Empire Comfort Systems DV25IN33LN-3 Installation Instructions And Owner's Manual

INSTALLATION INSTRUCTIONS
EMPIRE
EMPIRE
Comfort Systems
AND
OWNER’S MANUAL
DIRECT VENT
GAS FIREPLACE HEATER
MODELS
DV(25,33,35)IN33L(N,P)-3 DV(25,33,35)IN73L(N,P)-1
GAS-FIRED
UL FILE NO. MH30033
This appliance may be installed in an aftermarket, permanently located, manufactured home (USA only) or mobile home, where not prohibited by state or local codes.
This appliance is only for use with the type of gas indicated on the rating plate. This appliance is not
convertible for use with other gases, unless a certied
kit is used.
WARNING: If not installed, operated and maintained in accordance with the manufacturer’s instructions, this product could expose you to substances in fuel or from fuel combustion which can cause death or serious illness.
FIREPLACE INSERT
Installer: Leave this manual with the appliance. Consumer: Retain this manual for future reference.
WARNING: If the information in these instructions
are not followed exactly, a re or explosion may
result causing property damage, personal injury or loss of life.
— Do not store or use gasoline or other ammable
vapors and liquids in the vicinity of this or any other appliance.
— WHAT TO DO IF YOU SMELL GAS
Do not try to light any appliance.
Do not touch any electrical switch; do not use any phone in your building.
• Immediately call your gas supplier from a neighbor’s phone. Follow the gas supplier’s instructions.
If you cannot reach your gas supplier, call the
re department.
— Installation and service must be performed by a
qualied installer, service agency or the gas sup­plier.
Page 1
TABLE OF CONTENTS
SECTION PAGE
Important Safety Information .............................................................................................. 3
Safety Information for Users of LP Gas .............................................................................4
Introduction ........................................................................................................................ 5
Specications ..................................................................................................................... 6
Fireplace Insert Dimensions .............................................................................................. 7
Mantel and Trim Clearances .............................................................................................. 8
Gas Supply ........................................................................................................................ 9
Venting and Installation ............................................................................................... 10-12
Vertical Termination .......................................................................................................... 13
Alternate ON/OFF Switch Installation .............................................................................. 14
Surround Panel Installation .............................................................................................. 15
Blower Accessory Information ..........................................................................................16
Log Placement ................................................................................................................. 17
Operating Instructions ...................................................................................................... 18
Standing Pilot Lighting Instructions .................................................................................. 19
Standing Pilot Wiring ........................................................................................................ 20
Standing Pilot Troubleshooting ........................................................................................21
IPI Electronic System Operating Instructions ................................................................... 22
IPI Electronic System Wiring Diagram ............................................................................. 23
Intermittent Pilot Lighting Instructions .............................................................................. 24
Intermittent Control System Troubleshooting ................................................................... 25
Intermittent Control System Troubleshooting .............................................................. 26-27
Insert Maintenance and Service ...................................................................................... 28
Decorative Accessories .............................................................................................. 29 -30
Parts View ....................................................................................................................... 31
Parts List .....................................................................................................................32-33
Master Parts Distributor List ............................................................................................. 34
How To Order Repair Parts .............................................................................................. 34
Warranty ...........................................................................................................................35
29393-9-0514Page 2
IMPORTANT SAFETY INFORMATION
Before enclosing the vent pipe assembly, operate the appliance to ensure it is venting properly.
DO NOT OPERATE THIS APPLIANCE WITHOUT GLASS FRONT PANEL INSTALLED
DANGER: Indicates a hazardous situation which, if not
avoided, will result in death or serious injury.
WARNING: Indicates a hazardous situation which, if
not avoided, could result in death or serious injury.
CAUTION: Indicates a hazardous situation which, if not avoided, could result in minor or moderate injury. NOTICE: Addresses practices not related to personal
injury.
Children and adults should be alerted to the hazards
of high surface temperatures and should stay away to avoid burns or clothing ignition.
Young children should be carefully supervised when
they are in the same room as the appliance.
Clothing or other ammable material should not be
placed on or near the appliance.
Due to high temperatures the appliance should be
located out of trafc and away from furniture and
draperies.
Adequate accessibility clearances for servicing and proper operation should be maintained.
• Under no circumstances should any solid fuels (wood, coal, paper or cardboard etc.) be used in this appliance.
