Empire Comfort Systems DVF-36-2, DVF-36IP-2, DVF-42IP-2, DVF-42-2 User Manual

Page 1
INSTALLATION INSTRUCTIONS
AND
OWNER'S MANUAL
DIRECT VENT
GAS FIREPLACE
MODELS DVF-36-2 DVF-42-2 DVF-36IP-2 DVF-42IP-2
WARNING: If the information in this manual is not followed exactly , a fir e or explosion may result causing prop­erty damage, personal injury or loss of life.
— Do not store or use gasoline or other
flammable vapors and liquids in the vicinity of this or any other appliance.
— WHA T T O DO IF YOU SMELL GAS
Do not try to light any appliance.
Do not touch any electrical switch;
do not use any phone in your build­ing.
Immediately call your gas supplier
from a neighbor's phone. Follow the gas supplier's instructions.
If you cannot reach your gas sup-
plier, call the fire department.
— Installation and service must be per-
formed by a qualified installer , service agency or the gas supplier.
EFFECTIVE DATE
NOVEMBER, 2000
This appliance may be installed in an aftermarket permanently located, manu­factured (mobile) home, where not pro­hibited by state or local codes.
This appliance is only for use with the type of gas indicated on the rating plate. This appliance is not convertible for use with other gases, unless a certified kit is used.
W ARNING: If not installed, operated and maintained in accordance with the manu­facturer's instructions, this product could expose you to substances in fuel or from fuel combustion which can cause death or serious illness.
R-5627 Page 1
Page 2
TABLE OF CONTENTS
Section Page
Important Warnings................................................................. 2
Safety Information for Users of LP Gas.................................. 3
Specifications .......................................................................... 4
Fireplace Dimensions .............................................................. 4
Fireplace Component Installation............................................ 5
Introduction ............................................................................. 6
Planning Your Installation....................................................... 7
Installation ..........................................................................8-13
Termination Clearances......................................................... 14
Vent Clearances..................................................................... 15
Vent System Identification .................................................... 16
Framing/Finishing ............................................................17-19
Leak Testing Gas Line........................................................... 19
Log Placement ..................................................................19-20
Standing Pilot Operating Instructions ..............................21-23
Section Page
Standing Pilot Delayed Ignition Reset Switch ...................... 23
Standing Pilot Lighting Instructions...................................... 24
Standing Pilot Troubleshooting ............................................. 25
Intermittent Pilot Operating Instructions..........................26-27
Intermittent Pilot Delayed Ignition Reset Switch.................. 26
Intermittent Pilot Lighting Instructions ................................. 28
Intermittent Pilot Troubleshooting ...................................29-30
Maintenance and Service....................................................... 31
Parts View of Fireplace ......................................................... 32
Parts List ................................................................................ 33
Optional Automatic Blower Installation Instructions.......34-35
Optional Fresh Air Intake Installation Instructions ..........36-37
Accessory Parts ..................................................................... 38
Optional Brick Liner Installation Instructions....................... 39
IMPORTANT WARNINGS
Before enclosing the Simpson Dura-Vent 5 x 8 vent pipe assembly operate the appliance to ensure it is venting properly.
THIS IS A HEATING APPLIANCE WHEN HEATER BAFFLE IS INSTALLED, SEE PAGE 5
Do Not Operate This Appliance Without Glass Front Panel Installed.
• If this appliance is installed directly on carpeting, tile or other combustible material other than wood flooring the appliance shall be installed on a metal or wood panel extending the full width and depth of the appliance.
The base referred to above does not mean the fireproof base as used on wood stoves. The protection is for rugs that are extremely thick and light colored tile.
• Children and adults should be alerted to the hazards of high surface temperatures and should stay away to avoid burns or clothing ignition.
• Young children should be carefully supervised when they are in the same room as the appliance.
Due to high temperatures the appliance should be located out of traffic and away from furniture and draperies.
• The glass front or any part removed for servicing the appliance must be replaced prior to operating the appliance. Work should be done by a qualified service person.
• Keep burner and control compartment clean.
• Vent cap is hot while fireplace is in operation.
• Installation and repair should be done by a QUALIFIED SERVICE PERSON. The appliance should be inspected before use and at least annually by a qualified service person. More frequent cleaning may be required due to excessive lint from carpeting, bedding materials, etc. It is imperative that control compartments, burners and circulating air passageways of the appliance be kept clean.
• DO NOT put anything around the fireplace that will obstruct the flow of ventilation air.
• Clothing or other flammable material should not be placed on or near the appliance.
• Adequate accessibility clearances for servicing and proper operation.
• This appliance must not share or be connected to a flue serving a separate solid-fuel burning appliance.
• Keep the area around your appliance clear of combustible materials, gasoline and other flammable vapor and liquids.
• Under no circumstances should any solid fuels (wood, coal, paper or cardboard etc.) be used in this appliance.
• The flow of combustion and ventilation air must not be obstructed in any way.
• DO keep the appliance area clear and free from combustible material, gasoline and other flammable vapors and liquids.
• DO examine venting system periodically and replace damaged parts.
• DO make a periodic visual check of pilot and burners. Clean and replace damaged parts.
• CAUTION: The glass used in your fireplace is tempered glass. If the glass is cracked or damaged in any way, it should be replaced only with a complete glass frame assembly from Empire. See parts list on Page 33 for ordering.
• DO NOT use this fireplace if any part has been under water. Immediately call a qualified service technician to inspect the heater and to replace any part of the control system and any gas control which has been under water.
• Any safety screen or guard removed for servicing an appliance must be replaced prior to operating the appliance.
Page 2 R-5627
Page 3
SAFETY INFORMATION FOR USERS OF LP-GAS
Propane (LP-Gas) is a flammable gas which can cause fires and explosions. In its natural state, propane is odorless and colorless. You may not know all the following safety precau­tions which can protect both you and your family from an accident. Read them carefully now, then review them point
LP-GAS WARNING ODOR
If a gas leak happens, you should be able to smell the gas because of the odorant put in the LP-Gas.
That's your signal to go into immediate action!
by point with the members of your household. Someday when there may not be a minute to lose, everyone's safety will depend on knowing exactly what to do. If, after reading the following information, you feel you still need more informa­tion, please contact your gas supplier.
Do not operate electric switches, light matches, use your phone. Do not do anything that could ignite the gas.
Get everyone out of the building, vehicle, trailer, or area. Do that IMMEDIATELY.
Close all gas tank or cylinder supply valves.
LP-Gas is heavier than air and may settle in low areas such as basements. When you have reason to suspect a gas leak, keep out of basements and other low areas. Stay out until
NO ODOR DETECTED - ODOR FADE
Some people cannot smell well. Some people cannot smell the odor of the chemical put into the gas. You must find out if you can smell the odorant in propane. Smoking can decrease your
ability to smell. Being around an odor for a time can affect your sensitivity or ability to detect that odor. Sometimes other odors in the area mask the gas odor. People may not smell the gas odor or their minds are on something else. Thinking about smelling a gas odor can make it easier to smell.
The odorant in LP-gas is colorless, and it can fade under some circumstances. For example, if there is an underground
leak, the movement of the gas through soil can filter the odorant. Odorants in LP-Gas also are subject to oxidation. This fading can
firefighters declare them to be safe.
Use your neighbor's phone and call a trained LP-Gas service person and the fire department. Even though you may not continue to smell gas, do not turn on the gas again. Do not re­enter the building, vehicle, trailer, or area.
Finally, let the service man and firefighters check for escaped gas. Have them air out the area before you return. Properly trained LP-Gas service people should repair the leak, then check and relight the gas appliance for you.
occur if there is rust inside the storage tank or in iron gas pipes. The odorant in escaped gas can adsorb or absorb onto or into
walls, masonry and other materials and fabrics in a room. That will take some of the odorant out of the gas, reducing its odor intensity.
LP-Gas may stratify in a closed area, and the odor intensity could vary at different levels. Since it is heavier than air, there may be more odor at lower levels. Always be sensitive to the slightest gas odor. If you detect any odor, treat it as a serious leak. Immediately go into action as instructed earlier.
SOME POINTS TO REMEMBER
Learn to recognize the odor of LP-gas. Your local LP-Gas
Dealer can give you a "Scratch and Sniff" pamphlet. Use it to find out what the propane odor smells like. If you suspect that your LP-Gas has a weak or abnormal odor, call your LP-Gas Dealer.
• If you are not qualified, do not light pilot lights, perform service, or make adjustments to appliances on the LP-Gas system. If you are qualified, consciously think about the odor of LP-Gas prior to and while lighting pilot lights or perform­ing service or making adjustments.
• Sometimes a basement or a closed-up house has a musty smell that can cover up the LP-Gas odor. Do not try to light pilot lights, perform service, or make adjustments in an area where the conditions are such that you may not detect the odor if there has been a leak of LP-Gas.
• Odor fade, due to oxidation by rust or adsorption on walls of new cylinders and tanks, is possible. Therefore, people should be particularly alert and careful when new tanks or cylinders are placed in service. Odor fade can occur in new tanks, or reinstalled old tanks, if they are filled and allowed
R-5627 Page 3
to set too long before refilling. Cylinders and tanks which have been out of service for a time may develop internal rust which will cause odor fade. If such conditions are suspected to exist, a periodic sniff test of the gas is advisable. If you
have any question about the gas odor, call your LP-gas dealer. A periodic sniff test of the LP-gas is a good safety measure under any condition.
• If, at any time, you do not smell the LP-Gas odorant and you think you should, assume you have a leak. Then take the same immediate action recommended above for the occasion when you do detect the odorized LP-Gas.
• If you experience a complete "gas out," (the container is under no vapor pressure), turn the tank valve off immedi­ately. If the container valve is left on, the container may draw in some air through openings such as pilot light orifices. If this occurs, some new internal rusting could occur. If the valve is left open, then treat the container as a new tank. Always be sure your container is under vapor pressure by turning it off at the container before it goes completely empty or having it refilled before it is completely empty.
Page 4
SPECIFICATIONS
38 1/4"
33 1/2"
36 1/4"
31 1/2"
27 3/4"
13 7/8"
15 1/2"
4 3/4"
4 3/4"
RIGHT SIDE VIEW
GAS LINE ACCESS
FRESH AIR COVER PLATE
LEFT SIDE VIEW
GAS LINE
MODEL DVF-36/DVF-42
3 11/16"
GAS CONTROLS AND SWITCHES
INSIDE DOOR
RATING PLATE AND LABELS INSIDE DOOR
CORNER CABINET MANTEL, EHM-CU, EHM-CCF, EHM-COF
DIMENSION IS FROM CENTER OF FLUE OUTLET TO INSIDE OF WALL
Model DVF-36 DVF-36IP DVF-42 DVF-42IP Input BTU/HR (KW/H) Maximum 25,000 (7.3) 25,000 (7.3) 28,000 (8.2) 28,000 (8.2)
BTU/HR (KW/H) Minmum 17,500 (5.1) —— 18,500 (5.4) —— Height without standoff 36 1/4"" 36 1/4" 38 1/4" 38 1/4" Width 39" 39" 45" 45" Depth 21" 21" 24" 24" Gas Inlet (Pipe) 3/8" 1/2" 3/8" 1/2"
Accessories for All DVF-36 & DVF-42 Models
FRBC-1 Battery Operated Remote Control FRBTC-1 Battery Operated Remote Control with Thermostat (Only used when fireplace is converted into a heater. See Page 5.) FREC-1 Electric Remote Control FWS-1 Wall Switch
DVF-VKT-1 Direct Vent Fireplace Vent Kit (Top Vent) (standard through the wall venting) (Includes SD-1208, SD-1291, SD-1290 and
Firestop) DVF-VKR-1 Direct Vent Fireplace Vent Kit (Rear Vent) (standard through the wall venting) (Includes SD-1208, SD-1284 and Firestop) FB-AK-2 Kit for Fresh Air Plus for Direct Vent Fireplaces FB-BK-2 Automatic Blower
Accessories for All DVF-36 & DVF-42 Standing Pilot Models
GWSG-T 750 Millivolt Wall Thermostat (Only used when fireplace is converted into a heater. See Page 5.)
