We are pleased that you chose to buy one of our products, and want you to be just as
pleased with owning it. Before installing your new E-Mon product, please read the
information on the following pages carefully.
We believe that you will find the E-Mon D-Mon meters easy to install and to use for
monitoring and evaluating your electrical usage.
To be sure that you are 100% satisfied with your products, we provide toll-free
technical and sales support Monday through Friday, 8:00 am to 7:30 pm, EST:
(800) 334-3666. You may also reach us via email at info@emon.com.
If you have questions, we can handle them quickly and effectively with a telephone call.
Please let us try to help you BEFORE you remove your meter. And to help us help you,
we ask that you have all relevant information on hand when you call (model or part
numbers, nature of difficulty, etc.)
Be sure to forward this manual to the owner after installation is complete, so that they
may use it as a reference guide when reading the E-Mon D-Mon meter.
Thank you.
62-0390-022
CLASS 3200 METER
TABLE OF CONTENTS
Section 1.0Introduction4
Section 2.0Internal Electronic Assemblies6
Section 2.1Main Power Board6
Section 2.2Display Board7
Section 3.0Meter Technical Specifications8
Section 4.0Safety Label Definitions and Information10
Section 5.0Precautionary and Safety Information11
Section 6.0Meter Installation12
Section 6.1Mounting the Class 3200 Meter12
Section 6.2Main Power Board Connections12
Section 6.3Phasing of Line Voltage15
Section 6.4Current Sensor Installation & Wiring16
Section 6.5Main Power & Current Sensor Wiring Diagram18
Section 6.12Connecting Class 3200 Meters to USB Key using RS48528
Section 6.13Ethernet Communications29
Section 7.0Multiple-Load Monitoring30
Section 8.0Preventative/Scheduled Maintenance31
Section 9.0Lithium Battery Replacement32
Section 10.0Class 3200 Meter Operating Modes34
Section 10.1Start Up Screens34
Section 10.2Normal Mode Display Screens35
Section 10.3How to Program the Display Screens36
Section 11.0High Voltage Metering41
Section 12.0Class 3200 Protocol Definitions45
Section 13.0Meter Limited Warranty51
362-0390-02
CLASS 3200 METER
1.0 INTRODUCTION
The E-Mon D-Mon® Class 3200 meter is a 3-element meter with communications. The
device is used to monitor electric power usage of individual loads after the utility meter
and store kW and kVAR data for automatic meter reading. Installation must only be
performed by qualified personnel and in accordance with these instructions and all
applicable local and national electrical codes. E-Mon and its representatives assume
no responsibility for damages or injury resulting from the improper installation of this
meter.
Verify the input voltage rating and configuration on the unit panel label to ensure that it
is suitable for the intended electrical service. Class 3200 meters labeled for 120/208V
service MUST NOT be installed on service feeds of 277/480 volts or 347/600 and vice
versa.
Verify that the Class 3200 meter’s current sensors are sized suitably for the load to be
monitored. Compare the color of the arrows on the current sensors to the chart below
to confirm the correct current sensor is being used.
Sensor Arrow Color CodeSensor Rating
Brown100 A
Red200 A
Yellow400 A
Black800 A
Blue1600 A
White/Black3200 A
62-0390-024
CLASS 3200 METER
CAUTION
WARNING
Internal circuit components are extremely sensitive to electrostatic discharge.
Prior to handling or touching internal circuitry, discharge any static buildup on
your person. To discharge yourself, touch a grounded metal object such as
conduit or an earth-grounded enclosure.
Use of this instrument, the E-Mon D-Mon Class 3200 meter, in a manner
inconsistent with this manual or not specified by the manufacturer in writing,
can cause permanent damage to the unit and/or serious injury to the operator.
The protection and safety features provided by this equipment may become
impaired or otherwise compromised.
NOTE: If any trouble arises during the installation or functional verification opera-
tions, do not immediately remove the unit. Before removing the unit, contact
E-Mon’s technical support and/or engineering department at (800) 334-3666.
E-Mon’ s technical department will assist you in detailed troubleshooting of
the Class 3200 meter installation and assist you in getting the unit operating
correctly.
562-0390-02
CLASS 3200 METER
2.0 INTERNAL ELECTRONIC ASSEMBLIES
The units are comprised of two major subassembly boards, the main power board and
the display board. Both circuit boards are mounted inside a UL Type 1 or Type 4X
enclosure.
MAIN
POWER
BOARD
DISPLAY
BOARD
M33307
Fig. 1. Internal Electronic Assemblies.
2.1 Main Power Board
Connections to this board include the MAIN Power Input and current sensors.The
MAIN Power Input terminals are positions one through four on the four position screw
terminal block, TB1. These terminals are covered with a protective shield for safety
purposes. The current sensor assemblies interface to TB2, TB3 and TB4. Each
terminal block corresponds to an input voltage phase; care must be exercised to
ensure that each current sensor is connected to the correct terminal block. One three
terminal screw connector is provided for RS-485 communications.
TB1
POSITIONS
1-4
TB2, TB3,
TB4
Fig. 2. Main Power Board Connections.
62-0390-026
RS-485
M33308
CLASS 3200 METER
M33279
DOWN
UP
SELECT
MENU
2.2 Display Board
The display board connects to the main power board via a flex ribbon cable and the
board mounts on the inside of the housing door.
The Class 3200 meter features a 4-line LCD display that indicates multiple meter data
points.
Fig. 3. Display Board.
762-0390-02
CLASS 3200 METER
M33191
EXAMPLE:E 32- 208 200 J RTU KIT
E-MON
CLASS 3200 METER
INPUT VOLTAGE (208V)
CURRENT RATING (200A)
ENCLOSURE (METAL - TYPE 1)
PROTOCOL (MODBUS)
SENSORS (SPLIT-CORE)
3.0 METER TECHNICAL SPECIFICATIONS
Ordering Information: Define brand, class, input voltage, amperage, protocol, and
sensor type in the format A-BB-CCC-DDDD-E-FFF-GGG, where
A = Brand: E for E-Mon
BB = designates Class: 3200 (32), 3400 (34), or 5000 (50) meter
CCC = input voltage: (208, 480, 600, 120 volt for High Voltage)
DDDD = current rating: (100, 200, 400, 800, 1600, 3200, 25HV)
E = enclosure: J = metal (type 1), R = non-metallic (type 4X), M = MMU
FFF= protocol: RTU = Modbus, BAC = BACnet, EZ7 = proprietary
GGG = Sensors: KIT = split-core, SCS = solid-core, “blank” = none supplied
Input Voltage
3-wire (delta) Or 4-wire (wye)
Configuration
Mains Voltage InputUp To 600 VAC RMS available
Input Power6 VA maximum rating
Current Sensor
Up To 3200 amps RMS AC available
Rating
Power Factor 0.5 leading or lagging
Line Frequency50-60 Hz
Metering AccuracyANSI C12.20
Temperature Range -20C to +50C
Relative Humidity
0-95% non-condensing
Range
Altitude2000 meters maximum
Voltage Overload+25% continuously: +100% For 20 cycles
Current Sensor
100% for 1 minute
Overload
Pollution DegreeDegree 2 in accordance with IEC 664
Battery Cell:Description:Non-rechargeable cell used for
Manufacturer:Littlefuse
Mfg. Part No:KLDR.100
Rating:100mA, time-delay, 600VAC
cartridge fuse
memory retention
Manufacturer:Panasonic
Mfg Part No:CR2032
Working Voltage:3Vdc
Current Capacity225 mAHr
Electrolyte:Manganese Dioxide Lithium
962-0390-02
CLASS 3200 METER
4.0 SAFETY LABEL DEFINITIONS AND
INFORMATION
The 3200 meter may contain one or more of the following labels. Operator(s) should
familiarize themselves with the meaning of each label to minimize risk.
