The manufacturer offers the customer a 24-month functional warranty on the instrument for
faulty workmanship or parts from date of dispatch from the distributor. In all cases, this
warranty is valid for 36 months from the date of production. This warranty is on a return to
factory basis.
This warranty is only applicable to Multi-Mon instruments using Multi-Mon current
transformers.
The manufacturer does not accept liability for any damage caused by instrument
malfunction. The manufacturer accepts no responsibility for the suitability of the instrument
to the application for which it was purchased.
Failure to install, set up or operate the instrument according to the instructions herein will
void the warranty.
Only a duly authorized representative of the manufacturer may open your instrument. The
unit should only be opened in a fully anti-static environment. Failure to do so may damage
the electronic components and will void the warranty.
The greatest care has been taken to manufacture and calibrate your instrument. However,
these instructions do not cover all possible contingencies that may arise during installation,
operation or maintenance, and all details and variations of this equipment are not covered
by these instructions.
For additional information regarding installation, operation or maintenance of this
instrument, contact the manufacturer or your local representative or distributor.
WARNING
WARNING
WARNINGWARNING
Read the instructions in this manual before performing installation and take note of the
Read the instructions in this manual before performing installation and take note of the
Read the instructions in this manual before performing installation and take note of the Read the instructions in this manual before performing installation and take note of the
following precautions:
following precautions:
following precautions:following precautions:
Mult
Multiiii----Mon
Mon is intended for measurements performed in building installations, relating to
MultMult
measurement category III (UL61010
measurement category III (UL61010----1, 6.7.
measurement category III (UL61010measurement category III (UL61010
Ensure that all incoming AC power
Ensure that all incoming AC power and other power source
Ensure that all incoming AC powerEnsure that all incoming AC power
performing any work on the instrument. Failure to do so may result in serious or even
performing any work on the instrument. Failure to do so may result in serious or even
performing any work on the instrument. Failure to do so may result in serious or even performing any work on the instrument. Failure to do so may result in serious or even
fatal injury and/or equipment damage.
BeforeBefore
the instrument to ensure that your instrument is equipped with the appropriate rating
the instrument to ensure that your instrument is equipped with the appropriate rating
the instrument to ensure that your instrument is equipped with the appropriate rating the instrument to ensure that your instrument is equipped with the appropriate rating
input voltages and currents.
input voltages and currents.
input voltages and currents.input voltages and currents.
Under
Under no circumstances should the instr
UnderUnder
if it is damaged.
if it is damaged.
if it is damaged.if it is damaged.
To prevent
To prevent potential fire or shock haz ard, do not expose the
To prevent To prevent
moisture.
moisture.
moisture.moisture.
While installing
While installing Multi
While installing While installing
transformer
transformer, the external current transformer secondary output
transformertransformer
to
to be
toto
voltages, possibly resulting in equipment damage, fire and even
voltages, possibly resulting in equipment damage, fire and even serious or fatal inj
voltages, possibly resulting in equipment damage, fire and even voltages, possibly resulting in equipment damage, fire and even
Ensure that the current transformer wiring is secured using an external strain relief to
Ensure that the current transformer wiring is secured using an external strain relief to
Ensure that the current transformer wiring is secured using an external strain relief to Ensure that the current transformer wiring is secured using an external strain relief to
reduce mechanical strain on the screw terminals
reduce mechanical strain on the screw terminals, if necessary.
reduce mechanical strain on the screw terminalsreduce mechanical strain on the screw terminals
Only qualified personnel familiar with the instrument and its associated electrical
Only qualified personnel familiar with the instrument and its associated electrical
Only qualified personnel familiar with the instrument and its associated electricalOnly qualified personnel familiar with the instrument and its associated electrical
equipment must perform setup procedures
equipment must perform setup procedures.
equipment must perform setup proceduresequipment must perform setup procedures
Do not open the instrument under any circumstances when it is
Do not open the instrument under any circumstances when it is connected to a
Do not open the instrument under any circumstances when it isDo not open the instrument under any circumstances when it is
power
power source
powerpower
Do not use the instrument for primary protection functions where failure of the device
Do not use the instrument for primary protection functions where failure of the device
Do not use the instrument for primary protection functions where failure of the device Do not use the instrument for primary protection functions where failure of the device
can c
can cause fire, injury or death. The instrument can only be used for secondary
can ccan c
protection if needed.
protection if needed.
protection if needed. protection if needed.