DVF-36 Accessories Only
DVF-BL-36 36" Brick Liner FBF-36BL-2 Black Frame 36" DVFBF-36BR-1 Polished Brass Frame 36" FBF-36BP-2 Black Porcelain Frame 36" FBL-36BR-2 Polished Brass Louvers 36" FBL-36BP-2 Black Porcelain Louvers 36"
DVWT-36BR Brass Window Trim 36"
GAS LINE ACCESS
FRESH AIR COVER PLATE
LEFT SIDE VIEW
VENT COLLAR
STANDOFFS
NAILING
FLANGES
GLASS FRAME
ASSEMBLY
GAS LINE
ACCESS
RATING PLATE AND LABELS INSIDE DOOR
GAS CONTROLS AND SWITCHES
INSIDE DOOR
Page 4 R-5627
DVF-42 Accessories Only
DVF-BL-42 42" Brick Liner FBF-42BL-2 Black Frame 42" DVFBF-42BR-1 Polished Brass Frame 42" FBF-42BP-2 Black Porcelain Frame 42" FBL-42BR-2 Polished Brass Louvers 42" FBL-42BP-2 Black Porcelain Louvers 42" DVWT-42BR Brass Window Trim 42"
FIREPLACE DIMENSIONS MODEL DVF-36/DVF-42
D
E
B A
FRONT VIEW
H
CORNER CABINET MANTEL, EHM-CU, EHM-CCF, EHM-COF
DIMENSION IS FROM CENTER OF FLUE OUTLET TO INSIDE OF WALL
C
ELECTRICAL ACCESS
I
J
TOP VIEW
Figure 1
F
RIGHT SIDE VIEW
VENT COLLAR
L
K
DIM
A
99cm
G
36"
B
91cm
22"
C
559mm
39"
D
99cm
36 1/4"
E
92cm
21"
F
533mm
31 1/2"
G
800mm
4 3/4"
H
121mm
27 3/4"
I
705mm
13 7/8"
J
352mm
15 1/2"
K
394mm
3 11/16"
L
94mm
DVF-42DVF-36
45"39"
114cm
42"
107cm
24"
610mm
41"
104cm
38 1/4"
97cm
24"
610mm
33 1/2"
851mm
4 3/4"
121mm
32"
813mm
16"
406mm
N/A
N/A
N/A
N/A
Page 5
Installation of Upper Clearance Spacer for Vertical Vent (Figure 2)
Included with every fireplace is the upper clearance spacer. The upper clearance spacer must be attached to the top of the firebox before installation of fireplace in a vertical vent configuration.
1. Remove screw in firebox top that is behind 1/4" flange on vent cover plate and directly in front of adapter pipe.
2. Place the notched portion of upper clearance spacer facing the 1/4" flange on vent cover plate.
3. Flex firebox top and slide upper clearance spacer beneath vent cover plate.
4. Attach upper clearance spacer to firebox top with screw from Step
1.
5. Installation of upper clearance spacer is completed.
The upper clearance spacer will prevent combustible material from contacting adapter pipe.
VENT COVER
PLATE
R-5627 Page 5
Page 6
Introduction
This direct vent gas fireplace is designed to operate with all combustion air being siphoned from the outside of the building and all exhaust gases expelled to the outside of the building. The information contained in this manual pertains to all models and gas control systems unless otherwise noted.
Warning: This unit is not for use with solid fuel.
Approval Listings and Codes Appliance Certification
This fireplace is design certified in accordance with American National Standard/CSA Standard Z.21.88-1998/CSA 2.33-M98 and Z21.50b­1998/CSA 2.22b-M98 by UL/CUL Laboratories as a Direct Vent Gas Fireplace Heater/Direct Vent Gas Fireplace and should be installed according to these instructions.
Consult your local building code agency, prior to installation, to ensure compliance with local codes-including permits and inspections.
The fireplace, when installed, must be electrically grounded in accordance with local codes or, in absence of local codes, with the National Electric Code ANSI/NFPA 70 or Canadian Electric code, CSA C22.1, if an external electrical source is utilized.
These models may be installed in a bedroom or bed-sitting room in the U.S.A. and Canada.
Qualified Installing Agency
Installation and replacement of gas piping, gas utilization equipment or accessories and repair and servicing of equipment shall be performed only by a qualified agency. The term "qualified agency" means any individual, firm, corporation or company which either in person or through a representative is engaged in and is responsible for (a) the installation or replacement of gas piping or (b) the connection, installation, repair or servicing of equipment, who is experienced in such work, familiar with all precautions required and has complied with all the requirements of the authority having jurisdiction.
The installation must conform with local codes or, in the absence of local codes, with the National Fuel Gas Code, ANSI Z223.1 */ Canadian
Installation Code,CAN/CGA-B149. *Available from the American National Standards Institute, Inc. 11 West 42nd St., New York, N.Y. 10036.
Instructions to Installer
1. Installer must leave instruction manual with owner after installation.
2. Installer must have owner fill out and mail warranty card supplied with the fireplace.
3. Installer should show owner how to start and operate the fireplace.
WARNING: ANY CHANGE TO THIS FIREPLACE OR ITS CONTROLS CAN BE DANGEROUS.
Improper installation or use of the heater can cause serious injury or death from fire, burns, explosion or carbon monoxide poisoning.
Aftermarket Manufactured (Mobile) Home Installation
This fireplace may be installed in an aftermarket* manufactured (mobile) home, where not prohibited by state or local codes.
*Aftermarket: Completion of sale, not for purpose of resale, from the
manufacturer.
This fireplace is only for use with the type of gas indicated on the rating plate.
Installation in Residential Garages
Gas utilization equipment in residential garages shall be installed so that all burners and burner ignition devices are located not less than 18" (457mm) above the floor.
Such equipment shall be located, or protected, so it is not subject to physical damage by a moving vehicle.
High Altitude
When installing this unit at an elevation above 2000 feet (in the United States) it may be necessary to decrease the input rating by changing the existing burner orifice to a smaller size. Generally, input should be reduced 4 percent for each 1000 feet above sea level. However, if the heating value of the gas has been reduced, this general rule may not apply. Check with local gas utility for proper orifice size identification.
Canadian High Altitude
Altitude: 0-4500 feet (0-1370 m) APPLIES TO CANADIAN MODELS ONLY
When installing this unit at an elevation above 4500 feet (in Canada), check with local authorities.
Consult your local gas utility for assistance in determining the proper orifice for location.
Preparation
This direct vent gas fireplace and its components are tested and safe when installed in accordance with this Installation Manual. Report to your dealer any parts damaged in shipment, specifically check glass condition. Do not install unit with damaged, incomplete, or substitute parts. The vent system components and trim doors are shipped in separate packages. Read all instructions before starting installation and follow these instructions carefully during installation to insure maximum benefit and safety. Failure to follow them will void your warranty and may present a fire hazard.
The warranty will be voided by, and the warranter disclaims any responsibility for the following actions:
• Installation of any damaged fireplace or vent system component.
• Modification of the fireplace or direct vent system.
• Installation other than as instructed by Empire Comfort System, Inc.
• Improper positioning of the gas logs, glass door or lava rock.
• Installation and/or use of any component part not manufactured or approved by manufacturer.
Any alteration of the original design, installed other than as shown in these instructions or use with a type of gas not shown on the rating plate is the responsibility of the person and company making the change.
Important
All correspondence should refer to complete Model No., Serial No. and type of gas.
Page 6 R-5627
Page 7
1/2 FLEX TUBING
1/2 NPT
1/2 NPT NIPPLE
1/2 NPT UNION
1/2 NPT X 1/2 FLARE FITTING
TEE HANDLE
1/2 NPT CLOSE NIPPLE
TEE HANDLE
1/2 NPT GAS SUPPLY
1/2 NPT X 1/2 FLARE SHUT OFF VALV E
1/2 NPT SHUT OFF VALV E
RIGID GAS LINE CONNECTION
FLEXIBLE GAS LINE CONNECTION
1/2 NPT GAS SUPPLY
2" x 4" HEADER
STAND OFF 3" (76mm) HEIGHT
GLASS FRONT
FINISHED WALL
SEE MANTLE CHART
FOR MAXIMUM MANTLE
SEE MANTLE CHART
FOR MINIMUM HEIGHT OF MANTLE ABOVE UNIT
CLEARANCE TO COMBUSTIBLES
BACK 0" (0 mm)
SIDE 0" (0 mm)
FLOOR 0” (O mm)
TOP STAND OFF 0" (0 mm)
TOP FRAMING LEDGE 0" (0 mm)
Planning Your Installation
Locating Your Direct Vent Gas Fireplace (Figure 5)
Figure 5
Note:** Island (C) and Room Divider (D) installation is possible as long as the horizontal portion of the vent system (H) does not exceed 20 feet with a minimum vertical run of 8 feet. See details in Venting Section. *When you install your Direct Vent Fireplace in (D) Room divider or (E) Flat on wall corner positions, a minimum of 6 inches clearance must be maintained from the perpendicular wall and the front edge of the appliance.
Clearance to Combustibles (Figure 6)
CLEARANCE TO COMBUSTIBLES
BACK SPACER
BACK 0" (0 mm)
SIDE SPACER
SIDE 0" (0 mm)
FLOOR 0” (O mm)
TOP STAND OFF 0" (0 mm)
TOP FRAMING LEDGE 0" (0 mm)
SEE MANTLE CHART FOR MAXIMUM MANTLE DEPTH
SEE MANTLE CHART
FOR MINIMUM HEIGHT OF MANTLE ABOVE UNIT
FINISHED WALL
TOP FRAMING
LEDGE
GLASS FRONT
2" x 4" HEADER
STAND OFF 3" (76mm) HEIGHT ABOVE TOP OF FIREPLACE
ADJUSTABLE NAILING FLANGES
Gas Line Installation (Figure 7)
The gas pipeline can be brought in through the right or left side of the appliance. Consult the current National Fuel Gas Code, ANSI Z223.1 CAN/CGA-B149 (.1 or .2) installation code.
Recommended Gas Pipe Diameter
Pipe Length Schedule 40 Pipe Tubing, Type L
(Feet) Inside Diameter Outside Diameter
Nat. L.P. Nat. L.P.
0-10 1/2" 3/8" 1/2" 3/8"
1.3 cm 1.0 cm 1.3 cm 1.0 cm
10-40 1/2" 1/2" 5/8" 1/2"
1.3 cm 1.3 cm 1.6 cm 1.3 cm
40-100 1/2" 1/2" 3/4" 1/2"
1.3 cm 1.3 cm 1.9 cm 1.3 cm
100-150 3/4" 1/2" 7/8" 3/4"
1.9 cm 1.3 cm 2.2 cm 1.9 cm
Note: Never use plastic pipe. Check to confirm whether your local codes allow copper tubing or galvanized.
Note: Since some municipalities have additional local codes, it is always best to consult your local authority and installation code.
The use of the following gas connectors is recommended: — ANS Z21.24 Appliance Connectors of Corrugated Metal Tubing
and Fittings
— ANS Z21.45 Assembled Flexible Appliance Connectors of Other
Than All-Metal Construction
The above connectors may be used if acceptable by the authority having jurisdiction. The State of Massachusetts requires that a flexible appliance connector cannot exceed three feet in length.
FLEXIBLE GAS LINE CONNECTION
1/2 NPT GAS SUPPLY
TEE HANDLE
1/2 NPT X 1/2 FLARE SHUT OFF VALVE
RIGID GAS LINE CONNECTION
1/2 NPT CLOSE NIPPLE
TEE HANDLE
1/2 FLEX TUBING
1/2 NPT NIPPLE
1/2 NPT NIPPLE
1/2 NPT X 1/2 FLARE FITTING
R-5627 Page 7
Figure 6
1/2 NPT SHUT OFF VALVE
1/2 NPT GAS SUPPLY
1/2 NPT UNION
Figure 7
Page 8
VENTING RUNS
VERTICAL DIMENSION
FROM THE
BOTTOM
OF THE
UNIT
TO THE
CENTER
OF THE
HORIZONTAL PIPE
SIDEWALL VENTING GRAPH
()(DIMENSIONS
IN FEET)
To Use the Vent Graph (Figure 8)
1. Determine the height of the center of the horizontal vent pipe. Using this dimension on the Sidewall Vent Graph, locate the point it intersects with the slanted graph line.
2. From the point of this intersection, draw a vertical line to the bottom of the graph.
3. Select the indicated dimension, and position the unit in accordance with same.
EXAMPLE A:
If the vertical dimension from the floor of the unit is 22.5 feet, the horizontal run to the outer wall flange must not exceed 6.5 feet.
