If not installed, operated and maintained in
accordance with the manufacturer’s instructions, this product could expose you to substances in fuel or from fuel combustion which
can cause death or serious illness.
NOT INTENDED FOR USE AS A PRIMARY HEAT
SOURCE. This appliance is tested and approved as
either supplemental room heat or as a decorative
appliance. It should not be factored as primary heat
in residential heating calculations.
This appliance is only for use with the type of gas
indicated on the rating plate. This appliance is not
convertible for use with other gases, unless a certied
kit is used.
UL FILE NO.
MH45034
WARNING
HOT GLASS
CAUSE BURNS.
DO NOT TOUCH
UNTIL COOLED.
NEVER
A barrier designed to reduce the risk of burns from the
hot viewing glass is provided with this appliance and shall
be installed for the protection of children and other at-risk
individuals.
ALLOW CHILDREN
TO TOUCH GLASS.
WILL
GLASS
Page 1
TABLE OF CONTENTS
SECTION PAGE
Important Safety Information ...................................................................................................................................... 3
Safety Information for Users of Propane Gas ............................................................................................................. 4
Gas Supply .............................................................................................................................................................. 8-9
Standing Pilot Wiring Diagram .................................................................................................................................. 18
Standing Pilot Lighting Instructions ........................................................................................................................... 19
Standing Pilot Troubleshooting ................................................................................................................................. 20
Standing Pilot Propane Gas Conversion ............................................................................................................. 21-22
fire-parts.com
IPI Electronic System Operating Instructions ........................................................................................................... 23
IPI Electronic System Wiring Diagram ...................................................................................................................... 24
Intermittent Pilot Lighting Instructions ...................................................................................................................... 25
Intermittent Control System Troubleshooting ....................................................................................................... 26-28
Intermittent Pilot Propane Gas Conversion ......................................................................................................... 29-30
Maintenance and Service ......................................................................................................................................... 31
BVD34 Parts List ...................................................................................................................................................... 32
BVD34 Parts View .................................................................................................................................................... 33
BVD36 Parts List ...................................................................................................................................................... 34
BVD36 Parts View .................................................................................................................................................... 35
BVP42 Parts List ....................................................................................................................................................... 36
BVP42 Parts View .................................................................................................................................................... 37
Appliance Service History .................................................................................................................................... 43-44
Master Parts Distributor List ..................................................................................................................................... 45
How To Order Repair Parts ....................................................................................................................................... 45
Before enclosing the vent pipe assembly, operate the appliance to ensure it is venting properly.
DO NOT OPERATE THIS APPLIANCE WITHOUT GLASS FRONT PANEL INSTALLED
WARNING
1. “Due to high temperatures, the appliance should be
located out of trafc and away from furniture and
draperies.”
2. “Children and adults should be alerted to the hazards
of high surface temperature and should stay away to
avoid burns or clothing ignition.”
3. “Young children should be carefully supervised when they
are in the same room as the appliance. Toddlers, young
children, and others may be susceptible to accidental
contact burns. A physical barrier is recommended if there
are at-risk individuals in the house. To restrict access to a
replace or stove, install an adjustable safety gate to keep
toddlers, young children, and other at-risk individuals out
of the room and away from hot surfaces.”
4. For appliances requiring a barrier, as determined under
Clause 5.15.4: “A barrier designed to reduce the risk of
burns from the hot viewing glass is provided with this
appliance and shall be installed for the protection of
fire-parts.com
children and other at-risk individuals.”
5. “If the barrier becomes damaged, the barrier shall
be replaced with the manufacturer’s barrier for this
appliance.
”
6. “Clothing or other ammable material should not be
placed on or near the appliance.”
7. “Any safety screen, guard, or barrier removed for
servicing an appliance must be replaced prior to
operating the appliance” (see Clause 4.1.6).
8. “Installation and repair should be done by a qualied
service person. The appliance should be inspected
before use and at least annually by a professional service
person. More frequent cleaning might be required due to
excessive lint from carpeting, bedding material, et cetera.
It is imperative that control compartments, burners, and
circulating air passageways of the appliance be kept
clean.”
9. The instructions for an appliance optionally for use
with glass doors (or equivalent) shall state that, “Only
doors certied with the appliance shall be used.”
10. The instructions for an appliance not intended for use
with glass doors (or equivalent) shall emphasize that
the appliance is not for use with glass doors.
11. Where applicable, provide a means by which the
consumer can identify the barrier, (such as graphic
representation, clear description, or reference marking).
WARNING
CARBON MONOXIDE POISONING HAZARD
Failure to follow the steps outlined below for each appliance
connected to the venting system being placed into operation
could result in carbon monoxide poisoning or death.
The following steps shall be followed for each appliance
connected to the venting system being placed into operation,
while all other appliances connected to the venting system
are not in operation:
1. Seal any unused openings in the venting system.
2. Inspect the venting system for proper size and horizontal
pitch, as required in the National Fuel Gas Code ANSI
Z223.1/NFPA 54 or the National Gas and Propane
Installation Code CSA B149.1 and these instructions.