The presence of this label is a cautionary indicator identifying a
danger risk. The manual should be consulted prior to proceeding.
The presence of this label indicates an electrical shock hazard exists
in the location or area where the label is placed. Prior to proceeding,
the MAINS power must be disconnected and the manual consulted for
safety information.
62-0390-0210
CLASS 3200 METER
CAUTION
WARNING
WARNING
WARNING
5.0 PRECAUTIONARY AND SAFETY
INFORMATION
Internal circuit card components are extremely sensitive to electrostatic
discharge. Be careful not to touch internal circuitry prior to discharging any
static buildup on your person. To discharge yourself, touch a grounded metal
object such as conduit or an earth-grounded metal enclosure.
High voltages present on main PCB terminal block TB1 screw terminals. Risk
of serious injury and/or electrical shock exists. Prior to performing any wiring
operations, review all contents of the user manual and de-energize the MAINS
power switch. Only qualified personnel should perform installation wiring.
Installation wiring must comply with all local and national electrical codes.
Failure to ground the enclosure creates a possible shock hazard. Do not
operate the Class 3200 meter without a protective earth wire attached securely
to the PE terminal screw. After installing protective earth wiring, secure the
screw tightly (7in-lb torque.)
NEVER open front panel of unit while unit has MAINS power applied. Failure to
comply can increase the risk of serious injury and/or electrical shock.
1162-0390-02
CLASS 3200 METER
WARNING
6.0 METER INSTALLATION
6.1 Mounting the Class 3200 Meter
Use appropriately sized mounting hardware to fasten the Class 3200 enclosure to the
selected mounting surface. The four housing mounting holes are centered 6.75” H x 4”
W. When the meter is provided in the 4X rated enclosure, the hub must be mounted to
the conduit first before connecting it to the enclosure.
NOTE: Units housed in UL type 1 enclosures must only be installed in indoor loca-
tions, where they will not be affected by the elements.
6.2 Main Power Board Connections
1. Installing a temporary ground for ESD protection: With all circuits de-energized,
connect a temporary protective earth ground connection for ESD protection.
Prior to performing any unit wiring, be sure to discharge any static on your person.
2. Installing the Class 3200 protective earth ground: Connect an earth ground wire
to the Class 3200 (Type 1 enclosure) protective earth ground lug with a torque of
7 N-m.
Failure to attach the protective earth ground wire securely to the meter creates
a potential shock hazard. Do not loosen or remove the screw securing the
ground lug.
Fig. 4. Main Power Board Connections.
62-0390-0212
CLASS 3200 METER
6.2 Main Power Board Connections (continued)
3.
Wire Entry:
enclosures. This opening is used for bringing in MAINS power and for current
sensor wiring. One 1/2” conduit opening on the top of the metal enclosure
CL3200 can be utilized as an interface for the low- voltage signals, pulse input,
or RS-485 communications wiring to the unit. CL3200 meters are available in an
MMU (Multiple Meter Unit) enclosure that holds eight (8) meters. This enclosure
comes without knockouts and allows the user to choose entry points for the wiring.
Any unused openings must be sealed with a UL rated plugging device or hub
suitable for the rating of the enclosure - such as NEMA 1 or 4X
4. Unit MAINS wiring:
The four positions on terminal block TB1, located at the bottom left corner of the
main power board, are clearly labeled Phase A, B, C, N (neutral). Earth Ground
MUST be connected to the PCB mounting screw in the lower right corner.
A. Connect the NEUTRAL wire to the appropriate terminal block position.
One 3/4” conduit opening is located on the bottom of the CL3200
.
Fig. 5. Terminal Block TB1, TB2, TB3, and TB4.
NOTE: For 3-wire delta-type applications, do NOT connect the NEUTRAL wire.
Remove the terminal block screw for this position.
B. Earth Ground
Connect the Earth Ground to the PCB mounting screw in lower right corner.
C. External Switch Mechanism/In-Line Fuse Installation
To ensure a safe installation, the Class 3200 meter requires an external
switch mechanism, such as a circuit breaker, be installed on the meter’s
MAINS input wiring. The switch mechanism must be installed in close proximity to the meter and easily reachable for the operator. This device must
also be marked as the disconnecting device for the Class 3200 meter. 1/10
Amp Slow Activation in line fuses (KLDR.100, UL listed, Littelfuse rated
600V/100ma) must be installed for each conductor phase at the MAINS input
to the meter. The fuses must be labeled to indicate voltage and current rating
as well as element characteristics.The fuse element must be slow activating
type.
1362-0390-02
CLASS 3200 METER
6.2 Main Power Board Connections (continued)
D. Connect the three AC main power wires (Phases A, B and C) to their respec-
tive positions as labeled on terminal block TB1. After all conductors are connected to each of their respective terminal block positions and tightened to 7
in-lb, verify that each terminal block screw is securely fastened by gently tugging on each conductor. Verify that no conductor wires are frayed or shorting
to adjacent terminal block positions.
E. Turn ON the AC main power input. The meter display will light up and scroll
through 6 displays. Each display is visible for 5 seconds. Display screens are
as follows:
Screen 1 - Total kilowatt-hours (kWh) consumed
Screen 2 - Peak demand (kW) with date & time stamp
Screen 3 - Actual load (kW)
Screen 4 - RMS Amps
Screen 5 - RMS Volts Phase to Neutral
Screen 6 - RMS Volts Phase to Phase
Screen 7 - Power factor (PF) per phase
F. Verify the voltage readings on Screen 5 using an AC voltmeter. Typical read-
ings shown below are measured phase to neutral (L-N) for 4 wire and phase
to phase (L-L) for 3 wire. Readings should be +/- 10% of nominal.
Meter TypeNominal Voltage Limits (+/- 10%)
208V, 3ø, 4 Wire120 VAC (L-N)108 to 132 VAC
480V, 3ø, 4 Wire 277 VAC (L-N)249 to 305 VAC
600V, 3ø, 4 Wire347 VAC (L-N)312 to 380 VAC
240V, 3ø, 3 Wire240 VAC (L-L)216 to 264 VAC
480V, 3ø, 3 Wire480 VAC (L-L) 432 to 528 VAC
NOTE: Meters are powered by phases A and B. The displayed voltages will be the
measured AC voltage between phases.
62-0390-0214
CLASS 3200 METER
6.3 Phasing of Line Voltage
The 3-phase AC power input must be in proper phase sequence. If the sequence is
incorrect or a phase is missing, there will be a message on the meter’s display: “PH
Sequence Error” or “PH Missing:. (Refer to the section on Line Voltage Diagnostics if
this message is present.) When the line voltage is connected correctly, the meter’s
display will be blank (no message.)
Wait for the 4-line meter display to scroll to the voltage display. Verify that the meter
reads correct voltages on all three phases. Repeat Step 6.2.4F.
Once the meter displays the correct line voltages and there are no error messages,
you are ready to connect the current sensors to the meter. Before continuing with the
installation, verify that the six screens display as follows:
Screen 1 (kWh): Should read 0.0 kWh; if not, should be reset.
