EMI WLCA User Manual

NOMINAL CAPACITIES:
CAH/CAHW: 9,000 - 48,000 Btuh
CAF/CAF4: 8,000 - 36,000 Btuh
EMI DUCTLESS SPLIT SYSTEM
CASSETTE EVAPORATOR
INSTALLATION MANUAL/OPERATING INSTRUCTIONS
P/N# 240-4235 Rev. 1.6 [1/05]
SPARE PARTS: For ease of identification when ordering spare parts or contacting Enviromaster International LLC about your unit, please quote the model number and serial number. This information can be found on the rating plate attached to your unit.
PRODUCT DESCRIPTION
The EMI Cassette series is available in nominal capacities of 9,000 to 48,000 Btuh in DX refrigeration and reverse cycle heat pump (CAH) or DX with hot water coil (CAHW) ver­sions; also available are two pipe chilled water (CAF) and four pipe chilled and hot water versions (CAF4) in 8,000 to 36,000 Btuh capacities; and, depending on the model, elec­tric heat can also be factory fitted as an option. Designed for low noise levels, easy installation and maintenance and a slimline fascia, all ensure minimum obtrusion into the work­ing environment.
CONTROLS AND COMPONENTS
GENERAL STATEMENT
IMPORTANT: The information contained in this manual is critical to the correct operation and main­tenance of the EMI cassette and should be read by all persons responsible for the installation, start up and maintenance of the unit.
SAFETY: The equipment has been designed and manufac-
1. Service and maintenance of this equipment should only be carried out by skilled personnel.
2. When working with any air conditioning unit ensure that the electrical disconnect supplying the unit is switched off prior to servicing or repair work and that there is no power to any part of the equipment. In the case of a DX system, both the indoor and outdoor units should be switched off.
3. Also ensure that there are no other power feeds to the unit such as fire alarm circuits, BMS circuits, etc.
4. Electrical installation, start up and maintenance work on this equipment should be undertaken by competent and trained personnel in accordance with local relevant standards and codes of practice.
LOW VOL T TRANSFORMER (Standard): 24 V olt. ELECTRO-MECHANICAL (Standard): Thermostat options
are cooling only , cooling and one stage auxiliary heat, cool­ing and one stage mechanical heating (heat pump system) or cooling and two stage heating (heat pump & second stage auxiliary heat). An optional thermost at can be obtained through EMI or your local distributor.
NOTE: Make sure the thermostat is suitable for unit opera­tion (i.e., cooling only , cooling/electric heat, etc.)
MICROPROCESSOR (Optional): A custom designed mi­croprocessor is fitted to the cassette to enable room condi­tions to be maintained at a user defined setpoint. Communi­cation to the controller is by a hand held infrared transmitter, which includes a wall mounting bracket as standard.
The microprocessor allows five operating modes. These modes are - fan only , dry cooling, cooling only , heating only and heating/cooling auto changeover for maximum versatil­ity . A temperature setpoint between 58°F - 90°F can also be selected.
The microprocessor monitors indoor coil temperature and return air temperature. In heat pump units, a 24V AC signal from the condensing unit is also monitored to signal the in­door unit that defrost of the outdoor coil is taking place. This allows the same micro to control both heat pump and cool­ing only units. The receiver contains a self diagnostic fea­ture. When a low indoor coil temperature is detected the cooling action is stopped. If a sensor fails then an alarm is
EMI@ENVIROMASTER.COMENVIROMASTER INTERNATIONAL LLC 1
displayed on the fascia mounted receiver. The microproces­sor also limits the number of compressor starts per hour to reduce wear on the compressor.
The infrared transmitter is used to switch the unit on/off, change temperature settings, fan speed, operating mode and to toggle the motorized air sweep (where fitted). The micro­processor also has a built-in clock which can be activated to enable the unit to be programmed with up to two separate operating periods for the days of the week (Mon-Fri). The clock provides On/Off unit operation and is not a night set back or occupied/unoccupied control function. Mon-Fri will operate as a ‘block’ of days and cannot be programmed independently of one another. Saturdays and Sundays can each be programmed with up to two separate operating pe­riods and are programmed independently of weekdays and each other.
A fascia mounted receiver displays On/Off, cool or heat and timer/alarm status.
FIL TERS: Wire framed filters are fitted. These are reusable and may be vacuum cleaned.
