Emotron EMX-R-15S, EMX-R-15E, EMX-R Series, EMX-R-25S, EMX-R-25E Instruction Manual

...
EMX™-R DRIVE SYSTEM
INSTRUCTION MANUAL - English
Valid for the following models: EMX-R-15S EMX-R-15E EMX-R-25S EMX-R-25E EMX-R-35S EMX-R-35E
EMX™-R DRIVE SYSTEM
INSTRUCTION MANUAL - English
Document number: 01-3333-01 Edition: r2 Date of release: 2006-02-15 © Copyright Emotron AB 2005 - 2006 Emotron retain the right to change specifications and illustrations in the text, without prior notification. The contents of this document may not be copied without the explicit permission of Emotron AB.
The product is protected as follows:
Patents: US 4 868 478; EP 0 285 637; SE 8604308-0
US 5 315 224; EP 0 507 835; SE 9002217-9
US 6 628 100; SE 9902821-9
SE 0100814-3
Registered design: US 462 937; DE 400 05 393.4; SE 66 630

Safety instructions

During installation
Read the instruction manual completely before installation and commis­sioning.
The installation must be carried out by qualified personnel.
General conditions and regulations for the installation and operation of electrical machinery must be observed.
Measures to protect against personal injury and damage to the machine must be taken following local rules and regulations.
The drive system EMX-R is intended for permanent installation.
Cables may not be connected or disconnected while the supply voltage is on.
Check that the equipment is correctly connected before it is taken into use, see the instructions in the chapter on Mounting/Connection.
Faults that arise due to faulty installation or operation are not covered by the guarantee.
During operation
Measurements in the control unit, during operation, must only be carried out on the terminals and only by authorized personnel. NOTE! Great care must be taken.
The units may not be opened or disassembled during operation.
During disassembly and scrapping
The housing of the control unit is made from aluminium and steel. The material must be handled and recycled following the relevant laws.
The circuit board contains small amounts of tin and lead, which must be handled and recycled in accordance with the relevant laws.
The motor is made from copper, plastic, aluminium and iron. These materi­als must be handled and recycled in accordance with the relevant laws.
Emotron AB 01-3333-01r2 1
2 Emotron AB 01-3333-01r2

Contents

1. Description.................................................................................. 5
1.1 Introduction................................................................................................. 5
1.2 Product range ............................................................................................. 5
1.3 Operating indicators / built-in functions ................................................... 6
1.3.1 Automatic purging mode / holding torque................................................ 7
1.3.2 Rotation monitor (DIP switch 4)................................................................. 8
1.3.3 Protection of the control unit ..................................................................... 9
2. Mounting/connection.............................................................. 11
2.1 Mounting .................................................................................................. 11
2.1.1 Sensor for rotation monitor..................................................................... 12
2.2 Connection ............................................................................................... 12
2.2.1 When switching off .................................................................................. 13
2.2.2 Recommendations with respect to EMC................................................ 13
2.2.3 Priority switch / defrosting / manual control......................................... 14
2.2.4 Manual control using a 10 kOhm potentiometer .................................. 14
2.2.5 Test switch ............................................................................................... 15
2.2.6 Choice of maximum speed ..................................................................... 17
2.2.7 Setting DIP switches ................................................................................ 18
2.2.8 Speed controller ...................................................................................... 19
2.2.9 Parallel connection .................................................................................. 19
2.2.10 Heat recovery on cooling – summer/winter switch............................... 20
2.2.11 Analogue output signal (only available on Model E) ............................. 20
2.2.12 Potentiometer with low resistance, 100 Ohm to 5 kOhm
(only available on Model E) ..................................................................... 20
3. Maintenance/troubleshooting................................................ 21
3.1 Maintenance ............................................................................................ 21
3.2 Motor diagnosis ....................................................................................... 21
3.3 Troubleshooting ....................................................................................... 22
Emotron AB 01-3333-01r2 3
4. Technical data ......................................................................... 25
4.1 The drive system’s operation using different control signals................ 26
4.2 Choice for sizes of drive system and belt pulley .................................... 29
4.3 Accessories and documentation ............................................................ 30
5. Appendix ................................................................................... 31
4 Emotron AB 01-3333-01r2

1. Description

1.1 Introduction

EMX-R is a series of speed controlled drive systems specially designed for driv­ing rotary heat exchangers. The drive system consist of a motor and its associ­ated control unit.
EMX-R completely replaces drive systems EMS-VVX 1, 2-4N, 2-4N/ET and 2-4EM as well as the drive systems EMS-VVX 15, 25 and 35. All mentioned drive systems have completely been replaced by EMX-R.
The new drive system EMX-R is based, like its predecessor, on the SR-motors (SR=Switched Reluctance). These motors make it possible to drive heat exchanger rotors up to 3.5 metres in diameter without gears.