EXAMPLE B:
If the vertical dimension from the floor of the unit is 6.5 feet, the horizontal run to the outer wall flange must not exceed 14.5 feet.
SPECIAL NOTE: For each 45 degree elbow installed in the horizontal run, the length of the horizontal run MUST be reduced by 18" (45cm). This does not apply if the 45 degree elbows are installed on the vertical part of the vent system.
Example: According to the chart the maximum horizontal vent length is 20' and if two 45 degree elbows are required in the horizontal vent it must be reduced to 17'.
The maximum number of 45 degree elbows permitted per side wall installation is two (2). These elbows can be installed in either the vertical or horizontal run.
Venting Graph (Dimensions in Feet)
Installation
Framing and Finishing (Figure 9)
1. Choose unit location.
2. Frame in fireplace with a header across the top. It is important to allow for finished face when setting the depth of the frame.
3. Attach fireplace to frame using adjustable frame. Preset depth to suit facing material (adjustable to 1/2", 5/8" or 3/4" depths).
4. Use (8) 1/2" hex-head screws supplied in hardware package, to screw through slotted holes in drywall strip and then screw into pre-drilled holes on fireplace side. Measure from face of fireplace to face of drywall strip to determine final depth. (See Figure 9)
VERTICAL DIMENSION FROM THE BOTTOM OF THE UNIT
TO THE CENTER OF THE HORIZONTAL PIPE
25
24
23
22
21
20
19
18
17
16
15
14
13
12
11
10
9
8
7
6
5
4
3
A
Figure 9
Attention: When DVF is installed in optional full cabinet mantel or
corner mantel the (4) four nailing flanges shown in Figure 6 will not be installed on the side of outer casing. The DVF will be attached to the full cabinet mantel or corner mantel with the (2) two nailing flanges located on the top of the outer casing assembly.
B
8
76543
20181716 1915141311109 12
HORIZONTAL RUN
Figure 8
Acceptable vertical and horizontal vent run. Unacceptable vertical and horizontal vent run.
Page 8 R-5627
Page 9
Mantel Chart (Figure 11)
4" (102mm)
2 1/2"(64mm)
10 1/2"
TOP EDGE OF FIREPLACE
11 1/4"
9 3/4"
6" (152mm)
10" (254mm)
8" (203mm)
12" (305mm)
12 3/4"
12" (305mm)
MANTEL
10" (254mm)
12 3/4"
(324mm)
12"
(305mm)
11 1/4"
(286mm)
10 1/2"
(267mm)
9 3/4"
(248mm)
8" (203mm)
6" (152mm)
4" (102mm)
2 1/2"(64mm)
9"
(229mm)
TOP EDGE OF FIREPLACE
Figure 11
Combustible Material (Figure 12)
No greeting cards, stockings or ornamentation of any type should be placed on or attached to the fireplace. The flow of heat can ignite combustibles.
R-5627 Page 9
Page 10
Finishing (Figure 13)
FINISHED WALL
2 X 4
STAND OFF
FRONT TRIM OR NON-COMBUSTIBLE MATERIAL (INSTALLATION IS OPTIONAL)
JOINT BETWEEN FINISHED WALL AND UNIT SEALED WITH 300°F, 149°C SEALANT
Finish the walls with the material of your choice. Figure 11 shows the minimum vertical and corresponding maximum horizontal dimensions of mantels or other combustible projections above the top front edge of the fireplace.
Only non-combustible materials may be used to cover the black fireplace front.
WARNING: When finishing the fireplace never obstruct or modify the air inlet/outlet louvers in any manner. Provide adequate clearances around air openings into the combustion chamber.
Caution: If the joints between the finished wall and the fireplace surround (top and sides) are sealed, a 300
°F minimum sealant
material must be used. These joints are not required to be sealed. Only non-combustible material (using 300 needed), can be applied as facing to the fireplace surround
°F minimum adhesive if
.
2X4 HEADER
STAND OFF
FINISHED WALL
FRONT TRIM OR NON-COMBUSTIBLE MATERIAL (INSTALLATION IS OPTIONAL)
JOINT BETWEEN FINISHED WALL AND UNIT SEALED WITH 300°F, 149°C SEALANT MATERIAL
Page 10 R-5627
Page 11
VERTICAL, 90° ELBOW TO HORIZONTAL OUT THE WALL
275mm TO 344mm
240mm TO 268mm
356mm TO 421mm
14" TO 16 9/16"
10 13/16" TO 13 9/16"
9 7/16" TO 10 9/16"
14 3/4"
39 5/8"
55 7/8"
79 1/4"
69 1/8"
13 1/4"
34 1/2"
48 5/8"
WALL FIRESTOP
194mm TO 270mm194mm TO 270mm
102mm TO 191mm102mm TO
191mm
7 5/8"" TO 10 5/8"7
5/8"" TO 10 5/8"
4" TO 7 1/2"4" TO
7 1/2"
"B"
WALL FIRESTOP
9 7/16" TO 10 9/16"
240mm TO 268mm
10 13/16" TO 13 9/16"
275mm TO 344mm
14" TO 16 9/16"
356mm TO 421mm
CORNER INSTALLATION HORIZONTAL, 45° ELBOW TO
HORIZONTAL OUT THE WALL
Figure 18
CORNER INSTALLATION VERTICAL, 90° ELBOW TO
DIM
"A"
"B"
"C"
"D"
DVF-36
48 5/8" 124cm
34 1/2"
88cm
13 1/4"
337mm
69 1/8" 176cm
Figure 16
HORIZONTAL OUT THE WALL
"A"
"B"
"C"
DVF-42
55 7/8" 142cm
39 5/8" 101cm
14 3/4"
375mm
79 1/4" 201cm
"D"
Figure 17
WALL
FIRESTOP
Vertical Sidewall Application (Figures 19 and 20)
Figure 19
R-5627 Page 11
Page 12
Figure 20 and Chart 1 lists examples of possible venting systems using
SEE CHART FOR PERMISSIBLE "H" AND "V" DIMENSIONS
one (1) 90° elbow. Eight (8) feet is listed as maximum vertical vent run with 20 feet of maximum horizontal vent run. Vertical dimensions are based on centerline to centerline of pipe. Horizontal dimensions are based on centerline of pipe to end of termination.
SEE CHART FOR PERMISSIBLE "H" AND "V" DIMENSIONS
NOTE: H1 AND H2 MUST BE ADDED TOGETHER TO USE CHART
SEE CHART FOR PERMISSIBLE "H" AND "V" DIMENSIONS
Figure 20
CHART 1 (Figures 21, 22 and 23) Venting with One (1) 90
Total Vertical Total Horizontal
(With Fire Box) V H1 or H1 + H
° Elbow or Two (2) 90° Elbows
2
4.5' minimum 3' maximum
4.5' minimum 4' maximum 5' minimum 8' maximum 6' minimum 12' maximum 7' minimum 15' maximum 8' minimum 20' maximum
25' maximum vertical 20' maximum horizontal run
Figure 21 and Chart 1 list examples of possible venting systems using two (2) 90° elbows. V is listed as minimum vertical dimensions and H1 + H2 is listed as total of maximum horizontal dimensions. The maximum vertical and horizontal distances for two (2) 90° elbows as shown in Figure 21 are 20 feet.
Attention: Refer to Figure 8 for additional venting requirements.
Page 12 R-5627
Page 13
Positioning the Fireplace
(914 mm)
20' (6.1 M)
8' (244 cm)
TO BOTTOM
OF UNIT
PIPE STRAPS EVERY 3' (91cm)
Determine the exact position of the appliance so the direct vent termination will be centered (if possible) between two (2) studs. This will avoid any extra framing. All vent kit pipes should be assembled on the unit after the unit is moved into the final position.
Cutting the Hole (Figures 23 and 24)
After the fireplace has been positioned in its permanent location, the hole through the exterior wall of the house can be cut. This hole needs to be 12 3/8" high x 10 3/8" width rectangle with its center line determined by the amount of vertical arise and horizontal run of the termination. (See Figure
22) When locating the hole it must be noted that the bottom of the cap must be 12" above the ground level, and top of the cap must be no less than 18" below a combustible projection, and no closer than 9" to any wall running
parallel to vent termination. (See Figure 23)
Service Notes
MAXIMUM HORIZONTAL RUN WITH NO VERTICAL
MAX.
RISE AND 90° ELBOW
MAXIMUM HORIZONTAL RUN WITH MINIMUM
MAX.
VERTICAL RISE AND 90° ELBOW
Figure 23
3'
(914 mm)
20' (6.1 M)
PIPE STRAPS EVERY 3' (91cm)
8' (244 cm)
TO BOTTOM
OF UNIT
Figure 24
R-5627 Page 13
Page 14
Termination Clearances (Figure 25)
Termination clearance for buildings with combustible and noncombustible exteriors.
Figure 25
Vertical Sidewall Installations
Important! Minimum clearance between vent pipes and combustible materials is three (3") (76mm) on top, and (1") (25mm) on bottom and sides.
Important! When vent termination exits through foundation less than 20" below siding outcrop, the vent pipe must flush up with the siding. SD-1284 termination cap must also be used.
Information on Various Venting Routes and Components Important: It is always best to locate the fireplace in such a way that minimizes the number of offsets and horizontal vent length.
Since it is very important that the venting system maintain its balance between the combustion air intake and the flue gas exhaust, certain limitations as to vent configurations apply and must be strictly adhered to.
The graph showing the relationship between vertical and horizontal side wall venting will help to determine the various vent lengths allowable.
The horizontal vent run refers to the total length of vent pipe from the flue collar of the fireplace to the face of the outer wall. The maximum horizontal vent run is 20 feet (457 cm) when the vertical vent rise is 8 feet (244 cm) (See Figure 24) Venting terminals shall not be recessed into wall or siding.
Page 14 R-5627
Page 15
Figure 26
R-5627 Page 15
Page 16
Installing Vent Components (Figure 27)
Begin the vent system installation by installing the first component, 90° elbow to the starting collars or straight pipe on the top of the appliance, then the straight pipe length and then horizontal or vertical termination kit.
NOTE: All 8 inch outer connection joints must be sealed with aluminum tape or silicone sealant rated above 300 inch inner flue joints do not require any sealant.
All vent system components lock into place by sliding the concentric pipe section with four (4) equally spaced interior beads onto the appliance collar or previously installed component end with four (4) equally spaced indented sections. When the internal beads of each starting 8 inch outer pipe line up, rotate pipe section clockwise 90° (approximately 3 inches). The vent pipe is now locked together.
°F/149°C. The 5
Continue adding components per the pre-planned vent system configuration. Be certain that each succeeding vent component is securely fitted and locked into the preceding component in the vent system.
Installing Support Brackets (Figure 28)
A horizontal pipe support MUST BE used for each 3 feet of horizontal run. The pipe supports should be placed around 8 inch diameter pipe and nailed in place to framing members. There MUST BE a 3 inch clearance to combustibles above 8 inch diameter pipe and elbows and 1 inch clearance on both sides and bottom of 8 inch to combustibles on all horizontal pipe sections and elbows.
Vertical runs of this vent systems must be supported every 4 feet above the appliance flue outlet by wall brackets attached to the 8 inch vent pipe and secured with nails or screws to structural framing members.
Figure 27
Page 16 R-5627
Page 17
STUD WALL
FLUE OUTLET
PIPE STRAP
PIPE STRAP
1" MIN.
HOLE IS OFF-SET TOWARDS BOTTOM OF WALL OPENING.
12 3/8
10 3/8
10
1/2"
10 1/2"
267mm
CEILING BELOW
NEW FRAMING
EXISTING CEILING JOISTS
10
1/2"
CEILING FIRESTOP
NAILS, 4 REQUIRED
10
1/2"
CEILING FIRESTOP
10
1/2"
10
1/2"
NAILS, 4 REQUIRED92 98.774 11F725.751 168.1054650.476 163m4608189 l424.622.61569315 182.0822.615689 m319.38 335.294 l546.475 33.7.948 m346.4 10659.10l41645 4 173.189 5 139.1079 885464 l43583 l4l5.245 c36.380 179.245 c36.3352 71.245 c3457 m467.838 358331 60.262 35.7122 75.245 c36.380 179.245 c36.3352 71.245 c3457 m467.838 358331 60.262 35.7122 75.0.2679 495 58 62.948679 42.292 35.29.3834.1772 62.94859 42.65 167.29.383432 34 62.94859 4.7769 132.Q4
48"
(1219mm)
STUD WALL
1" MIN.