• Keep the area around your appliance clear of
combustible materials, gasoline and other ammable
vapor and liquids.
• This appliance must not share or be connected
to a ue serving a separate solid-fuel burning
appliance.
The ow of combustion and ventilation air must not
be obstructed in any way.
The replace insert must be installed in either a masonry or factory-built wood burning replace. See page 7 for replace opening size requirements.
• DO keep the appliance area clear and free from
combustible material, gasoline and other ammable
vapors and liquids.
The glass front or any part removed for servicing the appliance must be replaced prior to operating
the appliance. Work should be done by a qualied
service person.
Keep burner and control compartment clean.
Vent cap is hot while replace is in operation.
Installation and repair should be done by a QUALIFIED SERVICE PERSON. The appliance should be inspected before use and at least annually by a qualified service person. More frequent cleaning may be required due to excessive lint from carpeting, bedding materials, etc. It is imperative that control compartments, burners and circulating air passageways of the appliance be kept clean.
DO NOT put anything around the replace insert
that will obstruct the ow of ventilation air.
• Maintain clearances in accordance with local installation codes and the requirements of the gas supplier.
29393-9-0514 Page 3
• DO examine venting system periodically and replace damaged parts.
• DO make a periodic visual check of pilot and burners. Clean and replace damaged parts.
CAUTION: The glass used in your replace insert is ceramic glass. If the glass is cracked or damaged in any way, it should be replaced only with a complete glass frame assembly from Empire. See parts list on Pages 32 and 33 for ordering.
DO NOT use this replace insert if any part has been
under water. Immediately call a qualied service
technician to inspect the heater and to replace any part of the control system and any gas control which has been under water.
Any safety screen or guard removed for servicing an appliance must be replaced prior to operating the appliance.
SAFETY INFORMATION FOR USERS OF LP-GAS
Propane (LP-Gas) is a ammable gas which can cause res
and explosions. In its natural state, propane is odorless and colorless. You may not know all the following safety precautions which can protect both you and your family from an accident. Read them carefully now, then review them point by point with the members of your household. Someday when there may not be a minute to lose, everyone’s safety will depend on knowing exactly what to do. If, after reading the following information, you feel you still need more information, please contact your gas supplier.
LP-GAS WARNING ODOR
If a gas leak happens, you should be able to smell the gas
because of the odorant put in the LP-Gas.
That's your signal to go into immediate action!
Do not operate electric switches, light matches, use your phone. Do not do anything that could ignite the gas.
• Get everyone out of the building, vehicle, trailer, or area. Do that IMMEDIATELY.
• Close all gas tank or cylinder supply valves.
• LP-Gas is heavier than air and may settle in low areas such as basements. When you have reason to suspect a gas leak, keep out of basements and other low areas. Stay out until
reghters declare them to be safe.
• Use your neighbor’s phone and call a trained LP-Gas service
person and the re department. Even though you may not
continue to smell gas, do not turn on the gas again. Do not re-enter the building, vehicle, trailer, or area.
Finally, let the service man and reghters check for escaped gas. Have them air out the area before you return. Properly trained LP-Gas service people should repair the leak, then check and relight the gas appliance for you.
NO ODOR DETECTED - ODOR FADE
Some people cannot smell well. Some people cannot smell
the odor of the chemical put into the gas. You must nd out if
you can smell the odorant in propane. Smoking can decrease your ability to smell. Being around an odor for a time can affect your sensitivity or ability to detect that odor. Sometimes other odors in the area mask the gas odor. People may not smell the gas odor or their minds are on something else. Thinking about smelling a gas odor can make it easier to smell.
The odorant in LP-gas is colorless, and it can fade under some circumstances. For example, if there is an underground leak, the
movement of the gas through soil can lter the odorant. Odorants in
LP-Gas also are subject to oxidation. This fading can occur if there is rust inside the storage tank or in iron gas pipes.
The odorant in escaped gas can adsorb or absorb onto or into walls, masonry and other materials and fabrics in a room. That will take some of the odorant out of the gas, reducing its odor intensity.
LP-Gas may stratify in a closed area, and the odor intensity could vary at different levels. Since it is heavier than air, there may be more odor at lower levels. Always be sensitive to the slightest gas odor. If you detect any odor, treat it as a serious leak. Immediately go into action as instructed earlier.