1.2 Product range

EMX-R is available in three sizes for rotors up to around 3.5 m. They come in sizes 15, 25 and 35 (for other rotor sizes, please contact the local distributor or Emotron AB).
The control unit is available in two versions, S and E, where Model E has an extra circuit board for increased functionality. Built-in functions included in the Model S are:
Automatic purging operation
Rotation monitor - integrated electronics or with external rotation sensor
Alarm relay
•Test switch
Priority switch/defrosting
Heat recovery on cooling with external differential thermostat
In addition to the functions included in Model S, the Model E includes:
Display of the rotor speed in r/min when the external rotation sensor is con­nected.
Analogue output signal proportional to the speed of rotation of the motor.
Heat recovery on cooling with external temperature sensors.
Input for potentiometer with low resistance, 100 Ohm to 5 kOhm.
Emotron AB 01-3333-01r2 Description 5
Prepared for serial communication.

1.3 Operating indicators / built-in functions

Two LEDs, one red and one green, are used on the Model S for indication, while the Model E has an LED display as follows:
Table 1 Operating indication – Model S
Slow flashing – Purging mode/Low control signal
Green
Rapid flashing – Operation, the motor rotates continuously
Lit for two seconds – Magnet passing rotation sensor
Lit - RotoSens measures the load on the motor during acceleration
Lit or flashing LED indicates alarm, see also the chapter on troubles-
Red
hooting
Table 2 Operating indication – Model E
Purging mode. Low control signal
The speed of the rotor in rpm. At start a speed is displayed according to the gear ratio rotor/motor = 1:25. After 2 pulses from the rotation moni­tor, the correct speed of rotation of the rotor is displayed. Range 0.2–99 rpm.
RotoSens is selected using the DIP-switch (4) and with no rotation sen­sor connected
Lit for two seconds when the magnet passes the rotation sensor
RotoSens measures the load on the motor during acceleration
Summer operation/heat recovery on cooling
No rotation monitor - DIP 4 in the OFF position and jumper 31-32
An alarm is indicated by the letter F followed by a number. See also the chapter on troubleshooting.
6Description Emotron AB 01-3333-01r2

1.3.1 Automatic purging mode / holding torque

When the control signal is low, <1.5 V at 0–10 V, the drive system switches to purging mode. In purging mode the motor shaft turns two revolutions every 10 minutes, which is equivalent to around 30 degrees of rotation by the heat exchanger rotor. This slow rotation does not provide any significant heat trans­fer, but simply serves to keep the rotor clean.
Most of the time the rotor seals keep the rotor stationary, but if the rotor seals are not touching the rotor and the air flow is not perpendicular to the rotor, the air flow may cause the rotor to rotate. To prevent unintentional heat recovery in this situation the motor is used to provide a holding torque to keep the rotor stationary.
The first time the drive system goes into purging mode after the power is switched on this holding torque is not activated, since many rotors do not require an active holding torque to keep them stationary. A rotor that does require a holding torque will then begin to turn slowly. The drive system imme­diately brakes this motion, reducing the speed to zero, and then applies a con­stant holding torque to keep the rotor stationary. The drive system has now learned which rotors require a holding torque, and which do not. The holding torque is at least 50% higher than the torque required for operation just before is should stand still.
If a holding torque has been applied and you grasp the drive belt and try to turn the rotor by hand, the torque will progressively increase.
The holding torque is generated by passing a current through one of the motor phases. The higher the torque that is required, the higher the current. This cur­rent produces a noise that gets louder as the current increases. Integrated in the control unit are three motor protection breakers, one for each motor phase. The motor protection also protects the motor when the holding torque is activated.
Emotron AB 01-3333-01r2 Description 7