Screen 2 (kW Peak Demand): kW peak should read 0.0 kW. There will not
be a date/time stamp yet. If there is a kW
peak recorded, it should be reset later.
Screen 3 (kW Load): Should read 0.0 kW load.
Screen 4 (Amps per Phase): There should be 0.0 on all three phases.
Screen 5 (Volts RMS Phase to Neutral): See the section 6.2.4.F.
Screen 6 (Volts RMS Phase to Phase): See the section 6.2.4.F.
Screen 7 (Power Factor Per Phase): There should be 0.0 PF on all three phases.
NOTE: The meter will be reset later via the software during “startup” procedures.
1562-0390-02
CLASS 3200 METER
M33213
LOAD
SOURCE
6.4 Current Sensor Installation & Wiring
Once the AC voltages have been confirmed to be within acceptable limits, you are
ready to install the current sensors. TB2 is the input for Phase A, TB3 is the input for
Phase B and TB4 is the Phase C input.
The Class 3200 meter can be used with two types of current sensors:
1. Split-core current sensor. This sensor opens so that it can be attached around
the circuit being monitored without interrupting power.
2. Solid-core current sensor. This sensor does not open and requires the monitored
conductor to be removed from the circuit to install the current sensor. This type is
only supplied when specified at time of order.
NOTE: It is recommended that a UL listed current sensor be used for this application.
6.4.1 Installing the Split-Core Current Sensor Assembly
1. Each phase being monitored will require one two-piece current sensor assembly.
Open the two-piece current sensor assembly by releasing the nylon clamp using
a flathead screwdriver.
Fig. 6. Split Core Sensor.
2. Reassemble the current sensor assembly around the conductor(s) to be monitored. Ensure the current sensor halves marked “Load” are both facing the load
side of the conductor. The colored arrow will be on the source side of the conductor being monitored and MUST be pointed in a clockwise direction around the
conductor being monitored. Tighten the nylon clamp to complete the assembly.
Fig. 7. Split Core Sensor.
IMPORTANT:
When looking from the source side of the conductor(s) being monitored, you
should see the arrow on the current sensor assembly. The arrow should be
pointing in a clockwise direction around the conductor(s) being monitored. If
the arrow is not positioned on the source side, inaccurate readings will result.
62-0390-0216
CLASS 3200 METER
6.4.1 Current Sensor Wiring
Once the current sensors are installed onto their appropriate phase conductors, you
can begin terminating the current sensors onto the Class 3200 main board. The
current sensors can be extended up to 500 feet for remote monitoring applications. To
extend the length of the wires, use #22 AWG twisted-pair wire with one white and one
black wire.
The easiest way to connect the current sensors is to use the meter’s built-in current
sensor diagnostics. To do this, there must be at least 1% of the meter’s current rating
(amps) flowing in each of the conductors being monitored. The Class 3200 meter’s
diagnostic program (on the 4-line display) will provide data to ensure that the current
sensor installation is done properly.
The current sensor connection points are located at the bottom right of the main power
board. These are TB2, TB3, and TB4. Each sensor connects to two terminals one
labeled “Black” and the other “White.” Current sensors should be connected to the
meter one at a time and verified using the current sensor diagnostic program.
Connect one of the current sensors to the TB2 terminals (Phase A). Tighten the
terminal to 4.5 in-lb. Wait 5 seconds and look at the meter display.
If the meter displays an error message (see below), remove the wires from TB2 (Phase
A) and install them on TB3 (Phase B). if an error message occurs with the sensor
attached toTB3, try again on TB4 (Phase C). The wiring will be correct when the error
indication message is gone.
NOTE: If the power factor being monitored is <65%, the error message may be acti-
The “CT Error: * “message will disappear when the current sensor is connected to the
correct terminals (phase).
Error Messages: CT ERROR: A
Refer to the section on Current Sensor Diagnostics for assistance in troubleshooting
these errors.
vated until improved. This is normal and indicates poor power factor.
CT ERROR: A B
CT ERROR: A C
6.4.2 Main Power
After the meter circuit wiring has been examined for correctness, power may be
applied to the circuit board. There are three LEDs located in the upper right corner of
the Meter Board labeled BEAT, STATUS and LOAD. The BEAT and STATUS LEDs will
blink once per second when the meter is operating normally, twice per second if there
is a problem.If the monitored circuit is under load the LOAD LED will actively blink. A
heavy load will cause the LED to blink faster than a light load. Very light loads will
result in an extended blink time.
1762-0390-02
CLASS 3200 METER
LINE VOLTAGE
CURRENT SENSORS
N
LOAD SOURCE
M33185
3-PHASE, 4-WIRE INSTALLATION DIAGRAM
NOTES:
LINE VOLTAGE CONNECTIONS: #14-12 AWG
SENSOR CONNECTIONS: B = BLACK LEAD W = WHITE LEAD
NEUTRAL NOT USED IN DELTA SYSTEM. REMOVE NEUTRAL TERMINAL
BLOCK SCREW FOR DELTA SYSTEMS.
1/10A 600 VAC INLINE FUSE PER CONDUCTOR. LITTLEFUSE PART
NUMBER KLDR.100.
1
1
1
1
C
W B W B
N
PE
W B
6.5 Main Power & Current Sensor Wiring Diagram
Fig. 8. 3-phase- 4 Wire Installation Diagram
6.6 Line Voltage/Current Sensor Diagnostics
Following is a list of diagnostic messages that may appear on the meter display.
DIAGNOSTIC MESSAGES SHOULD NOT BE ON CONTINUOUSLY WHEN THE
METER IS INSTALLED PROPERLY AND IS IN WORKING ORDER.
6.6.1 Line Voltage Diagnostics
The diagnostics program detects line voltage faults by displaying one of two
messages:
PH Missing: B C or Phase sequence error.
Phase sequence error
proper phase sequence. This message should never be seen continuously on the
display during normal operation. The meter will not display correct electrical data in
this condition. The phase sequence problem must be remedied in order for the meter
to work properly.
Missing: B C
indicates that the line voltage is missing on Phase B and/or Phase C.
This message will appear whenever the power on either Phase B or Phase C is off.
Screen 5 (Voltage per Phase) will also indicate a loss of line voltage.
62-0390-0218
indicates that the 3-phase line voltage is not hooked up in the
CLASS 3200 METER
6.6.2 Current Sensor Diagnostics
The load current must be at least 1% of the meter’s rated load in order to use the
diagnostic function. Current sensor diagnostics can detect:
1. Reversed current sensors
2. Incorrect phase correspondence
3. Unusually low power factor (0.642 or lower)
CT Error: (ABC) is used to detect the swapping of current sensor phases. This
message could (in some rare cases) indicate a low (<65%) power factor condition. This
message may appear intermittently due to changes in line conditions. It should not be
on continuously. (See Section 6.4.1.)
NOTE: If you have connected the current sensor to all three terminals and the error
message is still appearing, reverse the black and white wires and repeat the
previous steps until the correct connection is found.
If the
CT Error:
however, the current sensor was not installed properly around the conductor, or the
sensor wires were extended and not spliced together correctly. Correct the sensor
installation, reconnect the black wire to the black terminal and the white wire to the
white terminal on the plug and reinstall the plug into the correct phase terminal for that
current sensor. The error message should disappear and the current sensor is now
installed properly.