SOME POINTS TO REMEMBER
Learn to recognize the odor of LP-gas. Your local LP-Gas Dealer can give you a “Scratch and Sniff” pamphlet. Use it to
nd out what the propane odor smells like. If you suspect that
your LP-Gas has a weak or abnormal odor, call your LP-Gas Dealer.
If you are not qualied, do not light pilot lights, perform service,
or make adjustments to appliances on the LP-Gas system. If
you are qualied, consciously think about the odor of LP-Gas
prior to and while lighting pilot lights or performing service or making adjustments.
Sometimes a basement or a closed-up house has a musty smell that can cover up the LP-Gas odor. Do not try to light pilot lights, perform service, or make adjustments in an area where the conditions are such that you may not detect the odor if there has been a leak of LP-Gas.
Odor fade, due to oxidation by rust or adsorption on walls of new cylinders and tanks, is possible. Therefore, people should be particularly alert and careful when new tanks or cylinders are placed in service. Odor fade can occur in new tanks, or
reinstalled old tanks, if they are lled and allowed to set too long before relling. Cylinders and tanks which have been out
of service for a time may develop internal rust which will cause odor fade. If such conditions are suspected to exist, a periodic sniff test of the gas is advisable. If you have any question
about the gas odor, call your LP-gas dealer. A periodic sniff test of the LP-gas is a good safety measure under any condition.
If, at any time, you do not smell the LP-Gas odorant and you think you should, assume you have a leak. Then take the same immediate action recommended above for the occasion when you do detect the odorized LP-Gas.
If you experience a complete “gas out,” (the container is under no vapor pressure), turn the tank valve off immediately. If the container valve is left on, the container may draw in some air
through openings such as pilot light orices. If this occurs, some
new internal rusting could occur. If the valve is left open, then treat the container as a new tank. Always be sure your con­tainer is under vapor pressure by turning it off at the container
before it goes completely empty or having it relled before it is
completely empty.
29393-9-0514Page 4
INTRODUCTION
Instructions to Installer
1. Installer must leave instruction manual with owner after installation.
2. Installer must have owner ll out and mail warranty card supplied with the replace.
3. Installer should show owner how to start and operate the
replace.
This direct vent gas replace heater is designed to operate with
all combustion air being siphoned from the outside of the building and all exhaust gases expelled to the outside of the building. The information contained in this manual pertains to all models and gas control systems unless otherwise noted.
WARNING
This unit is not for use with solid fuels
Appliance Certication
This replace is design certied in accordance with American
National Standard/CSA Standard ANSI Z.21-88/CSA 2.33 and by Underwriters Laboratories as a Direct Vent Gas Fireplace Heater and shall be installed according to these instructions.
Consult your local building code agency, prior to installation, to ensure compliance with local codes-including permits and inspections.
The replace insert, when installed, must be electrically grounded in
accordance with local codes or, in absence of local codes, with the National Electric Code ANSI/NFPA 70 or Canadian Electric code, CSA C22.1, if an external electrical source is utilized.
These models may be installed in a bedroom or bed-sitting room in the U.S.A. and Canada.
Qualied Installing Agency
Installation and replacement of gas piping, gas utilization equipment or accessories and repair and servicing of equipment shall be
performed only by a qualied agency. The term “qualied agency” means any individual, rm, corporation or company which either in
person or through a representative is engaged in and is responsible for (a) the installation or replacement of gas piping or (b) the connection, installation, repair or servicing of equipment, who is experienced in such work, familiar with all precautions required and has complied with all the requirements of the authority having jurisdiction.
State of Massachusetts: The installation must be made by
a licensed plumber or gas tter in the Commonwealth of
Massachusetts.
The installation must conform with local codes or, in the absence of local codes, with the National Fuel Gas Code ANSI Z223.1/NFPA
54* Natural Gas and Propane Installation Code, or CSA B149.1 in Canada. *Available from the American National Standards Institute, Inc. 11 West 42nd St., New York, N.Y. 10036.
WARNING
ANY CHANGE TO THIS FIREPLACE OR ITS CONTROLS CAN BE DANGEROUS.
Improper installation or use of the replace can cause serious injury or death from re, burns, explosions, or
carbon monoxide poisoning
Any alteration of the original design, installed other than as shown in these instructions or use with a type of gas not shown on the rating plate is the responsibility of the person and company making the change. Important
All correspondence should refer to complete Model Number, Serial Number and type of gas.
