualied service
person. More frequent cleaning may be required due
to excessive lint from carpeting, bedding materials, etc.
It is imperative that control compartments, burners and
circulating air passageways of the appliance be kept
clean.
• Do not put anything around the replace that will obstruct
the ow of ventilation air.
• Clearance in accordance with local installation codes
and the requirements of the gas supplier.
28649-2-0811Page 3
• CAUTION: The glass used in your replace is tempered
glass. If the glass is cracked or damaged in any way,
it should be replaced only with a complete glass frame
assembly from Empire. See parts list on Pages 68 to
71 for ordering.
• Do not use this replace if any part has been under
water. Immediately call a qualied service technician
to inspect the heater and to replace any part of the
control system and any gas control which has been
under water.
• Any safety screen or guard removed for servicing
an appliance must be replaced prior to operating the
appliance.
SAFETY INFORMATION FOR USERS OF LP GAS
Propane (LP-Gas) is a ammable gas which can cause res
and explosions. In its natural state, propane is odorless and
colorless. You may not know all the following safety precautions
which can protect both you and your family from an accident.
Read them carefully now, then review them point by point
with the members of your household. Someday when there
may not be a minute to lose, everyone’s safety will depend
on knowing exactly what to do. If, after reading the following
information, you feel you still need more information, please
contact your gas supplier.
LP-GAS WARNING ODOR
If a gas leak happens, you should be able to smell the gas because of the odorant put in the LP-Gas.
That’s your signal to go into immediate action!
• Do not operate electric switches, light matches, use your phone.
Do not do anything that could ignite the gas.
• Get everyone out of the building, vehicle, trailer, or area. Do
that IMMEDIATELY.
• Close all gas tank or cylinder supply valves.
• LP-Gas is heavier than air and may settle in low areas such as
basements. When you have reason to suspect a gas leak, keep
out of basements and other low areas. Stay out until reghters
declare them to be safe.
• Use your neighbor’s phone and call a trained LP-Gas service
person and the re department. Even though you may not
continue to smell gas, do not turn on the gas again. Do not
re-enter the building, vehicle, trailer, or area.
• Finally, let the service man and reghters check for escaped
gas. Have them air out the area before you return. Properly
trained LP-Gas service people should repair the leak, then
check and relight the gas appliance for you.
NO ODOR DETECTED - ODOR FADE
Some people cannot smell well. Some people cannot smell the
odor of the chemical put into the gas. You must nd out if you
can smell the odorant in propane. Smoking can decrease your
ability to smell. Being around an odor for a time can affect your
sensitivity or ability to detect that odor. Sometimes other odors in
the area mask the gas odor. People may not smell the gas odor
or their minds are on something else. Thinking about smelling a
gas odor can make it easier to smell.
The odorant in LP-Gas is colorless, and it can fade under some
circumstances. For example, if there is an underground leak, the
movement of the gas through soil can lter the odorant. Odorants
in LP-Gas also are subject to oxidation. This fading can occur if
there is rust inside the storage tank or in iron gas pipes.
The odorant in escaped gas can adsorb or absorb onto or into walls,
masonry and other materials and fabrics in a room. That will take
some of the odorant out of the gas, reducing its odor intensity.
LP-Gas may stratify in a closed area, and the odor intensity could
vary at different levels. Since it is heavier than air, there may be
more odor at lower levels. Always be sensitive to the slightest gas
odor. If you detect any odor, treat it as a serious leak. Immediately
go into action as instructed earlier.
SOME POINTS TO REMEMBER
• Learn to recognize the odor of LP-Gas. Your local LP-Gas
Dealer can give you a “Scratch and Sniff” pamphlet. Use it to
nd out what the propane odor smells like. If you suspect that
your LP-Gas has a weak or abnormal odor, call your LP-Gas
Dealer.
• If you are not qualied, do not light pilot lights, perform service,
or make adjustments to appliances on the LP-Gas system. If
you are qualied, consciously think about the odor of LP-Gas
prior to and while lighting pilot lights or performing service or
making adjustments.
• Sometimes a basement or a closed-up house has a musty
smell that can cover up the LP-Gas odor. Do not try to light
pilot lights, perform service, or make adjustments in an area
where the conditions are such that you may not detect the odor
if there has been a leak of LP-Gas.
• Odor fade, due to oxidation by rust or adsorption on walls of
new cylinders and tanks, is possible. Therefore, people should
be particularly alert and careful when new tanks or cylinders
are placed in service. Odor fade can occur in new tanks, or
reinstalled old tanks, if they are lled and allowed to set too
long before relling. Cylinders and tanks which have been out
of service for a time may develop internal rust which will cause
odor fade. If such conditions are suspected to exist, a periodic
sniff test of the gas is advisable. If you have any question
about the gas odor, call your LP-Gas dealer. A periodic
sniff test of the LP-Gas is a good safety measure under
any condition.
• If, at any time, you do not smell the LP-Gas odorant and you
think you should, assume you have a leak. Then take the same
immediate action recommended above for the occasion when
you do detect the odorized LP-Gas.
• If you experience a complete “gas out,” (the container is under
no vapor pressure), turn the tank valve off immediately. If the
container valve is left on, the container may draw in some air
through openings such as pilot light orices. If this occurs, some
new internal rusting could occur. If the valve is left open, then
treat the container as a new tank. Always be sure your container is under vapor pressure by turning it off at the container
before it goes completely empty or having it relled before it is
completely empty.