1.3.2 Rotation monitor (DIP switch 4)

Two different rotation monitors can be selected. The first, RotoSens, which is an integrated electronic rotation monitor, and secondly a rotation monitor using a rotation sensor.
RotoSens uses the motor as the sensor. By allowing the control unit to measure the load on the motor, you can determine whether the drive belt has broken. When the drive belt has broken the motor load will be low. As the rotors which rotate very easily also give a low load on the motor, it is necessary to also meas­ure the load during acceleration - you then get a measurement of the rotor’s moment of inertia. After 2 minutes of operation at a low load, a load measure­ment is made during acceleration. If the drive belt is broken an alarm is given, if it is undamaged the load measurement during acceleration is repeated again after 24 hours. In cleaning mode, measurement during acceleration is made once every 24 hours.
The rotation monitor with sensor has a magnet fitted on the periphery of the rotor. The magnet activates the sensor once every revolution. Should, for exam­ple, a belt break and the rotor stops, the pulses cease and an alarm is given. The time until the alarm is given is speed dependent and is 24 seconds at max. speed, 20 minutes at min. speed and about 8 hours in purge mode.
NOTE: In order to use RotoSens the load on the motor should not be to low. The minimum diameter for the rotor and belt pulley for each size of the drive system must be:
EMX-R-15: Belt pulley EMX-R-25: Belt pulley 63 mm, Rotor diameter 1200 mm EMX-R-35: Belt pulley 100 mm, Rotor diameter 2000 mm
If the belt pulley or rotor are smaller RotoSens can not be used, however, the rotation monitor with sensor can always be used.
63 mm, Rotor diameter 630 mm
The rotation monitors give alarms through operating indications and via the alarm relay, the motor does not stop with an alarm.
For operation without an external rotation sensor the DIP-switch 4 must be set in position “OFF” (downwards), which means the built-in electronic rotation monitor RotoSens is connected.
8Description Emotron AB 01-3333-01r2
For operation without both an external and the built-in electronic rotation monitor RotoSens the DIP-switch 4 also must be set in position “OFF”, but then a strap must be fitted between terminals 31 and 32.

1.3.3 Protection of the control unit

The control unit is protected by monitoring for both over-voltage and under­voltage. If the supply voltage goes over or under the allowed limits, the control unit is disconnected and the motor stops. The motor starts again automatically when the supply voltage returns to its normal value.
The control unit has built-in motor protection that protects against overload­ing, and external motor protection is not required. Power supply to the motor is cut in the event of overload. In order to restart the drive system, the supply volt­age to the control unit should be temporarily disconnected for at least 5 sec­onds.
Built-in short circuit protection protects against short circuits between the phases of the motor and between the phases and earth.
Table 3 Protection and alarm functions
Protective
function
Supply fault, over­voltage
Supply fault, under-voltage
Pre-alarm, rotation monitor
Rotation monitor
Pre-alarm, motor protection/over­load
Motor protection/ overload
Short circuit
1) RotoSens - manual, disconnect and reconnect the power supply. Rotation monitor with sensor - automatic.
Emotron AB 01-3333-01r2 Description 9
External alarm
with alarm relay
Yes, immediately Automatic
No
Yes
No
Yes, immediately
Restart Alarm reset
Motor not stop­ped
The system tries to reset three times
Manual, discon­nect and recon­nect power supply
Automatic
1)
Automatic
Manual, discon­nect and recon­nect power supply
10 Description Emotron AB 01-3333-01r2

2. Mounting/connection

2.1 Mounting

Both the motor and the control unit are usually mounted in the heat exchanger housing. In this way, they do not occupy any space outside of the heat exchanger housing and are well protected during transport. Furthermore, it is often advantageous from the point of view of interference (EMC) to place the motor and control unit in the rotor housing. The motor is usually mounted on a sprung motor support when a V-belt is used. In this way, problems arising if non-circular rotors are used can be prevented. Vibration dampers should be mounted between the motor and the motor support so that any vibration from the motor is not transmitted to the rotor housing
.
Control unit
Motor
10-F08
Fig. 1 Rotor and drive system
Emotron AB 01-3333-01r2 Mounting/connection 11

2.1.1 Sensor for rotation monitor

The magnet for the rotation sensor is screwed onto the periphery of the heat exchanger. If the rotor cover is magnetic, the magnet must be insulated from the cover. The rotation sensor is mounted such that the magnet passes at a distance of 5–8 mm, see below.
NOTE: Magnet and rotation sensor must not be mounted when RotoSens is used, which means the built-in electronic rotation sensor is used, DIP-switch 4 is used. To display the rotor speed an external sensor must be used (applicable for model E).
Magnet
Heat exchanger rotor
Rotation sensor
5-8 mm
Fig. 2 Mounting of the rotation sensor

