EMI T2HB, T4HB, T3HB, S2HB User Manual

EMI AMErIcA SErIES
MultI-ZonE HEAt PuMP
condEnSIng unItS
S2HB, T2HB, T3HB, and T4HB HeaT PumPS
Nominal Circuit Capacities: 9,000 12,000 18,000 & 24,000
Btuh units.
S2HB Multi-Zone
Enviromaster International LLC
5780 Success Dr. Rome, NY 13440 www.enviromaster.com
T2HB, T3HB, & T4HB
Multi-Zone
An ISO 9001-2000 Certied Company
P/N# 240006458 Rev. B [10/08]
EMI AMErIcA SErIES MultI-zonE HEAt PuMP condEnSIng unItS
inSTallaTion, oPeraTion and mainTenanCe manual
This manual is intended as an aid to qualied service personnel for proper installation, operation, and maintenance of these EMI America Series multi-zone heat pump condensing units. Read the instructions thoroughly and carefully before attempting installation or operation. Failure to follow these instructions may result in improper installation, operation, service, or maintenance, possibly resulting in re, electrical shock, property damage, personal injury, or death.
Shipping Damage MUST be Reported to the Carrier IMMEDIATELY!!!
Examine the carton for signs of damage if any is evident open packaging and
check the unit for shipping damage.
To THe inSTaller
SaFeTY inSTruCTionS
(1) Retain this manual and warranty for future
reference.
(2) Before leaving the premises, review this
manual to be sure the unit has been installed correctly and run the unit for one complete cycle to make sure it functions properly.
To obtain technical service or warranty assistance during or after the installation
of this unit, check our website @ www. enviromaster.com or call your installing
contractor or distributor. Our technical service department may be contacted at 1-800-228-9364.
When calling for assistance, please have the following information ready:
• Model Number___________________
• Serial Number___________________
• Date of installation________________
dAngEr
! !
Tampering with the emi america Series condenser is dangerous and may result in serious injury or death. Tampering voids all warran­ties. do not attempt to modify or change this unit in any way.
Read all instructions before using
the EMI America Series multi-zone heat pump condenser. Install or locate this unit only in accordance
with these instructions. Use this
unit only for its intended use as described in this manual.
Check the rating plate on the EMI
America Series multi-zone heat pump condenser before installation to make certain the voltage shown is the same as the electric supply
to the unit.
The EMI America Series multi-zone
heat pump condenser must be con­nected only to a properly grounded electrical supply. Do not fail to prop­erly ground this unit.
Turn off the electrical supply before
servicing the EMI America Series multi-zone heat pump condenser.
Do not use the EMI America Series
multi-zone heat pump condenser if it has damaged wiring, is not work­ing properly, or has been damaged or dropped.
[Save These instructions]
Recognize this symbol as an
indication of important
!
safety information.
!
multi-zone Heat Pump Condensing units
2
www.enviromaster.com
EMI AMErIcA SErIES MultI-zonE HEAt PuMP condEnSIng unItS
deSCriPTion
EMI offers the nest multi-zone heat pump outdoor units in the ductless split market, the S & T series (S2HB, T2HB, T3HB & T4HB) Condensing Units. The S & T series (S2HB, T2HB, T3HB & T4HB) allows the installation of two or more circuits from a single outside location when space or aesthetic requirements limit the use of the number of cabinets outdoors. Each zone is independent so no mixing of refrigerant
occurs.
When s p e c i f ying he a t p u m p(s), i t i s recommended that the matching indoor unit(s) be equipped with electric heat. All 9,000, and 12,000 Btuh circuit units are equipped with the
Duratec Performance Package which includes
a large capacity suction accumulator with surge baffles and enhanced oil management, and a factory installed solid core lter drier. All
18,000 and 24,000 Btuh circuit units include
a solid core lter drier and high pressure limit
switch. The 18,000 Btuh circuits also include a
large capacity suction accumulator with surge baffles and enhanced oil management.
noTe: The crankcase heater is installed with 9,000 and 12,000 Btuh heat pumps.