Determine that there is no blockage or restriction,
leakage, corrosion and other deciencies which could
cause an unsafe condition.
3. As far as practical, close all building doors and
windows and all doors between the space in which
the appliance(s) connected to the venting system are
located and other spaces of the building.
4. Close replace dampers.
5. Turn on clothes dryers and any appliance not connected
to the venting system. Turn on any exhaust fans, such
as range hoods and bathroom exhausts, so they are
operating at maximum speed. Do not operate a summer
exhaust fan.
6. Follow the lighting instructions. Place the appliance
being inspected into operation. Adjust the thermostat
so appliance is operating continuously.
7. Test for spillage from draft hood equipped appliances
at the draft hood relief opening after 5 minutes of main
burner operation. Use the ame of a match or candle.
8. If improper venting is observed during any of the
above tests, the venting system must be corrected
in accordance with National Fuel Gas Code, ANSI
Z223.1/NFPA and/or National Gas and Propane Installation Code, CSA B149.1.
9. After it has been determined that each appliance
connected to the venting system properly vents when
tested as outlined above, return doors, windows,
exhaust fans, replace dampers and any other gas-red
burning appliance to their previous conditions of use.
38142-2-0719Page 3
SAFETY INFORMATION FOR USERS OF PROPANE GAS
Propane is a ammable gas which can cause res and explosions.
In its natural state, propane is odorless and colorless. You may
not know all the following safety precautions which can protect
both you and your family from an accident. Read them carefully
now, then review them point by point with the members of your
household. Someday when there may not be a minute to lose,
everyone’s safety will depend on knowing exactly what to do.
If, after reading the following information, you feel you still need
more information, please contact your gas supplier.
PROPANE GAS WARNING ODOR
If a gas leak happens, you should be able to smell the gas
because of the odorant put in the Propane Gas. That's your
signal to go into immediate action!
• Do not operate electric switches, light matches, use your phone.
Do not do anything that could ignite the gas.
• Get everyone out of the building, vehicle, trailer, or area. Do
that IMMEDIATELY.
• Close all gas tank or cylinder supply valves.
• Propane Gas is heavier than air and may settle in low areas
such as basements. When you have reason to suspect a gas
leak, keep out of basements and other low areas. Stay out until
reghters declare them to be safe.
fire-parts.com
• Use your neighbor’s phone and call a trained Propane Gas
service person and the re department. Even though you may
not continue to smell gas, do not turn on the gas again. Do not
re-enter the building, vehicle, trailer, or area.
• Finally, let the service man and reghters check for escaped
gas. Have them air out the area before you return. Properly
trained Propane Gas service people should repair the leak,
then check and relight the gas appliance for you.
NO ODOR DETECTED - ODOR FADE
Some people cannot smell well. Some people cannot smell
the odor of the chemical put into the gas. You must nd out if
you can smell the odorant in propane. Smoking can decrease
your ability to smell. Being around an odor for a time can affect your
sensitivity or ability to detect that odor. Sometimes other odors in
the area mask the gas odor. People may not smell the gas odor or
their minds are on something else. Thinking about smelling a gas
odor can make it easier to smell.
The odorant in Propane Gas is colorless, and it can fade under
some circumstances. For example, if there is an underground
leak, the movement of the gas through soil can lter the odorant.
Odorants in Propane Gas also are subject to oxidation. This fading
can occur if there is rust inside the storage tank or in iron gas pipes.
The odorant in escaped gas can adsorb or absorb onto or into
walls, masonry and other materials and fabrics in a room. That will
take some of the odorant out of the gas, reducing its odor intensity.
Propane Gas may stratify in a closed area, and the odor intensity
could vary at different levels. Since it is heavier than air, there may
be more odor at lower levels. Always be sensitive to the slightest gas
odor. If you detect any odor, treat it as a serious leak. Immediately
go into action as instructed earlier.
SOME POINTS TO REMEMBER
• Learn to recognize the odor of Propane Gas. Your local Propane
Gas Dealer can give you a “Scratch and Sniff” pamphlet. Use
it to nd out what the propane odor smells like. If you suspect
that your Propane Gas has a weak or abnormal odor, call your
Propane Gas Dealer.
• If you are not qualied, do not light pilot lights, perform service,
or make adjustments to appliances on the Propane Gas system.
If you are qualied, consciously think about the odor of Propane
Gas prior to and while lighting pilot lights or performing service
or making adjustments.
• Sometimes a basement or a closed-up house has a musty
smell that can cover up the Propane Gas odor. Do not try to
light pilot lights, perform service, or make adjustments in an
area where the conditions are such that you may not detect
the odor if there has been a leak of Propane Gas.
• Odor fade, due to oxidation by rust or adsorption on walls of
new cylinders and tanks, is possible. Therefore, people should
be particularly alert and careful when new tanks or cylinders
are placed in service. Odor fade can occur in new tanks, or
reinstalled old tanks, if they are lled and allowed to set too
long before relling. Cylinders and tanks which have been out
of service for a time may develop internal rust which will cause
odor fade. If such conditions are suspected to exist, a periodic
sniff test of the gas is advisable. If you have any question
about the gas odor, call your Propane Gas Dealer. A periodic sniff test of the Propane Gas is a good safety measure
under any condition.