2.2 Connection

WARNING! Residual voltage remains for up to 1 minute after disconnection of the supply voltage.
The motor is delivered with a fixed connected motor cable to simplify installa­tion of the drive system. The length of the cable is 2.0 m for EMX-R 15M and
2.5 m for EMX-R 25M and EMX-R 35M. The motor cable cannot be
extended because this could interfere with the electronic tachometer that is built into the system.
12 Mounting/connection Emotron AB 01-3333-01r2
An external slow-blow fuse rated at 10 A must always be installed. The drive system does not contain a fuse. Electronic motor protection is built into the control unit, and monitors the motor at all times. The control unit is protected from short circuit within the motor.
A safety switch is to be installed between the mains supply and the control unit. An alarm for loss of power is given if the mains supply is disconnected.
WARNING! No switch is allowed between the motor and the control unit.

2.2.1 When switching off

When it is desired to switch off the heat exchanger, for example at night, this can be done using a relay connected in series with the control signal. This relay interrupts the signal to control signal terminal number 33. In this way, no alarm about interruption of power supply is given. The control signal can of course also be reduced to its minimum value, in order to achieve the same result. If the control signal is low or absent the drive system switches to purging mode.

2.2.2 Recommendations with respect to EMC

In order to fulfil the European EMC Directive 89/336/ECC regarding electro­magnetic compatibility, the following precautions must be taken:
The motor cable must be mounted as close to the heat exchanger housing as possible. If the cable is too long, the excess should be collected together in the form of, for example, a figure “8”. The area enclosed by the cable should be as small as possible. Electrical tape or cable ties can be used to achieve this.
Emotron AB 01-3333-01r2 Mounting/connection 13
WRONG RIGHT
Fig. 3 Excess motor cable should be arranged such that the area enclosed is as
small as possible
Special EMC couplings/glands are not necessary.
An EMC filter is built into all EMX-R models.

2.2.3 Priority switch / defrosting / manual control

A preselected speed of rotation can be specified by a potential-free connection between the priority inputs 34–35. When terminal 34 is connected to terminal 35, the speed of rotation is determined by the priority potentiometer, which is located next to the DIP switches in the control unit. The priority switch has higher priority than the summer/winter switch (only available on Model E) and the control signal.
The switch can be used, for example, when cleaning the rotor, defrosting using an external differential pressostat or for manual control of the speed of rotation.

2.2.4 Manual control using a 10 kOhm potentiometer

It is simple to control the drive system manually using a 10 kOhm potentiome­ter connected as shown in the figure.
Control unit
33
34
10 kOhm
14 Mounting/connection Emotron AB 01-3333-01r2
37

2.2.5 Test switch

The control unit is equipped with a test switch, placed under the cover between terminals 37 and 41. When this switch is in the “ON” position, the motor soft­starts and the speed increases to the maximum, independently of other signal sources. When in the “OFF” position (down), the test switch is not operational.
The test switch can also be used to run the motor at maximum speed if, for example, an external control signal is available.
8
IU
J1
54
53
51
5556 57 58
52
Extra circuit board in the Model E with LED­display,
ON
ON
1
2
345678
L
N
31
32 33 343536
37 414243654321
E-terminals 51-58 and jumper J1
10-F05
1
2
56 7
34
Fig. 4 Location of terminals, etc.
No. Designation
1 Supply terminal
2Motor terminal
3 Priority potentiometer
4 Control signal terminal
5 DIP switch
Emotron AB 01-3333-01r2 Mounting/connection 15
No. Designation
y
6Test switch
7Alarm terminal
8 Operating indicator for Model S, two LEDS
Extra circuit board in model E
51
52
Heat recovery on cooling 51-52 incoming air sensor 51-53 exhaust air sensor
Analogue output signal 0-10V/20mA
IU
J1
54
55
53
57
56
58
Potentiometer control
34
35
36
Priority switch
Alarm relay 42-43 closed on alarm
41
42
37
Heat recover on cooling
Model S and E
Modell S
L
N
L
N
Safety switch
32
31
3
4
2
1
M
6
5
Rotation sensor
33
Control signal
10-F11
Fig. 5 Wiring diagram
16 Mounting/connection Emotron AB 01-3333-01r2
43

2.2.6 Choice of maximum speed

The maximum speed can be limited to 80% (200 rpm) or 60% (150 rpm). This function is primarily intended for use with rotors smaller than 1.3 m, when it is desired to limit the speed of rotation and/or when using larger belt pulleys.
Emotron AB 01-3333-01r2 Mounting/connection 17