If the
CT Error:
ways, check the AC voltage input from the current sensor between the black and white
wires using an AC voltmeter. It will read approximately zero volts indicating that the
load current is very small (or zero) or the current sensors are not secured properly
(tight connection between core halves or lead splices not secure.)
message disappears, you have found the correct sensor connection;
message does not disappear at any time while trying all 3 inputs both
Once the first current sensor is connected properly and the error message disappears,
repeat the previous procedure for the remaining two current sensors. When all error
messages have disappeared and all sensors are installed correctly, the meter is
operational.
6.7 RS-485 Wiring
RS-485 communication allows a computer or modem to communicate with one or
more Class 3200 meters. You can connect as many as 52 meters along a 4000 foot
RS-485 cable run.
There are two communication protocols supported by the RS-485 connection; EZ7 and
Modbus RTU. The protocol is selectable via DIP switch S2, located on the Main Power
Board. If S2 position 1 is in the ON position, EZ7 is active. If S2 position 1 is in the OFF
position, Modbus RTU* is active. S2 position 2 is not used on the Class 3200. DIP
switch S2 positions 3 and 4 to select the Baud rate for the RS-485 communications.
See section 6.9.3 for details on Baud rate selection. After changing the DIP switch
positions, the CPU must be rebooted by pressing S1 to activate the changes.
1962-0390-02
CLASS 3200 METER
M33195
RS-485
TERMINAL
6.7 RS-485 Wiring (continued)
* An alternate version of firmware is available that replaces Modbus RTU with BACnet
MS/TP.
Modbus.
There are two connection methods, daisy-chain and wire terminal, for RS-485
communications.
Daisy-Chain Method
This is the simplest method for connecting meters together.
The meter must be ordered with this option if BACnet is desired instead of
M32776
Fig. 9. Daisy-chain Configuration.
1. Connect the +(high) terminal of PORT 1 of each meter together so that the + terminals on all meters are linked, + to + to +...
2. Connect the -(low) terminal of PORT 1 of each meter together so that the - terminals on all meters are linked, - to - to -...
3. Connect the GND terminals of PORT 1 to meter 1 ONLY. The GND terminals
should not be linked to each meter.
4. Torque screws to 2.2 in-lb.
Fig. 10. RS-485 Terminal.
62-0390-0220
CLASS 3200 METER
RJ−11
PLUG
FRONT VIEW
M33196
1 - NC
2 - GND
3 - HIGH
4 - LOW
GND (GREEN)
HIGH (BLACK)
LOW (RED)
2 3 4
6.7 RS-485 Wiring (continued)
6.7.1 RS-485 Bias Resistors
When interfacing the Class 3200 meter to certain RS-485 communication equipment, it
may be necessary to add bias resistance to the circuit. If this is required, there is a 2position DIP switch on the meter’s door mounted (display) circuit board. With both
positions in the “ON” position, bias resistance is added to the RS-485 circuit. When
both positions are in the “OFF” position, no bias is added to the RS-485 circuit.
Fig. 11. Bias Resistors DIP Switch.
After performing these steps, all of the meters will be connected in a daisy chain
configuration. This network of meters can then be connected to the RS-485 network
and communication can be established.
Local Computer
A local computer installed in the building can communicate with the RS-485 network
utilizing E-Mon’s RS-232 conversion key. The RS-232 key is connected to the RS-485
terminals in the closest meter using a cable with an RJ-11 plug terminating the end
that is plugged into the key and is open wiring on the other end for attachment to the
meter’s 3-screw RS-485 terminal block.
Fig. 12. RS-485 Wiring.
2162-0390-02
CLASS 3200 METER
6.8 RS-232 Communications
6.8.1 Hardwired System using the RS-232 Communication Key
The RS-232 communications key allows you to connect Class 3200 meters to a
personal computer that has the E-Mon Energy™ software installed. The computer
communicates with the meters through the RS-232 key.
The RS-232 key must be located within 15 feet of the host computer.
UP TO 4000
FEET TOTAL
~
~
~
~
CHANNEL 2
M33309
PC
RS-232 SERIAL
PORT COM1
OR COM2
15 FEET MAX
AC ADAPTER
CHANNEL 1
RS-232
KEY*
CHANNEL 3
UP TO 52
CLASS 3200
METERS
UP TO 4000
FEET TOTAL
UP TO 52
CLASS 3200
METERS
Fig. 13. RS-232 Configuration.
6.8.2 Connecting the RS-232 Key to the Computer
The RS-232 key is supplied with:
a. (1) 8-conductor cable fitted with RJ-45 plugs
b. (1) DB-9 serial COM port adapter
c. (1) AC adapter that converts 120VAC to 9VDC for powering the RS-232 key
Connection Steps:
1. Connect the 8-conductor cable to the left-side jack (labeled “RS232”) on the rear
panel of the RS-232 key.
2. Connect the appropriate COM port adapter (DB-9) to the serial port on the back
of the computer. Plug the 8-conductor cable from the RS-232 key into the COM
port adapter.
62-0390-0222
CLASS 3200 METER
6.8.2 Connecting the RS-232 Key to the Computer (continued)
3. Connect the provided AC adapter into the rear panel input on the RS- 232 key.
Plug the adapter into a 120VAC outlet. On the front panel of the RS-232 key, two
LEDs (POWER ON and AC ON) will light up.
NOTE: When the E-Mon Energy™ software is accessed on the computer, a third
LED (RS232 READY) will turn on. This indicator will light up as soon as the
E-Mon Energy software is booted up and the correct COM port is set up via
the settings provided in the software’s Locations menu.
6.8.3 Connecting Class 3200 Meters to the RS-232 Key using
RS-485
On the rear panel of the RS-232 key, there are three jacks labeled as channels A, B
and C. These are RS-485 serial communications ports used to connect the meters.
Each of these channels can be connected to as many as 52 individual meters over a
total cable distance of 4,000 feet. The channels are independent and must not be
connected to each other.
Modular Plug Method
This simple method requires using 4 stranded conductors inside a cable that is fitted
with an RJ-11 type plug for 4-conductor modular systems at the key end of the cable
and open conductors on the meter end.
*Do not use any pre-made telephone cables.
1. Plug the 4-wire RJ-11 cable/plug assembly into Channel A on the RS-232 key.
Connect the other end of this cable to the meter via the RS-485 port at the bottom right of the Class 3200 meter main power board.
NOTE: The total combined cable length must not be more than 4000 feet.
2. Each meter has one yellow (TX) and one green (RX) LED located on the right
side of meter board just below the ribbon cable. If the system is properly wired,
these two LEDs will be OFF. These LEDs will flash when the computer and
meter are communicating.
2362-0390-02
CLASS 3200 METER
CHANNEL 2
~
~
~
~
CHANNEL 3
UP TO 4000
FEET TOTAL
RS-232
KEY RM
RS-232 SERIAL
PORT COM1
THROUGH COM3
MAXIMUM 15 FEET
UP TO 52
CLASS 3200
METERS PER
CHANNEL
M33310
UP TO 4000
FEET TOTAL
UP TO 52
CLASS 3200
METERS PER
CHANNEL
CHANNEL 1
AC ADAPTER
PC OR WINDOWS
COMPATIBLE
LOCAL
MODEM
~
~
TELEPHONE
LINK
6.9 Modem Wiring
Fig. 14. Modem Configuration.
62-0390-0224
CLASS 3200 METER
6.9.1 Modem (RS-232 KEY RM)
The RS-232 key with modem connects the entire RS-485 network of Class 3200
meters to a telephone line.