(25.4mm)
FLUE OUTLET
Figure 28
Installing Firestops (Figures 29, 30, 31 and 32)
Firestops are required for safety whenever the vent system passes through an interior wall, an exterior wall, or a ceiling. These firestops act as a firebreak heat shield and as a means to insure that minimum clearances are maintained to the vent system.
Cut a 10-3/8 inch x 12-3/8 inch hole in wall. Position firestop (SD-1249) on interior side of wall for 10-3/8 inch x 12-3/8 inch hole. Attention: Wall firestop hole is off-set towards bottom of wall opening. Secure with nails or screws. Continue the vent run through the firestop. (See Figure 29)
Cut a 10-1/2 inch x 10-1/2 inch hole through the ceiling, using the center point previously marked. Frame the hole with framing lumber the same size as the ceiling joists. (See Figure 30) If the area above the ceiling is NOT an attic, position and secure the ceiling firestop (SD-1263) on the ceiling side of the previously cut and framed hole. (See Figure 31) If the area above the ceiling is an attic, position and secure the firestop on top of the previously framed hole. (See Figure 32)
NOTE: Remove insulation from the framed area in the attic before installing the firestop and/or vent pipe.
EXISTING CEILING JOISTS
NEW FRAMING
10 1/2"
m
267m
1/2"
10 267mm
CEILING BELOW
Figure 30
10 1/2" 267mm
10 1/2" 267mm
Vertical runs of this system which pass through ceilings require the use of ONE (1) ceiling firestop at the hole in each ceiling through which the vent passes.
Position a plumb bob directly over the center of the vertical vent component and mark the ceiling to establish the center point of the vent. Drill a hole or drive a nail through this center point and check the floor above for any obstructions such as wiring or plumbing runs. Reposition the fireplace and vent system, if necessary, to accommodate ceiling joists and/or obstructions.
R-5627 Page 17
10 3/8
12 3/8
WALL FIRESTOP HOLE IS OFF-SET TOWARDS BOTTOM OF WALL OPENING.
Figure 29
CEILING FIRESTOP
Figure 31
NAILS, 4 REQUIRED
NAILS, 4 REQUIRED
CEILING FIRESTOP
10 1/2"
267mm
10 1/2" 267mm
Page 18
Horizontal Terminations (Figure 33) NOTE: Termination cap should pass through the wall firestop from
the exterior of the building. Adjust the termination cap to its final exterior position on the building.
WARNING: Termination cap must be positioned so that arrow is pointing up.
Attach the termination cap with the four wood screws provided. Before attachment of the termination, run a bead of silicone sealant rated above 250°F on its outside edge too, so as to make a seal to the exterior wall.
NOTE: Wood screws can and should be replaced with appropriate
fasteners for use on stucco, brick, concrete or other types of siding.
CAUTION: If exterior walls are finished with vinyl siding, it is necessary to install the vinyl siding shield (SD-1250).
Vinyl siding shield (SD-1250) will be installed between the vent termination and the exterior wall. (See Figure 33) This horizontal vent termination bolts onto the flat portion of the vinyl siding standoff, so an air space will exist between the wall and the termination cap.
Determining Minimum Vent Height Above the Roof. WARNING: Major U.S. building codes specify minimum chimney
and/or vent height above the roof top. These minimum heights are necessary in the interest of safety. These specifications are summa­rized in Figure 34.
Figure 33
Vertical Terminations (Figures 34 and 35)
Locate and mark the center point of the venting pipe. Using a nail on the underside of the roof and drive this nail through this center point. Make the outline of the roof hole around this center point.
NOTE: Size of the roof hole dimensions depend on the pitch of the
roof. There must be a 1 inch clearance (25mm) to the vertical pipe sections. This clearance is to all combustible material.
Cover the opening of the vent pipe and cut and frame the roof hole. Use framing lumber the same size as the roof rafters and install the frame securely. Flashing anchored to frame must withstand high winds. The storm collar is placed over this joint to make a water-tight seal. Non­hardening sealant should be used to completely seal this flashing installation.
Page 18 R-5627
Page 19
Installing the Vent System in a Chase
A chase is a vertical box like structure built to enclose the gas appliance and/or it's vent system. Vertical vent runs on the outside of a building may be, but are not required to be installed inside a chase.
Figure 36
Figure 35
CAUTION: Treatment of firestop spacers and construction of the chase may vary with the type of building. These instructions are not substitutes for the requirements of local building codes. Therefore, your local building codes must be checked to determine the requirements for these steps.
NOTE: When installing this vent system in a chase, it is always good
building practice to insulate the chase as you would the outside walls of your home. This is especially important for cold climate installations. Upon completion of building your chase framing, install the vent system by following the instructions in this manual. Remember to build the chase large enough so that minimum clearance of combustible materials (including insulation) to the vent system are maintained.
Reassembly and Resealing Vent Pipe System
Attach adapter pipe to vent cover in either the vertical or horizontal position, replace horizontal and vertical pipe lengths, elbows and horizontal or vertical termination kit.
All vent system components lock into place by sliding the concentric pipe section with four (4) equally spaced interior beads onto the appliance collar or previously installed component end with four (4) equally spaced indented sections. When the internal beads of each starting 6-5/8 inch outer pipe line up, rotate pipe section clockwise 90° (approximately 3 inches). The vent pipe is now locked together.
Continue replacing components per the vent system configuration. Be certain that each succeeding vent component is securely fitted and locked into the preceding component in the vent system.
Vertical Through the Roof Applications (Figure 36)
Your Gas Fireplace has been approved for: a) Vertical installations up to 25 feet in height. b) Two sets of 45 degree elbow offsets within these vertical installations.
From 0 to a maximum of 8 ft. a vent pipe can be used between elbows.
c) Wall straps must be used to support offset pipe every 4'. This applications will require that you first determine the roof pitch and
use the appropriate venting components.
Leak Testing Gas Line
Consult the current National Fuel Gas Code, ANSI Z223.1 CAN/CGA­B149 (.1 or .2) installation code.
Compounds used on threaded joints of gas piping shall be resistant to the action of liquefied petroleum gases. The gas lines must be checked for leaks by the installer. This should be done with a soap solution watching for bubbles on all exposed connections, and if unexposed, a pressure test should be made.
Never use an exposed flame to check for leaks. Appliance must be disconnected from piping at inlet of control valve and pipe capped or plugged for pressure test. Never pressure test with appliance connected; control valve will sustain damage!
NOTE: The gas control is equipped with a captured screw type pressure
test point, therefore it is not necessary to provide a 1/8" test point up stream of the control.
A gas valve and ground joint union should be installed in the gas line upstream of the gas control to aid in servicing. It is required by the National Fuel Gas Code that a drip line be installed near the gas inlet. This should consist of a vertical length of pipe tee connected into the gas line that is capped on the bottom in which condensation and foreign particles may collect.
When using copper or flex connector use only approved fittings. Always provide a union so that gas line can be easily disconnected for burner or fan servicing. See gas specification for pressure details and ratings.
The appliance and it's individual shut off valve must be disconnected from supply piping system during any pressure testing of that system at test pressures in excess of 1/2 psig (3.5kPa).
The appliance must be isolated from the gas supply piping system by closing its individual manual shut off valve during any pressure testing of the gas supply piping system at test pressures equal to or less than 1/ 2 psig (3.5kPa).
Attention! If one of the procedures results in pressures in excess of 1/2 psig (14" w.c.) (3.5 kPa) on the fireplace gas valve, it will result in a hazardous condition
.
R-5627 Page 19
Page 20
Figure 37
Initial Set-Up and Operation
Before you begin: This unit is supplied with a set of four ceramic fiber logs. Do not handle these logs with your bare hands! Always wear gloves to prevent skin irritation from ceramic fibers. After handling logs, wash your hands gently with soap and water to remove any traces of fibers.
Every burner is shipped with a protective cover. This cover must be re­moved before log placement.
The positioning of the logs is critical to the safe and clean operation of this heater. Sooting and other problems may result if the logs are not properly and firmly positioned in the appliance.
Glass Removal
1. Push up and outward to remove top louver.
2. Lower door assembly.
3. Release two door latches at bottom of firebox.
4. Grasp bottom of glass frame, lift glass frame upward in order to release glass frame from lip on top of firebox.
2
1
Figure 38
Placement of Glowing Embers (Rock Wool) (Figure 39)
Provided with the log set is a small bag of glowing embers (rock wool) to be placed between logs on the flat metal surface of the burner.
TOP VIEW OF LOG SET
REAR LOG
4
3
Log Placement
Proper Installation Sequence (Figure 38)
1. Install the front log (#1) in front of the grate. The log is located into a
notch area in the front grate area.
2. Install the back log (#4) behind the pilot assembly directly on the
pins on each side of the rear log shield.
3. The right middle log (#3) will go directly on the two pins on the right
side of the flat portion of the burner.
4. The left middle log (#2) should be placed flat on the pin on the left
side of the flat portion of the burner. The left middle log will rest on a pin located on the right middle log.
Refer to Figure 38 for the following warning.
Warning: Failure to position the parts in accordance with this
diagram or failure to use only parts specifically approved with this appliance may result in property damage or personal injury.
Placement of glowing embers.
Figure 39
Placement of the glowing embers (rock wool) is very individual and light coverage of the areas indicated will provide your best effects. We recommend separation of the rock wool by hand and make your coverage as light and fluffy as possible.
Place just enough rock wool on the burner to obtain the glow and a gold yellow flame.
Do not place rock wool over large ports in rear portion of burner. A thin layer of glowing embers (rock wool) should be placed under open
space between the right and left middle logs. Rock wool should not be placed in the area of the pilot assembly.
Page 20 R-5627
Page 21
Placing Lava (Decorative) Rock in Front of Grate and Burner Pan
PIEZO IGNITOR
VALV E CONTROL KNOB
VARIABLE REGULATOR ("HI"-"LO") KNOB
REMOTE/ON/OFF SWITCH
DOOR ASSEMBLY (SHOWN OPEN)
GAS VALV E
on Fireplace Floor
Spread lava rocks on fireplace floor in front of grate. The rocks are for decorative effect and are not required for fireplace operation.
Attention: Do not place lava rocks on logs, branches or rock wool. The lava rocks should only be placed on the fireplace floor.
Glass Replacement
1. Align and place top of glass frame over lip on top of firebox.
2. Grasp bottom of glass frame, push inward and place glass frame onto firebox.
3. Attach two door latches onto bottom of glass frame.
4. Align and insert (4) mounting tabs on top louver with (4) slots casing top. Push downward to lock the top louver into position.
Checking Manifold Pressures
Both Propane and Natural gas valves have a built-in pressure regulator in the gas valve. Natural gas models will have a manifold pressure of approximately 3.5" w.c. (.871kPa) at the valve outlet with the inlet pressure to the valve from a minimum of 4.5" w.c. (1.120kPa) for the purpose of input adjustment to a maximum of 10.5" w.c. (2.615kPa). Propane gas models will have a manifold pressure approximately 10.0" w.c. (2.49kPa) at the valve outlet with the inlet pressure to the valve from a minimum of 11.0" w.c. (2.739kPa) for the purpose of input adjustment to a maximum of 13.0" w.c. (3.237kPa).
FLAME APPEARANCE
Flames from the pilot (rear right back side of the pan burner) as well as the main flame should be visually checked as the log set is installed.
In normal operation at full rate after 10 to 15 minutes, the flame appear­ance should be sets of yellow flames.
NOTE: Flames will be random by design, flame height will go up and down.
Glowing embers (rock wool) can cover the pan burner in between the front and middle logs, but very little is necessary to cover this area. Ex­cess rock wool material causes the yellow flame to become orange and stringy. Apply just enough to obtain slow glow and a bright yellow flame.
During manufacturing, fabricating and shipping, various components of this appliance are treated with certain oils, films or bonding agents. These chemicals are not harmful, but may produce annoying smoke and smells as they are burned off during the initial operation of the appliance, possibly causing headaches or eye or lung irritation. This is a normal and temporary occurrence.