2.2.7 Setting DIP switches

Control signal Speed controller
0-10 V 10 kOhm
1ON23
V-belt
2-10V Other belts
1ON23
0-20V
1ON23
Direction of rotation
Clockwise
4-20mA
1ON23
Counterclockwise
0-20mA
1ON23
Rotation monitor Maximum speed
With rotation sensor
ON
100%
4
ON
5
ON
5
ON
6
ON
6
ON
7 8
RotoSens 80%
ON
4
60%
ON
7 8
ON
7 8
WARNING! Disconnect the voltage supply before changing the DIP switch settings.
18 Mounting/connection Emotron AB 01-3333-01r2

2.2.8 Speed controller

DIP switch 5 on the control unit can be used to select between two speed con­trollers. One controller provides gentler operation and is used if resilient belts such as round belts, flat belts and resilient V-belts are fitted. In this case DIP switch 5 should be set “OFF”. The other controller is faster and stiffer, and is intended for use with stiff belts. In this case DIP switch 5 should be set “ON”.
If the stiffer controller is not adequate for smooth operation when the max. speed is set to 100%, an even stiffer and faster controller can be selected by set­ting DIP switches 5 and 7 “ON” and setting DIP switch 8 “OFF”.
ON
5 7 8

2.2.9 Parallel connection

If several rotary heat exchangers are to be used in parallel using one control sig­nal or sensor, each heat exchanger rotor must be equipped with its own drive system (motor and control unit).
The control signal is connected to the first drive system according to the instructions for connection. The other control units are connected by connect­ing terminals 33 and 34 of the other control units to terminals 33 and 34, respectively, on the first control unit.
The DIP switches on the first control unit are set as described in “Setting DIP switches”. DIP switch 1 and DIP switch 3 on the other control units are set as described in “Setting DIP switches”, while DIP switch 2 is always set as described below:
ON
2
The control units give individual alarms. The alarm outputs can be connected in parallel or in series in order to obtain a collective alarm.
Model E can also use the analogue output signal in order to control other drive systems. Terminals 54(-) and 55(+) are connected to terminals 34(–) and 33(+), respectively. The DIP switches on all control units are set as described in “Set­ting DIP switches”.
Emotron AB 01-3333-01r2 Mounting/connection 19
2.2.10 Heat recovery on cooling – summer/winter switch
Heat recovery on cooling refers to the mode of operation when the incoming air temperature exceeds the exhaust air temperature. By driving the rotary heat exchanger at maximum speed, a cooling effect is achieved on the incoming air. The heat recovery on cooling function is most simply obtained by using an external regulator which has this function built-in. EMX-R is then controlled by a control signal, e.g. 0–10 V.
If for example, an external regulator is already installed, you can obtain the heat recovery on cooling function by directly connecting a separate differential ther­mostat to EMX-R, terminals 36–37
Model E has a built-in differential thermostat. This makes it possible to connect two NTC sensors of resistance 2000 Ohm (for example EGL 511), one in the incoming air duct and one in the exhaust air duct, directly to EMX-R, terminals 51–53. If the exhaust air is colder than the incoming air, the rotor rotates at its maximum speed, and cooling is recovered. If the exhaust air is warmer than the incoming air (as is normally the case) the speed is controlled by the control sig­nal, and heat is recovered.

2.2.11 Analogue output signal (only available on Model E)

The output signal, 0–20 mA or 0–10 V, is proportional to the speed of the motor. Maximum value, 20 mA or 10 V, is always obtained at the selected max. speed (60, 80 or 100% of the motor’s maximum rpm). The choice between the 0–20 mA output signal and the 0–10 V output signal is made with jumper J1 positioned behind the control terminals 51–58.
2.2.12 Potentiometer with low resistance, 100 Ohm to 5
kOhm (only available on Model E)
When control is provided by a potentiometer with a total resistance value between 100 Ohm and 5 kOhm, the three leads are connected to terminals 56–
58. DIP switches 1–3 are set in the same way as for a control signal of 0–10 V.
20 Mounting/connection Emotron AB 01-3333-01r2

3. Maintenance/troubleshooting

WARNING! Residual voltage remains for up to 1 minute after disconnection of the supply voltage. The test switch and the DIP switches may only be adjusted when the supply voltage has been disconnected.