• If, at any time, you do not smell the Propane Gas odorant and
you think you should, assume you have a leak. Then take the
same immediate action recommended above for the occasion
when you do detect the odorized Propane Gas.
• If you experience a complete “gas out,” (the container is under
no vapor pressure), turn the tank valve off immediately. If the
container valve is left on, the container may draw in some air
through openings such as pilot light orices. If this occurs, some
new internal rusting could occur. If the valve is left open, then
treat the container as a new tank. Always be sure your container is under vapor pressure by turning it off at the container
before it goes completely empty or having it relled before it is
completely empty.
38142-2-0719Page 4
INTRODUCTION
Instructions to Installer
1. Installer must leave instruction manual with owner after
installation.
2. Installer must have owner ll out and mail warranty card supplied
with the replace.
3. Installer should show owner how to start and operate the replace.
This is a B-Vent gas appliance and must be installed with a listed
B-Vent vent system. The information contained in this manual pertains
to all models and gas control systems unless otherwise noted.
WARNING
This unit is not for use with solid fuels.
Appliance Certication
This replace is design certied in accordance with American
National Standard/CSA Standard ANSI Z.21-50/CSA 2.22 and by
Underwriters Laboratories as a Vented Gas Appliance and shall be
installed according to these instructions.
Consult your local building code agency, prior to installation, to ensure
compliance with local codes-including permits and inspections.
The replace, when installed, must be electrically grounded in
accordance with local codes or, in absence of local codes, with
the National Electric Code ANSI/NFPA 70 if an external electrical
source is utilized.
These models may be installed in a bedroom or bed-sitting room
in the U.S.A.
fire-parts.com
Qualied Installing Agency
Installation and replacement of gas piping, gas utilization equipment
or accessories and repair and servicing of equipment shall be
performed only by a qualied agency. The term “qualied agency”
means any individual, rm, corporation or company which either in
person or through a representative is engaged in and is responsible for
(a) the installation or replacement of gas piping or (b) the connection,
installation, repair or servicing of equipment, who is experienced in
such work, familiar with all precautions required and has complied
with all the requirements of the authority having jurisdiction.
The installation must conform with local codes or, in the absence of
local codes, with the National Fuel Gas Code ANSI Z223.1/NFPA
54* Natural Gas and Propane Installation Code, or CSA B149.1 in
Canada. *Available from the American National Standards Institute,
Inc. 11 West 42nd St., New York, N.Y. 10036.
Commonwealth of Massachusetts: The installation must be
made by a licensed plumber or gas tter in the Commonwealth
of Massachusetts. The Commonwealth of Massachusetts
requires that a exible appliance connector cannot exceed three
feet in length.
Any alteration of the original design, installed other than as
shown in these instructions or use with a type of gas not
shown on the rating plate is the responsibility of the person
and company making the change.
Important
All correspondence should refer to complete Model Number, Serial
Number and type of gas.
High Altitude
When installing this unit at an elevation above 2000 feet (in the
United States) it may be necessary to decrease the input rating by
changing the existing burner orice to a smaller size. Generally,
input should be reduced 4 percent for each 1000 feet above sea
level. However, if the heating value of the gas has been reduced,
this general rule may not apply. Check with local gas utility for proper
orice size identication.
Canadian High Altitude
Altitude: 0-4500 feet (0-1370 m)
When installing this unit at an elevation above 4500 feet (in Canada),
check with local authorities.
Consult your local gas utility for assistance in determining the proper
orice for location.
Preparation
This gas replace and its components are tested and safe when
installed in accordance with this Installation Manual. Report to your
dealer any parts damaged in shipment, specically check glass
condition. Do not install unit with damaged, incomplete, or substitute
parts. Read all instructions before starting installation and follow
these instructions carefully during installation to insure maximum
benet and safety. Failure to follow them will void your warranty and
may present a re hazard.
The warranty will be voided by, and the warrantor disclaims any
responsibility for the following actions:
• Installation of any damaged replace or vent system component.
• Modication of the replace or vent system.
• Installation other than as instructed by Empire Comfort Systems,
Inc.
• Improper positioning of the logs, glass door, optional accessories
or decorative rock.
• Installation and/or use of any component part not manufactured
or approved by manufacturer.
Glass Specications
Optional glass door kits manufactured with tempered glass
may be installed in hazardous locations such as bathtub
enclosures as dened by the Consumer Product Safety Commission
(CPSC). The tempered glass has been tested and certied to the
requirements of ANSI Z97.1 and CPSC 16 CFR 1202(Safety Glazing Certication Council SGCC# 1595 and 1597.
Architectural Testing, Inc. Reports 02-31919.01 and
02-31917.01).