28649-2-0811Page 4
REQUIREMENTS FOR MASSACHUSETTS
For all side wall horizontally vented gas fueled equipment installed
in every dwelling, building or structure used in whole or in part for
residential purposes, including those owned or operated by the
Commonwealth and where the side wall exhaust vent termination
is less than seven (7) feet above nished grade in the area of
the venting, including but not limited to decks and porches, the
following requirements shall be satised:
1. INSTALLATION OF CARBON MONOXIDE DETECTORS.
At the time of installation of the side wall horizontal vented
gas fueled equipment, the installing plumber or gastter shall
observe that a hard wired carbon monoxide detector with an
alarm and battery back-up is installed on the oor level where
the gas equipment is to be installed. In addition, the installing
plumber or gastter shall observe that a battery operated
or hard wired carbon monoxide detector with an alarm is
installed on each additional level of the dwelling, building or
structure served by the side wall horizontal vented gas fueled
equipment. It shall be the responsibility of the property owner
to secure the services of qualied licensed professionals for
the installation of hard wired carbon monoxide detectors
a. In the event that the side wall horizontally vented gas
fueled equipment is installed in a crawl space or an attic,
the hard wired carbon monoxide detector with alarm and
battery back-up may be installed on the next adjacent
oor level.
b. In the event that the requirements of this subdivision can
not be met at the time of completion of installation, the
owner shall have a period of thirty (30) days to comply with
the above requirements; provided, however, that during
said thirty (30) day period, a battery operated carbon
monoxide detector with an alarm shall be installed.
2. APPROVED CARBON MONOXIDE DETECTORS. Each
carbon monoxide detector as required in accordance with the
above provisions shall comply with NFPA 720 and be ANSI/
UL 2034 listed and IAS certied.
3. SIGNAGE. A metal or plastic identication plate shall be
permanently mounted to the exterior of the building at a
minimum height of eight (8) feet above grade directly in line
with the exhaust vent terminal for the horizontally vented
gas fueled heating appliance or equipment. The sign shall
read, in print size no less than one-half (1/2) inch in size,
“GAS VENT DIRECTLY BELOW. KEEP CLEAR OF ALL
OBSTRUCTIONS”.
4. INSPECTION. The state or local gas inspector of the side
wall horizontally vented gas fueled equipment shall not
approve the installation unless, upon inspection, the inspector
observes carbon monoxide detectors and signage installed
in accordance with the provisions of 248 CMR 5.08(2)(a) 1
through 4.
(b) EXEMPTIONS: The following equipment is exempt from
248 CMR 5.08(2)(a)1 through 4:
1. The equipment listed in Chapter 10 entitled
“Equipment Not Required To Be Vented” in the most
current edition of NFPA 54 as adopted by the Board;
and
2. Product Approved side wall horizontally vented gas
fueled equipment installed in a room or structure
separate from the dwelling, building or structure
used in whole or in part for residential purposes.
(d) MANUFACTURER REQUIREMENTS - GAS
EQUIPMENT VENTING SYSTEM NOT PROVIDED.
When the manufacturer of a Product Approved side
wall horizontally vented gas fueled equipment does not
provide the parts for venting the ue gases, but identies
“special venting systems”, the following requirements
shall be satised by the manufacturer:
1. The referenced “special venting system” instructions
shall be included with the appliance or equipment
installation instructions; and
2. The “special venting systems” shall be Product
Approved by the Board, and the instructions for
that system shall include a parts list and detailed
installation instruction.
(e) A copy of all installation instructions for all Product
Approved side wall horizontally vented gas fueled
equipment, all venting instructions, all parts lists for
venting instructions, and/or all venting design instructions
shall remain with the appliance or equipment at the
completion of the installation.
28649-2-0811Page 5
INTRODUCTION
Instructions to Installer
1. Installer must leave instruction manual with owner after
installation.
2. Installer must have owner ll out and mail warranty card supplied
with the replace.
3. Installer should show owner how to start and operate the
replace.
This direct vent gas replace heater is designed to operate with
all combustion air being siphoned from the outside of the building
and all exhaust gases expelled to the outside of the building. The
information contained in this manual pertains to all models and gas
control systems unless otherwise noted.
Warning: This unit is not for use with solid fuels.
Appliance Certication
This replace is design certied in accordance with American
National Standard/CSA Standard ANSI Z21.88/CSA 2.33 and by
Underwriters Laboratories as a Direct Vent Gas Fireplace Heater
and shall be installed according to these instructions.
Consult your local building code agency, prior to installation, to ensure
compliance with local codes-including permits and inspections.
The replace, when installed, must be electrically grounded in
accordance with local codes or, in absence of local codes, with the
National Electric Code ANSI/NFPA 70 or Canadian Electric code,
CSA C22.1, if an external electrical source is utilized.
These models may be installed in a bedroom or bed-sitting room
in the U.S.A. and Canada.
Qualied Installing Agency
Installation and replacement of gas piping, gas utilization equipment
or accessories and repair and servicing of equipment shall be
performed only by a qualied agency. The term “qualied agency”
means any individual, rm, corporation or company which either in
person or through a representative is engaged in and is responsible for
(a) the installation or replacement of gas piping or (b) the connection,
installation, repair or servicing of equipment, who is experienced in
such work, familiar with all precautions required and has complied
with all the requirements of the authority having jurisdiction.
State of Massachusetts: The installation must be made
by a licensed plumber or gas tter in the Commonwealth
of Massachusetts.
Any alteration of the original design, installed other than as
shown in these instructions or use with a type of gas not
shown on the rating plate is the responsibility of the person
and company making the change.
Important
All correspondence should refer to complete Model Number, Serial
Number and type of gas.