ConTrolS and ComPonenTS
(FACTOR Y INSTALLED OR SUPPLIED)
• Compressor and Fan Motor Contactor
• Capacitor
• Low Voltage Connections
• Large Capacity Suction Accumulator (9, 12, & 18 Only)
• High Pressure Control (18 & 24 Only)
• Solid Core Filter Drier
• Thermostatically controlled crankcase
heater (9&12 Only)
• Common suction pressure access point
• Hard Start Capacitor
Thermostatically controlled crankcase heater – This feature energizes the crank-
case heater only when needed, removes the heate r from the electrical circuit at conditions where it’s not required, saving unnecessary Watts, and increasing overall system efciency.
SYSTem oPTionS
• Sea Coast Style Coated Coils / Copper-Copper coils
• Wind Baffles - Louvers
inSTaller SuPPlied iTemS
• Power wiring
• Low Volt wiring - 18 AWG minimum
• Secure mounting pad or foundation
• Refrigerant piping
• Disconnect switch
iTemS For ConSidera Tion
• Locate the unit as close to the indoor sec­tion as possible. Maximum length allowed is 100 equivalent feet.
• Avoid high trafc areas and prevailing
wind locations.
• Surface must be level.
• Mount unit above typical snow levels.
Ensure free air flow through the unit. Air must not recirculate from discharge to in­take. Air is drawn through the coil with side or top and discharged through the fan grille.
A minimum 48” clearance is necessary for the condenser discharge. Intake (coil side) clearance is 12” minimum.
Consider how power will be run to the unit from the power source. Refrigerant piping must be a direct line to the indoor unit.
Heat pump units produce condensate in the heat pump mode. Water will drain from the unit at the base. Place the unit so as not to create a hazard for pedestrians.
SiTe PreP araTion
Place the unit on a flat concrete surface or
pad if on the ground. Roof mounting should use a build up platform. Piping is through the wall or roof directly to the unit. In areas of heavy snowfall, condensers should be set above the level of maximum anticipated snowfall (12” is usually adequate).
multi-zone Heat Pump Condensing units
3
www.enviromaster.com
S2HB InStAllAtIon InStructIonS SEctIon
noTe: For T2HB, T3HB, & T4HB installation refer to the T2HB, T3HB, & T4HB
Installation Instruction section in this manual.
S2HB uniT mounTing SeCTion
Side discharge unit allows for permanent mounting through the feet. This is highly recommended due to the vertical design of the unit.
1. Loosen the screws on left and right sides of the front panel. (Do not remove these
Accumulator
Compressor Capacitor
screws.)
Filter Driers
Lag Bolts
5. Insert lag bolts through the holes in the bottom of the unit and tighten to
secure.
2. Remove the screws on the front of the panel.
3. To remove front panel:
4. Slide front panel forward to clear side
screws and remove.
multi-zone Heat Pump Condensing units
6. Insert lag bolts through the holes in the feet on the back of the unit and tighten
to secure.
7. Replace the front panel, do not tighten
the side screws at this time.
4
www.enviromaster.com
S2HB ElEctrIcAl WIrIng InStAllAtIon SEctIon
dAngEr
! !
The EMI America Series condensing unit must:
• Be connected to a properly grounded electrical supply with the proper voltage as stated on the rating plate.
• Have proper over current protection (i.e. time- delay fuse/HACR-Breaker) as listed on the Rating Plate.
Failure to follow these instructions can re­sult in a re, explosion, or electrical shock causing property damage, personal injury,
or death.
dAngEr
! !
Do not use the EMI America Series condensing unit with any electrical supply voltage other than the one listed on the rating plate.
Check the rating plate on the unit for the correct voltage rating. Failure to use the correct voltage may result in death, serious bodily injury or property damage. If you have any questions or doubts, consult the factory before installing this unit.
1. All electrical wiring must be run according
to NEC and local codes.
2. Refer to the unit rating plate for voltage, minimum circuit ampacity and over cur­rent protection requirements.
Rating
Plate
3. Use only HACR type breakers or time delay fuses. Select the wire size accord­ing to the ampacity rating.
4. To access electrical connections and
wiring diagram:
a) Remove the screws on the side panel
adjacent to the back panel.
b) The screws adjacent to the front
panel should already be loose (don't
remove them).
c. Slide the side panel out to access the
high/low electrical connections and wire diagram.