This statement is in compliance with CPSC 16 CFRSection
1201.5 "Certication and labeling requirements" which refers
to 15 U.S. Code (USC) 2063 stating "...Such certicate shall
accompany the product or shall otherwise be furnished to any distributor or retailer to whom the product is delivered."
WARNING
ANY CHANGE TO THIS FIREPLACE OR ITS CONTROLS
CAN BE DANGEROUS.
Improper installation or use of the replace can cause
serious injury or death from re, burns, explosions, or
carbon monoxide poisoning.
38142-2-0719Page 5
RIGHT SIDE VIEW
J
H
GAS CONTROLS BEHIND LOWER
LOUVER OR UNDER SLIDING
HEARTH ACCESS DOOR
K
K
L
M
M
G
O
N
P
G
SPECIFICATIONS
BVD34FPBVD36FPBVP42FP
Input Btu/hr
Maximum
KWH (Maximum)6.27.38.8
B-Vent Size4" Diameter6" Diameter6" Diameter
Orice
Air Shutter Opening1/8" (3.2mm)1/8"(3.2mm)1/8" (3.2mm)
*PROPANE (CONVERSION KIT REQUIRED)
Orice
Air Shutter Opening 5/16" (7.9mm)5/16" (7.9mm)Full Open
Height without
standoff
Width37" (940mm)39" (990mm)43" (1,092mm)
Depth
Gas Inlet Shutoff
Valve (Pipe)
*NOTE: Refer to page 21 for millivolt valve conversion kit numbers. Refer
to page 29 for IP valve conversion kit numbers.
REMOTE CONTROL
OPTIONS AND ACCESSORIES
FRBCMillivolt Battery Remote On/Off
fire-parts.com
FWS-1Direct Ignition/Millivolt Wall Switch
21,00025,00030,000
NATURAL (STANDARD)
#44 (.086)
P-252
1.35mm
P-289
32 3/4"
(832mm)
14 7/8"
(378mm)
1/2 NPT1/2 NPT1/2NPT
#42 (.0935)
P-286
1.45 mm
P-208
34 3/4"
(883mm)
18 3/8"
(467mm)
DESCRIPTION
#37 (.104)
P-213
1.65mm
P-250
34 3/4"
(883mm)
18 3/8"
(467mm)
NOTE: Air shutter settings are factory minimum settings. Some
venting congurations may require minor air shutter adjustments
for optimum performance.
GAS CONVERSION KITS
Conversion KitConversion TypeUsed On
BVCK34PNatural To Propane BVD34FP30
BVCK36PNatural To Propane BVD36FP30
BVCK42PNatural To Propane BVP42FP30
38146Natural To Propane BVD34FP70
38147Natural To Propane BVD36FP70
38148Natural To Propane BVP42FP70
FIREPLACE DIMENSIONS
DimBVD34BVD36BVP42
37" 940mm39" 990mm43" 1092mm
A
34" 864mm36" 914mm40" 1,016mm
B
22 7/8" 581mm24 7/8" 632mm24 7/8" 632mm
C
35 5/8" 905mm37 5/8" 956mm37 5/8" 956mm
D
32 3/4" 832mm34 3/4" 883mm34 3/4" 883mm
E
14 7/8" 378mm18 3/8 467mm18 3/8" 467mm
F
6 3/8" 162mm6 3/8" 162mm6 3/8" 162mm
G
5 7/8" 149mm8 3/8" 213mm6 3/8" 162mm
H
24 1/2" 622mm22 1/2" 572mm26 1/2" 673mm
I
12 1/4" 311mm11 1/4" 286mm13 1/4" 337mm
J
1 1/4" 32mm1 1/4" 32mm1 1/4" 32mm
K
31 3/4" 807mm33 3/4" 857mm33 3/4" 857mm
L
32 11/16" 830mm 34 11/16" 881mm 34 11/16" 881mm
M
2 1/16" 53mm2 1/16" 53mm2 1/16" 53mm
N
Figure 1
5 5/8" 143mm5 5/8" 143mm5 5/8" 143mm
O
4 7/8" 124mm4 7/8" 124mm4 7/8" 124mm
P
38142-2-0719Page 6
SEE MANTLE CHART FOR
MAXIMUM MANTLE DEPTH
NAILING
FLANGES
GLASS FRONT
(OPTIONAL)
TOP FRAMING
LEDGE
FINISHED WALL
(COMBUSTIBLE)
SEE MANTLE CHART
FOR MINIMUM HEIGHT
OF MANTLE ABOVE UNIT
2"x4" HEADER
STAND OFF
3" (76 mm) HEIGHT
ABOVE TOPOF
FIREPLACE
CLEARANCES
CLEARANCE TO COMBUSTIBLES
Back0" (0 mm)
Side0" (0 mm)
Floor0" (0 mm)
Top Stand-off0" (0 mm)
Top Framing Edge1" (25mm)
Mantel Chart (Figure 3)
12”(305mm)
10”(254mm)
MANTEL
COMBUSTIBLE TRIM AND MANTELS
ALLOWED IN SHADED AREA
3”
21/4”
1½”
3/4”
12”
10 3/4”
8”
TOP EDGE OF FIREPLACE
8”
6”
4½”
33/4”
6”
5”
4”
3”
2”
1”
1/4”
(6.35mm)
Figure 3
Clearances (Figure 4)
Clearance from top front edge of replace to ceiling is 36"
Clearance from side of replace to adjacent sidewall is 6".
fire-parts.com
Combustible Material
No greeting cards, stockings or ornamentation of any type
should be placed on or attached to the replace. The ow of
heat can ignite combustibles.
