Emotron VFX 2.0 Quick Setup Manual

Quick Setup Card
Emotron VFX 2.0 AC drive
Using the function keys
Fig. 1 Example of menu navigation when entering motor
voltage
Remote control
A standard 4-pole motor for 400 V, an external start button and a reference value will also be used.
Switch on the mains
Once the mains is switched on, the internal fan in the AC drive will run for 5 seconds.
Set the Motor Data
Enter correct motor data for the connected motor. The motor data is used in the calculation of complete operational data in the AC drive.
Change settings using the keys on the control panel.
Menu [100], Preferred View is displayed when started.
1. Press to display menu [200], Main Setup.
2. Press and then to display menu [220], Motor Data.
3. Press to display menu [221] and set motor voltage.
4. Change the value using the and keys. Confirm with .
5. Set motor frequency [222].
6. Set motor power [223].
7. Set motor current [224].
8. Set motor speed [225].
9. Set power factor (cos ϕ) [227].
10. Select supply voltage level used [21B]
11. Set Motor type[22I].
12. [229] Motor ID run: Choose Short, confirm with ENTER and give start command .
The AC drive will now measure some motor parameters. The motor makes some beeping sounds but does not rotate. When the ID run is finished after about one min­ute ("Test Run OK!" is displayed), press to continue.
13. Use AnIn1 as input for the reference value. The default range is 4-20 mA. If you need a 0-10 V reference value, change switch (S1) on control board.
14. Switch off power supply.
15. Connect digital and analogue inputs/outputs as in figure below.
Fig. 2 Connecting reference signal
16. Ready!
17. Switch on power supply.
Run the AC drive
Now the installation is finished, and you can press the start button to start the motor.
This example will show that the main connections are OK and that the motor will run with the load.
Default toggle loop
Figure 3 shows the default toggle loop. This loop contains the necessary menus that need to be set before starting. Press Toggle to enter menu [211] then use the Next key to enter the sub menus [212] to [21A] and enter the parameters. When you press the Toggle key again, menu [221] is dis­played.
step to lower menu level or confirm changed setting
step to higher menu level or ignore changed setting
step to next menu on the same level
step to previous menu on the same level
increase value or change selection
decrease value or change selection
Toggle between menus in the toggle loop Change the sign of a value Switching between local and remote control
100
200
300
220
221
210
NEXT
ESC
NEXT
ESC
NEXT
NEXT
NEXT
X1
PE
1
12
22
11
2
3
4
5
6
7
8
9
10
13
14
15
16
17
18
19
20
21
Start
Referenc e 4-20 mA
0V
+
CG Drives & Automation Sweden AB, Box 222 25, SE-250 24 Helsingborg, T +46 42 16 99 00
www.emotron.com/www.cgglobal.com
CG Drives & Automation, 01-5328-01r1, 2015-04-17
Fig. 3 Default toggle loop
Overview of the main menu
Control connections
Fig. 4 Connection example.
Input configuration with the switches
Fig. 5 Location of switches and connectors.
The switches S1 to S4 are used to set the input configuration for the 4 analogue inputs AnIn1, AnIn2, AnIn3 and AnIn4 as described in table 2. See Fig. 5 for the location of the switches.
[100] Preferred view. Displayed at power-up. Shows
actual values (default: speed and torque).
[200] Main Setup. Main settings to get the inverter opera-
ble e.g. motor data, autoreset and language.
[300] Process and Application parameters. Settings more
relevant to the application such as Reference Speed, torque limitations, PID control settings, etc.
[400] Shaft power monitor and process protection. The
monitor function enables the AC drive to be used as a load monitor to protect machines and processes against mechanical overload and underload.
[500] Inputs/outputs and virtual connections. All settings
for analogue and digital inputs and outputs.
[600] Logical functions and timers. All settings for condi-
tional signals are entered here.
[700] View operation and status. Viewing all the operatio-
nal data like frequency, load, power, current, etc.
[800] View Trip log. Viewing the last 10 trips in the trip
memory.
[900] Service information and AC drive data. Electronic
type label for viewing the software version and AC drive type.
Table 1 Description of used terminals.
Terminal Name Function (Default)
2 AnIn 1 Process reference, default: speed
7 Common Signal ground
9 DigIn 2 RunR; rotation right
11 +24V +24VDC Supply voltage
12 Common Signal ground (If desired)
13 AnOut 1 Min speed to max speed (If desired)
14 AnOut 2 0 to max torque (If desired)
22 DigIn 8 Reset
100
211
221
331
341
511
Toggle loop
Table 2 Switch settings
Input Typ e Switch
AnIn1
Voltage
S1
Current (default)
S1
AnIn2
Voltage
S2
Current (default)
S2
AnIn3
Voltage
S3
Current (default)
S3
AnIn4
Voltage
S4
Current (default)
S4
L1
L3
L1 L2
PE
2
U V W
13 21 14
12
7 9
11
22
0-10 V 4-20 mA
DC+
R
DC -
RTGX PGZV GUE
GPVGT
TGUGV
NQE1 TGO
CE"FTKXG
AnIn1
Common
DigIn2:
+24 VDC
DigIn8:
Common AnOut1
AnOut2
RunR
Reset
RFI­filter
Option
Motor
X2
X3
X1
S2S1
PE
S3 S4
U
II
UU
I
I
U
1
12
22
11
41
42 43
31 32
33
51
52
U
I
U
I
U
I
UIU
I
UIU
I
U
I
Loading...