High Altitude
When installing this unit at an elevation above 2000 feet (in the
United States) it may be necessary to decrease the input rating by
changing the existing burner orice to a smaller size. Generally,
input should be reduced 4 percent for each 1000 feet above sea
level. However, if the heating value of the gas has been reduced,
this general rule may not apply. Check with local gas utility for proper
orice size identication.
Canadian High Altitude
Altitude: 0-4500 feet (0-1370 m)
When installing this unit at an elevation above 4500 feet (in Canada),
check with local authorities.
Consult your local gas utility for assistance in determining the proper
orice for location.
Preparation
This direct vent gas replace and its components are tested and
safe when installed in accordance with this Installation Manual.
Report to your dealer any parts damaged in shipment, specically
check glass condition. Do not install unit with damaged, incomplete,
or substitute parts. Read all instructions before starting installation
and follow these instructions carefully during installation to insure
maximum benet and safety. Failure to follow them will void your
warranty and may present a re hazard.
The warranty will be voided by, and the warranter disclaims any
responsibility for the following actions:
• Installat io n of any damaged fireplace or vent syst em
component.
• Modication of the replace or direct vent system.
• Installation other than as instructed by Empire Comfort Systems,
Inc.
• Improper positioning of the logs, glass door or decorative rock.
• Installation and/or use of any component part not manufactured
or approved by manufacturer.
The installation must conform with local codes or, in the absence of
local codes, with the National Fuel Gas Code ANSI Z223.1/NFPA
54* Natural Gas and Propane Installation Code, or CSA B149.1 in
Canada. *Available from the American National Standards Institute,
Inc. 11 West 42nd St., New York, N.Y. 10036.
Warning: ANY CHANGE TO THIS FIREPLACE OR ITS
CONTROLS CAN BE DANGEROUS.
Improper installation or use of the replace can cause
serious injury or death from re, burns, explosions, or carbon
Air Shutter OpeningFULL OPENFULL OPEN
Height without standoff34 3/4"(3.2mm)34 3/4"(3.2mm)
Width43"(1092mm)49"(1245mm)
Depth19 7/8"(505mm)19 7/8"(505mm)
Gas Inlet Shutoff Valve
(Pipe)
19,00020,500
#37 (.1040) P-213 - (DVP48FP(3,7,9))
#34 P-270 - (DVP48FP5)
#52 (.0635")
P-185
1.65MM
P-250
1/2 NPT1/2 NPT
NOTE: Air shutter settings
a r e f a cto r y m in i m u m
se tti ngs. Some venting
c o n f i g u r a t i o n s m a y
require minor air shutter
adjustments for optimum
SEE MANTLE CHART
FOR MINIMUM HEIGHT
OF MANTLE ABOVE UNIT
2"x4" HEADER
STAND OFF
3" (76 mm) HEIGHT
ABOVE TOPOF
FIREPLACE
3"
”
CLEARANCES
(914mm)
FRONT FACE (SIDE)
FIREPLACE
(TOP VIEW)
3
MAX.
PERPENDICULAR
SIDE WALL
45°
6
COMBUSTIBLE
MATERIALS ALLOWED
IN SHADED
AREAS
Clearance to Combustibles
Back0" (0 mm)
Side0" (0 mm)
Floor0" (0 mm)
Top Stand-off0" (0 mm)
Top Framing Edge3" (76 mm)
Mantel Chart (Figure 4)
Figure 3
Figure 2
Combustible Material
No greeting cards, stockings or ornamentation of any type should
be placed on or attached to the replace. The ow of heat can
ignite combustibles.
Figure 3
Clearances (Figure 5)
Clearance from top front edge of replace to ceiling is 36"
Clearance from side of replace to adjacent sidewall is 6".
Figure 5
28649-2-0811Page 8
CABINET
INSTALLATION
FLUSH WALL
INSTALLATION
ROOM DIVIDER
INSTALLATION
CORNER
INSTALLATION
ANGLED CORNER
INSTALLATION
ISLAND
INSTALLATION
LOCATING FIREPLACE
Note: Island (C) and Room Divider (D) installation is possible
as long as the horizontal portion of the vent system (H) does not
exceed 20 feet with a minimum vertical run of 8 feet. See details
in Venting Section.
When you install your Direct Vent Fireplace in (D) Room divider or
(E) Flat on wall corner positions, a minimum of 6 inches clearance
must be maintained from the perpendicular wall and the front edge
of the appliance.
Figure 6
28649-2-0811Page 9
GAS SUPPLY
The gas pipeline can be brought in through the right or left side of
the appliance. Consult the current National Fuel Gas Code, ANSI
Z223.1 CAN/CGA-B149 (.1 or .2) installation code.
Recommended Gas Pipe Diameter
Pipe LengthSchedule 40 Pipe
Inside Diameter
Nat.L.P.Nat.L.P.
0-10ft
0-3m
11-40ft
4-12m
41-100ft
13-30m
101-150ft
31-46m
Note: Never use plastic pipe. Check to conrm whether your local
codes allow copper tubing or galvanized.
Note: Since some municipalities have additional local codes, it is
always best to consult your local authority and installation code.
The use of the following gas connectors is recommended:
— ANS Z21.24 Appliance Connectors of Corrugated Metal Tubing
and Fittings.
— ANS Z21.45 Assembled Flexible Appliance Connectors of Other
Than All-Metal Construction
The above connectors may be used if acceptable by the authority
having jurisdiction. The state of Massachusetts requires that a exible
appliance connector cannot exceed three feet in length.