High Altitude
When installing this unit at an elevation above 2000 feet (in the United States) it may be necessary to decrease the input rating by
changing the existing burner orice to a smaller size. Generally,
input should be reduced 4 percent for each 1000 feet above sea level. However, if the heating value of the gas has been reduced, this general rule may not apply. Check with local gas utility for proper
orice size identication.
Canadian High Altitude
Altitude: 0-4500 feet (0-1370 m)
When installing this unit at an elevation above 4500 feet (in Canada), check with local authorities.
Consult your local gas utility for assistance in determining the proper
orice for location.
Preparation
This direct vent gas replace insert and its components are tested
and safe when installed in accordance with this Installation Manual.
Report to your dealer any parts damaged in shipment, specically
check glass condition. Do not install unit with damaged, incomplete, or substitute parts. Read all instructions before starting installation and follow these instructions carefully during installation to insure
maximum benet and safety. Failure to follow them will void your warranty and may present a re hazard.
The warranty will be voided by, and the warranter disclaims any responsibility for the following actions:
• Installation of any damaged replace insert or vent system
component.
• Modication of the replace insert or direct vent system.
• Installation other than as instructed by Empire Comfort Systems, Inc.
• Improper positioning of the logs or glass door assembly.
• Installation and/or use of any component part not manufactured or approved by manufacturer.
• This appliance comes standard with a 120 VAC cord assembly to accommodate control options and the blower accessory. An outlet box may be installed in a bottom back corner of the existing
solid fuel masonry or factory built replace to plug in the cord
assembly, or the supplied power cord may be routed out onto the hearth to a nearby outlet.
• A 120 VAC circuit fort this product must be protected with ground-fault circuit-interrupter protection, in compliance with the applicable electrical codes, when it is installed in locations such as in bathrooms or near sinks.
• Low voltage and 120 VAC voltage cannot be shared within the same wall box.
• Once the appliance installation is completed, the installer should check that control compartment wiring is secured in a manner as to not interfere with door latches, valve controls, or the louver assembly.
29393-9-0514 Page 5
SPECIFICATIONS
DV25IN(3,7)3L MODELS LP Nat
Input Btu/hr Maximum 25,000 25,000
Btu/hr Minimum 17,000 17,000
KWH (Maximum) 7.30 7.30
(Minimum) 5.00 5.00
Orice #53 (0.0596) #42 (0.0935)
Air Shutter Opening Full Open 1/8”
DV33IN(3,7)3L MODELS LP Nat
Input Btu/hr Maximum 33,000 33,000
Btu/hr Minimum 25,000 23,000
KWH (Maximum) 9.57 9.57
(Minimum) 7.30 6.67
Orice 1.65 mm #36 (0.1065)
Air Shutter Opening Full Open 5/16”
DV35IN(3,7)3L MODELS LP Nat
Input Btu/hr Maximum 35,000 35,000
Minimum 27,000 25,000
KWH (Maximum) 10.15 10.15
(Minimum) 7.83 7.30
Orice #51 (0.067) #33 (0.113)
Air Shutter Opening Full Open 3/16”
Venting
Kits
DVKI
DVVK3FV
DVK35
NOTICE: When installing vent caps, special locally made
ashings may be required to properly seal the vent system to the
existing chimney termination.