The initial break-in operation should last 2-3 hours with the burner at the highest setting. Provide maximum ventilation by opening windows or doors to allow odors to dissipate. Any odors remaining after this initial break-in will be slight and will disappear with continued use.
Standing Pilot Operating Instructions
The standing pilot (750 millivolt system) is a continuous burning pilot. The pilot remains ON even when the main burner is OFF.
750 Millivolt System (Figures 40 and 41)
When you ignite the pilot, the thermocouple produces millivolts (electrical current) which energizes the magnet in the gas valve. After 30 seconds to 1 minute time period you can release the gas control knob and the pilot will stay ON. Allow your pilot flame to operate an additional one (1) to two (2) minutes before you turn the gas control knob from the PILOT position to the ON position. This time period allows the millivolts (electrical current) to build-up to a sufficient level allowing the gas control to operate properly.
1. Follow the SAFETY and LIGHTING INSTRUCTIONS for standing
pilot controls found in this manual and on labels found in control compartment behind the door assembly.
CAUTION: During the initial purging and subsequent lightings, never allow the gas valve control knob to remain depressed in the "pilot" position without pushing the red ignitor button at least once every second.
2. During the heating season, leave the control valve knob in the "ON" position. This will allow the pilot flame to remain lit. Turn the burner flame on or off with the fireplace ON/OFF rocker switch, wall switch, remote control kit or 750 millivolt wall thermostat.
NOTE: The gas control valve allows you to increase or decrease the height of the main burner flame. The control valve has a pressure regulator with a knob as shown in Figure 40. Rotate the knob clockwise to "HI" to increase the flame height and counterclockwise to "LO" to decrease the flame height.
3. When the heating season is over, turn the on/off switch to "OFF" and the control valve to "OFF". The system, including the pilot light, will be shut down.
PIEZO IGNITOR
HI/LO REGULATOR
CONTROL KNOB
The OWNER should carefully read and follow these operating instructions at all times. Lower the door assembly to view the gas controls for the fireplace. Your model has a push button piezo ignitor, the fireplace has a STANDING PILOT IGNITION SYSTEM. (See Figure 41) Follow the Safety, Lighting and Operating instructions applicable to your fireplace.
REMOTE/ON/OFF SWITCH
Figure 40
VARIABLE REGULATOR ("HI"-"LO") KNOB
PIEZO IGNITOR
VALVE CONTROL KNOB
GA S VALV E
DOOR ASSEMBLY (SHOWN OPEN)
Figure 41
R-5627 Page 21
Page 22
Initial Lighting
Upon completing the gas line or turning the gas valve on after it has been in the "OFF" position, a small amount of air will be in the lines. When first lighting the fireplace, it will take a few minutes for the lines to purge themselves of this air. Once the purging is complete, the fireplace will light and operate satisfactorily.
Subsequent lightings of the appliance will not require such purging if the gas valve is not turned to "OFF."
Pilot Flame (Figure 42)
The thermopile/thermocouple (standing pilot) tips should be covered with flame.
Figure 42
Attention: Only, after the fireplace has been converted to a heater can the 750 millivolt wall thermostat, GWSG-T or battery operated remote control with thermostat, FRBTC-1 be used. See installation of heater baffle on Page 5.
OPERATING INSTRUCTIONS ON/OFF/REMOTE Switch
DVF is equipped with an ON/OFF/REMOTE switch. A wire harness is attached to the ON/OFF/REMOTE switch. The red, black and green (wires) female push-ons attach to the ON/OFF/REMOTE switch. At the opposite end of the wire harness, the black and green (wires) female push-ons attach to the gas valve. An additional green wire and the red wire, which are stripped and bare, will attach to the 750 millivolt wall thermostat accessory, or, to one of the other accessories that can be purchased for use with your log set.
Operation of ON/OFF/REMOTE Switch with no Accessories
To ignite main burner, turn the control knob on the gas valve from the PILOT position to the ON position. Turn the ON/OFF/REMOTE switch from the OFF position to the ON position. The additional green wire and red wire, which are stripped and bare are not used.
Operation of ON/OFF/REMOTE Switch with Accessories 750 Millivolt Wall Thermostat, GWSG-T
Connect the green and red, stripped and bare, wires on the ON/OFF/ REMOTE switch wire harness to the wall thermostat. Turn the ON/OFF/ REMOTE switch to the REMOTE position. Set the wall thermostat to the desired temperature.
It is important to use wire of a gauge proper for the length of the wire:
RECOMMENDED WIRE GAUGES
Maximum Wire
Length Gauge
1' to 10' 18 10' to 25' 16 25' to 35' 14
Wall Switch, FWS-1
Connect the green and red, stripped and bare, wires on the ON/OFF/ REMOTE switch wire harness to the wall switch. Turn the ON/OFF/ REMOTE switch to the REMOTE position. Pivot the rocker switch on the FWS-1 to the ON position.
Battery Operated Remote Control, FRBC-1 and FRBTC-1
Connect the green and red, stripped and bare, wires on the ON/OFF/ REMOTE switch wire harness to the remote receiver that is a component in the FRBC-1 and FRBTC-1. Turn the ON/OFF/REMOTE switch to the REMOTE position. Follow instructions in the FRBC-1 and FRBTC­1 to complete installation.
Note: If batteries fail in FRBC-1 or FRBTC-1, and immediate heat is desired, turn the ON/OFF/REMOTE switch from the REMOTE posi­tion to the ON position.
Electric (120 volt) Operated Remote Control, FREC-1
Connect the green and red, stripped and bare, wires on the ON/OFF/ REMOTE switch wire harness to the wires on remote receiver that is a component in the FREC-1. Turn the ON/OFF/REMOTE switch to the REMOTE position. Follow instructions in the FREC-1 to complete installation.
Note: If electric (120 volt) fails in FREC-1, and immediate heat is desired, turn the ON/OFF/REMOTE switch from the REMOTE position to the ON position.
Wiring of ON/OFF/REMOTE Switch with 750 Millivolt Wall Thermostat Accessory and Another Accessory
Connect the green and red, stripped and bare, wires on the ON/OFF/ REMOTE switch wire harness to the 750 millivolt wall thermostat AND to the remote receiver that is a component in the FRBC-1, FREC-1 OR to the FWS-1, wall switch.
1. Connect (1) wire from the 750 millivolt wall thermostat and (1) wire from appropriate accessory to the GREEN, stripped and bare wire from the ON/OFF/REMOTE wire harness.
2. Connect (1) wire from the 750 millivolt wall thermostat and (1) wire from appropriate accessory to the RED, stripped and bare wire from the ON/OFF/REMOTE wire harness. Note: When the appliance is in the MANUAL mode and the batteries fail in the FRBC-1 or if the electric (120 volt) fails in the FREC-1, and immediate heat is desired, turn the ON/OFF/REMOTE switch from the REMOTE position to the ON position.
Manual Operation
1. Turn ON/OFF/REMOTE switch to REMOTE position.
2. Turn wall thermostat OFF.
3. Turn accessory, FRBC-1, FRBTC-1, FREC-1 or FWS-1, ON. Appliance is now in the manual mode. You must turn the appliance ON or OFF with appropriate accessory.
Wall Thermostat Operation
1. Turn the ON/OFF/REMOTE switch to REMOTE position.
2. Turn accessory, FRBC-1, FRBTC-1, FREC-1 or FWS-1, OFF.
3. Turn wall thermostat ON and set appropriate temperature. Wall thermostat will cycle the appliance ON and OFF.
Installation of Remote Receiver
Place remote receiver on the floor of fireplace behind the louver as far forward as possible.
Attention: The velcro loop and hook are not necessary in this installation but can be used to secure remote receiver.
Page 22 R-5627
Page 23
Millivolt Control
The valve regulator controls the burner pressure which should be checked at the pressure test point. Turn captured screw counter clockwise 2 or 3 turns and then place tubing to pressure gauge over test point (Use test point “A” closest to control knob). After taking pressure reading, be sure and turn captured screw clockwise firmly to re-seal. Do not over torque. Check for gas leaks.
Millivolt thermopile is self powered gas valve and does not require 110 volts.
Check System Operation
Millivolt system and all individual components may be checked with a millivolt meter 0-1000 MV range.
Standing Pilot Wiring Diagram (Figure 43)
Figure 43
Reassembly and Resealing Gas Accumulation Relief System (Relief Doors) and Combustion Chamber
Whenever the relief door is pivoted open by a delayed ignition in the main burner, the relief door gaskets and combustion chamber must be examined by a qualified service person for damage. All damaged gaskets on the relief door and combustion chamber must be replaced by a qualified service person. If damage occurs to the combustion chamber, it must be replaced by a qualified service person. Contact Empire Comfort Systems, Inc. for replacement parts.
R-5627 Page 23
Page 24
STANDING PILOT (MILLIVOLT) MODEL
FOR YOUR SAFETY READ BEFORE LIGHTING
WARNING: If you do not follow these instructions exactly, a fire or explosion may result
causing property damage, personal injury or loss of life.
A. This fireplace has a pilot which must be lighted by hand.
When lighting the pilot, follow these instructions ex­actly.
B. BEFORE LIGHTING smell all around the appliance
area for gas. Be sure to smell next to the floor because some gas is heavier than air and will settle on the floor.
WHAT TO DO IF YOU SMELL GAS
• Do not try to light any appliance.
• Do not touch any electrical switch; do not use any phone in your building.
• Immediately call your gas supplier from a neigh­bor's phone. Follow the gas supplier's instructions.
LIGHTING INSTRUCTIONS
1. STOP! Read the safety information above.
2. Set REMOTE/OFF/ON switch to OFF.
3. Turn off all electric power to the fireplace (if appli­cable).
4. Lower louver front assembly.
5. Push in gas control knob slightly and turn clockwise
to "OFF."
PIEZO IGNITOR
HI/LO REGULATOR
CONTROL KNOB
NOTE: Knob cannot be turned from "PILOT" to "OFF"
unless knob is pushed in slightly. Do not force.
6. Wait ten (10) minutes to clear out any gas. Then smell for gas, including near the floor. If you then smell gas, STOP! Follow "B" in the safety information above. If you do not smell gas, go to the next step.
• If you cannot reach your gas supplier, call the fire department.
C. Use only your hand to push in or turn the gas control
knob. Never use tools. If the knob will not push in or turn by hand, don't try to repair it; call a qualified service technician. Force or attempted repair may result in a fire or explosion.
D. Do not use this appliance if any part has been under
water. Immediately call a qualified service techni­cian to inspect the appliance and to replace any part of the control system and any gas control which has been under water.
7. Find pilot — Follow metal tube from gas control. The pilot is behind the second log on the left side.
8. Turn gas control knob counterclockwise to "PILOT."
9. Push in control knob all the way and hold in. Imme­diately light the pilot with the Piezo Pilot Ignitor or use a match. Continue to hold the control knob in the for about one (1) minute after the pilot is lit. Release knob, and it will pop back up. Pilot should remain lit. If it goes out, repeat steps 5 through 9.
• If the control knob does not pop up when released, STOP and IMMEDIATELY call a qualified service technician or gas sup­plier.
• If the pilot will not stay lit after several tries, turn the gas control knob to "OFF" and call your service technician or gas supplier.
10. Turn gas control knob counterclockwise to the "ON."
11. Close louver front assembly.
12. Turn on all electric power to the appliance (if appli­cable).
13. Set REMOTE/OFF/ON switch to REMOTE or ON.
TO TURN OFF GAS TO FIREPLACE
1. Set REMOTE/OFF/ON switch to OFF.
2. Turn off all electric power to the fireplace if service is to be performed (if applicable).
3. Lower louver front assembly.
Page 24 R-5627
4. Push in gas control knob slightly and turn clock­wise to "OFF." Do not force.
5, Close louver front assembly.
Page 25
STANDING PILOT-TROUBLE SHOOTING
With proper installation and maintenance, your new Gas Direct Vent Fireplace should provide years of trouble-free service. If you do experience a problem, refer to the Trouble Shooting Guide below. This guide will assist a qualified service person in the diagnosis of problems and the corrective action to be taken.
1. Spark ignitor will not light pilot after repeated triggering of piezo ignitor button.
a. Defective ignitor (no spark electrode)
—Check for spark at electrode and pilot; if no spark and electrode wire is properly connected, replace ignitor.
b. No gas or low gas pressure.