1/2"
12.7mm
1/2"
12.7mm
1/2"
12.7mm
3/4"
19mm
3/8"
9.5mm
1/2"
12.7mm
1/2"
12.7mm
1/2"
12.7mm
Figure 7
Tubing, Type L
Outside Diameter
1/2"
12.7mm
5/8"
15.9mm
3/4"
19mm
7/8"
22.2mm
3/8"
9.5mm
1/2"
12.7mm
1/2"
12.7mm
3/4"
1.9 mm
Installing a New Main Gas Cock
Each appliance should have its own manual gas cock.
A manual main gas cock should be located in the vicinity of the unit.
Where none exists, or where its size or location is not adequate,
contact your local authorized installer for installation or relocation.
Compounds used on threaded joints of gas piping shall be resistant
to the action of liqueed petroleum gases. The gas lines must be
checked for leaks by the installer. This should be done with a soap
solution watching for bubbles on all exposed connections, and if
unexposed, a pressure test should be made.
Never use an exposed ame to check for leaks. Appliance must
be disconnected from piping at inlet of control valve and pipe
capped or plugged for pressure test. Never pressure test with
appliance connected; control valve will sustain damage!
NOTE: The millivolt gas controls are equipped with a captured screw
type pressure test point, therefore it is not necessary to provide a
1/8" test point up stream of the control.
On direct ignition valves, hex plugs may be replaced with hose ttings
for pressure checks, then reinstalled before operating replace.
When using copper or ex connector use only approved ttings.
The appliance and it’s individual shut off valve must be disconnected
from supply piping system during any pressure testing of that system
at test pressures in excess of 1/2 psig (3.5kPa).
The appliance must be isolated from the gas supply piping system
by closing its individual manual shut off valve during any pressure
testing of the gas supply piping system at test pressures equal to
or less than 1/2 psig (3.5kPa).
Attention! If one of the procedures results in pressures in excess of
1/2 psig (14" w.c.) (3.5 kPa) on the replace gas valve, it will result
in a hazardous condition.
Checking Manifold Pressures
Both Propane and Natural gas valves have a built-in pressure
regulator in the gas valve. Natural gas models will have a manifold
pressure of approximately 3.5" w.c. (.871kPa) at the valve outlet
with the inlet pressure to the valve from a minimum of 4.5" w.c.
(1.120kPa) for the purpose of input adjustment to a maximum of
14.0" w.c. (3.484kPa). Propane gas models will have a manifold
pressure approximately 10.0" w.c. (2.49kPa) at the valve outlet
with the inlet pressure to the valve from a minimum of 10.8" w.c.
(2.68kPa) for the purpose of input adjustment to a maximum of
14.0" w.c. (3.484kPa).
Gas Supply Pressure (inches w.c.)
MinimumNormalMaximum
Natural Gas4.5"7.0"*14.0"
LP (Propane)10.8"11.0"*14.0"
Manifold Pressure (inches w.c.)
Normal (HI)
Natural Gas3.5"
LP (Propane)10.0"
*NOTE: Remote "RF" Models - 10.5" w.c. maximum
Figure 8
28649-2-0811Page 10
REAR VENT CONVERSION
Note: Discard insulation
& retainer when using
vertical venting off
VERTICAL VENTING
HORIZONTAL VENTING
FLUE INSULATION
INSULATION
RETAINER
INLET VENT COLLAR
INLET VENT COLLAR
FLUE OUTLET
COLLAR
FLUE COVER PLATE
(See note above)
INLET VENT
COVER PLATE
FLUE COVER PLATE
INLET VENT
COVER PLATE
Note:Itis recommended that the
flue cover plate tab be pulled
outward prior to removal.
This will ensure that the plate
is not accidentally dropped
inside the rear air chamber.
Note: Discard insulation
& retainer when venting off
top of fireplace.
Converting ue take-off to rear venting
When switching out the ue and inlet vent collars to run horizontally
off the rear vent, the following steps must be taken.
1. Remove the inlet vent collar (8 screws) and ue collar (4 screws)
from the top of the replace, and set to the side.
2. Remove the inlet cover plate and ue cover plate located on
the back of the replace. These will be used to close the top
ue and inlet openings.
VENT SYSTEMS
The following vent systems are acceptable for use with the
DVP (42,48) series replaces:
Simpson Duravent® GS 5" - 8", Refer to Page 37.
American Metal Products 5" - 8"
Selkirk Direct-Temp® 5" - 8"
Security Secure Vent® 5" - 8"
Empire Flexvent Kit DVVK-5F, Refer to Page 42.
3. Insert the insulation retainer bracket and insulation into the top
ue pipe before reinstalling the ue cover plate over the top
ue with 4 screws.
4. Reinstall the inlet cover plate over the top inlet opening with 4
screws. See illustration above.
5. Install the ue collar assembly to the rear ue with 4 screws.
6. Install the inlet vent collar to the rear of the replace with 8
screws.
7. This completes the conversion for a rear vent application.
Note: For top vented installations, the insulation and retainer are
to be removed from the ue pipe and discarded.
The following vent systems are acceptable for use with the DVA-47
adaptor vertically off top of replace only:
Simpson Duravent® GS 4" - 6⅝", refer to page 36.
American Metal Products 4" - 6⅝"
Selkirk Direct-Temp® 4" - 6⅝"
Security Secure Vent® 4" - 6⅝"
Empire Horizontal Round Termination Kit DVVK-4RE, refer to page
30.
Empire Flexvent Kit DVVK-4F, refer to page 33.
Empire Direct Vent Kit DVVK-4FV, refer to page 21.
