EMI VCH Series Installation, Operation And Maintenance Manual

VERTICAL (VCH ) AND HORIZONTAL (HCA/HCH)
IN-WALL STRAIGHT COOL CONDENSING UNITS
Nominal Circuits:
VCH
(18,000, 24,000 & 30,000 Btuh)
(18,000 & 24,000 Btuh)
HCH
(24,000 & 30,000 Btuh)
Enviromaster International LLC 5780 Success Dr. Rome, NY 13440 Email: emi@enviromaster.com
INSTALLATION, OPERATION AND MAINTENANCE MANUAL
VCH
HCH
HCA
An ISO 9001-2000 Certified Company
P/N 240000664, Rev. 2.1 [06/04]
VCH
INSTALLATION, OPERATION, AND MAINTENANCE
VERTICAL (VCH) AND
HORIZONTAL (HCA/HCH)
IN-WALL STRAIGHT COOL
CONDENSING UNITS
HCH
HCA
NOMINAL CAPACITIES: VCH (18,000, 24,000, & 30,000 Btuh), HCA
(18,000 & 24,000 Btuh), HCH (24,000 & 30,000 Btuh)
INSTALLER RESPONSIBILITIES
SAVE THESE INSTRUCTIONS
FOR FUTURE REFERENCE!!
This manual is intended as an aid to qualified service personnel for proper installation, operation, and maintenance of the EMI AmericaSeries Vertical and Horizontal In-Wall Condensing Unit (VCH, HCA, or HCH). Please read these instructions thoroughly and carefully before attempting installation or operation. Failure to follow these instructions may result in improper installation, operation, service, or maintenance, possibly resulting in fire, electrical shock, property damage, personal injury, or death.
Shipping Damage MUST be Reported to
the Carrier IMMEDIATELY!!!
Examine the exterior. Remove cover and examine
compressor and piping for signs of damage.
To obtain technical service or warranty assistance during or after the installation of this unit, call toll free:
1-800-228-9364
When calling for assistance, please have the following information ready:
• Model Number_____________________________
• Serial Number_____________________________
• Date Of Installation_________________________
WARNINGS
!
Install or locate the EMI AmericaSeries Vertical or
Horizontal In-Wall Condensing Unit only in accordance with these instructions. Use this unit only for its intended purpose as described in this instruction manual.
Before installation, check the unit rating plate to make
certain the voltage shown is the same as the electrical supply to the unit.
The EMI AmericaSeries V ertical or Horizont al In-Wall
Condensing Unit must be connected to a properly grounded electrical supply. Do not fail to properly
ground this unit.
Before servicing the EMI AmericaSeries Vertical or
Horizontal In-Wall Condensing Unit, be sure to disconnect the electrical supply to the unit.
Do not use the EMI AmericaSeries Vertical or
Horizontal In-Wall Condensing Unit if it:
- is not working properly
- has damaged wiring
- has been dropped or otherwise damaged.
Before leaving the premises, review this manual to
be sure the EMI AmericaSeries V ertical or Horizontal In-Wall Condensing Unit has been correctly installed and run the unit for one complete cycle to make sure it functions properly.
P/N# 240000664, Rev. 2.1 [6/04]
!
Made in Rome, New York, USAComfort Where It Counts 2
IMPORTANT
!
!
INSTALLATION
The HCA Condensing Unit does not meet federal en­ergy efficiency standards for new central air condition­ing and is NOT to be used in new construction. EMI has a D.O.E. waiver to sell the HCA as a replacement unit only.
PRE-INSTALLATION
1. Unpack the unit and inspect for damage. Make any freight claims immediately.
2. Inspect the planned locations of the evaporator and condenser for proper fit as well as clearance for access and service. If this is a replacement job, wall openings may have to be modified for proper fit. Make any necessary wall opening modifications and/or provide fillers. Make certain the wall remains weather tight.
3. Eliminate any outdoor obstructions that may cause discharge air to recirculate to the intake. If this is not possible, an alternate location must be found.
4. Plan the routing for piping and wiring, noting the location of access holes for tubing and high voltage wiring on the unit. Do not block service access to the unit panels, control box, blower, etc.
5. Use a low voltage wall thermostat, assuming evaporator unit is remote controlled and supplied by Enviromaster International or a suitable equivalent. If in doubt, contact the factory for assistance. Low voltage access is in the bottom rear of the VCH and the side panels of the HCA and HCH.
6. The wall thermostat should be located on an inside wall where it will not be subject to drafts, sun exposure, or heat from electrical fixtures or appliances. Follow the manufacturer’s instructions enclosed with the thermostat for general installation procedures. Color­coded insulated wires (#18 AWG) should be used to connect the thermostat to the unit.
1. Install the outdoor louver to the chassis if it is not already factory installed.
NOTE: Use of an outdoor louver other than one sup­plied by Enviromaster International must receive prior approval or the warranty may be voided.
2. Set the EMI AmericaSeries Vertical or Horizontal In­Wall Condensing Unit in the wall opening. Provide a minimum 1/4” pitch to the outside. Secure the unit to the wall using lag bolts or other suitable fasteners. Caulk weather tight.
3. Wiring electrical connections: All wiring must be done in accordance with the National Electrical Code (NEC), ANSI/NFPA No. 70 (latest edition); or local codes, where they prevail. Any alteration of internal wiring will void certification and warranty.
Use wiring with a temperature limitation of 75°C
minimum. Run the 208 or 230 Volt, 60 hertz electric power supply through a fused disconnect switch to the control box of the unit and connect as shown in wiring diagram located on the inside of the control access panel.
The unit must be electrically grounded in accordance
with local codes or, in the absence of local codes, with the National Electrical Code ANSI/NFPA No. 70 (latest edition) or CSA C22.2 Part 1 (latest edition).
Power supply to the unit must be NEC Class 1 and
must comply with all applicable code. A fused disconnect switch should be field provided for the unit. The switch must be separate from all other circuits. If any of the wire supplied with the unit must be replaced, replacement wire must have an equivalent rating.
Electrical wiring must be sized to minimum circuit
ampacity marked on the unit. Use copper conductors only. Each unit must be wired with a separate branch circuit and properly fused.
7. If using an EMI evaporator, make certain a 24V step­down transformer must has been installed in the evaporator section to supply control power between the evaporator and the condenser. If ordering, specify a 20va transformer. Avoid ordering larger transformers as mounting space is limited.
NOTE: When matching an EMI AmericaSeries Vertical or Horizontal In-Wall Condensing Unit to another manufacturer’s evaporator, the evaporator section must be approved by Enviromaster International. Failure to secure approval may void the warranty.
4. Run interconnecting refrigerant lines (not to exceed 100’ with 35’ of vertical lift included) according to chart data for specific unit. Use clean refrigeration tubing only , and guard against kinking the tubes. Protect the tubes from transmitting noise to walls, cabinets, etc. Insulate the suction line. Connections are made at the unit service valves. When making sweat connections, use high temperature brazing alloys only and protect the valves from overheating. If using flux, protect the unit from contamination.
emi@enviromaster.comEnviromaster International LLC 3