CONDENSA TE PUMP: A condensate pump is fitted to carry water out of the unit. The pump is fixed to a mounting bracket which can be withdrawn from the side of the chassis and incorporates an inspection hole to allow a visual check of the pump during operation. A float switch is fitted to stop the cooling action should the pump become blocked or fail.
loosening the four M5 screws retaining the fascia in place. The fascia can now be slid sideways and pulled away from the chassis. When removing the Cassette chassis from the box the four corner brackets should be utilized for lifting. In order to protect the fascia from dirt and damage, it should be returned to the box until it is ready to be installed.
BLANKING OFF: When branch ducting is to be used, two polystyrene pieces for blanking off fascia open­ings are Included with the fascia packing. Up to two opposing sides may be blanked off.
POSITIONING
CASSETTE - The Cassette installation position should
be selected with the following points in mind:
1. Pipe work, electrical connections and condensate pump access panel should be readily accessible.
2. When installing a unit with an externally mounted electrical control panel, ensure that sufficient access to the panel is provided for maintenance purposes. Access to the condensate pump access panel should be provided on all model sizes.
3. The unit should not be positioned less than 5 ft. from a wall or similar obstruction, or in a position where the discharge air could blow directly on the thermostat.
IMPORTANT: TOT AL LIFT FOR THIS PUMP
IS 18” OR LESS.
AIR V ANES: Air outlet vanes are manufactured from alumi-
num and covered with nylon flock to prevent condensation from forming. Vanes are manually adjustable on the 2 x 2 model units or driven by an electric motor on all other model units. Where fitted, the motorized air vanes can be set to auto sweep or can be stopped in a fixed position.
HEATING: The cassette may be fitted with either electric heaters or a hot water coil. It is recommended that heat pumps be fitted with the electric heat option to offset the defrost cycle. Electric heaters are fitted with over-heat cut out switches.
FRESH AIR CONNECTION: Fresh air may be introduced to the unit by the addition of ducts connected to the fresh air knockouts on the Cassette case. It is usually advised that the fresh air volume is approximately 10% of the unit’s pub­lished maximum air flow.
SITE INSTALLATION
UNPACKING: The cassette fascia and main chassis are
supplied together for increased protection. Remove the band­ing straps and lift the cardboard lid. Remove the bubble wrap and polystyrene packing pieces to expose the unit. The fas­cia should be unpacked first by unclipping the inlet grille and
4. The unit should not be positioned directly above any obstructions.
5. The condensate drain should have sufficient fall (1” per 10’) in any horizontal run between Cassette and drain. Maximum condensate pump lift is 18".
6. There should be sufficient room above the false ceiling for installing the Cassette as shown below (see “dimensions” in this IOM for cabinet sizing):
Small Cabinet A = 12-3/4” min. Medium Cabinet A = 1 1-1/2” min. Large Cabinet A = 13-1/2” min.
ELECTRO-MECHANICAL THERMOST AT - In addition to po­sitioning the Cassette correctly , it is very important to locate the wall mounted thermostat in the optimum position to en­sure good temperature control. Therefore the installation should be selected with the following points in mind:
EMI@ENVIROMASTER.COMENVIROMASTER INTERNATIONAL LLC 2
1. Position the thermostat approximately 5 ft. above floor level.
2. Do not position thermostat where it can be directly affected by the unit’s discharge air stream.
3. A void external walls and drafts from windows and doors.
4. Avoid positioning near shelves and curtains as these restrict air movement.
OUTER CASE INSULATION
CASSETTE CASE
INNER CASE INSULATION
5. Avoid heat sources (direct sunlight, heaters, dimmer switches, etc.)
CEILING OPENING: Before beginning the installation, in­spect the unit location, test the strength of the unit mountings (see “Mechanical Information” in this IOM). An opening in the false ceiling will then have to be cut to the following sizes:
Small Cabinet 23-1/4” x 23-1/4” Medium Cabinet 33-7/8” x 33-7/8” Large Cabinet 46 x 33-7/8”
A template for ceiling cut-out and rod positions can be found with the Cassette unit.
NOTE: Make sure the ceiling grid is supported separately from the Cassette. The ceiling must not be supported by any part of the Cassette unit, fascia or any associated wir­ing or pipe work.