Read this manual thoroughly before connecting the device to the current carrying circuits.
Read this manual thoroughly before connecting the device to the current carrying circuits.
Read this manual thoroughly before connecting the device to the current carrying circuits. Read this manual thoroughly before connecting the device to the current carrying circuits.
During operation of the device, hazardous voltages are present on in
During operation of the device, hazardous voltages are present on input terminals
During operation of the device, hazardous voltages are present on inDuring operation of the device, hazardous voltages are present on in
to observe precautions can result in serious or even fatal injury or damage to equipment.
to observe precautions can result in serious or even fatal injury or damage to equipment.
to observe precautions can result in serious or even fatal injury or damage to equipment.to observe precautions can result in serious or even fatal injury or damage to equipment.
is intended for measurements performed in building installations, relating to
MonMon
is intended for measurements performed in building installations, relating to is intended for measurements performed in building installations, relating to
connecting the instrument to the power
connectinconnectin
no circumstances should the instr ument be connected to
no circumstances should the instrno circumstances should the instr
be open circuit when the primary is energized. An open circuit can cause high
open circuit when the primary is energized. An open circuit can cause high
bebe
open circuit when the primary is energized. An open circuit can cause high open circuit when the primary is energized. An open circuit can cause high
source....
source source
ause fire, injury or death. The instrument can only be used for secondary
ause fire, injury or death. The instrument can only be used for secondary ause fire, injury or death. The instrument can only be used for secondary
g the instrument to the power source
g the instrument to the powerg the instrument to the power
potential fire or shock hazard, do not expose the instrument to
potential fire or shock hazard, do not expose thepotential fire or shock hazard, do not expose the
Multi----Mon CTs
Mon CTs to the
MultiMulti
, the external current transformer secondary output must never be
, the external current transformer secondary output , the external current transformer secondary output
Mon CTsMon CTs
1, 6.7.4).
4).
1, 6.7.1, 6.7.
4).4).
and other power sources are turned OFF before
and other power source and other power source
source, check the labels at the front of
source source
ument be conn ected to a p ower
ument be conn ected toument be conn ected to
to the secondary
secondary of an external
to the to the
secondary secondary
of an external third party
of an external of an external
, if necessary.
, if necessary., if necessary.
s are turned OFF before
s are turned OFF before s are turned OFF before
, check the labels at the front of
, check the labels at the front of , check the labels at the front of
a power source
a powera power
instrument to rain or
instrument toinstrument to
third party cu
third party third party
must never be allowed
must never bemust never be
serious or fatal injury
serious or fatal injserious or fatal inj
connected to a
connected to a connected to a
put terminals. Failure
put terminalsput terminals
current
rrent
cucu
rrent rrent
allowed
allowed allowed
. Failure
. Failure . Failure
source
sourcesource
rain or
rain or rain or
ury.
uryury
.
. .
All trademarks are property of their respective owners.
August 2013
The Multi-Mon is a 3-phase, multi-channel, multi-function energy meter
suitable for use in single-phase and multi-phase electrical networks.
Meter highlights
Meter highlights
Meter highlightsMeter highlights
Fea
Features
FeaFea
•Multi-channel submetering – up to 36 single-phase or 18 two-phase
or 12 three-phase submeters in a single device. Any combination of
single-, two-, and three-phase consumers can be chosen up to a
total of 36 current inputs.