** Refer to Section 6.7 for RS-485 network connections.
On the back panel of the RS-232 key/modem, the left jack (RS232) is not used in most
cases since there is no local host computer.
The two jacks at the top center of the rear panel on the RS-232 key/modem are for
connecting the phone line. Connect either one of these two jacks to the telephone line.
IMPORTANT:
The telephone line should be dedicated exclusively to the automatic meter
reading system. Never connect to a telephone line used by other modems or
fax machines. If there are telephones connected to this phone line, the proprietor must be aware that all phones must be on “hook” in order for the modem
to work. A dedicated phone line is suggested for system reliability.
2562-0390-02
CLASS 3200 METER
M33195
BAUD RATE
SELECTION
SWITCHES
3 4 BAUD RATE
ON ON 9600
OFF ON 19200
ON OFF 38400
OFF OFF 76800
6.9.2 External Modem
1. All meters should be connected to the RS-232 key as described in 6.8.2.
2. DISCONNECT POWER TO THE RS-232 KEY. Remove the cover by removing
the 2 screws from the bottom of the enclosure.
3. On the circuit board, locate the blue jumpers J7 (MODEM) and J8 (ex-MODEM).
If these jumpers are set in the DIRECT position, you must move the jumpers so
they are set in the MODEM position. Replace the cover and secure the enclosure.
4. Connect the RS-232 key to the external modem using the supplied 8-conductor
flat modular cable.
5. Connect the 9VDC adapter to the power input on the back of the RS-232 key
and plug it into a 120VAC outlet.
IMPORTANT:
The modem should use a phone line that is dedicated exclusively to the AMR
system. Do not use a phone line that is shared by another modem or fax
machine.
6.9.3 Baud Rate Selection
The communication Baud rate on the Class 3200 meter is set through positions 3 and
4 on DIP switch S2 on the meter circuit board. The default is 9600 Baud.
1. Select 9600 when using the Class 3200 meter with a modem.
2. The Baud rate on the meter must always match the Baud rate selected in the EMon Energy software; otherwise, communications will not function.
3. After a Baud change, press the CPU reset button to register the change.
4. All meters in the daisy-chain circuit must be set at the same Baud rate.
62-0390-0226
Fig. 15. Baud Rates.
CLASS 3200 METER
6.10 Modbus RTU Wiring
The Class 3200 Modbus option meter communicates with building automation
equipment over a 2-wire (3-conductor) RS-485 network using Modbus RTU protocol.
The meters are networked in a daisy-chain configuration with BELDEN 1120A cable or
equivalent required. The cable rating of 600V allows the RS-485 network to be
connected to 480-volt meters. Up to 52 meters can be installed on a network string.
The maximum combined length of all daisy-chained cables must not exceed 4000 feet.
The meter-to-network connection is through the 3-screw terminal which is located on
the Main Power Board of the meter. Tighten the terminals to 2.2 in-lb.
Fig. 16. RS-485 Terminal.
The meter is shipped with a Modbus ID number of 02. NOTE: Modbus address must
be changed to 01 for open protocol for BACnet (Optional) to function as specified. This
must be changed if the network has more than one meter installed. The change must
be done before the meter is introduced into the network. The meter can be numbered
from 1 to 247. There can be no duplicate numbers on a network, so caution must be
taken when assigning a meter ID number prior to its installation on the RS-485
network.
2762-0390-02
CLASS 3200 METER
6.11 BACnet MS/TP Wiring
BACnet MS/TP wiring is the same as Modbus and EZ7 wiring. See Sections 10 and 11
for instructions on changing I.D. and IP addresses.
6.12 Connecting Class 3200 Meters to USB Key using
RS485
The USB Key plugs into the PC’s USB port and provides a termination point for the
RS485 wiring from the meters. Up to 52 meters can be “Daisy chained” with up to 4000
feet total RS485 wiring. The USB Key is labeled for “plus (+)”, “minus (-)“, and ground
and the wiring must match the same positions on the meters. If more than 52 meters
are to be monitored, additional USB Keys can be utilized to connect them to the PC.
Fig. 17. Connecting Class 3200 Meters to the USB Key using RS485.
62-0390-0228
6.13 Ethernet Communications
M33311
ETHERNET
NETWORK
RS-485 DAISY CHAIN (SECTION 6.7)
EKM-E
ETHERNET
KEY
Ethernet communications connections are available through an optional EKM-E key,
which converts the meter’s RS-485 output to an ethernet connection. The key provides
data only with the EZ-7 protocol and is not designed to support Modbus or BACnet.
NOTE: The meter is not designed to connect directly through an Ethernet connec-
tion, but must utilize an appropriate RS485/Ethernet converter module/
modem.
Class 3200 Ethernet/IP Addressable meters can be tied into a local Ethernet network
individually, or a single Ethernet-connected meter can communicate with multiple RS485 daisy-chained conventional (EZ-7) class 3200 meters using a single IP address.
Each device (EKM-E) that is connected directly to the ethernet network requires a
unique IP address. With a public IP address, the system can be addressed with E-Mon
Energy software through the internet for remote reading capabilities.
Fig. 18. Ethernet Communications.
2962-0390-02
7.0 MULTIPLE-LOAD MONITORING
The E-Mon D-Mon Class 3200 meter provides extreme flexibility by allowing additional
sets of current sensors to be used in parallel so multiple load locations can be
monitored by one meter. This feature allows a totalized display readout from two or
more load circuits.
You may use parallel sensors to monitor specific breakers from one panel, specific
breakers from more than one panel, two or more complete panels, etc.
When paralleling current sensors, the following rules must be followed for accurate
readings:
1. Current sensors must be installed in complete sets of three, with a maximum of
three sensors installed in parallel per phase.
2. All sensors used in parallel must be of the same amperage rating (all 100-amp,
all 400-amp, etc.) The rating is determined by the current rating of the meter. For
example, a 200-amp meter must use extra sets of 200-amp current sensors.
3. All locations being monitored must have the same power source. A 480-volt
meter cannot monitor a 208-volt load, nor can a meter monitor two-480 volt loads
if they are from different originating power sources or from different transformers.
4. Multiply the meter display readings by the number of sets of current sensors
installed. Example: Meter readings of 5 kWh with 2 sets of current sensors - 10
kWh is the actual usage. (5 x 2=10.)
62-0390-0230
7.0 MULTIPLE-LOAD MONITORING
LINE VOLTAGE
Ø
A
Ø
B
LOAD SOURCE
N
LOAD A
LOAD B
CURRENT SENSORS
LOAD SOURCE
Ø
A
Ø
B
N
M31603
ØC
ØC
Ø
AØBØC
Ø
A
ØBØ
C
W B W B W BN
(CONTINUED)
NOTE: One set of current sensors equates to three sensors, one per phase. The
multiplier only applies when extra sets of current sensors are installed on one
meter. If you are using only one set of three current sensors, the multiplier is
not required.
Fig. 19. Multiple-load Wiring Diagram.
8.0 PREVENTATIVE/SCHEDULED
MAINTENANCE
The unit is shipped in a calibrated and fully functional tested condition. Since the unit is
factory-calibrated using proprietary firmware algorithms, no internal unit adjustments
are necessary.
This unit contains no internal adjustments, so no preventative or scheduled
maintenance is required.
No cleaning or decontamination procedures are required for this instrument.
