EMI VPAC30, VPAC36, VPHP30, VPHP36 Installation, Operation And Maintenance Manual

VP AC/VPHP 30-36
INST ALLA TION, OPERA TION, AND MAINTENANCE MANUAL
Nominal Cooling Capacity: 30,000 - 36,000 Btuh
P/N 240-4554 Rev. 1.0 [03/04]
VPAC/VPHP 30-36 Single Package Vertical Air Conditioner
(SPVAC) and Heat Pump (SPVHP)
The VPAC/VPHP 30-36 offers an economic benefit when used in a multi-room suite by supplying condi­tioned air to more than one room without the need to install another PTAC/PTHP. This is also a design ad­vantage since the second room does not need an ex­terior wall for a second unit.
The VPHP 30-36 heat pump is intended to be a lim­ited range heat pump, which means utilizing a supple­mented heat option is recommended since heat pump operation will cease at approximately 40°F outdoor temperature. Consult factory for availability of a full range defrosting heat pump version.
PRODUCT DESCRIPTION
The VPAC/VPHP 30-36 single package vertical air conditioner (SPVAC) and heat pump (SPVHP) cre­ates new options in layout and space utilization. The VP AC/VPHP 30-36 offers low cost operation and quiet, comfortable air distribution, especially when used in multi-room suites, apartments, healthcare facilities, and homes.
Framed into a concealed closet enclosure for low op­erating sound levels, the VPAC/VPHP 30-36’s verti­cal discharge vent allows ducting to the top of the room(s) for superior air circulation and distribution. Mul­tiple air supply grilles can distribute air when used with a soffit and intake grilles can be located on the sides of the enclosure.
The VPAC/VPHP 30-36 can be applied in a ducted return air application or can remain non-ducted as de­livered. If ducted, the closet enclosure does not re­quire minimum clearances other than what is recom­mended for adequate service access. If non-ducted, minimum clearance options must be adhered to as dictated for optimal performance and sound. See note on minimum clearance dimensions in the illustation titled ”Exploded View Of Typical Installation” on page 2 of this document. (Figure 1)
Enviromaster International, LLC
Each system is supplied with a ready-to-install wall sleeve and outdoor louver . The cabinet is constructed with 20 gauge galvanized steel with a G-90U corro­sion resistant rating and the insulated top discharge evaporator compartment provides quiet ducted, con­ditioned air delivery to other room location(s).
The VPAC/VPHP 30-36 is backed by EMI and ECR International and is tested and rated in accordance with ARI standard 390 and UL-1995. Due to ongoing product development, product designs and specifica­tions may change without notice. Please contact the factory for more information.
CONDENSA TE REMOV AL
The VP AC/VPHP 30-36 requires an internal drain sys­tem due to its unique draw-thru condenser design. Condenser side drain stub(s) are integral to the chas­sis and are very easy to connect a drain hose to.
AIR SYSTEMS
Motors are thermally protected PSC type. Air stream surfaces are insulated with 1/4 inch fiberglass or 1/8 inch volara. The evaporator fan is a forward curved type directly mounted to the motor shaft. The con­denser propeller utilizes a draw-thru design for im­proved efficiency.
1
www.enviromaster.com/vpac
ELECTRICAL WIRING
WARNING
! !
Before accessing the control compartment, discon­nect power to the unit. Failure to do so could result in serious injury or electrical shock.
All field wiring must be done in accordance to NEC and local codes. Check the unit rating plate for circuit ampacity and breaker(s) or fuse size(s). Use only HACR type breakers or time delay fuses. Select the proper wire for the ampacity rating. Some units re­quire more than one power supply. Check the name­plate and wiring diagram for further instructions.
IMPORTANT: The unit is wired for 230V primary voltage from the factory. The transformer must be rewired by the installer if the jobsite voltage is 208V .
Each vertical unit is equipped for a 24V wall thermo­stat connection.
• Front mounted control box
• Manual fresh air damper
• Microprocessor control board
- Universal control board: can be used in straight cool electric, hydronic heat, or cooling/heat pump applications.
- Fan purge: fan remains on for 60 seconds af­ter heat/cool call is dropped (“auto” mode only)
- Anti-short cycle compressor protection
- Random start timer: prevents multiple units from simultaneous start-ups (straight cool only)
- Freeze protection: prevents evaporator freeze ups
- Low ambient lockout: prevents compressor op­eration in cold outdoor temperatures.