•Automatic totalization energy from different sub-consumers
tures
turestures
•Calibrated to meet Class 0.5S active energy and Class 1 reactive
energy meter accuracy
Multi-Mon offers maximum flexibility of current connections by using the
variety of Highly Accurate Current Transformer (HACS) options and by wiring
any Highly Accurate Current Transformer to any current input of the device.
The following drawings present applications serviced by the Multi-Mon.
Befor
Before installation ensure that all incoming power
e installation ensure that all incoming power source
BeforBefor
e installation ensure that all incoming powere installation ensure that all incoming power
Failure to observe this practice can result in serious or even fatal injury and
Failure to observe this practice can result in serious or even fatal injury and
Failure to observe this practice can result in serious or even fatal injury and Failure to observe this practice can result in serious or even fatal injury and
damage to equipment.
Highly Accurate Current Transformer wiring and labeling
Highly Accurate Current TransformerHighly Accurate Current Transformer
USE ONLY WITH SUPPLIED BFM CURRENT TRANSFORMERS!
USE ONLY WITH SUPPLIED BFM CURRENT TRANSFORMERS!
USE ONLY WITH SUPPLIED BFM CURRENT TRANSFORMERS!USE ONLY WITH SUPPLIED BFM CURRENT TRANSFORMERS!
Connect the wires to the + and - inlets according to the following polarity
colors:
Polarity
Polarity
PolarityPolarity
It is recommended to mark the cables and CTs with the supplied tie markers.
CTs stickers I1 through I36 correspond to the Multi-Mon current inputs with
matching labels. Cable stickers 1 through 12 correspond to the Multi-Mon
current terminal blocks with matching labels.
Use the table from Appendix B to annotate your input assignments and
wiring connections.
Label
Labeling example:
LabelLabel
Assume you want to connect three HACSs to the device terminal block 3 so
these three HACSs would be connected to the device inputs I7, I8, and I9
respectively:
1. Take a CT connection cable, attach a tie wrap marker to each side of
2. Put the CT label stickers I7, I8, and I9 directly on HACSs to indicate that
Solid Core
Solid Core Current Transformer
Solid Core Solid Core
++++ RED WHITE
---- ORANGE BLACK
ing example:
ing example: ing example:
the cable and mark them as 3 to indicate that it should be connected to
the device terminal block 3.
these HACSs will be associated with the device current terminals I7, I8,
and I9.
Current Transformer
Current TransformerCurrent Transformer
secondary
secondary
secondarysecondary
wiring and labeling
wiring and labeling wiring and labeling
Split Core
Split Core Current Transformer
Split Core Split Core
Current Transformer
Current TransformerCurrent Transformer
secondary
secondary
secondarysecondary
14
Multi-Mon Multiple Circuit Energy Monitor
Chapter 2 Installation
Electrical Installation
Safety Req
Safety Requirements
Safety ReqSafety Req
To ensure safety requirements the Multi-Mon must be grounded - the
protective ground terminal should be connected to protective earth with a
copper conductor or strap with minimal length (less than 1 m desirable) and
cross-section 5.3 mm
The properly marked external 3-pole disconnect device with circuit-breaker
and a fuse 6A, 600V in every pole should be installed between voltage
measurement terminals and power lines, located as close as possible (less
than 2 m recommended) to the Multi-Mon, as shown in figure 2-5 .
uirements
uirementsuirements
2
(AWG10) at least.
Figure 2
Figure 2----7 External
Figure 2Figure 2
7 External CT
7 External 7 External
CT connection to
CTCT
Multi-Mon Multiple Circuit Energy Monitor
connection to meter CT
connection to connection to
meter CT
meter CTmeter CT
15
Chapter 2 Installation
DEVICES
485
)
PC
+
Communications
Communications
CommunicationsCommunications
Several communication options are available for the Multi-Mon.
The flashing yellow CPU LED shows that the device is operational and is
functioning normally.