3.1 Maintenance

The motor and the controller do not normally require any maintenance. How­ever, it should be regularly checked that the cabling is not damaged and that all fixing screws are securely tightened.

3.2 Motor diagnosis

Disconnect the supply voltage. Disconnect the motor cables from the control unit. Measure the motor resistance between 1–2, 3–4 and 5–6. The values should be:
15M: 30–90 Ohm; 25M: 5–15 Ohm; 35M: 5–15 Ohm
The resistance should not differ by more than 5 Ohm between the phases for 15M, and by no more than 2 Ohm for 25M/35M. Also check the insulation resistance between 1–3, 1–5, 3–5, 1–earth, 3–earth and 5–earth.
Emotron AB 01-3333-01r2 Maintenance/troubleshooting 21

3.3 Troubleshooting

Check that the equipment has been correctly installed, i.e. that the cables are properly stripped, that there are no loose cables, etc., and check that the DIP switches are correctly set.
It is always possible to test run the drive system using the TEST switch located under the cover next to terminal 37, see Fig. 4. The switch has two fixed posi­tions, when it is in the up position, the motor accelerates to its maximum speed independent of the control signal, and when it is in the down position the rota­tion speed is controlled by the control signal.
If the motor does not reach maximum speed or respond to the control signal, check DIP switches 1–3 and 7 and 8. If the heat exchanger rotates in the wrong direction, change the setting of DIP switch 6. Reset, vibration, noise and built­in protection are described in the chapters Description and Mounting/Connec­tion.
If the control unit is to be exchanged, the complete covered box containing the circuit boards must be exchanged.
22 Maintenance/troubleshooting Emotron AB 01-3333-01r2
Table 4 Troubleshooting
Alarm indication
SEFault
Green LED flashes slowly
Red and green LED flash rapidly
Red LED flashes rapidly
Red LED is lit and green LED flashes rapidly
Purging/ low control signal
Pre-alarm rotation monitor
Rotation monitor
Pre-alarm, overload/ motor protection
Fault condition/Action required
Check the EMX-R by running the drive sys­tem with the test switch located next to terminal 37. The motor should accelerate to its maximum speed. If the motor does accelerate to the maximum speed when the test switch is activated, the fault is external. Can 0–10 V (2–10 V) be measured between 33(+) and 34 (-)? Have + and - been swapped?
The drive system has switched to a softer speed controller because the motor shaft is jerking sharply. Check that the drive belt is not slipping on the pulley.
The exchanger rotor does not rotate; check the drive belt. The rotor rotates; check that the indication is given when the magnet passes the rota­tion sensor, see the section Operating indicators, if not replace the rotation sen­sor. If RotoSens is used, check that the rotor or belt pulley are not smaller than 630 mm respective 63 mm.
The motor protection has been activated due to excessive load. After a cool-down period of 10 minutes the system restarts automatically. If the overload protection trips 3 times within 120 minutes the drive system will be shut down, see also over­load (F5).
Emotron AB 01-3333-01r2 Maintenance/troubleshooting 23
Table 4 Troubleshooting
Alarm indication
SEFault
Overload/
Red LED is lit
No LED lit -
Red and green flash slowly and alternately
Red and green LED flash rapidly and alter­nately
Red LED flashes slowly
motor protection
Supply volt­age missing
Overvoltage The supply voltage exceeds 264 VAC.
Under­voltage
Earth fault in the motor
Short circuit in the motor
Circuit break in the motor
Fault condition/Action required
The motor protection has been activated due to excessive load. Check that the motor cables are connected correctly, see the chapter on Mounting/Connection. Check also that the rotor runs freely and that the diameters of the rotor and pulley are not too large. If the fault remains, carry out motor diag­nosis. Replace the motor if it is faulty. If the fault does not lie within the motor, replace the control unit.
Check that 230 VAC ±15% is connected to the supply terminal.
The supply voltage lies below 196 VAC.
Disconnect the supply voltage, check the connection of the motor cable and check that the correct motor is connected. If the fault remains, carry out motor diagnosis. If the motor is faulty, replace it. If the fault does not lie with the motor, replace the control unit.
24 Maintenance/troubleshooting Emotron AB 01-3333-01r2