Note: Remove the plastic edge guards
from the holes and replace with a water­tight strain relief tting (High V) and a
split grommet tting (low V)
5. Power should be run to a weather proof disconnect box usually within 3 feet of
the unit.
6. From the disconnect box, run the power through the 7/8" hole on the side of the unit and into the electrical box and an­chor with the strain relief tting.
multi-zone Heat Pump Condensing units
7. Run wires to the high Volt pigtail in the con­trol box and attach L1 and L2 connections. Also run green wire to ground wire.
5
www.enviromaster.com
S2HB ElEctrIcAl WIrIng InStAllAtIon SEctIon
Note: Refer to the
units’ wiring diagram for all wiring.
Inside electrical
access panel.
8. Check wiring diagram for the re­quired number of low voltage wires to be run between indoor and out-
door sections.
low Volt Connection
Completed
electrical Connections
Wire diagram
Low Volt
Plastic edge guards
9. Connect the 24 Volt wiring matching color to color. Refer to the wiring diagram on the inside panel of the condenser, and also refer to the wiring diagram on the indoor
unit. Low Volt interconnect should be at least 18 AWG.
10. To replace side panel slide the slotted
holes of the panel onto the loosened sc r e w s of th e fr o n t panel so that the edge of the front panel c o v e r s the edge of the side panel.
High Volt
multi-zone Heat Pump Condensing units
11. Tighten all remaining loose screws.
6
www.enviromaster.com
t2HB, t3HB, And t4HB InStAllAtIon InStructIonS SEctIon
noTe: For S2HB installation refer to the S2HB Installation Instruction in this manual.
After the T2HB, T3HB, or T4HB unit is positioned on the concrete slab or platform (refer
to the Site Preparation in the front of this manual) the T2HB, T3HB, or T4HB is ready
for installation:
1. Remove the screw on the back panel.
2. Remove panel to expose eletrical
wiring.
Mounting
Screw
Low Volt
High Volt
3. Location of electrical and tubing connec-
tions on back of unit.
Common Suction Pressure Access
Point
Vapor (Suction)
Liquid
High
Pressure
Reset
(18 & 24)
eleCTriCal Wiring
1. All electrical wiring must be run according
to NEC and local codes.
2. Refer to the unit rating plate for voltage, minimum circuit ampacity and over cur­rent protection requirements.
3. Use only HACR type breakers or time
delay fuses. Select the wire size accord­ing to the ampacity rating.
Remove the
four screws on the front panel
4. To access wiring diagram:
a) Remove the four screws on the front
panel of the unit and slide the panel
down until
th e up p er edge is free,
then remove
the panel.
b) The wiring
di agr am is
located on the inside
of the front panel.
wiring
Diagram
multi-zone Heat Pump Condensing units
7
www.enviromaster.com
t2HB, t3HB, And t4HB InStAllAtIon InStructIonS SEctIon
eleCTriCal Wiring
5. with a screw-
drive r p u n c h
out and remove
Mounting
Screw
the knock-outs
in the low &
high Volt elec-
trical connec-
tion box.
Knock-out
High VoltLow Volt
Note: Po wer should be ru n to a
weather proof disconnect box usually within 3 feet of the unit.
6. From the disconnect box feed the high
Volt wires through a weather proof con-
duit and run the power through the 7/8"
hole (from knock-out) in the unit’s electri­cal box. Anchor with a strain relief tting.
Refer to the wiring diagram.
7. Following the wiring diagram, run wires
to the High Volt pigtail in the control box and attach L1 and L2 connections. Also run green wire to ground lug.
9. Connect the 24 Volt wiring matching color to terminal block designation for each zone as labeled. Refer to the wiring diagram on the inside front panel of the condenser, and also refer to the wiring diagram on the
indoor unit. Low Volt interconnect should be at least 18 AWG.