The green TX and RX LEDs indicate activity on the COM1 communication
port. The LEDs flash when the port is receiving or transmitting data.
The red “Wh” LED flashes at a user-programmed rate when a load is applied
to the device. In normal mode, the LED pulses indicate imported Wh for a
selected submeter. In energy test mode, the LED pulses indicate either
imported Wh, or imported (inductive) varh for a selected submeter. Energy
test mode is used for testing the device energy measurement accuracy. In
test mode, the energy and demand accumulators do not account for
consumed energy.
See Device Options in Chapter 3 and General Meter Setup in Chapter 4 on
how to put the device into energy test mode and how to select the LED pulse
rate and a submeter for testing.
The Multi-Mon is provided with an LCD display and four push buttons that
are used for local meter reading and setup. See Multi-Mon Display
Operations in Chapter 3 for information on using the front panel display.
20
Multi-Mon Multiple Circuit Energy Monitor
Chapter 2 Installation
Device Settings
Device Settings
Device SettingsDevice Settings
Password
Password
PasswordPassword
Submeter System
Submeter System
Submeter SystemSubmeter System
Device Settings
Before operating your Multi-Mon, provide the device with information about
your particular environment. The device front display (see Display
Operations (Multi-Mon)) and the supplementary Power Software (see Power
Software Application Software) allow you to configure the Multi-Mon for your
particular use.
The Multi-Mon configuration setups are secured by a factory-preset
password. Contact your dealer for your primary password. Later, you will be
able to change the password via the device Access Menu (see Meter
Security).
The Multi-Mon provides up to 36 submeters with separate measurement and
energy registers. Each submeter can service current inputs dedicated to a
particular consumer (metering submeter) or be used as a totalization meter
for automatic totalization of energy from different sub-consumers (totalization
submeter). Additionally, the Multi-Mon provides four more totalization
submeters (37 through 40) that you can use for totalization purposes when
all 36 metering submeters have been utilized.
A submeter remains inactive while there are no current inputs associated
with the submeter (see Channel Assignments), or until you link another
submeter as a source to its energy registers making it a totalization submeter
(see Setting up Total and Tariff Registers). The Channel Assignment setup
allows you to link one to three current inputs to each submeter and to specify
the primary rating of the current transformers. A totalization submeter
provides totalization of energy from any number of metering and totalization
submeters.
By default, your device is configured for 12 three-phase metering submeters
with 100A (maximum) current inputs (50A nominal rating).
Submeter
Submeter Addressing
SubmeterSubmeter
Addressing
Addressing Addressing
The Multi-Mon uses the Modbus communication protocol for data
transmission and accessing setups through communications. A full
description of the communications protocol is found in the Multi-Mon
Modbus Reference Guide provided with your device.
Each active submeter in the Multi-Mon is assigned a unique communication
address that allows accessing its private registers and setups. All submeter
addresses are assigned automatically in a sequential order starting with the
device base address that is programmed through the device Communication
Setup (see Setting Up Communication Ports ). The following table illustrates
submeter addressing in the device with the base address N.
Device Ba
Device Base Address
Device BaDevice Ba
N
Your device is factory preset to address 1 and occupies the range of
addresses 1 through 12, configured for 12 three-phase submeters.
NOTES
NOTES
NOTESNOTES
1111.... Device setup settings, excluding the alarm setpoints and data log setup,
se Address Submeter Number
se Addressse Address
Device setup settings, excluding the alarm setpoints and data log setup,
Device setup settings, excluding the alarm setpoints and data log setup, Device setup settings, excluding the alarm setpoints and data log setup,
are shared across all submeters. Though you can read or write them
are shared across all submeters. Though you can read or write them
are shared across all submeters. Though you can read or write them are shared across all submeters. Though you can read or write them
using any submeter address, your changes affect all submeters in the
using any submeter address, your changes affect all submeters in the
using any submeter address, your changes affect all submeters in the using any submeter address, your changes affect all submeters in the
device.
device.
device. device.