NOTE: When you install your Fireplace on
wall corner positions, a minimum of 6 inches
clearance must be maintained from the
perpendicular side wall and the screened
opening of the appliance.
Figure 2
Figure 4
LOCATING FIREPLACE
38142-2-0719Page 7
Figure 5
GAS SUPPLY
The gas pipeline can be brought in through the right or left
side of the appliance. Consult the current National Fuel Gas
Code, ANSI Z223.1 CAN/CGA-B149 (.1 or .2) installation code.
RECOMMENDED GAS PIPE DIAMETER
Pipe
Length
(Feet)
0-10
11-40
41-100
101-150
NOTE: Never use plastic pipe. Check to conrm whether your
local codes allow copper tubing or galvanized.
NOTE: Since some municipalities have additional local
codes, it is always best to consult your local authority and
installation code.
fire-parts.com
The use of the following gas connectors is recommended:
—ANSI Z21.24 Appliance Connectors of Corrugated Metal
the authority having jurisdiction. The Commonwealth of
Massachusetts requires that a exible appliance connector
cannot exceed three feet in length.
Schedule 40 Pipe
Inside Diameter
NaturaLPropaneNaturalPropane
1/2"
12.7mm
1/2"
12.7mm
1/2"
12.7mm
3/4"
19mm
3/8"
9.5mm
1/2"
12.7mm
1/2"
12.7mm
1/2"
12.7mm
Tubing, Type L
Outside Diameter
1/2"
12.7mm
5/8"
15.9mm
3/4"
19mm
7/8"
22.2mm
3/8"
9.5mm
1/2"
12.7mm
1/2"
12.7mm
3/4"
1.9 mm
Installing a New Main Gas Shut-Off
Each appliance should have its own manual gas shut-off.
A manual main gas shut-off should be located in the vicinity of
the unit. Where none exists, or where its size or location is not
adequate, contact your local authorized installer for installation or relocation.
Compounds used on threaded joints of gas piping shall be
resistant to the action of liqueed petroleum gases. The gas
lines must be checked for leaks by the installer. This should
be done with a soap solution watching for bubbles on all
exposed connections, and if unexposed, a pressure test
should be made.
Never use an exposed ame to check for leaks. Appliance
must be disconnected from piping at inlet of control valve
and pipe capped or plugged for pressure test. Never
pressure test with appliance connected; control valve
will sustain damage!
NOTE: The millivolt gas controls are equipped with a captured
screw type pressure test point, therefore it is not necessary
to provide a 1/8" test point up stream of the control.
On direct ignition valves, hex plugs may be replaced with
hose ttings for pressure checks, then reinstalled before
operating replace.
When using copper or ex connector use only approved
ttings
.
The appliance and it’s individual shut off valve must be
disconnected from supply piping system during any pressure
testing of that system at test pressures in excess of 1/2 psig
(3.5kPa).
The appliance must be isolated from the gas supply piping
system by closing its individual manual shut off valve during
any pressure testing of the gas supply piping system at test
pressures equal to or less than 1/2 psig (3.5kPa).
Attention! If one of the procedures results in pressures in
excess of 1/2 psig (14" w.c.) (3.5 kPa) on the replace gas
valve, it will result in a hazardous condition.
Figure 6
Gas Supply Pressure (inches w.c.)
MinimumNormalMaximum
Natural Gas4.5"7.0"14.0"
Propane Gas10.8"11.0"14.0"
Manifold Pressure (inches w.c.)
Normal (HI)
Natural Gas3.5"
Propane Gas10.0"
38142-2-0719Page 8
BURNER
GAS SUPPLY (CONT'D)
Checking Manifold Pressures
Both Propane and Natural Gas valves have a built-in pressure
regulator in the gas valve. Natural Gas models will have a
manifold pressure of approximately 3.5" w.c. (.871kPa) at
the valve outlet with the inlet pressure to the valve from a
minimum of 4.5" w.c. (1.120kPa) for the purpose of input
adjustment to a maximum of 14.0" w.c. (3.484kPa). Propane
Gas models will have a manifold pressure approximately 10.0"
w.c. (2.49kPa) at the valve outlet with the inlet pressure to the
valve from a minimum of 10.8" w.c. (2.68kPa) for the purpose
of input adjustment to a maximum of 14.0" w.c. (3.484kPa).