28649-2-0811Page 11
VENT PIPE
1" MINIMUM CLEARANCE AROUND VENT PIPE
Combustibles NOT
allowed in shaded
area
5” Diameter flue
8” Diameter
intake vent
1”
(25 mm)
1” (25 mm)
3” (76 mm)
To pofVent
INSTALLATION
Framing and Finishing
1. Choose unit location.
2. Frame in replace with a header across the top. It is important
to allow for nished face when setting the depth of the frame.
3. Attach replace to frame using adjustable frame. Preset depth to
suit facing material (adjustable to 1/2", 5/8" or 3/4" depths).
4. Use (8) 1/2" hex-head screws supplied in hardware package,
to screw through slotted holes in drywall strip and then screw
into pre-drilled holes on replace side. Measure from face of
replace to face of drywall strip to determine nal depth.
Vent Pipe Clearance
Note: Maintain one inch (1") of clearance around vertical vent
pipe. See Figure 10. For horizontal vent, maintain a minimum 1"
clearance to the bottom and sides of the vent, and 3" clearance to
combustibles above the vent pipe. See Figure 11.
Figure 10
Figure 9
Figure 11
28649-2-0811Page 12
NAILOR OTHER SUITABLEFASTENER
INSTALLATION (continued)
Flush Mount Mantel Installation (Figure 12)
The replace must extend 3/4" beyond nished wall surface when
using a ush mount mantel. Refer to Figure 12 to locate nailing
anges on replace sides. Mark and drill two (2) 1/8" holes into
replace side to mount each nailing ange. Use eight (8) 1/2" hexhead screws supplied in hardware package to attach nailing anges
to replace sides.
DVP42DVP48
"A"37 3/4"37 3/4"
"B"43 3/8"49 3/8"
"C"19 7/8"19 7/8"
Figure 13
Figure 12
Framing (Figure 13)
Fireplace framing can be built before or after the replace is set in
place. Framing should be positioned to accommodate wall covering
and replace facing material. The replace framing should be
constructed of 2 x 4 lumber or heavier. The framing headers may
rest on the replace standoffs. Refer to Figure 13 for minimum
framing dimensions.
CAUTION: MEASURE FIREPLACE DIMENSIONS AND VERIFY
FRAMING METHODS, AND WALL COVERING DETAILS BEFORE
FRAMING CONSTRUCTION BEGINS.
Framing dimension "A" includes a three inch clearance for
standoffs on rebox. After installing rebox into framing,
the nished wall surface must cover the three inch opening
above the rebox.
Attention: If a base or mantel is not used and the appliance is
installed directly on carpeting, tile or other combustible material
other than wood ooring, it shall be installed on a metal or wood
panel extending the full width and depth of the appliance. The
vertical dimension in Figure 13 must be adjusted when a metal or
wood panel is placed beneath the appliance.
Finishing (Figures 14 and 15)
Finish the walls with the material of your choice. Figure 4 on page 8
shows the minimum vertical and corresponding maximum horizontal
dimensions of mantels or other combustible projections above the
top front edge of the replace.
Only non-combustible materials may be used to cover the black
replace front.
Warning: When nishing the replace never obstruct or modify
the air inlet/outlet louvers in any manner. Provide adequate
clearances around air openings into the combustion chamber.
Caution: If the joints between the nished wall and the replace
surround (top and sides) are sealed, a 300°F minimum sealant
material must be used. These joints are not required to be sealed.
Only non-combustible material (using 300°F minimum adhesive if
needed), can be applied as facing to the replace surround.
28649-2-0811Page 13
Flush Wall Installation
Attention: Cold climate installation recommendation: When
installing this unit against a non-insulated exterior wall, it is
recommended that the outer walls be insulated to conform
to applicable insulation codes.
Vent Runs (Figures 16, 17, 18, 19 and 20)
In planning the installation for the replace, it is necessary to install
certain components before the appliance is completely positioned
and installed. These include the direct vent system, gas piping for
the appliance and the electrical wiring. (If the fan option is used.)
The appliance can be mounted on any of the following surfaces:
1. A at, hard combustible (burnable) surface.
2. A raised wooden platform.
3. Four (4) corner supports. (Example: Four (4) concrete masonry
blocks.) These supports must be positioned so they contact all
four (4) perimeter edges on the bottom of the unit.