Description Contents
One piece of 35’ FlexVent (split for 17 1/2’ vent run), Round Cap,
Vertical Vent
Kit 17 1/2’
Vertical Vent
Kit 25’
Vent
Extension Kit
Flashing, connectors, and clamps. Recommended when installing to
an existing round replace chimney
pipe. Two pieces of 25’ FlexVent,
Rectangle Cap, Flashing, connectors, and clamps Recommended when installing to a
square or rectangular clay ue. 35’ ex vent extension section with
2 connectors and 4 clamps
Surround
Kit
S253BL
S333BL
S353BL
S256BL
S336BL
S356BL
DS25661BL
DS33661BL
DS35661BL
SC256BL
SC336BL
SC356BL
Surround
Cover
C253BL Surround Bottom Cover for DV25IN for S253BL
C333BL Surround Bottom Cover for DV33IN for S333BL
C353BL Surround Bottom Cover for DV35IN for S353BL
C256BL Surround Bottom Cover for DV25IN for S256BL
C336BL Surround Bottom Cover for DV33IN for S336BL
C356BL Surround Bottom Cover for DV35IN for S356BL
Shroud Description
SH1BL
Description
Contemporary Black Surround for DV25IN, 6 x 3 inch
Contemporary Black Surround for DV33IN, 6 x 3 inch
Contemporary Black Surround for DV35IN, 6 x 3 inch
Contemporary Black Surround for DV25IN, 6 x 6 inch
Contemporary Black Surround for DV33IN, 6 x 6 inch
Contemporary Black Surround for DV35IN, 6 x 6 inch
3-sided Black Surround for DV25IN, 6 x 6 inch - Required to use any Decorative Doors, Fronts, or Contemporary Frames
3-sided Black Surround for DV33IN, 6 x 6 inch - Required to use any Decorative Doors, Fronts, or Contemporary Frames
3-sided Black Surround for DV33IN, 6 x 6 inch - Required to use any Decorative Doors, Fronts, or Contemporary Frames
Traditional Cast Iron Surround for DV25IN, 6 x 6 inch
Traditional Cast Iron Surround for DV33IN, 6 x 6 inch
Traditional Cast Iron Surround for DV35IN, 6 x 6 inch
Description
Shroud, Black (For replace openings up to 48”x 36”
- Requires a surround)
Remote Control
Accessories
FRBC Millivolt Battery Remote ON/OFF
FRBTC Millivolt Battery Remote Thermostat
TRW Millivolt WIRELESS Wall Thermostat
TMV Millivolt Reed Switch Wall Thermostat
FWS-1 Millivolt Wall Switch
Description
Firescreen Description
DVFS25TBL Firescreen accessory for DV25IN series
DVFS25TBL Firescreen accessory for DV33IN series
DVFS25TBL Firescreen accessory for DV35IN series
For additional information on decorative accessories, refer to pages 29 and 30.
29393-9-0514Page 6
FIREPLACE INSERT DIMENSIONS
When planning a replace insert installation, it’s necessary to
determine:
The vent system conguration to be used.
Gas supply piping.
Whether optional accessories - devices such as a wall switch
or remote control - are desired.
Electrical supply requirements for blower.
Proper opening size of replace required for installation of
the replace insert.
DV FIREPLACE INSERT DIMENSIONS
MODEL A B C D E F G H I J K L M N
DV25IN 19-3/4” 28 14-1/2” 11-1/8” 25-1/4” 12-3/4” 17” 18-5/16” 27” 6-3/4” 9” 20” 25-5/8” 40”
DV33IN 22-3/4” 31 16 14-1/8” 28-1/4” 14-1/4” 18-3/4” 21-5/16” 30” 8-1/4” 10-1/2” 21-1/2” 28-5/8” 43”
DV35IN 24-3/4” 34 16 16-1/8” 31-1/4” 14-1/4” 21-3/4” 23-5/16” 33” 8-1/4” 10-1/2” 23” 30-5/8” 46”
Figure 1
Fireplace Opening Dimensional Information/Sizing
MINIMUM FIREPLACE OPENING DIMENSIONS
MODEL
NO.
DV25IN 18-3/8” 27-1/2” 12-3/4” 17-1/4”
DV33IN 21-3/8” 30-1/2” 14-1/4” 19”
DV35IN 23-3/8” 33-1/2” 14-1/4” 22”
*NOTICE: If the replace lintel is wider than 8” (203mm), the height of the replace opening must be increased a few inches to
allow for a gradual offset in the exhaust and/or intake vent pipes.
HEIGHT
A*
FRONT
WIDTH
B
DEPTH
C
REAR
WIDTH
D
C
D
A
B
29393-9-0514 Page 7
Figure 2
MANTEL AND TRIM CLEARANCES
Figure 3
Distance from
Face of Fireplace
A 10” N 23”
B 9-1/4” O 22”
C 8-3/4” P 21”
D 8” Q 20”
E 7-1/4” R 19”
F 6-1/2” S 18”
G 6” T 17”
H 5-1/4” U 16”
I 4-1/2” V 15”
J 3-3/4” W 14”
K 3” X 13”
L 2-1/2” Y 12”
M 1-3/4” Z 11”
Combustible Material
No greeting cards, stockings or ornamentation of any type should
be placed on or attached to the replace. The ow of heat can
ignite combustibles.