GAS LINE HOLE
3½”
FROM FRONT OF
APPLIANCE TO
GAS LINE HOLE
BVD34 SERIES-10”
BVD,P (36,42)-13½”
Figure 7
fire-parts.com
ASSEMBLY
REAR TA B (BURNER BASE)
LOCATIONS
FLEXIBLE GAS CONNECTOR
GAS SUPPLY LINE
PIEZO
IGNITER
FIREBOX BOTTOM
CUTOUT ACCESS
SLIDING
VALV E ACCESS
COVER
Figure 8
38142-2-0719Page 9
INSTALLATION
NAILOR OTHER SUITABLE FASTENER
MOUNTING
BRACKETS
B-
TO
COMBUSTIBLES
Framing and Finishing
1. Choose unit location.
2. Frame in replace with a header across the top. It is
important to allow for the nished face thickness when
setting the depth of the frame. See Figures 9 & 11.
3. Attach replace to framing using (4) adjustable nailing
anges. Preset depth to suit facing material (adjustable
to 1/2", 5/8" or 3/4" depths).
4. Use (8) 1/2" hex-head screws supplied in hardware
package to screw through slotted holes in nailing anges,
then screw into pre-drilled holes on replace side. Measure
from face of replace to face of the nailing anges to
determine nal depth.
fire-parts.com
Install the Fresh Air Kit - BVA1
A fresh air kit is available as an optional feature with this
appliance. The fresh air kit helps to decrease the amount
of room air taken by utilizing outside air for combustion. It is
strongly recommended that it be installed. Installation of the
fresh air kit should be performed at the framing stage of the
replace installation.
The fresh air kit installs on the left side of the replace.
To install the BVA1 fresh air kit, refer to the installation
instructions provided with the kit.
NOTE: The outside air kit can terminate at any level with
the exception that it must terminate at least 1 ft below the
vent termination cap. The fresh air kit inlet hood should be
positioned at least 2 ft above the ground level, in a manner
that will not allow snow, leaves, etc. to block the inlet.
WARNING
Exhaust products of gasoline engines are hazardous.
The outside air must not be taken from a garage
space, attic spaces, basements, or above the roong
where other heating appliance, fans, or chimneys
exhaust or utilize the air.
Framing (Figure 11)
Fireplace framing can be built before or after the replace is
set in place. Framing should be positioned to accommodate
wall covering and replace facing material. The replace
framing should be constructed of 2 x 4 lumber or heavier. The
framing headers may rest on the replace standoffs. Refer
to Figure 11 for minimum framing dimensions.
Figure 9
Vent Pipe Clearance
NOTE: Maintain one inch (1") of clearance around vertical
vent pipe. Follow the B-Vent system instructions for installation
requirements and clearances. Failure to follow the B-Vent
manufacturer's instructions may cause improper draft and
possible re hazard.
CAUTION
Measure replace dimensions and verify framing
methods, and wall covering details before framing
construction begins
Framing dimension "A" includes a three inch
clearance for standoffs on rebox.
Figure 10
38142-2-0719Page 10
INSTALLATION (CONT'D)
FINISHED WALL
JOINT BETWEEN FINISHED WALLAND
UNIT SEALED WITH 300°F149
MATERIAL (SEALANT IS OPTIONAL)
°C
SEALANT
COMBUSTIBLE SURROUND
MANTELSHELF
2X4
HEADER
STAND OFF
FRONT TRIM OR NON-COMBUSTIBLE
MATERIAL MAY OVERLAP BLACK PAINTED
FACE (INSTALLATION IS OPTIONAL)
Combustible Surround Installation
Minimum Framing Dimensions
BVD34BVD36BVP42
"A"
"B"
"C"
fire-parts.com
35 3/4"
(908mm)
37 3/8"
(949mm)
14 3/8"
(378mm)
37 3/4"
(959mm)
39 3/8"
(1,000mm)
17 7/8"
(454mm)
37 3/4"
(959mm)
43 3/8"
(1,102mm)
17 7/8"
(454mm)
NOTE: Dimension "C" is the minimum with the replace face extending 1/2"
in front of the framing to allow for nishing materials.
Figure 11
Attention: Add 3-3/4" to “A” dimensions when using a ush
mantel base.
Attention: If a base or mantel is not used and the appliance
is installed directly on carpeting, tile or other combustible
material other than wood ooring, it shall be installed on a
metal or wood panel extending the full width and depth of
the appliance. The vertical dimension in Figure 11 must be
adjusted when a metal or wood panel is placed beneath the
appliance.
Finishing (Figure 12)
Finish the walls with the material of your choice. Only
non-combustible materials may be used to cover the black
replace front.
WARNING
When nishing the replace never obstruct or modify
the air inlet/outlet louvers in any manner. Provide
adequate clearances around air openings into the
combustion chamber.
Caution: If the joints between the nished wall and the re-
place surround (top and sides) are sealed, a 300°F minimum
sealant material must be used. These joints are not required
to be sealed. Only non-combustible material (using 300°F
minimum adhesive if needed), can be applied as facing to
the replace surround.
Louvered Models
Figure 12a
Flush Face Models
Figure 12b
Attention: Cold climate installation recommendation:
When installing this unit against a non-insulated
exterior wall, it is recommended that the outer walls
be insulated to conform to applicable insulation
codes.