3162-0390-02
9.0 LITHIUM BATTERY REPLACEMENT
WARNING
CAUTION
M33197
BATTERY
+
–
The Class 3200 meter has a lithium coin cell battery, which is used to retain the
contents of SRAM and the RTC during power outages. The battery’s life expectancy is
greater than 5 years.
Nominal Working Voltage3 Vdc Output
Nominal Current Capacity225 mAHr
Cell ChemicalManganese Dioxide Lithium
Operating Temperature Range-30 to +60 Degrees Celsius
ManufacturerPanasonic
Manufacturer’s Part NumberCR2032
Table 1. Battery specifications at 25 degrees Celsius.
Replace battery with Panasonic part number CR2032 only. Use of another
battery may present a risk of fire or explosion. See owner’s manual for safety
instructions.
The battery cell is mounted in a coin cell holder on the upper right side of the main
power board. The internal unit firmware will set a flag to indicate the low battery
condition. When the unit data is next downloaded, the monitoring facility will be alerted
of the low battery condition and will schedule a service call.
Battery may explode if mistreated. Do Not recharge, disassemble, or dispose
of in fire.
62-0390-0232
Fig. 20. Lithium Battery Cell.
9.0 LITHIUM BATTERY REPLACEMENT
CAUTION
CAUTION
(CONTINUED)
Use the following procedure to replace the lithium battery cell.
The battery is not completely discharged; therefore, DO NOT short the
terminals on the battery with any conductive material.
Internal circuit card components are extremely sensitive to electrostatic
discharge. Be careful not to touch internal circuitry prior to discharging any
static buildup on your person. T o discharge yourself, touch a grounded metal
object such as conduit or a metal enclosure interior.
1. Disconnect power from the meter at the unit external circuit breaker.
2. Remove the battery from its holder and place on a non-conductive surface.
3. Install new battery into the PCB battery holder.
NOTE: Care should be taken to ensure that the replacement battery is installed with
the same polarity as the battery that was removed. No damage to the unit or
battery will occur if battery is inadvertently installed in the wrong polarity.
4. Dispose of the used battery in accordance with the manufacturer’s (Panasonic’s)
instructions.
3362-0390-02
10.0 CLASS 3200 METER
OPERATING MODES
The E-Mon D-Mon® Class 3200 meter is used to monitor electric power usage of
individual loads after the utility meter and store kW and kVAR data for automatic meter
reading.
Fig. 21. Class 3200 Stand Alone Meter with 4 Line Display.
10.1 Start Up Screens
When the meter starts up, the screen displays firmware image type.
CL3200 and M, After approximately 4 seconds, the screen displays active
configurations: EZ7 ID, Meter configurations – phase, voltage, amperage, Calibration
factors or serial number, Date/time and firmware version.
Fig. 22. Start Up Screens.
62-0390-0234
10.2 Normal Mode Display Screens
Screen 1:Total Kilowatt-Hours (kWh)
Delivered
Screen 2: Peak Demand (kW)
with Date & Time Stamp
Screen 3: Actual Load (kW)
with Present Time
Screen 4: Average Current (amps)
Per Phase
Screen 5: Average Voltage (volts)
Per Phase
Screen 6: Average Voltage (volts)
Phase to Phase
Screen 7: Power Factor (pf)
Per Phase
The Class 3200 meter features seven Normal Mode Display Screens for monitoring
the meter. Each screen is displayed for 5 second intervals, before scrolling onto the
next screen.
You can “lock” the scrolling display on any one of the seven screens. This will be
explained in detail on following pages.
Explanations of the Normal Mode Display Screens are as follows:
Fig. 23. Class 3200 Meter Display Screens.
3562-0390-02
Fig. 24. Push Buttons.
M33279
DOWN
UP
SELECT
MENU
10.3 How to Program the Display Screens
The display information can be programed using four push buttons switches. The push
buttons (DOWN, UP, SELECT, MENU) are located at the bottom of the display board
on the inside front door of the meter. The buttons are used to program the following:
• Date & Time (This field sets the month, day, year, and time.)
• Device ID (This field changes the default setting, which is 1A for EZ7 and 1 for
ModBus.)
• Reset KW/KWH Read (This field resets the Peak kW Demand to zero.)
62-0390-0236
10.3.1 Date & Time
Date & Time
Device ID
Reset KW/KWH Read
Exit
DATE: 02-16-2012
TIME: 01:57:36
To change the date and time, complete the following steps:
1. Press the MENU button.
2. The following screen will appear:
3. Press the SELECT button. The date and time screen will appear, and the 2 digit
month will be blinking.
4. Use UP or DOWN button to make changes, press SEL button to advance to the
next field. Press MENU button to return to main menu.
5. If changes were made, you’ll be asked to save, press UP or DOWN to select Y or
N; press SEL to proceed returning to main menu. In main menu, select EXIT to
get out of programming mode and return to normal display mode.
3762-0390-02
10.3.2 Device I.D.
Date & Time
Device ID
Reset KW/KWH Read
Exit
EZ7 ID: 1A
MODBUS ID: 2
Save Change? Y
To change Device I.D., complete the following steps:
1. Press the MENU button.
2. The following screen will appear:
3. Use the UP and DOWN buttons to select the Device ID line.
Press the SELECT button. The Device I.D. screen will appear.
4. Use UP or DOWN button to make changes, press SEL button to advance to the
next field. Press MENU button to return to main menu.
.
5. If changes were made, you’ll be asked to save, press UP or DOWN to select Y or
N; press SEL to proceed returning to main menu. In main menu, select EXIT to
get out of programming mode and return to normal display mode.
62-0390-0238
10.3.3 Peak Demand Reset
Date & Time
Device ID
Reset KW/KWH Read
Exit
Reset kW only? N
Reset all? N
To reset the recorded peak kW demand, complete the following steps:
1. Press the MENU button until “Reset kW/kWh Read” is indicated by the arrow on
the display.
2. Press the SELECT button. The following screen will appear on the display.
3. Press the UP button to change the N to a Y after “Reset kW only?”.
4. The peak demand will be reset to zero and the meter will return to its normal
scrolling display mode.
3962-0390-02
10.3.4 Display Hold Feature
You can “lock” the scrolling display so that it will stay locked on any one of the seven
screens.
To stop the display from scrolling, complete the following steps:
1. Press the UP and DOWN buttons to choose which of the six screens you would
like to display.
2. Press the Select button. At the top of the display, you will see the message
HOLD1. This will lock the display for 1 HOUR.
NOTE: The display hold feature has different selectable time periods.
3. Pressing Select again will show the message HOLD6. This will lock the display
for 6 HOURS.
4. Continuing to press the Select button will provide additional timing choices:
HOLD12: Locks the display for 12 HOURS
HOLD24: Locks the display for 24 HOURS
HOLD: Locks the display indefinitely
To exit the HOLD mode:
Press the Select button as many times as needed until the HOLD message disappears
from the display.
** Be sure to exit from the HOLD mode when you are done using this feature.
62-0390-0240
11.0 HIGH VOLTAGE METERING
kWh Meter Installation Instructions for Use with E-MON
Meters in High Voltage Applications
The E-MON model # E34-12025HV kWh meter is designed to be used for monitoring
high voltage (2400, 4160, 13200, etc) circuits, either “stand alone” or in an AMR
application.
This meter is intended to be used with the appropriate high voltage Potential
Transformers (PTs) and Current Transformers CTs) supplied by others. The meter
application is centered around a 120 VAC secondary output from the high voltage PTs
and a 5 amp secondary output from the high voltage CTs.