4. Technical data

Table 5 Technical data
EMX-R
Function
15 25 35
Rotation speed [rpm] 5-250
1)
Tor que
Power [W] 40 100 160
Direction of rotation Selectable
Purging mode Built-in function
Motor protection Built-in function
Output data
Soft start and stop [s] 15/15 25/25 35/35
Alarm output Alternating contact, max 5 A 230 VAC
Supply voltage 230 VAC ±15%, 50/60 Hz
Current [A] 0.7 1.3 1.7
Control signal
Input data
Protection class IP 54
Weight, control unit [kg] 1.7
Weight, motor [kg] 5 8 11
Terminals 1 pc M12 and 4 pc M16 (glands)
Ambient temperature -30 - +40º C
General
Tac home ter
EMC, Emission EN 50081-1
EMC, Immunity EN 50082-2
1)
Torque is constant over entire speed range.
[Nm] 1.5 4 6
0–10 V, 2–10 V, 0–20V phase cut, 0–20 mA, 4–20 mA, 10 kOhm potentiometer
Electronic tachometer, tachometer cable is not needed
Emotron AB 01-3333-01r2 Technical data 25
4.1 The drive system’s operation using
different control signals
The drive system has a built-in linearity function that gives a linear relationship between the control signal and the efficiency of the heat exchanger rotor, rather than having the speed of rotation proportional to the control signal. This pro­vides good conditions for stable temperature control.
Motor speed [rpm]
Purging 2 rev./10 min.
250
200
150
5
Purging Max. Speed
100%
80%
60%
Control signal
Control signal Purging Maximum speed
0-10 V 1,5 V 9,7 V
2-10 V 3 V 9,7 V
0-20 V 3 V 19,4 V
4-20 mA 6 mA 19,4 mA
0-20 mA 3 mA 19,4 mA
Table 6 Motor model designations
Article number Designation Notes
01-2160-00 EMX-R-15M Cable 2.0 m
01-2162-00 EMX-R-25M Cable 2.5 m
01-2163-00 EMX-R-35M Cable 2.5 m
26 Technical data Emotron AB 01-3333-01r2
K1
F
K2
K
FA
FC
FB
LC
HD
HA
H
10-F06
LA
HB
L
M
Fig. 6 Motor dimensions
Table 7 Motor dimensions (mm)
EMX-R F FA FB FC H HA HB HD
15 88 96 10 7 56 8 119 134
25 82 140 12 7 81 10 173 180
35 109 140 12 7 81 10 173 180
EMX-R K K1 K2 L LA LC M
15 14j6 5h9 20 113 30 145 110
25 14j6 5h9 20 114 35 152 160
35 14j6 5h9 20 141 35 179 160
Emotron AB 01-3333-01r2 Technical data 27
Table 8 Control unit model designations
Article number Designation
01-2170-11 EMX-R-15S
01-2171-11 EMX-R-15E
01-2174-11 EMX-R-25S
01-2175-11 EMX-R-25E
01-2176-11 EMX-R-35S
01-2177-11 EMX-R-35E
200
150
58
10-F07
6
29,5
113
188
ø 4,5 (4x)
Fig. 7 Control unit dimensions (mm)
28 Technical data Emotron AB 01-3333-01r2
4.2 Choice for sizes of drive system and belt
pulley
Table 9 Choice of size for drive system and belt pulley
Rotor
diameter
[mm]
700 15 63 60 13.5
700 15 30 100 10.7
900 15 63 60 10.5
900 15 40 100 11.1
1100 15 63 80 11.5
1100 15 50 100 11.4
1300 15 71 80 10.9
1300 15 63 100 12.1
1500 15 71 100 11.8
1700 25 80 100 11.8
1900 25 80 100 10.5
2100 25 100 100 11.9
2300 25 100 100 10.9
2500 25 100 100 10.0
2700 35 118 100 10.9
3100 35 140 100 11.3
3500 35 140 100 10.0
EMX-R model
Belt pulley
diameter
[mm]
Maximum speed
of revolution
[%]
Rotor speed
[rpm]
NOTE: Higher rotor speeds than those given in the table above increase the loading and a larger drive system may be necessary. Tight rotor seals may also require the use of a larger size. Rotors that have a high capacity to absorb humidity, such as dehumidification rotors in desiccant cooling system requires a larger drive system, see separate documentation.
Emotron AB 01-3333-01r2 Technical data 29