38142-2-0719Page 11
LOWEST
VENTING
Vent Runs
In planning the installation for the replace, it is necessary to
install certain components before the appliance is completely
positioned and installed. These include the vent system, gas
piping for the appliance, Fresh Air Kit, and the electrical wiring.
(The fan option is available for louvered models only. Electric
ignition models will require electrical service to junction box).
The appliance can be mounted on any of the following surfaces:
1. A at, hard combustible (burnable) surface.
2. A raised wooden platform.
3. Four (4) corner supports. (Example: Four (4) concrete
masonry blocks.) These supports must be positioned so
they contact all four (4) perimeter edges on the bottom
of the unit.
Locate and mark the center point of the vent pipe using a
nail on the underside of the roof. Drive the nail through the
center point. Mark the outline of the roof hole around this
center point.
NOTE: Size of the roof hole dimensions depend on the pitch
of the roof. There must be a 1 inch clearance (25mm)
to the vertical pipe sections. This clearance is to all
combustible material.
Cover the opening of the vent pipe and cut and frame the roof
hole. Use framing lumber the same size as the roof rafters
fire-parts.com
and install the frame securely. Flashing anchored to frame
must withstand high winds. The storm collar is placed over
this joint to make a water-tight seal. Non-hardening sealant
should be used to completely seal this ashing installation.
Determining Minimum Vent Height Above the Roof.
WARNING: Major U.S. building codes specify minimum
chimney and/or vent height above the roof top. These
minimum heights are necessary in the interest of safety.
These specications are summarized in Figures 14 and 15.
DISCHARGE
VENT CAP
GAS VENT
ROOF PITCHH (Min.)
Flat to 6/1212" (305 mm)
6/12 to 7/1215" (381 mm)
Over 7/12 to 8/1218" (457 mm)
Over 8/12 to 16/1224" (610 mm)
Over 16/12 to 21/1236" (914 mm)
OPENING
H
ROOF PITCH IS X/12
H (Min.)-Minimum height from
roof to lowest discharge opening
Note that for steep roof pitches, the vent height must be
increased. In high wind conditions, nearby trees, adjoining
roof lines, steep pitched roofs, and other similar factors can
result in poor draft, or down-drafting. In these cases, increasing
the vent height may solve this problem.
General Maintenance
Conduct an inspection of the venting system semi-annually.
Recommended areas to inspect are as follows:
1. Check areas of the venting system which are exposed
to the elements for corrosion. These will appear as rust
spots or streaks and, in extreme cases, holes. These
components should immediately be replaced.
2. Remove the cap and shine a ashlight down the vent.
Remove any bird nests or other foreign material.
3. Check for evidence of excessive condensate, such as
water droplets forming in the inner liner and subsequently
dripping out at joints. Condensate can cause corrosion
of caps, pipe and ttings. It may be caused by having
excessive lateral runs, too many elbows and exterior
portions of the system being exposed to cold weather.
4. Inspect joints to verify that no pipe sections or ttings have
been disturbed and, consequently, loosened. Also, check
mechanical supports, such as wall straps or plumbers’
tape for rigidity.
A removable panel or other means must be provided in the
enclosure for visual inspection of the ue connection.
NOTE: This also pertains to vertical vent systems installed
on the outside of the building.
Installing the Vent System in a Chase
A chase is a vertical box-like structure built to enclose the
gas appliance and/or it’s vent system. Vertical vent runs on
the outside of a building may be, but are not required to be
installed inside a chase.
CAUTION: Treatment of restop spacers and construction
of the chase may vary with the type of building. These
instructions are not substitutes for the requirements
of local building codes. Therefore, your local building
codes must be checked to determine the requirements
for these steps.
NOTE: When installing this vent system in a chase, it is always
good building practice to insulate the chase as you would the
outside walls of your home. This is especially important for cold
climate installations. Upon completion of building your chase
framing, install the vent system by following the instructions in
this manual. Remember to build the chase large enough so
that minimum clearance of combustible materials (including
insulation) to the vent system are maintained.
WARNING
This appliance must not be connected to a chimney
ue servicing a separate solid fuel or gas fuel burning
appliance.
Figure 13
38142-2-0719Page 12
40
11
90-degree or
45-degree Elbows
Straight Section
2 ft. Minimum offtop of
unit before using elbows
Vent supports per
manufacturers vent
specifications
Horizontalvent
to maintaina1/4”
rise per ft. Min.
11 ft. Min.
Maximum horizontal
distanceis 50% of
vertical ventheight
5 ft. Max.
Horizontal at
11 ft. Min.
Vertical
VENTING (CONT'D)
Vent Size
Model BVD34FP series uses a 4" B-Vent for operation.
Models BVD36FP and BVP42FP series use a 6" B-Vent for
operation.
Never downsize venting diameters.
Clearances
Vent clearances are per vent manufacturer's specications
Vent Conguration
Various venting congurations are shown in Figures 14 and
15 from which maximum vent runs can be determined.