Items addressed by this document include the installation of the E34-12025HV kWh
meter on high voltage circuits as well as the calculations to provide the correct meter
multiplier based on the PT and CT sizes used on the high voltage conductors.
Installation should be performed by qualified personnel and only according to all
applicable electrical codes.
High Voltage CTs (supplied by others) reduce the primary current (amps) to a directly
proportional 0~5 amp secondary output. As an example, a 0~400 amp primary
becomes a 0~5 amp proportional signal from the secondary output. In our application,
the high voltage CT secondary is installed as a continuous “loop”, with a single
conductor connected to both secondary terminals.
To convert the 0~5 amp signal to a 0~ 2 volt signal, E-MON’s Current Sensors are
installed on the CT secondary conductor. A set of 25 amp sensors is used in this
application. These sensors have the high voltage CT secondary conductor passed
through them five (5) times (see below) by looping the secondary conductor as shown
in the drawing. The reason for this is so that the 5 amp secondary now appears to the
current sensor as a 0~25 amp signal. This creates a conversion of the CT’s primary
current to a directly proportional 0~ 2 volt signal which is utilized by the E-MON meter.
The example from the first paragraph has now become a 400 amp to 2 volt device, by
this technique.
4162-0390-02
Fig. 25. High Voltage CT’s.
M34227
Fig. 26. Wiring Diagram For 3-wire High Voltage Circuits.
M34228
62-0390-0242
This special high voltage meter installation shows the correct wiring procedure for 4wire high voltage circuits. In this application, the 3 element meter connection is used
on the secondary circuits of the user supplied high voltage PTs and CTs.
The E-MON meter used in this application is the model E34-12025HV kWh meter.
Installation of these meters requires the use of three (3) current sensors mounted on
the secondaries of the high voltage Current Transformers. See the drawing above for
proper wiring. For correct operation, the meter must be installed correctly.
This special high voltage meter installation utilizes high voltage PTs (Potential
Transformers) and CTs (Current Transformers) supplied by others. The E-MON meter
is installed using the secondary outputs of these devices.
High voltage PTs reduce the primary voltage (4160v, 13200v, etc.) to a Secondary
output of 120v. This secondary is connected to the E-MON meter voltage inputs as
shown in the wiring diagram. High voltage CTs reduce the primary current (amps) to a
directly proportional 0~5 amp output. As an example, a 0~400 amp primary becomes a
0~5 amp proportional signal from the secondary output. This allows much smaller
wiring to be utilized in the meter hookup. The high voltage CT secondary is installed as
a continuous “loop”, with a single lead connected to both secondary terminals.
E-MON meters accept a 0~2 volt signal from their Current Sensors. To convert the 0~5
amp signal, the Current Sensors are installed on the CT secondary lead. A set of 25
amp sensors is used in this application. These sensors have the high voltage CT
secondary lead passed through them five (5) times by looping the wire as shown in the
drawing. This allows a direct conversion of the CTs primary current to a directly
proportional 0~2 volt signal, which is used by the meter.
Since there is a signal ratio introduced by the high voltage CTs and PTs, it will be
necessary to multiply the number on the meter’s display for a correct reading. The
meter multiplier is calculated by using the CT ratio and the PT Ratio. [PTr x CTr /
Number of Secondary Lead Passes Through Sensor]. The E-MON 25 amp HV kWh
meter with 5 wraps of the high voltage CT secondary will have its multiplier calculated
by the formula shown below.
EXAMPLE: CT = 400:5 = 80:1 (CTr = 80)
PT = 4200:120 = 35:1 (PTr = 35)
Wraps (Passes) = 5
METER MULTIPLIER
= PTr x (CTr/Wraps)
35 x (80/5)
35 x (16) = 560
4362-0390-02
12.0 CLASS 3200 PROTOCOL DEFINITIONS
ModBus Customer Point Map: CL3200
Address Registers FormatDescriptionUnits
1
40001
40001
40005
40007
41001
41003
41005
41007
2Integer Energy deliveredWh PulseR/W
1
2Integer Energy receivedWh PulseR/W
1
2Integer Reactive energy deliveredVARh Pulse R/W
1
2Integer Reactive energy receivedVARh Pulse R/W
1
2FloatEnergy deliveredkWhR/W
1
2FloatEnergy receivedkWhR/W
1
2FloatReactive energy deliveredkVARhR/W
1
2FloatReactive energy receivedkVARhR/W
410092FloatReal powerkWR
410112FloatReactive powerkVARR
410132FloatApparent powerkVAR
3200
CL
410152FloatPower factor% PFR
410172FloatPeak demandkWR
410192FloatCurrent averageAmpsR
410212FloatVoltage line-neutralVolts-NR
410232FloatVoltage line-lineVolts-LR
410252FloatFrequencyHzR
410272FloatPhase angleDegreeR
410292FloatReal power, phase AkWR
410312FloatReal power, phase BkWR
62-0390-0244
ModBus Customer Point Map: CL3200
Address Registers FormatDescriptionUnits
410332FloatReal power, phase CkWR
410352FloatReactive power, phase AkVARR
410372FloatReactive power, phase BkVARR
410392FloatReactive power, phase CkVARR
410412FloatApparent power, phase AkVAR
410432FloatApparent power, phase BkVAR
410452FloatApparent power, phase CkVAR
410472FloatPower factor, phase A% PFR
410492FloatPower factor, phase B% PFR
410512FloatPower factor, phase C% PFR
410532FloatCurrent, phase AAmpsR
410552FloatCurrent, phase BAmpsR
CL
3200
410572FloatCurrent, phase CAmpsR
410592FloatVoltage, line to neutral, phase A-N Volts-NR
410612FloatVoltage, line to neutral, phase B-N Volts-NR
410632FloatVoltage, line to neutral, phase C-N Volts-NR
410652FloatVoltage, line to line, phase A-BVolts-LR
410672FloatVoltage, line to line, phase B-CVolts-LR
410692FloatVoltage, line to line, phase C-AVolts-LR
410712FloatPhase angle, phase ADegreeR
410732FloatPhase angle, phase BDegreeR
4562-0390-02
ModBus Customer Point Map: CL3200
CL
Address Registers FormatDescriptionUnits
3200
410752FloatPhase angle, phase CDegreeR
2
41083
41085
44001
44007
45501
46025
46049
2FloatExternal Input 1PulseR/W
2
2FloatExternal Input 2PulseR/W
3
6Custom Interval Day BlockR/W
4
1 per
Integer Interval DataPulseR
interval
5
2 per day Custom Interval Data HeadersR
6
8Custom RTC Date/TimeR/W
7
8Custom EZ7 ID, ModBus ID, Serial
Number
R/W
460578Custom Recorder Info., Demand IntervalR/W
465138Custom Flags L1: Power Failure, BatteryR
465218Custom Flags L2: Power Failure DateR
1. To clear single meter kWh/kVARh, set multiple points at 40001 or 41001 for 8
points with data set to 0000 0000 0000 0000 0000 0000 0000 0000.
2. External inputs are standard on Class 5000 meters and optional on Class 3400
meters (Part of Expanded Feature Package).
To clear external inputs, set multiple points at 41083 or 41085 for 2 points with data
set to 0000 0000. Jumper J6 must be closed.
3. To set the interval data day block, set multiple points at 44001 for 6 points with data
set to 0C0I 0000 MMDD YYYY 0000 0000.