- Test operation: all timers are eliminated to al­low ease of testing after installation (straight cool only)
- Compatible with fossil fuel, electric heat, mer­cury or electronic thermostats
- Refrigerant hot gas bypass for operation in low outdoor ambient conditions (cooling cycle only)
ST ANDARD CONTROLS AND COMPONENTS
• Cooling or heat pump chassis w/high efficiency scroll or reciprocating type compressor
• Custom wall sleeve
• Anodized aluminum outdoor louver for field in­stallation (optional colors available)
FIGURE 1 - EXPLODED VIEW OF TYPICAL INST ALLATION
ROUGH W AL L SLEEVE OPENI NG
Unit Size Width Height
30 28 9/16" 32 3/8" 36 28 9/16" 36 1/4"
For designed performance, sound levels, and service, maintain a minimum of 6” on both sides and front for non-ducted return
air applications only.
6”
6”
OPTIONAL CONTROLS AND COMPONENTS
• Supplemental electric heat
• 265/277V (contact factory for availability)
• Painted condenser louver
• Remote wall thermostat
• Return air access panel (w/disposable return air filters)
Ducted return air applications only require
6”
minimal spacing for service requirements. Consult ECR Engineering if these mini-
mums can not be met. Depending on the application and return air introduction, some reconfiguration is likely to be accom­modated.
VPAC/VPHP
2
Manufactured in Rome, NY, USA
INSPECTION
Carefully check the shipment against the bill of lad­ing. Make sure all chassis, wall sleeves, and louvers (as well as any options) have been received. Inspect each component for damage. The carrier must make proper notation on the delivery receipt of all damage identified and complete a carrier inspection report. Concealed damage must be reported to the carrier within 15 days of the receipt of the shipment.
IMPORTANT: The purchaser must notify the EMI
traffic department of all damage and is responsible for filing any necessary claims with the carrier.
APPLICA TION LIMIT A TIONS
The VPAC/VPHP 30-36 should be installed in accordance with all national and local safety codes.
Minimum and maximum operation conditions must be observed to assure maximum system performance with minimum service required. Refer to table below for application limitations of the VPAC/VPHP 30-36.
APPLICATION L IM ITAT IONS
Outdoor Ambient Air Temperature °F
Mi nimum DB Maximum D B
Cool
67
Cool Heat
115 75
in the wall for the wall sleeve and louver be the cor­rect dimension and in the exact position necessary for installation. (Figure 1)
The platform height should be the same level as the bottom of the wall opening. Because wall sleeve depths can vary depending on overall wall thickness, it is critical that wall thickness be determined
before ordering the wall sleeve. (Figure 2) Consult factory for available wall sleeve sizes.
FIGURE 2 - DETERMINING WALL SLEEVE DEPTH
½” x ½” Foam Gasket
Outdoor Louver
Drip edge will extend outside exterior wall when installed to guide con­densate away from building
Wall Sleeve Depth = Overall W all Thickness - 1.25” (Louver Depth)
Overall Wall
Thickness
Exterior Wall
Wall Sleeve
Interior Wall
Lag Holes
(4 Per Side)
Indoor Ambient Air Temperature °F
Minimum Maximum
DB/WB D B DB/WB DB
Cool Heat Cool Heat
67/57 50 90/72 80
CAUTION
! !
Avoid possibility of electric shock and personal in­jury. Disconnect all power before removing chas­sis or performing any cleaning, servicing, or main­tenance.
GENERAL INST ALLA TION
Enviromaster International recommends installing the VPAC/VPHP 30-36 before any carpentry work is started for the enclosure. It is very important for proper air flow and sound levels that a minimum clearance of 6” between the enclosure and the chassis be main­tained. It is also very important that the rough opening
Wall Sleeve
Assembly
Cross Section of Typical Wall
1. Install 1/2” x 1/2” or 1” x 1” foam tape (supplied) to the unit condenser top and sides to seal against the wall sleeve. (Figure 3)
FIGURE 3 - INSULATION & WEATHER ANGLES
Install supplied 1/2” x 1/2” foam insulation along top and sides of condenser box. (IMPORTANT: Position as far forward toward outdoor side as possible.)
Weather Angle
Position (One on
each side)
Enviromaster International, LLC
3
www.enviromaster.com/vpac
Loading...
+ 5 hidden pages