The hanger bolts can now be installed (use 3/8 all thread rod) at the centers shown below:
FALSE CEILING
GUIDE IN POSITION
NOTE: If the ceiling is not level or even, it is important that the Cassette is installed level to ensure correct pump operation and to maintain fan clearances. Any slight discrepancy between the Cassette and ceiling will be taken up by the fascia foam seal.
Secure unit in position with locknuts and washers on either side of the Cassette bracket. Ensure threaded rod does not protrude more than 2” (dimension C) below the mounting bracket.
CABINET A B
SMALL
MEDIUM
LARGE
19-1/2" 23" 29-5/8" 31-1/2" 29-5/8" 43-11/16"
Prepare the installation guides by folding the metal bracket by hand along the row of holes.
FOLDED GUIDE
The Cassette can now be lifted onto the hanging rods and leveled at the correct distance from the ceiling with the aid of the installation guides as shown.
The unit can now be piped up in accordance with good refrig­eration and/or plumbing practices.
CONDENSA TE PIPEWORK: The Cassette is supplied with a 1/2" diameter flexible PVC hose for connection to copper or plastic drain pipework. When installing the Cassette the following points should be remembered:
1. Maximum pump lift is 18”.
2. The highest point in the condensate pipework should be as close to the unit as possible. This prevents a large volume of water draining back into the unit when it is switched off.
EMI@ENVIROMASTER.COMENVIROMASTER INTERNATIONAL LLC 3
3. Condensate pipework should slope downwards in the direction of water flow with a minimum gradient of (1” per 10’). There must not be any uphill gradients other than in the first 18” of pipework from the Cassette.
4. When multiple Cassettes are connected to a common condensate drain, ensure the drain is large enough to cope with the volume of condensate from several Cassettes. It is also recommended to have an air vent in the condensate pipework to prevent any air locks.
DUCT COLLARS: Branch duct and fresh air duct collars can be attached to the Cassette chassis by following the steps below:
1. Refer to the relevant illustration for your Cassette (pages 6 -7 in this IOM) to become familiarized with knock-out hole locations.
2. The insulation is pre-cut to aid location and removal of the relevant section. Rub hand across surface of insulation to reveal exact location of knock-out.
3. Remove the metal knockout from the chassis.
4. Attach the duct collar to the chassis using self tapping screws.
NOTE: Branch ducts are round and 5 - 6” in diameter. Fresh Air ducts are square and 3” in diameter.
INSULATION: Refrigerant, chilled water and condensate pipes should be insulated right up to the Cassette chassis. Chilled water valves must also be insulated to prevent sweat­ing.
ASSEMBLY: Once the services have been connected the four fascia mounting bolts can be unscrewed approximately 1” from the condensate tray support channels.
The fascia can now be unpacked ready for fitting to the Cas­sette chassis. Ensure the black fir tree fasteners holding the fascia polystyrene are pushed in firmly in case of transit vibration. If a fascia aperture needs blanking off, then take one of the polystyrene blanking pieces and push it into the recess in the polystyrene fascia insulation. Fit by removing the inlet grilles and filters, locating the four fascia mounting bolts on the chassis through the four keyhole brackets on the fascia and then sliding the fascia sideways until it locks into position.
NOTE: Up to two non-adjacent sides can be blanked off.
NOTE: On electro-mechanical units, the fascia must be installed with the EMI logo along the same edge of the unit as the electrical panel. On units fitted with microprocessor controls, orient the fascia with the dis­play panel along the same edge of the unit as the electrical panel.
FASCIA BLANKING PIECE
SECTION THROUGH FASCIA
Before tightening the fascia to the unit, connect the two halves of the vane motor’s plug and socket connection (where ap­plicable).
On microprocessor controlled units, ensure that the display panel cable is routed to the electrical panel and securely fastened to its connector on the microprocessor circuit board. (Refer to the unit’s electrical wiring schematic). Take care to ensure that the connector is connected in the proper ori­entation and that the wires are not routed such that they may become trapped, cut, broken or chaffed.
The fascia can now be tightened up to the Cassette chassis until a good seal is obtained between fascia and chassis.
NOTE: Do not over tighten the bolts. To do so may cause damage to the fascia.
With filters in place, the inlet grilles can now be fitted to the fascia to complete the installation.
ELECTRICAL DATA
(See Appendix 1 on page 18 for wiring charts and instruc­tions.)