Height Above Top of Insert
Figure 4
29393-9-0514Page 8
GAS SUPPLY
The gas pipeline can be brought in through the right or left side of the appliance. The insert has a Flexline with shutoff valve located on the right side when facing the unit. See Figures 5 and 6. Consult the current National Fuel Gas Code, ANSI Z223.1 CAN/CGA-B149 (.1 or .2) installation code.
Recommended Gas Pipe Diameter
Pipe Length Schedule 40 Pipe
Inside Diameter
Nat. L.P. Nat. L.P.
0-10ft
0-3m
11-40ft
4-12m
41-100ft
13-30m
101-150ft
31-46m
NOTICE: Never use plastic pipe. Check to conrm whether your
local codes allow copper tubing or galvanized. NOTICE: Since some municipalities have additional local codes, it is always best to consult your local authority and installation code.
The use of the following gas connectors is recommended:
— ANS Z21.24 Appliance Connectors of Corrugated Metal Tubing
and Fittings.
— ANS Z21.45 Assembled Flexible Appliance Connectors of Other
Than All-Metal Construction The above connectors may be used if acceptable by the authority having jurisdiction. The state of Massachusetts requires that a
exible appliance connector cannot exceed three feet in length.
1/2"
12.7mm
1/2"
12.7mm
1/2"
12.7mm
3/4"
19mm
3/8"
9.5mm
1/2"
12.7mm
1/2"
12.7mm
1/2"
12.7mm
Tubing, Type L Outside Diameter
1/2"
12.7mm
5/8"
15.9mm
3/4"
19mm
7/8"
22.2mm
3/8"
9.5mm
1/2"
12.7mm
1/2"
12.7mm
3/4"
1.9 mm
Installing the Main Gas Cock
Each appliance should have its own manual gas cock. A manual main gas cock should be located in the vicinity of the unit. Where none exists, or where its size or location is not adequate, contact your local authorized installer for installation or relocation. Compounds used on threaded joints of gas piping shall be resistant
to the action of liqueed petroleum gases. The gas lines must be
checked for leaks by the installer. This should be done with a soap solution watching for bubbles on all exposed connections, and if unexposed, a pressure test should be made.
Never use an exposed ame to check for leaks. Appliance must
be disconnected from piping at inlet of control valve and pipe capped or plugged for pressure test. Never pressure test with appliance connected; control valve will sustain damage!
NOTICE: The millivolt gas controls are equipped with a captured screw type pressure test point, therefore it is not necessary to provide a 1/8” test point up stream of the control.
When using copper or ex connector use only approved ttings.
The appliance and it’s individual shut off valve must be disconnected from supply piping system during any pressure testing of that system at test pressures in excess of 1/2 psig (3.5kPa). The appliance must be isolated from the gas supply piping system by closing its individual manual shut off valve during any pressure testing of the gas supply piping system at test pressures equal to or less than 1/2 psig (3.5kPa). Attention! If one of the procedures results in pressures in excess of
1/2 psig (14” w.c.) (3.5 kPa) on the replace gas valve, it will result
in a hazardous condition.
Checking Manifold Pressures
Both Propane and Natural gas valves have a built-in pressure regulator in the gas valve. Natural gas models will have a manifold pressure of approximately 3.5” w.c. (.871kPa) at the valve outlet with the inlet pressure to the valve from a minimum of 4.5” w.c. (1.120kPa) for the purpose of input adjustment to a maximum of
14.0” w.c. (3.484kPa). Propane gas models will have a manifold pressure approximately 10.0” w.c. (2.49kPa) at the valve outlet with the inlet pressure to the valve from a minimum of 10.8” w.c. (2.68kPa) for the purpose of input adjustment to a maximum of
14.0” w.c. (3.484kPa).
Figure 5
Gas Supply Pressure (inches w.c.)
Minimum Normal Maximum
Natural Gas 4.5" 7.0" 14.0"
LP (Propane) 10.8" 11.0" 14.0"
Manifold Pressure (inches w.c.)
Normal (HI)
Natural Gas 3.5"
LP (Propane) 10.0"
29393-9-0514 Page 9
Figure 6
VENTING AND INSTALLATION
1. Before beginning, remove glass door and log package from
unit. Also check to make sure there is no hidden damage to
the unit. Take a minute and plan out the gas, venting and elec-
trical route. It is best to start with the gas line rst, followed by
the chimney liner and electrical supply requirements.