WARNING
Always maintain minimum clearances or greater
around the vent system. Do not pack air spaces with
insulation or other material.
Minimum clearances are
per vent manufacturer’s
specifications
fire-parts.com
ft. Max.
ft. Min.
Vertical Venting - No Elbows
Vent supports are per
vent manufacturer’s
specifications
Figure 14
Offset Venting - With Elbows
Figure 15
38142-2-0719Page 13
3
1
2
LOG PLACEMENT (5 LOG SET)
Before you begin: if you are installing logs into the BVD34
or BVD36 model, then this replace is supplied with a set of
ve ceramic ber logs. Do not handle these logs with your
bare hands! Always wear gloves to prevent skin irritation from
ceramic bers. After handling logs, wash your hands gently
with soap and water to remove any traces of bers.
The positioning of the logs is critical to the safe and clean
operation of this replace. Sooting and other problems may
result if the logs are not properly and rmly positioned in
the replace. Please refer to Figure 16 and Figure 17 and
corresponding WARNING when completing following log
placement instructions.
1. Place front logs (#1 and #2) between front grate ange
and main burner. Align notches on front logs with locator
tabs in base.
2. Place middle log (#3) between front and rear loop of
burner.
Note: Do not place log on top of pilot assembly.
3. Place rear log (#4) on rear log shelf. Bottom ange of log
must be placed between the log shelf and burner tube.
4. Place branch (#5) onto (#1) log and at area on (#3) log.
The bottom of the branch is to be placed behind the grate
tang that is second from the left.
5. Place decorative rock in front of grates and sides of main
fire-parts.com
burner pan.
ATTENTION: Do not place decorative rock on logs or
burner. The decorative rock should only be placed on the
replace oor.
EMBER MATERIAL PLACEMENT ON BURNER
5
WARNING: Failure to position the parts in accordance
with this diagram or failure to use only parts
specically approved with this appliance may result
in property damage or personal injury.
Attention: Do not use Figure 16 or Figure 17 to order
logs. Refer to parts list on pages 32 and 34 and parts view
on pages 33 and 35 to order logs and/or ember material for
your appropriate replace model.
4
1
Figure 16
2
3
5
6. After all logs are positioned properly, apply Rockwool
ember material to the front burner port area. To apply,
carefully separate the ember material into small amounts
no larger than "dime size" pieces. Fluffed up pieces one
layer thick on top of the burner generally works best, and
will provide the best ember glow. Do not place ember
material more than one layer thick. No more than (1)
small packet of ember material (part no. 15999) evenly
placed on the burner, is recommended on BVD34 and
BVD36 models. Using additional ember material will
decrease the amount of ember glow effect. Extra ember
material should be saved for future ember applications
as necessary. See Figure 17.
Optional Platinum Bright Ember Kits are available from your
Fireplace Dealer. These embers may be used with all BVD/
BVP Series replaces. Order and use as indicated as below.
Platinum Bright EmbersPE-20-1
Note: A signle layer of embers is to be used when applying
Platinum Bright Embers (alone or in combination with
production embers) to the burner.
4
EMBER MATERIAL
PLACEMENT
Figure 17
38142-2-0719Page 14
REAR LOG
LOCATOR PINS
LOG PLACEMENT (4 LOG SET)
Before you begin: This replace is supplied with a set of
four ceramic ber logs. Do not handle these logs with your
bare hands. Always wear gloves to prevent skin irritation
from ceramic bers. After handling logs, wash your hands
gently with soap and water to remove any traces of ber.
The positioning of logs is critical to safe and clean operation
of this replace. Sooting and other problems may result
if the logs are not properly and rmly positioned in the
replace. Please refer to Figure 18, Figure 19, and Figure
20 and corresponding WARNING, when completing the
following log placement steps.
1. Place rear (#1) log onto two (2) pins on rear log support.
2. Place left, front (#2) log onto two (2) left, front pins on
burner pan.
3. Place right, front (#3) log onto two (2) right, front pins
on burner pan.
4. Place Branch (#4) onto one (1) pin on rear log
5. Place decorative rock in front of grates and sides of
main burner.
Figure 19
WARNING: Failure to position the parts in accordance
with this diagram or failure to use only parts specically
approved with this appliance may result in property
damage or personal injury.
Attention: Do not use Figure 19 or Figure 20 to order logs.
Refer to parts view on page 37 and parts list on page 36
to order logs and/or ember material for your appropriate
replace model.
ATTENTION: Do not place decorative rock on logs or
on burner. The decorative rock should only be placed
on the replace oor.
#4-TOP BRANCH
fire-parts.com
6. After all logs are properly positioned, place small "dime"
size pieces of Rockwool lightly across the front round
"blueame" ports. Place the ember material (Rockwool
pieces) side by side. Do not stack more than one layer
of embers across the burner ports. See Figure 18.
LOCATORTABS
FRONT LOG
EMBER
PLACEMENT
Figure 18
#1-REAR LOG
#2-FRONT
LEFT LOG
Figure 20
#3-FRONT
RIGHT LOG
38142-2-0719Page 15