4. Each register represents a 15 or 5 minute kWh pulse value based on the interval
day block. 96 registers max with 15 minute intervals. 288 registers max with 5 minute
intervals. The first interval data register 44007 represents the pulse count for the first
15 or 5 minute interval beginning at midnight.
5. The interval data headers represent days with available interval data. Each day
represents 2 registers. Format: MMDD YYYY.
6. To set the date and time, set multiple points at 46025 for 4 points with data set to
HHMM SSDW MMDD YYYY (DW=day of week)
7. To change the ModBus ID, set single point at 46050 with data set to new ModBus
ID (e.g. 1 to 247). Jumper J6 must be closed.
62-0390-0246
Instance IDBACnet
ObjectDescriptionUnits
1
1
1
2
1
3
1
4
5Analog
Analog
Input
Analog
Input
Analog
Input
Analog
Input
Energy deliveredkWhPresent Value R
Energy receivedkWhPresent Value R
Reactive energy deliveredkVARhPresent Value R
Reactive energy receivedkVARhPresent Value R
Real powerkWPresent Value R
Input
6Analog
Reactive powerkVARPresent Value R
Input
7Analog
Apparent powerkVAPresent Value R
Input
8Analog
Power factor% PFPresent Value R
Input
9Analog
Peak demandkWPresent Value R
Input
10Analog
Current averageAmpsPresent Value R
Input
11Analog
Voltage line-neutralVolts-NPresent Value R
Input
12Analog
Voltage line-lineVolts-LPresent Value R
Input
13Analog
FrequencyHzPresent Value R
Input
14Analog
Phase angleDegreePresent Value R
Input
15Analog
Real power phase AkWPresent Value R
Input
16Analog
Real power phase BkWPresent Value R
Input
17Analog
Real power phase CkWPresent Value R
Input
18Analog
Reactive power phase AkVARPresent Value R
Input
19Analog
Reactive power phase BkVARPresent Value R
Input
BACnet Object Descriptors: CL3200
BACnet
PropertyCL3200
4762-0390-02
Instance IDBACnet
ObjectDescriptionUnits
20Analog
Input
21Analog
Input
22Analog
Input
23Analog
Input
24Analog
Input
25Analog
Input
26Analog
Input
27Analog
Input
28Analog
Input
29Analog
Input
30Analog
Input
31Analog
Input
32Analog
Input
33Analog
Input
34Analog
Input
35Analog
Input
36Analog
Input
37Analog
Input
38Analog
Input
BACnet Object Descriptors: CL3200
BACnet
PropertyCL3200
Reactive power phase CkVARPresent Value R
Apparent power phase AkVAPresent Value R
Apparent power phase BkVAPresent Value R
Apparent power phase CkVAPresent Value R
Power factor phase A% PFPresent Value R
Power factor phase B% PFPresent Value R
Power factor phase C% PFPresent Value R
Current phase AAmpsPresent Value R
Current phase BAmpsPresent Value R
Current phase CAmpsPresent Value R
Voltage line-neutral phase A-N Volts-NPresent Value R
Voltage line-neutral phase B-N Volts-NPresent Value R
Voltage line-neutral phase C-N Volts-NPresent Value R
Voltage line-line phase A-BVolts-LPresent Value R
Voltage line-line phase B-CVolts-LPresent Value R
Voltage line-line phase C-AVolts-LPresent Value R
Phase angle phase ADegreePresent Value R
Phase angle phase BDegreePresent Value R
Phase angle phase CDegreePresent Value R
62-0390-0248
BACnet Object Descriptors: CL3200
Instance IDBACnet
ObjectDescriptionUnits
39Analog
Reserve ANo units Present Value R
BACnet
PropertyCL3200
Input
40Analog
Reserve BNo units Present Value R
Input
41Analog
Reserve CNo units Present Value R
Input
2
42
43
Analog
Input
2
Analog
Input
External Input 1PulsePresent Value
External Input 2PulsePresent Value
1. To clear single meter kWh/kVARh, select reset kW/kWh on the display menu of the
meter. This function will also reset external inputs. Jumper J6 must be closed.
2. External inputs are standard on Class 5000 meters and optional on Class 3400
meters (Part of Expanded Feature Package). To clear external inputs, select reset kW/
kWh on the display menu of the meter. This function will also reset kW/kVARh. Jumper
J6 must be closed.
Subject to the exclusions listed below, E-Mon will either repair or replace (at its option)
any product that it manufactures and which contains a defect in material or
workmanship.
The following exclusions apply:
1. This Limited Warranty is only effective for a period of (5) five years following the
date of manufacture when installed in accordance with manufacturer’s instructions by qualified personnel.
2. E-Mon must be notified of the defect within ninety (90) days after the defect
becomes apparent or known.
3. Buyer’s remedies shall be limited to repair or replacement of the product or component which failed to conform to E-mon’s express warranty set forth above.
4. Buyer shall be responsible for all freight costs and shall bear all risk of loss or
damage to returned goods while in transit.
5. This Limited Warranty does not cover installation, removal, reinstallation, or labor
costs, and excludes normal wear and tear. Buyer shall provide labor for the
removal of the defective component or item and installation of its replacement at
no charge to E-Mon.
6. This Limited Warranty does not cover any product if: (i) a product is altered or
modified from its original manufactured condition, (ii) any repairs, alterations or
other work has been performed by Buyer or others on such item, other than work
performed with E-Mon’s authorization and according to its approved procedures;
(iii) the alleged defect is a result of abuse, misuse, improper maintenance,
improper installation, accident or the negligence of any party; (iv) damaged as a
result of events beyond E-Mon’s control or other force majeure events or (v) used
in conjunction with equipment, components, accessories, parts or materials not
supplied or approved by E-Mon.
7. This Limited Warranty is limited to the obligation to repair or replace the manufactured product. This is the sole and exclusive remedy for any breach of warranty. IN NO EVENT SHALL E-MON BE LIABLE FOR ANY INDIRECT,
INCIDENTAL, SPECIAL, CONSEQUENTIAL OR PUNITIVE DAMAGES
(INCLUDING ANY DAMAGE FOR LOST PROFITS) ARISING OUT OF OR IN
CONNECTION WITH THE FURNISHING OF PRODUCTS, PARTS OR SERVICES, OR THE PERFORMANCE, USE OF, OR INABILITY TO USE ANY
PRODUCTS, PARTS OR SERVICES, SALE OF OR OTHERWISE, WHETHER
BASED IN CONTRACT, WARRANTY, TORT, INCLUDING WITHOUT LIMITATION, NEGLIGENCE, OR ANY OTHER LEGAL OR EQUITABLE THEORY.
8. EXCEPT AS EXPRESSLY PROVIDED HEREIN, E-MON MAKES NO WARRANTY OF ANY KIND, EXPRESS OR IMPLIED WITH RESPECT TO ANY
PRODUCTS, PARTS OR SERVICES PROVIDED BY E-MON INCLUDING, BUT
NOT LIMITED TO, THE IMPLIED WARRANTIES OF MERCHANTABILITY AND
FITNESS FOR A PARTICULAR PURPOSE. PRODUCTS OR COMPONENTS
DISTRIBUTED, BUT NOT MANUFACTURED, BY E-MON ARE NOT WARRANTED BY E-MON AND BUYER MUST INSTEAD RELY ON THE REPRESENTATIONS AND WARRANTIES, IF ANY, PROVIDED DIRECTLY TO THE
BUYER BY THE MANUFACTURER OF SUCH PRODUCT OR COMPONENT.