—Check remote shut off valves from fireplace. Usually there is a valve near the main. There can be more than one (1) valve between the fireplace and main. —Low pressure can be caused by a variety of situations such as a bent line, too narrow diameter of pipe, or low line pressure. Consult with plumber or gas supplier.
c. No LP in tank.
—Check LP (propane) tank. Refill tank.
2. Pilot will not stay lit after carefully following lighting instructions.
a. Defective thermocouple.
—Check that pilot flame impinges on thermocouple. Clean and/ or adjust pilot for maximum flame impingement. —Ensure the thermocouple connection at the gas valve is fully inserted and tight (hand tight plus 1/4 turn). Faulty thermocouple if reading is below specified minimum of 15 millivolts. —Disconnect the thermocouple from the valve, place one millivolt meter lead wire on the end of the thermocouple and the other millivolt meter lead wire on the thermocouple copper wire. Start the pilot and hold the valve knob in. If the millivolt reading is less than 15 millivolt, replace the thermocouple.
b. Defective valve.
—If thermocouple is producing more than 15 millivolts, replace faulty valve.
3. Pilot burning, no gas to burner, valve knob "ON", on/off switch "ON."
a. "On/Off" switch, wall switch, remote control or wires defective.
—Check "on/off" switch and wires for proper connections. Place jumper wires across terminal at switch - if burner comes on, replace defective switch. If OK, place jumper wires across switch wires at gas valve-if burner comes on, wires are faulty or connections are bad.
b. Thermopile may not be generating sufficient millivolts.
—If the pilot flame is not close enough physically to the thermopile, adjust the pilot flame. —Be sure the wire connections from the thermopile at the gas valve terminals are tight and the thermopile is fully inserted into the pilot bracket. —Check the thermopile with a millivolt meter. Take the reading at TH-TP & TP terminals of the gas valve. The meter should read 350 millivolts minimum, while holding the valve knob depressed in the PILOT position, with the pilot lit, and the ON/OFF switch in the OFF position. Replace the faulty thermopile if the reading is below the specified minimum.
c. Cotter pin disconnected from delayed ignition reset switch.
—Refer to page 23 for description of delayed ignition reset switch and replacement of cotter pin into delayed ignition reset
switch.
—With the pilot in the ON position, disconnect the thermopile leads from the valve. Take a reading at the thermopile leads. The reading should be 350 millivolts minimum. Replace the thermopile if the reading is below the minimum.
d. Defective valve.
—Turn valve knob to "ON." Place ON/OFF switch to "ON." Check with millivolt meter at thermopile terminals. Millivolt meter should read greater than 200 millivolts. If the reading is okay and the main burner does not ignite, replace the gas valve.
e. Plugged main burner orifice.
—Check main burner orifice for blockage and remove.
4. Frequent pilot outage problem.
a. Pilot flame may be too high or too low, or blowing (high), causing
pilot safety to drop out. —Clean and adjust flame for maximum flame impingement on the thermocouple. Follow lighting instructions carefully.
5. The pilot and main burner extinguish while in operation.
a. No LP (Propane) in tank. Check LP (Propane) tank. Refill fuel tank. b. Inner vent pipe leaking exhaust gases back into system
—Check for leaks.
c. Glass too loose, gasket leaks in corners after usage.
—Be certain glass assembly is installed correctly and tighten screws.
d. Horizontal vent improperly pitched.
—The horizontal vent cap should slope down only enough to prevent any water from entering the unit. The maximum downwards slope is 1/4 inch.
e. Bad thermopile or thermocouple.
—Replace if necessary.
f. Improper vent cap installation.
—Check for proper installation and freedom from debris or blockage.
6. Glass soots.
a. Flame impingement on logs.
—Contact Empire Comfort Systems, Inc.
b. Debris around throat of main burner.
—Inspect the opening at the base of the main burner. It is imperative that
7. Flame burns blue and lifts off main burner.
a. Insufficient oxygen being supplied.
—Check to make sure vent cap is installed properly and free of debris. Make sure that vent system joints are tight and have no leaks. —Check to make sure that no material has been placed at the main burner base. —Be sure glass is tightened properly on unit, particularly on top corners.
NO material be placed in this opening.
R-5627 Page 25
Page 26
Intermittent Pilot Operating Instructions
The intermittent pilot (120/24 volt system) is ON when the main burner is ON. When the main burner is OFF the intermittent pilot is OFF.
IP-Model Pilot (Figure 44)
This fireplace is using a Honeywell "Smart Valve" system for intermittent pilot ignition.
On a call for flame the control turns on a 24 volt mini hot surface ignitor which lights a pilot that in turn lights the main burner.
Pilot Flame Adjustment (Figure 45)
The pilot flame should envelop 3/8 to 1/2 inch (10 to 13mm) of the tip of the flame rod. (See Figure 44)
To adjust:
1. Remove the pilot adjustment cover screw.
2. Turn the inner adjustment screw clockwise to decrease
or counterclockwise to increase pilot flame. Pilot adjust­ment is shipped at full flow rate. Turn the inner adjustment screw clockwise
3. Replace the cover screw after the adjustment to prevent gas leakage.
3/8" TO 1/2" PILOT FLAME
if the inlet pressure is too high.
GROUND ELECTRODE
Intermittent Pilot Wiring Diagram (Figure 46)
PILOT
PRESSURE REGULATOR ADJUSTMENT-UNDER CAP SCREW
INLET PRESSURE TAP
TO 24 V."HOT" ON TRANSFORMER
HOT SURFACE IGNITOR
IP-MODEL PILOT
FLAME ROD
Figure 44
GAS FLOW
OFF
ON
CONTROL
IGNITOR
CONTROL
BURNER
IGNITOR
OUTLET PRESSURE TAP
PILOT ADJUSTMENT­UNDER CAP SCREW
PILOT OUTLET
IGNITOR-PILOT ASSY.
WIRING
TO 24 V. THERMOSTAT
TO 24 V. COMMON ON TRANSFORMER
I P-MODEL GAS VALVE AND WIRING
Figure 45
Page 26 R-5627
Page 27
JUNCTION BOX
NEUTRAL
BLACK
WHITE
GROUND
Electrical Junction Box Connection
Figure 47
Attention: Only, after the fireplace has been converted to a heater can a 24 volt wall thermostat or battery operated remote control with thermostat, FRBTC-1 be used. See installation of heater baffle on Page 5.
OPERATING INSTRUCTIONS
Provided on the intermittent pilot wiring harness are two (2) stripped and bare wires that are labeled THERMOSTAT. The wires will be used for attachment of 24 volt thermostat, optional FWS-1 wall switch or will attach into the receiver on an optional FRBC-1, FRBTC-1 or FREC-1 remote control.
Installation of Remote Receiver
Place remote receiver on the floor of fireplace behind the louver as far forward as possible.
Attention: The velcro loop and hook are not necessary in this installation but can be used to secure remote receiver.
R-5627 Page 27
Page 28
FOR YOUR SAFETY READ BEFORE OPERATING
WARNING: If you do not follow these instructions exactly, a fire or explosion may result
causing property damage, personal injury or loss of life.
A. This fireplace is equipped with an ignition device which
automatically lights the pilot. Do not try to light the pilot by hand.
B. BEFORE OPERATING smell all around the appliance
area for gas. Be sure to smell next to the floor because some gas is heavier than air and will settle on the floor.
WHAT TO DO IF YOU SMELL GAS
• Do not try to light any appliance.
• Do not touch any electrical switch; do not use any phone in your building.
• Immediately call your gas supplier from a neigh- bor's phone. Follow the gas supplier's instructions.
1. STOP! Read the safety information above.
2. Set accessory to OFF.
3. Turn off all electric power to the fireplace.
4. This fireplace is equipped with an ignition device which automatically lights the pilot. Do not try to light the pilot by hand.
If you cannot reach your gas supplier, call the fire department.
C. Use only your hand to slide the gas control knob.
Never use tools. Force or attempted repair may result in a fire or explosion.
D. Do not use this appliance if any part has been under
water. Immediately call a qualified service techni- cian to inspect the appliance and to replace any part of the control system and any gas control which has been under water.
Page 28 R-5627
Page 29
START
INTERMITTENT PILOT
SEQUENCE OF OPERATION
Apply 24 VAC
Apply 24 VAC
to Appliance
to Fireplace
Thermostat
Switch "ON"
Calls for Heat
5 Minute Retry
Delay
System Check
Trial for
Ignition
Main Burner
Operation
Flame Signal
Detected
NO
Internal Check
OK
YES
• Pilot Valve Opens
• Ignitor Powered
Pilot Light and Flame is
Sensed During Trial
For Ignition (1)
YES
• Ignitor OFF
• Main Valve Opens
YES
NO
NO
• Pilot Valve Ignition OFF
• Wait for Flame Signal to Disappear
• Pilot Valve Closes
• Ignition OFF
3 Second Flame Failure Recycle
Delay
YES
Flame Signal
Lost?
NO
Thermostat Call
Switch "OFF"
for Heat Ends
END
Main Pilot Valves
Close
(1) Ignitor will turn OFF about 30 seconds into the trial for ignition if the pilot flame has not lit. It will turn back ON for the final 30 seconds
of the 90 second trial for ignition. The pilot valve will be energized during the entire trial for ignition. This is normal operation for this gas ignition system.
R-5627 Page 29
Main Pilot
Valves Close
Flame Lost More
Than 5 Times in
One Call for Heat
YES
NO
Page 30
IP SYSTEM TROUBLESHOOTING SEQUENCE
START
• Turn OFF Gas Supply
• Disconnect System Control Harness
• Set witch ON
Check for Proper Voltage at Control Harness (See Inset A
-Voltage Should be 24V Between Thermostat and 24V Common, and 24V Between 24V Common and 24V Hot.)
YES
Plug Harness into SmartValve Control W ait for Internal Check Delay (SV9501)
Igniter Warms UP and Glows Red
Note: Igniter Will Cycle OFF and Back ON Once During the 90 Second Ignition Trial
SmartValve™ System Troubleshooting Sequence Note: Before Troubleshooting, Become Familiar
with the Sequence of Operation
CHECK
• Line V oltage Power
NO
NO
• Low V oltage T ransformer
• Thermostat
• Wiring
Unplug Pilot Burner Cable. Measure Voltage at SmartValue HSI Element Output (See Inset B) 24V Nominal
YES
Replace Igniter/Flame Rod Assembly
NO
INSET A
24Volt Thermostat
24 Volts
24 Volt Common
INSET B
Replace SmartValve Control
Reconnect Pilot Burner Cable
24
Volts
HSI Terminals
End View of Control Harness Connector
EFT Output
24 Volt Hot
YES
• Turn On Gas Supply
• Pilot Burner Lights
YES
Main Valve Opens and Main Burner Lights
YES
NO
NO
Reconnect Pilot Burner Cable
• Check that Pilot Gas is Flowing Wait to Assure Pilot Gas Tubing is Purged.
YES
• Measure Voltage Between 24V Hot and 24V Common Leads to SmartValve Control. Must Measure at Least 19.5 VAC with Igniter Powered. See Inset A to Identify Proper Lead. This Check Must be Done with the SmartValve Control Connected and Igniter Powered.
YES
Replace Igniter/Flame Rod Assembly
Check that Pilot Flames Makes
Check that Pilot Flame Makes Good Good Contact with Pilot Burner
Contact with Pilot Burner Flame Rod
Flame Rod
Check for Good Electrical
• Check for Good Electrical Connection Through the Pilot
Connection Through the Pilot Tubing
Tubing
If Both of the Above are Good,
• If Both of the Above are Good, Replace Igniter/Flame Rod
Replace Igniter/Flame Rod
NO
NO
Cotter Pin Disconnected from Delayed Ignition Reset Switch. Refer to Page 23 for Description of Delayed Ignition Reset Switch and Replacement of Cotter Pin into Delayed Ignition Reset Switch.
Replace SmartValve Control
Check Transformer and Line Volt Supply
System is Okay
Page 30 R-5627
Switch OFF and Back ON
Main Burner Lights
NO
Replace SmartValve Control
Page 31
Maintenance and Service
DOOR LATCH
GLASS FRAME
It is not unusual for your Empire gas fireplace to give off some odor the first time it is burned. This is due to the curing of the paint and any undetected oil from the manufacturing process.
Please ensure that your room is well ventilated - open all windows.