VERTICAL, 90° ELBOW WITH HORIZONTAL TERMINATION
Figure 14
Combustible Surround Installation
Figure 16
Figure 15
28649-2-0811Page 14
INSTALLATION (continued)
VENT CAP
A
"
PIPE LENGTH
WALL FIRESTOP/
THIMBLE
"
WALL FIRESTOP/
THIMBLE
VENT
CAP
WALL FIRESTOP/
THIMBLE
WALL FIRESTOP/
THIMBLE
HORIZONTAL ONLY, STRAIGHT OUT THE BACK
"A""B"MODEL
6"(152mm)5 1/8"(130mm) to 6 /2"(165mm)DVP 42,48
9"(229mm)8 1/8"(206mm) to 91/2"(241mm)DVP 42
12"(305mm) 11 1/8"(283mm) to 12 1/2"
DVP 42
(317mm)
Figure 17
VERTICAL, 90° ELBOW TO
HORIZONTAL OUT THE WALL
CORNER INSTALLATION VERTICAL, 90° ELBOW TO
HORIZONTAL OUT THE WALL
Dim.DVP42DVP48
C
D
A
B
45 3/8"
1152mm
32 1/8"
816mm
13 3/8"
34 mm
64 1/8"
1628mm
49 5/8"
1260mm
35 1/8"
892mm
15 1/2"
39 mm
70 1/8"
1781mm
Figure 19
CORNER INSTALLATION HORIZONTAL, 45° ELBOW TO
HORIZONTAL OUT THE WALL
"A""B""C"
6"(152mm)11 1/4"(286mm) to
12 3/4"(324mm)
9"(229mm)14 1/4"(362mm) to
15 3/4"(400mm)
12"(305mm)17 1/4"(438mm) to
18 3/4"(476mm)
4 3/4"(121mm) to
6 1/4"(159mm)
7 3/4"(197mm) to
9 1/4"(235MM)
10 3/4"(273mm) to
12 1/4"(311mm)
Figure 18
28649-2-0811Page 15
DVP42DVP48
"A""B""B"
6"(152mm)4"(102mm) to
5 1/2"(140mm)
9"(229mm)6"(152mm) to
7 /2"(191mm)
12"(305mm) 9"(229mm) to
10 1/2"(267mm)
Figure 20
4"(102mm) to
5"(127mm)
6"(152mm) to
7 1/2"(191mm)
9"(229mm) to
10 1/2"(267mm)
VERTICAL DIMENSION FROM THE BOTTOM OF THE UNIT
TO THE CENTER OF THE FLUE OUTLET
WITH VERTICAL OR HORIZONTAL TERMINATION CAPS
VENTING FIREPLACE - TOP
To Use the Vent Graph (Figure 21)
1. Determine the height of the center of the horizontal vent
pipe. Using this dimension on the Sidewall Vent Graph,
locate the point it intersects with the slanted graph
line.
2. From the point of this intersection, draw a vertical line to
the bottom of the graph.
3. Select the indicated dimension, and position the unit in
accordance with same.
EXAMPLE A:
If the vertical dimension from the oor of the unit is 35 feet,
the horizontal run to the outer wall ange must not exceed
6.5 feet.
EXAMPLE B:
If the vertical dimension from the oor of the unit is 6.5 feet,
the horizontal run to the outer wall ange must not exceed
14.5 feet.
Special Note: For each 45 degree elbow installed in the
horizontal run, the length of the horizontal run MUST be
reduced by 18" (45cm). This does not apply if the 45 degree
elbows are installed on the vertical part of the vent system.
Reduce 3' for every 90° elbow.
Example: According to the chart the maximum horizontal
vent length is 20' and if two 45 degree elbows are required
in the horizontal vent it must be reduced to 17'.
The maximum number of 45 degree elbows permitted per
side wall installation is two (2). These elbows can be installed
in either the vertical or horizontal run.
Note: On vertical venting the rst elbow does not get
counted.
Venting Graph (Dimensions in Feet)
Acceptable vertical and horizontal vent run.
(40' maximum vertical and 20' maximum horizontal)
Unacceptable vertical and horizontal vent run.
Figure 21
28649-2-0811Page 16
VENTING FIREPLACE - TOP (continued)
Below Grade Installation
When it is not possible to meet the required vent terminal clearances
of 12" (305mm) above grade level, a snorkel kit is recommended.
It allows installation depth down to 7" (178mm) below grade level.
The 7" (178mm) is measured from the center of the horizontal vent
pipe as it penetrates through the wall.
Ensure the sidewall venting clearances are observed. If venting
system is installed below ground, we recommend a window
well with adequate and proper drainage to be installed around
the termination area.
Firestop at
Ceiling Level
TYPICAL BASEMENT INSTALLATION
Figure 22
Examples of possible venting systems using one (1) 90° elbow.
Eight (8) feet is listed as minimum vertical vent run with 20 feet of
maximum horizontal vent run. Vertical dimensions are based on
centerline to centerline of pipe. Horizontal dimensions are based
on centerline of pipe to end of termination.
Figure 23
Examples of possible venting systems using two (2) 90° elbows.
V is listed as minimum vertical dimensions and H1 + H2 is listed
as total of maximum horizontal dimensions. The maximum vertical
and horizontal distances for two (2) 90° elbows as shown in Figure
24 is 20 feet.
Attention: Refer to Figure 21 for additional venting requirements.
Firestop at
Ceiling Level
28649-2-0811Page 17
Figure 24
MAXIMUM HORIZONTAL
RUN WITH NO VERTICAL
RISE AND 90° ELBOW
MAXIMUM HORIZONTAL
RUN WITH MINIMUM
VERTICAL RISE AND
90° ELBOW
minimum
A
CENTER OF ELBOW
STRAIGHT OUT
(MINIMUM)
2
30
VENTING FIREPLACE - TOP (continued)
Figure 25
MINIMUM HOLE LOCATION DIMENSIONS FOR THROUGH
THE WALL HORIZONTAL INSTALLATIONS WITH 90 DEGREE
ELBOW OFF TOP OF FIREPLACE
Figure 26
FIREPLACE
SERIES
DVP42FP43-1/2"
DVP48FP43-1/2"
FIREPLACE
SERIES
DVP42FP46"
DVP48FP46"
Positioning the Fireplace
Determine the exact position of the appliance so the direct vent
termination will be centered (if possible) between two (2) studs. This
will avoid any extra framing. All vent kit pipes should be assembled
on the unit after the unit is moved into the nal position.
Cutting the Hole (Figures 25)
After the replace has been positioned in its permanent location,
the hole through the exterior wall of the house can be cut. This hole
must be 12" (305mm) high x 10" (254mm) wide with its center line
determined by the amount of vertical rise and horizontal run of the
termination. See Figure 25. When locating the hole it must be noted
that the bottom of the cap must be 12" (305mm) above the ground
level, and top of the cap must be no less than 18" (457mm) below a
combustible projection, and no closer than 9" (229mm) to any wall
running parallel to vent termination. See Figure 26.