Submeter Number Submeter Address
Submeter NumberSubmeter Number
SM 1 N
SM 2 N+1
…
SM 36 N+35
SM 37 N+36
…
SM 40 N+39
Submeter Address
Submeter AddressSubmeter Address
Multi-Mon Multiple Circuit Energy Monitor
21
Chapter 2 Installation
Basic Device Settings
Basic Device Settings
Basic Device SettingsBasic Device Settings
Energy/TOU System
Energy/TOU System
Energy/TOU SystemEnergy/TOU System
Device Diagnostics
2222.... When using the ExpertPower
When using the ExpertPower client, submeter address 99 on the
When using the ExpertPowerWhen using the ExpertPower
Ethernet port COM2 is reserved for the
Ethernet port COM2 is reserved for the Multi
Ethernet port COM2 is reserved for the Ethernet port COM2 is reserved for the
fall inside the range of the submeter addresses for this port.
fall inside the range of the submeter addresses for this port.
fall inside the range of the submeter addresses for this port.fall inside the range of the submeter addresses for this port.
Select your submeters (both metering and totalization) in a sequence without
gaps so that your device does not occupy unnecessary network addresses.
If you connect a number of devices to a serial network, allocate a range of
addresses for each device so that they do not overlap. For example, if you
use three devices with 12 submeters in each one, assign the base address 1
to the first device, the address 13 to the second, and the address 25 to the
third device so that they will occupy three non-overlapped address ranges 1
through12, 13 through 24, and 25 through 36.
For proper device operation, select the correct power frequency (see Basic
Device Settings) and set the correct primary ratings for device current inputs
(see Channel Assignments) before you connect the device to your network.
The Multi-Mon provides 4 separate billing energy (total/summary and
parallel tariff and maximum demand) registers for each individual submeter.
Each register can be linked to any internal energy source or another
submeter. The first billing register in your meter is linked to the kWh
accumulator by default. Other registers are not operational unless you
configure them through the Energy/TOU Setup (see Configuring Billing
Energy and TOU Registers).
client, submeter address 99 on the
client, submeter address 99 on the client, submeter address 99 on the
Multi----Mon
Mon router and must not
MultiMulti
router and must not
MonMon
router and must not router and must not
Device Diagnostics
Device Diagnostics
Device DiagnosticsDevice Diagnostics
Device diagnostic messages may appear as a result of the Multi-Mon built-in
diagnostic tests performed during start-up and device operation. See Device
Diagnostic Codes in Appendix F for the list of diagnostic codes and their
meanings.
The device diagnostics status is stored in a non-volatile register, which may
be inspected and cleared via Power Software, from the meter display or from
a user application. All diagnostic events with time stamps are also recorded
in the device Event log and can be inspected via Power Software (see
Retrieving the Event Log in Chapter 4).
See Diagnostics Display and Reset in Chapter 3 on how to inspect and clear
the device diagnostics status from the display. See Viewing and Clearing
Device Diagnostics in Chapter 4 on how to inspect and clear the device
diagnostics status via Power Software. Refer to the Multi-Mon Modbus
Reference Guide for the diagnostic register address and layout.
In the event of a device fault, check the fault reason and clear the device
diagnostics. In the event of a time fault, update the device clock. In the event
of a configuration reset, check the setup affected by the fault via the device
Event log, and then verify the setup data.
Hardware failures are normally non-critical recoverable faults that do not
cause a system failure but may cause data loss. Hardware failures are often
caused by excessive electrical noise in the region of the device.
If the device continuously resets itself, contact your local distributor.
22
Multi-Mon Multiple Circuit Energy Monitor
Loading...
+ 50 hidden pages
You need points to download manuals.
1 point = 1 manual.
You can buy points or you can get point for every manual you upload.