It is recommended that you burn your Empire unit for at least six (6) hours the first time you use it. If optional fan kit has been installed, place fan in the "OFF" position during this time.
IMPORTANT: Turn off gas before servicing appliance. It is
recommended that a competent service technician perform these check­ups at the beginning of each heating season.
• Clean Burner and Control Compartment
• Check Vent System
Glass Cleaning
It will be necessary to clean the glass periodically. During start-up condensation, which is normal, forms on the inside of the glass and causes lint, dust and other airborne particles to cling to the glass surface. Also initial paint curing may deposit a slight film on the glass. It is therefore recommended that the glass be cleaned two or three times with a non-abrasive household cleaner and warm water (we recommend gas fireplace glass cleaner). After that the glass should be cleaned two or three times during each heating season depending on the circumstances present.
General Glass Information
Only glass approved for use by the manufacturer in fireplace may be used for replacement. The glass replacement should be done by a licensed or qualified service person.
WARNING:
1. The use of substitute glass will void all product warranties.
2. Care must be taken to avoid breakage of the glass.
3. Under no circumstances should this appliance be operated without
4. Do not abuse the glass by striking or hitting the glass.
PLEASE NOTE It is normal for appliances fabricated of steel to give off some expansion and/or contraction noised during the start up or cool down cycle. Similar noises are found with your furnace heat exchanger or car engine.
Keep the control compartment, logs, and burner areas surrounding the logs clean by vacuuming or brushing at least twice a year.
Cleaning Procedure
1. Turn off pilot light at gas valve.
2. Remove glass front. (See Glass Removal)
3. Vacuum burner compartment.
4. Reinstall glass front.
5. Ignite pilot. (See Lighting/Operating Section of Manual)
6. Operate the pilot burner and visually check to make sure the flame pattern appears similar to the pictorial illustration shown in Figure
45. If it appears abnormal call a service person.
The appliance and venting system should be inspected before initial use and at least annually by a qualified field service person. Inspect the external vent cap on a regular basis to make sure that no debris is interfering with the air flow.
WARNING: Do not operate appliance with the glass front removed, cracked or broken. Replacement of the glass should be done by a licensed or qualified service person.
the glass front or with a broken glass front. Replacement of the glass (with gasket) as supplied by the manufacturer should be done by a qualified service person.
WARNING: Do not use abrasive cleaners on glass. Do not attempt to clean glass when glass is hot.
Glass Removal and Replacement (Figure 49)
1. Push up and outward to remove top louver.
2. Lower door assembly.
3. Release two door latches at bottom of firebox.
4. Grasp bottom of glass frame, lift glass frame upward in order to release glass frame from lip on top of firebox.
5. Align and place top of glass frame over lip on top of firebox.
6. Grasp bottom of glass frame, push inward and place glass frame onto firebox.
7. Attach two door latches onto bottom of glass frame.
8. Align and insert (4) mounting tabs on top louver with (4) slots on casing top. Push downward to lock the top louver into position.
GLASS FRAME
DOOR LATCH
Figure 49
Installation of Louvers (Figure 50) Attention: The top louver has (4) mounting tabs. The bottom louver has
(2) clearance holes.
1. Align and insert (4) mounting tabs on top louver with (4) slots on casing top. Push downward to lock the top louver into position.
2. Align (2) clearance holes on bottom louver with (2) screw holes on casing. Attach bottom louver to casing with (2) 10 x 1/2" screws.
Figure 50
R-5627 Page 31
Page 32
22
23
25
26
24
28
How To Order Repair Parts...
Parts can be ordered only through your service person or dealer. For best results, the service person or dealer should order parts through the distributor. Parts can be shipped directly to the service person/dealer.
All parts listed in the Parts List have a Part Number. When ordering parts, first obtain the Model Number from the name plate on your equipment. Then determine the Part Number (not the Index Number) and the Description of each part from the following appropriate illustration and list. Be sure to give all this information . . .
Fireplace Number Part Description Fireplace Serial Number Type of Gas (Propane or Natural) Part Number Do not order bolts, screws, washers or nuts. They are standard hardware items and can be purchased at any local hardware store. Shipments contingent upon strikes, fires and all causes beyond our control.
Page 32 R-5627
Empire Comfort Systems, Inc. Nine Eighteen Freeburg Ave. Belleville, Illinois 62222-0529
Page 33
PLEASE NOTE: When ordering parts, it is very important that part number and description of part coincide.
Index Part No. Number Description
1 10816 UPPER CLEARANCE SPACER 2 10013 TOP STANDOFF (DVF-36) (2 REQUIRED) 2 10038 TOP STANDOFF (DVF-42) (2 REQUIRED) 3 10988 VENT COVER PLATE ASSEMBLY 4 10829 OUTER WRAPPER TOP (DVF-36) 4 10831 OUTER WRAPPER TOP (DVF-42) 5 10776 TOP HEAT SHIELD (DVF-36) 5 10777 TOP HEAT SHIELD (DVF-42) 6 10578 OUTER WRAPPER - LEFT (DVF-36) 6 10582 OUTER WRAPPER - LEFT (DVF-42) 7 10855 OUTER WRAPPER BACK (DVF-36) 7 10856 OUTER WRAPPER BACK (DVF-42) 8 10579 OUTER WRAPPER - RIGHT (DVF-36) 8 10583 OUTER WRAPPER - RIGHT (DVF-42)
9 10779 CORNER SHIELD 10 10054 JUNCTION BOX WELDED ASSEMBLY 11 10018 AIR DILLUTION COVER PLATE 12 10574 CORNER BRACE 2 13 10573 CORNER BRACE 1 14 10860 OUTER WRAPPER BOTTOM WELDED
ASSEMBLY (DVF-36)
14 10938 OUTER WRAPPER BOTTOM WELDED
ASSEMBLY (DVF-42) 15 10586 LOUVER ASSEMBLY - UPPER (DVF-36) 15 10588 LOUVER ASSEMBLY - UPPER (DVF-42) 16 10898 GLASS FRAME ASSEMBLY (DVF-36) 16 10951 GLASS FRAME ASSEMBLY (DVF-42) 17 10587 LOUVER ASSEMBLY - LOWER (DVF-36) 17 10589 LOUVER ASSEMBLY - LOWER (DVF-42) 18 R-5137 ADAPTER PIPE 19 M-169 8" ADAPTER GASKET 20 10900 AIR DROP BACK ASSEMBLY 21 10554 NAILING FLANGE (4 REQ’D) 22 11222 AIR DROP FRONT ASSEMBLY 23 CI-364 BLOW PLATE ASSEMBLY (DVF-36) 23 10945 PRESSURE DOOR RELEIF ASSEMBLY
(DVF-42) (2 REQ’D) 24 CI-375 BLOW PLATE BRACKET (2 REQ’D) 25 M-170 FLUE OUTLET GASKET 26 10976 DIVERTER OUTLET TUBE 27 10893 FIREBOX TOP ASSEMBLY (DVF-36) 27 10944 FIREBOX TOP ASSEMBLY (DVF-42) 28 10798 COMBUSTION DOME DIVERTER (DVF-36) 28 10799 COMBUSTION DOME DIVERTER (DVF-42) 29 10993 HEATER BAFFLE 30 11218 SUPPORT COLUMN - LEFT (DVF-36) 30 11220 SUPPORT COLUMN - LEFT (DVF-42) 31 10788 FIREBOX SIDE - LEFT (DVF-36) 31 10790 FIREBOX SIDE - LEFT (DVF-42) 32 10789 FIREBOX SIDE - RIGHT (DVF-36) 32 10791 FIREBOX SIDE - RIGHT (DVF-42) 33 11219 SUPPORT COLUMN - RIGHT (DVF-36) 33 11221 SUPPORT COLUMN - RIGHT (DVF-42) 34 10784 FIREBOX BACK (DVF-36) 34 10785 FIREBOX BACK (DVF-42) 35 10806 COMBUSTION AIR BAFFLE (DVF-42) 36 10802 REAR LOG SUPPORT (DVF-36) 37 10854 REAR LOG SUPPORT (DVF-42) 38 P-200 ORIFICE FITTING 39 P-255 #53 ORIFICE - LP (DVF-36) 39 P-256 #41 ORIFICE - NAT (DVF-36) 39 P-258 #1.55mm ORIFICE - LP (DVF-42) 39 P-257 #40 ORIFICE - NAT (DVF-42) 40 R-4665 AIR SHUTTER LP 40 R-4666 AIR SHUTTER NAT 41 P-251 COUPLING (NAT GAS ONLY) 42 10895 BURNER BOX ASSEMBLY - NATURAL
(DVF-36) (INCLUDES AIR SHUTTER) 42 10896 BURNER BOX ASSEMBLY - LP (DVF-36)
(INCLUDES AIR SHUTTER)
Index Part No. Number Description
42 10947 BURNER BOX ASSEMBLY - NATURAL
(DVF-42) (INCLUDES AIR SHUTTER)
42 10948 BURNER BOX ASSEMBLY - LP (DVF-
42) (INCLUDES AIR SHUTTER)
43 10213 BURNER SUPPORT - LEFT WELDED
ASSEMBLY
44 10974 GRATE ASSEMBLY COMPLETE (DVF-
36)
44 10975 GRATE ASSEMBLY COMPLETE (DVF-
42)
45 10212 BURNER SUPPORT - RIGHT WELDED
ASSEMBLY
46 R-5143 PILOT ASSEMBLY - NATURAL -
ROBERTSHAW
46 R-5144 PILOT ASSEMBLY - LP -
ROBERTSHAW
46 R-3232 PILOT ASSEMBLY (IP)- NATURAL
HONEYWELL (IP)
46 R-3233 PILOT ASSEMBLY (IP)- LP
HONEYWELL (IP) 47 11163 PILOT BRACKET 48 11210 FIREBOX BOTTOM WELDED
ASSEMBLY (DVF-36) 48 11214 FIREBOX BOTTOM WELDED
ASSEMBLY (DVF-42) 48 11211 FIREBOX BOTTOM WELDED
ASSEMBLY (DVF-36-IP) 48 11215 FIREBOX BOTTOM WELDED
ASSEMBLY (DVF-42-IP) 49 10889 SEAL BRACKET 50 M-167 GASKET - SEAL BRACKET 51 R-4053 DOOR LATCH (2 REQ’D) 52 R-5454 GAS VALVE - NATURAL -
HONEYWELL 52 R-5456 GAS VALVE - LP - HONEYWELL 53 R-5155 GAS VALVE - NATURAL HONEYWELL
(IP) 53 R-5156 GAS VALVE - LP HONEYWELL (IP) 54 UH-810 TRANSFORMER MOUNTING
BRACKET (IP) 55 R-1995 TRANSFORMER (IP) 56 UH451 JUNCTION BOX COVER (IP) 57 DV-802 JUNCTION BOX (IP) 58 R-5160 CORD SET - 18" (IP) 59 R-4589 FRONT LOG (DVF-36) 59 R-4594 FRONT LOG (DVF-42) 60 R-4585 LEFT MIDDLE LOG (DVF-36) 60 R-4590 LEFT MIDDLE LOG (DVF-42) 61 R-4586 RIGHT MIDDLE LOG (DVF-36) 61 R-4591 RIGHT MIDDLE LOG (DVF-42) 62 R-4592 REAR LOG (DVF-36) 62 R-4597 REAR LOG (DVF-42)
NOT SHOWN R-3436 REMOTE/OFF/ON SWITCH (DVF-36
DVF-42)
NOT SHOWN R-3435-A WIRE ASSEMBLY (DVF-36 DVF-42) NOT SHOWN R-5592 WIRE ASSEMBLY
(DVF-36IP DVF-42IP)
NOT SHOWN 10891 PILOT TUBING ASSEMBLY (DVF-36IP) NOT SHOWN 10892 INLET TUBING ASSEMBLY (DVF-36IP) NOT SHOWN 11035 PILOT TUBING ASSEMBLY (DVF-36) NOT SHOWN 11036 INLET TUBING ASSEMBLY (DVF-36) NOT SHOWN 11037 PILOT TUBING ASSEMBLY (DVF-42IP) NOT SHOWN 11038 INLET TUBING ASSEMBLY (DVF-42IP) NOT SHOWN 11039 PILOT TUBING ASSEMBLY (DVF-42) NOT SHOWN 11040 INLET TUBING ASSEMBLY (DVF-42) NOT SHOWN 10173 SHIPPING PLATE (DVF-36) NOT SHOWN 10174 SHIPPING PLATE (DVF-42) NOT SHOWN 10260 LAVA (DECORATIVE) ROCK NOT SHOWN 10261 ROCK WOOL
USE ONLY MANUFACTURER'S REPLACEMENT PARTS. USE OF ANY OTHER PARTS COULD CAUSE INJURY OR DEATH.