HARD ELBOW DIMENSIONS
"A""B""C"
5"
(1105mm)
(1105mm)
FLEX PIPE 90 DEGREE BEND
"A""B""C"
(1143mm)
(1143mm)
(127mm)
5"
(127mm)
5"
(127mm)
5"
(127mm)7" (178mm)
(178mm)
(178mm)
7" (178mm)
7"
7"
Figure 27
28649-2-0811Page 18
24”
24” MINIMUM
CLEARANCE TO
COMBUSTIBLES
EXAMPLES - TOP VENT RUN
Figure 28
Figure 29
28649-2-0811Page 19
Figure 30
VENTING EXAMPLES WHEN USING DVA47 ADAPTOR
Vertically Off Top of Fireplace Only
Figure 31
Figure 32
Figure 33
28649-2-0811Page 20
DVVK-4FV DIRECT VENT TERMINATION KIT
NOTE: For top vent installation only. Use of DVA47 adaptor required.
Installation Instructions
This termination kit can only be used with Empire Comfort Systems direct vent replaces listed for
use with DVVK-4FV Vertical Flex Vent Kit. Please review the instructions packaged with your replace and verify the replace model number. Check that this ex vent system is listed for use with
your replace model prior to starting the installation.
This vent kit may be installed as an OEM installation in a manufactured home (USA only) or
mobile home and must be installed in accordance with the manufacturer’s instructions and
the manufactured home construction and safety standard, Title 24 CFR, Part 3280 or Standard
for Installation in Mobile Homes, CAN/CSA Z240 MH.
CAUTION
All Fireplaces listed for use with the DVVK-4FV will operate safely when installed in accordance with this instruction
manual. Read all instructions before starting installation, then follow these instructions carefully to maximize replace
performance and safety. Report damaged parts to your dealer.
WARNING
Any common venting of the gas appliance using the DV vent kit with other gas appliances is not allowed. Do not connect
this appliance to a chimney ue servicing a separate solid fuel-burning appliance.
WARNING
Failure to follow these instructions may create a possible re hazard and will void the warranty.
WARNING
Always maintain minimum clearances around vent systems. The minimum clearance to combustibles for horizontal runs
of vent pipe is 3 inches from the top, and 1 inch from the sides and bottom of the vent system. Do not pack the open air
spaces around the replace or ue with insulation or other materials. Any horizontal run must have a 1/4” rise for every
one (1) foot of run towards the vent termination. The vent above the roof must terminate vertically.
WARNING
Contact your Local Building and Fire Ofcials about restrictions and installation inspections in your area.
IMPORTANT SAFETY INFORMATION
• The vertical termination cap MUST be vented directly to
the outside. The termination kit MUST NEVER be connected to a chimney ue(s) servicing a separate solid-
fuel burning appliance or any other appliances.
• Termination cap MUST NOT be mounted horizontally.
• The exible vent pipe cannot be intermingled with any
of the rigid vent pipe section(s). DO NOT connect two
sections of exible vent pipe together to achieve a lon-
ger length without the use of approved connectors.
• The installation must conform with local codes or in
the absence of local codes, with the National Fuel Gas
Code, ANSI Z223.1 (in the United States) or with the
current installation code CAN/CGA B149 (in Canada).
• Only Direct Vent replaces approved for use with Em-
pire Comfort Systems, Inc. DVVK-4FV termination kit
shall be used. See PARTS LIST/ILLUSTRATIONS section for vent component identication.
• Horizontal vent runs must be supported every 2 feet us-
ing wall straps. Vertical runs must be supported every
3 feet using wall straps. Slip wall straps loosely on to
pipe. Attach installer provided straps to framing members using nails or screws.
• The replace and venting system should be inspected
before initial use and at least annually by a qualied
eld service person. Inspect the external vent cap on a
regular basis to make sure that no debris is interfering
with the airow. Inspect entire venting system to ensure
proper function.
• Please refer to the replace instructions for information
on Termination Cap clearances.
28649-2-0811Page 21
DVVK-4FV DIRECT VENT TERMINATION KIT (cont.)
PRE-INSTALLATION INFORMATION:
Items Required For Installation:
ToolsBuilding Supplies
Phillips Screwdriver
Hammer
Saw and/or saber saw
Level
Measuring Tape
Electric Drill and Bits
Pliers
Square
Tin Snips
Before You Start:
Plan your installation. Read these instructions and the replace installation manual before installing unit and vent system.
Set unit in place and survey how best to vent the unit. After the vent conguration has been decided, stretch the ex pipe
components out, then trim off what will not be needed.
Refer to the replace installation manual for information on vertical venting requirements. The maximum length of vent when
using ex venting is 35 feet total. Contact your dealer or distributor for information on ex vent extension kits that may be
added to the DVVK-4FV kit, in order to terminate up to 35 feet. Available extension kits include the DVEK-10 (10’ Flex) or
the DVEK-25 (25’ Flex) extension kits. The extension kits include connection hardware.
Framing Materials
Wall Finishing Materials
Caulking Material (Noncombustible)
Support Strap supplies
Installation of the Vertical Flex Termination Kit
WARNING
Ensure that the venting system exits the structure through the roof and does not terminate less than 12 inches (305mm) above the
roof.
WARNING
Refer to your replace homeowner’s manual for the minimum and maximum venting requirement of your replace prior to installation.
Failure to do so may cause a re hazard.
WARNING
This exible pipe termination kit is ONLY for vertical terminations.