2. Minimum replace opening requirements are shown in
Figure 2 of this installation manual. The rebrick (refractory),
glass doors, screen rails, screen mesh and log grates can be
removed from a factory built replace in order to gain mini-
mum gas insert opening requirements prior to installing the
gas replace insert.
3. This insert requires no hearth extensions. Combustible ma-
terial on the oor may be installed up to the insert. Do not
obstruct the lower louver of the insert. The original replace
cannot be returned to solid fuel in this condition.
4. The metal oor of the solid fuel rebox may be removed to
facilitate the installation of the insert. CLEARANCE TO COM-
BUSTIBLE MATERIAL UNDER THE INSERT IS 1/4”. YOU
MUST USE THE LEVELING LEGS TO RAISE THE INSERT
A MINIMUM OF 1/4” IF THE INSERT IS TO SIT ON COM-
BUSTIBLE MATERIAL. The side walls and top structure of the
rebox may not be altered with the exception of removable
bafes and dampers. Smoke shields, shelves and bafes may
be removed if attached with mechanical fasteners. The origi-
nal replace cannot be returned to solid fuel in this condition.
5. The original specied clearances of a factory-built re-
place must be maintained, with the exception of the hearth.
Clearances on a masonry replace must be maintained
at 12” from the opening for combustible projections over
1 1/2”. Clearances for combustible projections under
1 1/2” must be maintained at 6” from the opening per
NFPA211. Plan the surround size accordingly. A surround
must be used with the insert. UNDER NO CIRCUMSTANCE
CAN COMBUSTIBLE MATERIAL BE PLACED BEHIND THE
SURROUND!
6. The insert surround is tested and approved with this gas in-
sert and may cover existing air circulation vents or grills on the
solid fuel replace it is installed into. If the surround does not
cover the entire ventilation grill surface, the exposed grill area
should be left open.
NOTICE: Surround panel kits have been tested and approved to cover existing air circulation vents or grills.
NOTICE: Cutting of sheet metal parts of a replace in order to install the replace insert is prohibited.
WARNING
Only the surround as supplied may be used to cover inte­gral grills on the solid fuel-burning replace. No other com­ponents such as shrouds, sheet metal plates, etc. may be used to seal off vents.
7. To assure top performance, safety and efciency, inserts must be installed with an approved ue liner as per CAN/CGA B-149
or National Fuel Code ANSI Z223 and these instructions.
NOTICE: The following statement is also provided on a sepa­rate label plate in the instruction packet. Prior to installation
of the replace insert, the installer must mechanically secure this warning plate to the inside of the replace for future ref-
erence as required.
WARNING
The solid fuel replace has been converted for use with gas
only and cannot be used for burning wood or solid fuels un-
less all original parts have been replaced and the replace
has been reapproved by the authority having jurisdiction.
8. The solid fuel replaces’ ue damper must be fully locked in the open position or removed for installation of the gas re-
place insert.
9. The replace and replace chimney must be cleaned and in
good working order and constructed of noncombustible mate­rials.
10. Make sure that all chimney cleanouts t properly so air cannot
leak into the chimney.
11. Install the insert without the surround panels attached and make all gas, venting, and electrical connections.
12. To complete the installation, install surround panel assembly. Please refer to instructions included with the surround panel kit.
CAUTION
Ensure there are no obstructions to side air passages of decorative trim once installed on insert.
INSTALLING THE VENT SYSTEM
Vent System Installation Precautions
Before starting installation of vent kits, the installer should read these instructions and the Vent Kit Instructions to ensure that a proper vent installation is completed. Consult your local Building Codes before beginning the Installation.
WARNING
THIS GAS INSERT AND VENT ASSEMBLY MUST BE VENTED DIRECTLY TO THE OUTSIDE AND MUST NEVER BE ATTACHED TO A CHIMNEY SERVING A SEPARATE SOLID FUEL BURNING APPLIANCE. EACH GAS APPLIANCE MUST USE A SEPARATE VENT SYSTEM. COMMON VENT SYSTEMS ARE PROHIBITED.