R-5627 Page 33
Page 34
VFC 30
DVF/DVT
FIREBOX TOP
VFFB- 36 / VFC 3 6
VFFB-4 2/ VFC 4 2
"12 1/2"
9 1/4"
3 1/2"
3 3/4"
DVF/DVT UNITS
FA N CONTROL
VFFB/ VFC UN I TS
FA N CONTROL
OPTIONAL
AUTOMATIC FAN KIT
INSTALLATION
INSTRUCTIONS
OPTIONAL FAN MODEL NUMBER
FB-BK-2 VFFB-30C VFFB-36C VFFB-42C
VFFB-36D VFFB-42D DVF-36 DVF-36IP DVF-42 DVF-42IP
FKA-160 VFC-30 VFC-36 VFC-42
VFD-36 VFD-42 DVT/R-36 DVT/RE-36 DVT/R-42 DVT/RE-42
Installing Optional Fan Kit
1. If applicable, turn OFF electric supply to fireplace.
2. Lower the bottom louver.
3. With a 5/16" socket, loosen but do not remove either left screw or right screw that attaches bottom louver to fireplace side.
4. When the screw is sufficiently loosened you will be able to pull and pivot the bottom louver out of fireplace.
5. Centered in the rear are (2) weld studs which protrude upward into the bottom of fireplace for attachment of fan.
6. Insert fan into interior, bottom of fireplace. The clearance holes on fan mounting bracket must be facing toward the front of fireplace. Do not damage gas inlet supply line when fan is inserted into fireplace.
7. Align and place (2) clearance holes that are 2 1/2" from end of fan mounting bracket onto (2) weld studs.
8. Use (2) wing nuts to attach fan to weld studs.
9. Located in the right, front are (2) weld studs which protrude upward into the bottom of fireplace for attachment of speed control.
10. Insert speed control into interior, bottom of fireplace. Align and place (2) clearance holes on speed control onto (2) weld studs.
11. Use (2) wing nuts to attach speed control to weld studs.
12. Remove top louver from firebox.
13. Refer to Figure 1 for mounting hole location on right side of firebox top that applies to your appliance. Measure from front edge of firebox top to determine mounting hole location. Remove appropriate screw from firebox top.
14. Refer to Figure 2 for fan control bracket location that applies to your firebox. Align clearance hole on fan control bracket with screw hole on firebox top. Attach fan control bracket to firebox top with one (1) screw from Step 13.
15. Route fan control wires between the inner casing and outer casing.
16. Connect fan control wires to speed control wires.
17. Plug speed control electric cord into junction box on the right side of fireplace.
18. Replace and attach top louver and bottom louver onto fireplace.
19. Installation of fan kit is completed.
VFFB/ VFC UN ITS
FAN CONTROL
BRAC KET
FIREBOX
DVF/DVT UNITS
FAN CONTROL
BRAC KET
FIREBOX
Figure 2
Wiring
The appliance, when installed, must be electrically grounded in accordance with local codes or, in the absence of local codes, with the National Electrical Code, ANSI/NFPA 70, if an external electrical source is utilized. This appliance is equipped with a three-prong [grounding]
plug for your protection against shock hazard and should be plugged directly into a properly grounded three-pr ong receptacle. Do not cut or remove the grounding prong from this plug. For an ungrounded
receptacle, an adapter, which has two prongs and a wire for grounding, can be purchased, plugged into the ungrounded receptacle and its wire connected to the receptacle mounting screw. With this wire completing the ground, the appliance cord plug can be plugged into the adapter and be electrically grounded.
CAUTION: Label all wires prior to disconnection when servicing controls. Wiring errors can cause improper and dangerous operation. Verify proper operation after servicing.
Blower Motor
FIREBOX TOP
3 1/2"
DVF/DVT
VFFB-4 2/ VFC 4 2
VFFB- 36 / VFC 3 6
VFFB-3 0
VFC 30
3 3/4"
9 1/4"
12 1/2
The blower motor does not have oiling holes. Do not attempt to oil the blower motor.
Blower Wheels
The blower wheels will collect lint and could require periodic cleaning. If the air output decreases or the noise level increases, it indicates a dirty blower wheel. Remove fan and clean blower wheels.
Page 34 R-5627
Figure 1
Page 35
FAN SWITCH
FAN KIT
FAN KIT
SPEED CONTROL
JUNCTION BOX
FAN SWITCH
JUNCTION BOX
SPEED CONTROL
Parts List
Part FB-BK-2 Quantity Description Supplied
Fan Kit 10131 1 Speed Control 10103 1 Hardware Package 10104 1 Fan Control R-2503 1
R-5627 Page 35
Page 36
OPTIONAL FRESH FIREPLACE AIR INTAKE KIT MODEL NUMBERS
FB-AK-2 DVF-36 DVF-36IP
DVF-42 DVF-42IP
Optional Fresh AIr Intake Kit (Figure 1)
Installation of our 6" fresh air intake kit is simple and easy to complete. This system MUST BE installed before the fireplace is enclosed with finishing material. The air will be drawn into the cooling layer of the fireplace and be completely separated from the combustion casing of the direct vent fireplace. Cooler outside air will mix with room air, circulating around the firebox to reduce the heat output and bring heated, fresh air into the house to provide a more positive balance.
RAIN CAP INCLUDES OUTSIDE AIR
*DAMPER
ROD
BRACKET
TUBE ASSEMBL Y
Figure 1 Fresh Air Intake Kit
Installing Fresh Air Intake Kit (Figures 2, 3, 4, 5)
1. Remove air dilution cover plate from left side of outer casing by removing (4) 10 x 1/2" screws (See Figure 2).
2. Attach damper assembly onto left side of outer casing with (4) 10 x 1/2" screws from Step 1. The 3" damper door tab will be positioned to the right as the damper assembly is attached to left side of outer casing.
3. As you face the fireplace, insert damper rod bracket into left, interior bottom of fireplace. The 3/4" flange on damper rod bracket must face toward the rear of fireplace. Align (2) clearance
OUTER CASING
DAMPER
ASSEMBLY
INCLUDES
COVER
PLATE
DAMPER
ROD
holes on damper rod bracket with (2) screw holes on left side of hearth pan. Attach damper rod bracket to the underside of hearth pan with (2) 10 x 1/2" provided screws (See Figure 3).
*Attention:
GASKET
DAMPER ASSEMBLY
OUTER CASING
COVER PLATE
DAMPER ROD BRACKET
DAMPER
REMOVE AIR DILUTION COVER PLATE
Figure 2 Damper Assembly Location
Page 36 R-5627
DAMPER ROD (OPEN)
TOP VIEW
Figure 3 Top View of Air System Installation
ROD (CLOSED)
Page 37
4. Two cover plates are provided in kit. Use cover plate that measures 6 3/8" in height. Do not use cover plate that measures 7" in height. Discard 7" cover plate.
5. Insert and position 6 3/8" cover plate into left, interior bottom of fireplace. The 3/8" diameter hole in cover plate will be positioned upward and to the left.
6. Insert damper rod through damper rod bracket and 3/8" diameter hole in cover plate. Insert damper rod into 1/4" diameter hole in damper door tab. Place smooth side of 1/2" diameter pushnut over end of damper rod. Press the pushnut onto the damper rod approximately 1/8". The pushnut will prevent the damper rod from falling out of 1/4" diameter hole in damper door tab.
7. Attach cover plate to support legs with (4) 10 x 1/2" provided screws. The support legs are on the left side, to the rear, in the interior bottom of fireplace.
8. The 1 1/4" offset on damper rod is used to secure the damper door in an open or closed position.
9. Refer to Figure 4 for options available for installation of 6" diameter duct. The duct run can be a maximum length of 40 feet. Insulated duct is recommended when ducting through a heated space. Note: 6" C vent or 6" flex vent can be used.
10. Cut a 6" diameter hole in structure after determining duct termination (rain cap) location.
11. Caulk exterior of structure that will be contacted by outside air tube assembly (See Figure 5).
12. Insert outside air tube assembly into 6" diameter hole in structure. Align clearance holes on rain cap with clearance holes on outside air tube assembly. Attach rain cap and outside air tube assembly to structure with (6) 1 1/2" provided screws.
13. Attach 6" diameter duct to 1 1/2" collar on damper assembly.
14. Route 6" diameter duct to outside air tube assembly.
15. Attach 6" diameter duct to outside air tube assembly.
16. Installation of fresh air intake kit is completed.
PARTS LIST
Part Part Quantity Description Number Supplied
Damper Assembly 10098 1 6 3/8" Cover Plate 10083 1 Damper Rod Bracket 10086 1 Rain Cap 10124 1 Damper Rod R-4182 1 Pushnut R-4607 1 10 x 1/2" Screw R-2737 6 10 x 1 1/2" Screw R-1134 6
Figure 4 Example of Installation
NO ELBOWS USED ON FRESH AIR KIT
CAULKING
RAIN CAP
DUCT TERMINATION
WALL
Figure 5 Caulk and Install Duct Termination
WHEN 90° OR 45° ELBOWS ARE USED ON FRESH AIR KIT
R-5627 Page 37
Page 38
ACCESSORY PARTS
The following accessory parts can be obtained from your Empire Comfort Systems, dealer. Should you need additional information beyond what your dealer can furnish, contact Empire Comfort Systems, Inc., Nine Eighteen Freeburg Ave., Belleville, Illinois 62222-
0529. Accessory Description Model Number
Fan Kit Designed to provide forced air flow. FB-BK-2
Simulated Brick Panels Designed to enhance appearance looking more DVF-BL-36
like real masonry. DVF-BL-42
Fresh Air Intake Kit Designed to provide heated fresh air to the house. VFFB-AK-2
Trim Kit Frame — Brass DVFBF-36BR-1
DVFBF-42BR-1
Frame — Porcelain Black FBF-36BP-2
FBF-42BP-2
Frame — Black FBF-36BL-2
FBF-42BL-2
Louvers Brass Louvers FBL-36BR-2
FBL-42BR-2
Black Porcelain Louvers FBL-36BP-2
FBL-42BP-2
Glass Window T rim DVWT-36BR-1
DVWT-42BR-1
Page 38 R-5627
Page 39
OPTIONAL SIMULATED BRICK LINER
SIDE PANEL
SIDE PANEL
BACK PANEL
Z BRACKET
INSTALLING OPTIONAL SIMULATED BRICK PANELS
1. If installed, turn OFF gas supply to fireplace.
2. If installed, remove log assembly from fireplace.
3. The back panel is to be installed before the side panels. Place back panel against the rear wall in fireplace.
4. Place one side panel against the side wall in fireplace. Align the brick pattern on back panel and side panel.
5. To install the brick panel (Z) bracket you must first remove the top and bottom screw on the side of the inner casing front as it attaches to the outer casing. Now, place the brick panel (Z) bracket over the front edge of the side panel. The clearance holes on the brick panel (Z) bracket will align with the top and bottom screw holes on the side of the inner casing front. Reattach the top and bottom screws through the clearance holes on the brick panel (Z) bracket and into the inner casing front.
6. Repeat Step 4 and Step 5 to attach the second side panel to fireplace.
7. Installation of optional simulated brick panels is completed.
INSTALLATION INSTRUCTIONS
Direct Vent Fireplace
BRICK LINER KIT MODEL NUMBER
DVF- BL-36 DVF-36 DVF-36IP DVF-BL-42 DVF-42 DVF-42IP
SIDE PANEL
BACK PANEL
SIDE PANEL
Z BRACKET
PARTS LIST
Part Description Kit Number Kit Number Quantity
Brick Panel (Z) Bracket 10990 10991 2 Brick Panel - Side Right R-5201 R-5205 1 Brick Panel - Side Left R-5202 R-5206 1
Brick Panel - Back R-5200 R-5204 1
DVF-BL-36 DVF-BL-42 Supplied
R-5627 Page 39