WARNING
Any horizontal run section must have a 1/4” rise for every one (1) foot of run towards the vent termination. Never allow the vent pipe to
run downward. This could cause high temperatures and may present a re hazard. This vertical kit may incorporate two (2) 90 degree
bends, but must terminate vertically.
CAUTION
This ex vent kit can be installed either vertically or horizontally off of Direct Vent Series replaces but must only terminate vertically.
WARNING
Because of sharp edges, always use gloves when handling the ex vent components.
CAUTION
Vent connections should overlap a minimum of 1” for proper sealing.
Always stretch and secure venting with metal strapping secured with nails (nails and strapping not supplied) to ensure that the ex vent
runs remain true.
If space permits, it is generally easier to attach venting in the top vent conguration.
CAUTION
INSTALLATION NOTE:
28649-2-0811Page 22
FLEX OUTER
AIR INTAKE PIPE
SPACER SPRINGS
FLEX FLUE PIPE
SPACER SPRINGS
4" FLEX
VENT PIPE
12”
305mm
12”
305mm
12”
305mm
12”
305mm
DVVK-4FV DIRECT VENT TERMINATION KIT (cont.)
Step-By-Step Installation For Flex DV Kit
1. Unpack vent components and check all items for shipping
damage.
2. For this venting system to operate as designed it is dependent
on the use of all parts and procedures detailed in these instructions. Failure to follow these instructions may potentially
affect the performance of this vent system and the attached
appliance.
3. As per the replace manufacturer’s instructions, replace the
existing 6 5/8” diameter replace vent adapter with the 7”
diameter ex vent replace adapter included in the vent kit.
Install the adapter collar with the screws removed from the
standard replace collar. Refer to the replace manual for additional information on the vent collar removal and installation.
4. Once the replace location has been determined, mark the
ceiling where the ex vent will pass through. Cut an opening
for installation of the restop thimble assembly. The opening
must measure a minimum of 9-1/2” x 9-1/2” square. See Figure 34.
5. Next, determine the location for the cutout in the roof opening.
This opening must be large enough to provide a minimum 1”
air space clearance from the vertical vent pipe to any combustible framing.
6. Install the Firestop/Thimble assembly to the framed opening
in the ceiling using common nails or screws. Note: The thimble assembly is adjustable up or down as
needed within the restop. It is also designed with a pivoting
restop for use with 0 - 3/12 pitch cathedral ceilings.
7. To begin vent system assembly, rst layout all the vent components on the oor in the order in which they will be assem-
bled.
8. Stretch the 4” diameter inner ex ue and 7” diameter outer
ex vent to the maximum length of 6 feet.
9. Install the spring spacers provided around the 4” diameter ex
ue at 1 foot intervals, then slide the ue pipe with spacers into
the 7” diameter outer ex vent pipe. Make sure the springs are
spaced evenly starting at 12 inches from the replace collar.
See Figure 35.
Figure 34
28649-2-0811Page 23
Figure 35
WING NUT (2)
PIPE CLAMP
ROOF BRACKET (2)
NUT (2)
SCREW (2)
H
X
12
ROOF PITCH IS X/12
H (Min.)-Minimum height from
roof to lowest discharge opening
DISCHARGE
LOWEST
OPENING
VENT CAP
GAS VENT
DVVK-4FV DIRECT VENT TERMINATION KIT (cont.)
10. With the ex vent assembly and the 48” long hard pipe components laid out on the oor, begin securing these parts to-
gether. First, apply a generous bead of silicone sealant to the
inside of the 4” diameter ex ue (not the end with the pre-installed connector), then slide the ex ue over the 4” diameter
hard pipe ue. Be sure to overlap at least 1-1/4”. Secure this
connection with a 4” diameter band clamp provided. Be care-
ful not to damage or tear the ex ue when tightening clamp.
11. Repeat the connection process for the outer 7” diameter ex
vent to hard pipe connection. Use silicone sealant at this joint
also, overlap at least 1-1/4”, then secure the joint with the 7”
diameter band clamp provided. Be careful not to damage or
tear the ex vent pipe when tightening the clamp.
12. While the venting is still on the oor, assemble the roof jack
components as shown in Figure 36 and pre-install the roof
jack assembly to the hard pipe approximately 18” from the top
end of the hard pipe.
13. Now the pre-assembled vent system may be carried to the
roof, then lowered through the roof cutout opening (see step
5). Feed the ex vent end down through the roof opening and
restop/thimble assembly installed in steps 4 through 6.
14. Secure the roof support assembly to the roof sheathing with
at least (4) nails/screws through each support bracket. Check
that the combustible clearances through the roof framing will
maintain at least a 1” clearance from the vent pipe.
15. Determine how high the vent terminal should be located
above the roof line based on the roof pitch information shown
in Figure 37. Adjust the vent system height by loosening the
pre-installed roof support pipe clamp and sliding the vent pipe
up or down as pre-determined, then re-tighten the pipe clamp.
Install a couple of sheet metal screws through the pipe clamp
into the outer hard vent pipe to lock in place.
16. Check to make sure that the bottom end of the ex vent is
long enough to reach the replace adapter collars. If too long,
trim off the extra ex vent not needed.
Figure 36
ROOF PITCHH (Min.)
Flat to 6/1212” (305mm)
6/12 to 7/1215” (381mm)
Over 7/12 to 8/1218” (457mm)
Over 8/12 to 16/1224” (610mm)
Over 16/12 to 21/1236” (914mm)
Figure 37
28649-2-0811Page 24
Loading...
+ 56 hidden pages
You need points to download manuals.
1 point = 1 manual.
You can buy points or you can get point for every manual you upload.