29393-9-0514Page 10
VENTING AND INSTALLATION
Vent System Approvals Figure 8 shows the vent termination caps and systems approved
for use with these models. Approved vent system terminations are
labeled for identication. 3-inch diameter listed exible aluminum
or stainless steel gas vent is used for both the incoming combustion air and exhaust vent pipes. NO OTHER VENTING SYSTEMS OR COMPONENTS MAY BE USED. Detailed installation instructions are included with each vent termination kit and should be used in conjunction with this manual.
Horizontal Venting The vent system on this model CANNOT be terminated horizontally.
Vertical Venting
The inlet and exhaust vent pipes MUST be connected to the proper collars on the unit AND to the termination cap or the unit will not
operate. The intake vent collar is identied by a stamped “I” on the
top collar sliding vent plate assembly.
WARNING
MAJOR U.S. BUILDING CODES SPECIFY MINIMUM CHIMNEY AND/OR VENT HEIGHT ABOVE THE ROOF TOP. THESE MINIMUM HEIGHTS ARE NECESSARY IN THE INTEREST OF SAFETY. SEE FIGURES 8 THROUGH 10 FOR MINIMUM HEIGHTS, PROVIDED THE TERMINATION CAP IS AT LEAST 2-FEET FROM A VERTICAL WALL AND 2-FEET BELOW A HORIZONTAL OVERHANG.
Note: This also pertains to vertical vent systems installed on the
outside of the building.
WARNING
THE EXHAUST PIPE MUST ONLY BE CONNECTED TO THE EXHAUST STARTING COLLAR OF THE UNIT AND TO THE EXHAUST COLLAR OF THE TERMINATION CAP.
THE INLET AIR PIPE MUST ONLY BE CONNECTED TO THE INLET AIR STARTING COLLAR OF THE UNIT AND TO THE INLET AIR COLLAR OF THE TERMINATION CAP. BOTH THE INLET VENT AND THE FLUE VENT MUST BE CONNECTED FROM THE INSERT TO THE VENT TERMINATION CAP.
NOTICE: The minimum vertical vent rise is 10 feet and the maximum vertical vent rise is 35 feet. These dimensions are measured from the starting collars of the unit to the end of the last section of vent pipe. See Figure 8. NOTICE: The damper of the masonry chimney may need to be
removed to allow installation of the exible-vent pipe.
When installing into a zero clearance, factory built wood-burning
replace, the use of the DVKI Round Vertical Termination Kit should
allow you to mount the vent adaptor and cap to the exposed round chimney pipe easily.
Connecting the Vent Pipe
CAUTION
Sharp edges. Always use gloves when installing.
Install the 3-inch exible vent pipes down through the chimney.
Attach the pipe-to-cap adaptor to the termination cap and the top of
the exible vent pipe, then install the cap to the top of the chimney.
Remove the vent slide plate assembly from the top of the insert. See Figure 7. Trim off excess venting then attach and secure
the bottom ends of the ex pipes to the starting collars with the
adjustable band clamps provided. Slide the gas insert into place,
and position any excess ex vent pipe back up into the chimney. Begin installation of the insert into the replace opening. Align the
vent slide plate assembly with the guides located on top of the
insert. Work the insert inch by inch into the replace cavity as you
pull forward on the vent slide plate assembly. Do not use excessive force on the vent slide plate. Once the vent slide plate is close to seating, install the black button head 5/16-18 x 2 1/2” long bolt
through the center hole of the insert top ange, and into the vent
slide plate nut. Using the hex key wrench provided, tighten the bolt until the vent slide plate is seated forward completely.
Positioning, Leveling, and Securing Insert
1. Place the insert into position.
NOTICE: The front anges of the insert (without surround panels)
should be set at approximately 1”(inch) in front of the face of the
replace.
2. Level the insert from side to side and front to back.
3. If necessary, use the leveling bolts included in the instruction pack. Screw the legs into the nuts installed in the bottom of the insert. Turn legs in until insert is level. Note: If desired, it is acceptable to attach metal strapping or
brackets (not provided) from the replace cavity to the insert outer jacket to secure the Fireplace Insert to the replace
hearth or opening.
CAUTION
TO AVOID DOWNDRAFTS AND/OR COLD AIR PROBLEMS, IT IS RECOMMENDED TO SEAL OFF THE AREA BETWEEN THE TERMINATION CAP AND THE TOP OF THE SOLID­FUEL CHIMNEY OPENING INTO WHICH THE VENT CAP HAS BEEN INSTALLED.
29393-9-0514 Page 11
Figure 7