When connecting to the rear terminal strip
there are two approaches.
a) Using a long straight screw driver over
the top of the front terminal strip while holding the wire with needle nose pliers from below.
b) Remove the mounting screw (stubby
screwdriver), then pull the entire front terminal strip forward, disengaging the tab on left from slot. When nished, reinsert terminal strip tab into slot and reinstall mounting screw.
CauTion
!
!
Make sure that Low Volt wiring for each circuit is connected to the matching Low Volt wiring.
8. Check wiring diagram for the required num­ber of low voltage wires to be run between
indoor and outdoor sections.
multi-zone Heat Pump Condensing units
10. Replace the unit’s electric box cover and
the front panel and tighten screws
8
www.enviromaster.com
.
MultI-zonE HEAt PuMP rEfrIgErAnt PIPIng InStAllAtIon
noTe: Refrigerant Piping Installation for all of the multi-zone heat pump models.
inTerConneCTing TuBing SPeCS
S2HB, T2HB, T3HB, & T4HB models:
Nominal
Circuit
Capacity
12,000 100’ 35’ 1/4” 1/2” 18,000 100’ 35’ 3/8” 5/8”* 24,000 100’ 35’ 3/8” 3/4”
* CAH24, UNH24, WLH24 Suction Connection size
Maximum
Length
9,000 100’ 35’ 1/4” 1/2”
is 3/4” O.D. and must bush down to 5/8” for 18,000 Btuh circuits at the indoor unit.
Maximum
Lift
Liquid
Line
OD
Suction
Line
OD
Schrader ttings for charging and taking pressure readings. The following precau­tions should be made:
• Be certain no burrs remain on the ttings.
• Use only clean refrigeration tubing.
• Use tube benders to guard against kinking.
• Avoid piping on wet and rainy days
and insulate suction line. Be certain
that plastic end caps remain in place when inserting through wall openings. Isolate tubing from transmitting vibra-
The system will support refrigerant runs to the inside unit of up to 100' equivalent feet with a 35' rise included. The units are furnished with sweat connections and are equipped with refrigerant valves and
tion to the building or unit and avoid
contact with sharp edges. refrigera-
tion valves should be wrapped with a wet rag "heat sink" to protect valves while brazing.
PiSTon/oriFiCe CHange KiT inSTallaTion
When a WLH24 or UNH24 air handler is matched with a T2HB or T3HB contain­ing a 24,000 Btuh nominal capacity circuit, the air handler must have it’s stock piston changed from 0.059 to 0.063.
Air Handler
A 24,000 Btuh nominal circuit can be identied by the “4” in
the model number capacity eld (i.e.
T2HBx4xx). Refer to the instructions sup-
plied with kit part number; 240006777.
Circuit Designators: 9 = 9000 Btuh • 2 = 12000 Btuh • 8 = 18000 Btuh • 4 = 24000 Btuh
(ex. - 8400 consists of one 18000 Btuh compressor and one 24000 Btuh compressor)
model #
air Handler
WLH24
or
UNH24
Condenser
Btuh
T2HB2400 T2HB8400 T2HB4400 T3HB9940 T3HB9240 T3HB2240
Note: This kit is only supplied with the above Heat Pump models.
multi-zone Heat Pump Condensing units
Factory installed
Piston/Orice Size
.059” .063”
9
Field Changeover
Piston/Orice Size
www.enviromaster.com
P-trAP InStAllAtIon
Condenser
Evaporator
• A P-trap is recommended when the suc­tion riser is equal to or greater than 20 feet in height.
• When the condenser is installed above the evaporator, the P-trap will help the return of oil back to the compressor.
• The placement of the P-trap should be at the halfway mark of the suction riser. For example if the suction riser is 30 feet tall then a P-trap is recommended at the 15 foot
mark of the suction riser (see Figure #1).
Figure #1
• A P-trap may be fabricated using;
(2) street elbows and (2) regular elbows.
A prefabricated trap may be purchased from a Wholesaler or Distributor how­ever the trap should be shallow as the: (4) elbow conguration. Each elbow is approximately 2 equivalent feet. One P­trap is equal to approximately 8 equiva­lent feet.
multi-zone Heat Pump Condensing units
10
www.enviromaster.com
Loading...
+ 22 hidden pages