All power and interconnecting wiring between units should be carried out to conform with local/national electrical codes. A fused and dedicated electrical supply of the appropriate phase, frequency and voltage should be installed by the cus­tomer. It is also recommended that a local disconnect switch be connected within 3’ of the unit. In some areas this may be a code requirement.
EMI equipment in its standard form is designed for an elec­trical supply of 208-230V , 1Ph, 60Hz. When connection to a 115V, 1Ph, 60Hz supply is necessary, a factory mounted buck boost transformer will be fitted to the unit.
The wires should be capable of carrying the maximum load current under non-fault conditions at the stipulated voltages. Avoid large voltage drops on cable runs, particularly in low voltage wiring. The correct cable size must be used to en­sure a voltage drop of less than 1 volt in the control wiring. Once the refrigeration pipe work is complete, the electrical supply can be connected by routing the cable through the appropriate casing hole and connecting the supply and ground cables to the unit’s power terminals. On the medium and large cabinets, it will be necessary to remove the insulated condensate tray support rail, adjacent to the casing hole.
EMI@ENVIROMASTER.COMENVIROMASTER INTERNATIONAL LLC 4
ELECTRICAL SPECIFICATION S
E
E
STANDARD UNIT DATA
POWER SUPPLY 230V/1PH/60HZ 230V/1PH/60HZ 230V/1PH/60HZ FULL LOAD AMPS A 0.4 0.6 0.9 MIN. CIRCUIT AMPACITY (MCA) A 0.5 0.75 1.13 REC. FUS
WITH OPTIONAL ELECTRIC HEAT
POWER SUPPLY 230V/1PH/60HZ 230V/1PH/60HZ 230V/1PH/60HZ ELECTRIC HEAT CAPACITY KW 1.5 3.0 5.0 HEATER AMPS A 6.52 13.1 21.7 FULL LOAD AM PS A 7.0 13.7 22.6 MIN. CIRCUIT AMPACITY (MCA) A 8.8 17.1 28.3 REC. FUSE WITH HEAT A 15 20 30
WITH OPTIONAL BOOST TRANSFORMER
POWER SUPPLY 115V/1PH/60HZ 115V/1PH/60HZ 115V/1PH/60HZ FULL LOAD AMPS A 0.8 1.2 1.8 MIN. CIRCUIT AMPACITY (MCA) A 1.0 1.5 2.26 REC. FUS
(1) STANDARD UNIT FITTED WITH OPTIONAL ELECTRIC HEATING ELEMENTS. AV AILABLE WITH 230V M ODEL UNITS ONLY. (2) STANDARD UNIT FITTED WITH OPTIO NAL BOOS T TRANSFORMER FOR CONNECTI O N TO A 115V ELECTRICAL SUP P LY. ELECTRIC HEAT
IS NO T AVAILABLE WITH THIS O PTION.
1
A151515
2
A151515
SMALL MED IU M LARGE
SMALL MED IU M LARGE
SMALL MED IU M LARGE
REFRIGERATION SYSTEM (DX UNITS)
PIPE INSTALLATION NOTES
1. When cooling only or heat pump units are being installed, it is usually only necessary to insulate the suction line. However, if the liquid line is subject to high temperature or exposed to direct sunlight, this should also be insulated.
2. Maximum equivalent pipe run should be no more than 100’, with a maximum rise of 35’.
3. Horizontal pipe runs should be slightly inclined, so as to encourage oil to flow in the direction of the compressor, for better oil return.
4. Good refrigeration practices must be employed to ensure the correct pressure drop and good oil return.
PRESSURE TESTING: When installation is complete, fill the Cassette and interconnecting pipework with dry nitrogen to a pressure of 150 PSIG . Record the pressure over a pe­riod of time (a minimum period of 60 minutes should be suf­ficient to detect any major leaks, however, ideally 24 hours should be allowed). If there is any reduction in pressure, trace the leak and repair before conducting a further pres­sure test.
EVACUATION: Evacuation should be carried out with a high vacuum pump. The pump should be connected to the high and low pressure sides of the system via a gauge manifold fitted with compound gauges. A high vacuum gauge should be fitted to the system at the furthest point from the vacuum pump.
Triple evacuation should be used to ensure that all contami­nants are removed or at least reduced to significantly low proportions.