4.3 Accessories and documentation

Table 10 Accessories
Article number Designation
01-2184-00 Rotation sensor with magnet M12 x 75 mm
01-3549-00 Rotation sensor with magnet M12 x 35 mm
01-2179-00 Cable fixture for control unit 15-35
01-2182-00 Mounting kit, expander type for motor 15-35
01-2183-00 Mounting kit 2*M6 for motor 15-35
01-2182-00
01-2183-00
Fig. 8 Mounting kits with vibration damping for motor
Table 11 Operating instructions
Article number Designation
01-3333-00 Swedish
01-3333-01 English
01-3333-02 German
01-3333-03 Dutch
01-3333-05 Danish
01-3333-06 Norwegian
01-3333-07 Finnish
01-3333-08 French
30 Technical data Emotron AB 01-3333-01r2

5. Appendix

Connection lable
Model E (optional)
51-52-53 Kylåtervinning, Heat recovery on cooling,
54-55 Analog ut, Analogue out, Analog aus 56-57-58 Pot. Styrning, Pot. Control, Pot. Betrieb
Kälterückgewinnung
IU
2
13
+
J1
1-2: 0-20mA 2-3: 0-10V
57565554535251 58
100ohm -
5kohm
Model S
Restspänning
Residual voltage
Restspannung
NÄT
MAINS
NETZ
NL
01-2271-00 R1
MOTOR MOTOR MOTOR
STYRSIGNAL
CONTROL SIGNAL
STEUERSIGNAL
0-10V
ON
12345678
2-10V
ON
12345678
4-20mA
ON
12345678
ROTATIONSVAKT
ROT. MONITOR
ROT. GEBER
Ja, Yes, Ja
ON
12345678
Nej, No, Nein
ON
12345678
31-32 Rotationsgivare, Rotation sensor, Rotationsgeber 33-34 Styrsignal, Control signal,
Steuersignal
34-35 Prioritetomkopplare, Priority switch,
Prioritätsschalter
36-37 Kylåtervinning, Heat recovery on
cooling, Kälterückgewinnung
REMTYP
TYPE OF BELT
RIEMENTYP
ON
12345678
ON
12345678
654321NL37363534333231 434241
PRIORITETSPOT.
PRIORITY POT.
+
PRIORITÄT POT.
ROT. RIKTNING ROT. DIRECTION DREHRICHTUNG
ON
12345678
ON
12345678
TEST PÅ TEST ON
TEST EIN
TEST AV TEST OFF TEST AUS
MAX. VARVTAL
MAX. RPM
MAX. DREHZAHL
100%
ON
12345678
80%
ON
12345678
60%
ON
12345678
LARM RELÄ
ALARM RELAY
ALARM RELAIS
42-43 Slutande vid larm
Closed on alarm Geschlossen bei alarme
Emotron AB 01-3333-01r2 Appendix 31
32 Appendix Emotron AB 01-3333-01r2
Model S Model E
EMX-R
GRÖN GREEN GRÜN
Långsamt blinkande - Renblåsningsdrift Snabbt blinkande - Drift Lyser i 2 s - Magneten passerar
Slowly flashing - Cleaning operation Fast flashing - Operation Lit for 2 sec. - The magnet passes the
Langsam blinkend - Intervallbetrieb Schnell blinkend - Betrieb Leuchtet 2 Sek. lang - Rotormagnet passiert
RÖD RED ROT
Blinkande - Rotationslarm Lyser - Överlast
Flashing - Rotation alarm Lit - Overload
Blinkend - Rotationsalarm Leuchtet - Überlast
VARNING! WARNING! ACHTUNG! Bryt spänningen innan locket öppnas
Turn off supply before removing cover Gerät vor dem Öffnen vom Netz trennen
rotationsgivaren
rotation sensor
Rotationsgeber
EMX-R
Integrerad elektr. rotationsvakt Integrated electr. rotation monitor Integriert elektr. Rotationswächter
Rotorvarvtal; Ext. rotationsgivare Rotor speed; Ext. rotation sensor Rotor Drehzahl; Ext. Rotationsgeber
Renblåsningsdrift Cleaning operation Intervallbetrieb
Signal från extern rotationsgivare Signal from external rotation sensor Signal von extern Rotationsgeber
Rotationslarm Rotation alarm Rotationsalarm
Överlast Overload Überlast
VARNING! WARNING! ACHTUNG! Bryt spänningen innan locket öppnas
Turn off supply before removing cover Gerät vor dem Öffnen vom Netz trennen
Emotron AB, Mörsaregatan 12, SE-250 24 Helsingborg, Sweden
Tel: +46 42 16 99 00, Fax: +46 42 16 99 49
E-mail: info@emotron.se
Internet: www.emotron.com
Emotron AB 01-3333-01r2 2006-02-15
Loading...