The vacuum pump should be operated until a pressure of 500 microns absolute pressure is reached, at which time the vacuum pump should be stopped and the vacuum bro­ken with oxygen free nitrogen until the pressure rises above zero.
The above operation should be repeated a second time. The system should then be evacuated a third time but this
time to 100 microns absolute pressure. After stopping the pump, open the condensing unit’s service valves to break the vacuum.
START UP PROCEDURES
PRE-START: Once installation is complete it is important
that the following pre-start checks are made.
1. All pipe work is complete and insulated where nec­essary.
2. All fans are able to rot ate freely .
3. The Cassette and interconnecting pipe work have been evacuated correctly and the Condensing Unit’s service valves are open (DX units only).
4. All electrical connections (both power and control) are properly terminated.
5. All condensate drains are inst alled correctly .
6. The power supply is of the correct voltage and fre­quency .
7. The units are properly grounded in accordance with current electrical codes.
EMI@ENVIROMASTER.COMENVIROMASTER INTERNATIONAL LLC 5
E
O
CO
OJEC
START UP PROCEDURES
8. For microprocessor controlled units, check that the display panel cable is properly connected to
Once the above pre-start checks have been carried out sat­isfactorily , the main start up operation can begin.
the microprocessor main circuit board and that the jumper links are correctly set (refer to unit wiring schematic). If the links are set incorrectly , remove main power before making any changes.
9. For microprocessor controlled units, check that the battery on the main circuit board is in place and properly connected. Check also that the bat­teries are installed in the infrared unit.
STAR T UP SHEET EXAMPLE
EMI CASSETTE - CAH/W, CAF/ 4
TO BE COMPLETED IN CONJUNCTION WIT H START UP PROCEDUR
TECHNICIAN: M
DEL/SERIA L NO:
1.0 PRE START UP CHECKLIST
1.1 UN I T CONDITI ON SATIS FA CTORY
1.2 PRESSURE TEST WI T H DRY NIT RO G EN
1.3 DESIGN WATER FLOW AVAILABLE IF CHILLED W ATER UNIT
1.4 VOLTAGE AT O UT D O OR UNIT
1.5 VOLTAGE AT I NDOOR UNI T
1.6 ELECTRICA L CO NNECTI O NS T IGHT
1.7 JUMPERS SET CORRECTLY (MICRO ONLY)
2.0 START UP CHECKLIST - INDOOR UNIT
2.1 DISA BLE COMPRESSOR SIGNAL
2.2 ON/OFF WORKS
2.3 INDOOR UNIT : THREE F ANS SPEEDS AVAIL ABLE (MICRO ONLY)
2.4 VA NE SWEEP FUNCTIONS
2.5 TIMER FUNCTIONS OPERATE (MI CRO ONLY)
2.6 CONDENSATE PUMP OPERATES
3.0 START UP CHECKLIST - OUTDOOR UNIT
3.1 OPERA T I NG PRESSURES
3.2 SUCTI O N
3.3 DISCHARGE
3.4 AM BIENT TEM PERAT URE
35. INDOOR AI R TEMPERATURE
: A START UP SHEET FOR EVERY UNIT MUST BE RETURNED TO EMI TO VALIDATE THE WARRANTY .
NOTE
RETURN ONE COPY TO EM I AND RETAIN ORIGINAL FOR YOUR REC OR DS
(REFE R TO THE RELE VANT O UTDOOR UNIT M ANUAL AND, IN ADDITION, NO TE THE FOLLOW ING:
MPANY:
PR
T:
COMMENT: INITIAL TEST PRESSURE
IMPORTANT: The jumper links referenced in step 8 must be correctly set before applying mains power, to ensure correct operation of unit. (micro units only)
DATE:
FINAL TEST PRESSURE
ENVIROMASTER INTERNATIONAL LLC
HT TP://WWW.ENVIROMASTER.C OM
TE S T DU RATIO N
5780 SUCCESS DRIVE
ROM E, NY 13440
TEL: 1-800-228-9364
FAX: 1-800-232-9364
YES/NO YES/NO
YES/NO YES/NO
YES/NO YES/NO YES/NO
GPM
V V
PSIG PSIG
ºF ºF
EMI@ENVIROMASTER.COMENVIROMASTER INTERNATIONAL LLC 6
Loading...
+ 14 hidden pages