5780 Success Dr.
Rome, NY 13440
www.enviromaster.com
T2HB, T3HB, & T4HB
Multi-Zone
An ISO 9001-2000 Certied Company
P/N# 240006458 Rev. B [10/08]
EMI AMErIcA SErIES MultI-zonE HEAt PuMP condEnSIng unItS
inSTallaTion, oPeraTion and mainTenanCe manual
This manual is intended as an aid to qualied service personnel for proper installation, operation,
and maintenance of these EMI America Series multi-zone heat pump condensing units. Read
the instructions thoroughly and carefully before attempting installation or operation. Failure to
follow these instructions may result in improper installation, operation, service, or maintenance,
possibly resulting in re, electrical shock, property damage, personal injury, or death.
Shipping Damage MUST be Reported to the Carrier IMMEDIATELY!!!
Examine the carton for signs of damage if any is evident open packaging and
check the unit for shipping damage.
To THe inSTaller
SaFeTY inSTruCTionS
(1) Retain this manual and warranty for future
reference.
(2) Before leaving the premises, review this
manual to be sure the unit has been
installed correctly and run the unit for
one complete cycle to make sure it
functions properly.
To obtain technical service or warranty
assistance during or after the installation
of this unit, check our website @ www.enviromaster.com or call your installing
contractor or distributor. Our technical
service department may be contacted at
1-800-228-9364.
When calling for assistance, please have
the following information ready:
• Model Number___________________
• Serial Number___________________
• Date of installation________________
dAngEr
! !
Tampering with the emi america
Series condenser is dangerous
and may result in serious injury or
death. Tampering voids all warranties. do not attempt to modify or
change this unit in any way.
Read all instructions before using
the EMI America Series multi-zone
heat pump condenser. Install or
locate this unit only in accordance
with these instructions. Use this
unit only for its intended use as
described in this manual.
Check the rating plate on the EMI
America Series multi-zone heat
pump condenser before installation
to make certain the voltage shown
is the same as the electric supply
to the unit.
The EMI America Series multi-zone
heat pump condenser must be connected only to a properly grounded
electrical supply. Do not fail to properly ground this unit.
Turn off the electrical supply before
servicing the EMI America Series
multi-zone heat pump condenser.
Do not use the EMI America Series
multi-zone heat pump condenser if
it has damaged wiring, is not working properly, or has been damaged
or dropped.
[Save These instructions]
Recognize this symbol as an
indication of important
!
safety information.
!
multi-zone Heat Pump Condensing units
2
www.enviromaster.com
EMI AMErIcA SErIES MultI-zonE HEAt PuMP condEnSIng unItS
deSCriPTion
EMI offers the nest multi-zone heat pump
outdoor units in the ductless split market, the
S & T series (S2HB, T2HB, T3HB & T4HB)
Condensing Units. The S & T series (S2HB,
T2HB, T3HB & T4HB) allows the installation of
two or more circuits from a single outside location
when space or aesthetic requirements limit the
use of the number of cabinets outdoors. Each
zone is independent so no mixing of refrigerant
occurs.
When s p e c i f ying he a t p u m p(s), i t i s
recommended that the matching indoor unit(s)
be equipped with electric heat. All 9,000, and
12,000 Btuh circuit units are equipped with the
Duratec Performance Package which includes
a large capacity suction accumulator with
surge baffles and enhanced oil management,
and a factory installed solid core lter drier. All
18,000 and 24,000 Btuh circuit units include
a solid core lter drier and high pressure limit
switch. The 18,000 Btuh circuits also include a
large capacity suction accumulator with surge
baffles and enhanced oil management.
noTe: The crankcase heater is installed
with 9,000 and 12,000 Btuh heat pumps.
ConTrolS and ComPonenTS
(FACTOR Y INSTALLED OR SUPPLIED)
• Compressor and Fan Motor Contactor
• Capacitor
• Low Voltage Connections
• Large Capacity Suction Accumulator (9,
12, & 18 Only)
• High Pressure Control (18 & 24 Only)
• Solid Core Filter Drier
• Thermostatically controlled crankcase
heater (9&12 Only)
• Common suction pressure access point
• Hard Start Capacitor
Thermostatically controlled crankcase
heater – This feature energizes the crank-
case heater only when needed, removes
the heate r from the electrical circuit at
conditions where it’s not required, saving
unnecessary Watts, and increasing overall
system efciency.
• Locate the unit as close to the indoor section as possible. Maximum length allowed
is 100 equivalent feet.
• Avoid high trafc areas and prevailing
wind locations.
• Surface must be level.
• Mount unit above typical snow levels.
Ensure free air flow through the unit. Air
must not recirculate from discharge to intake. Air is drawn through the coil with side
or top and discharged through the fan grille.
A minimum 48” clearance is necessary
for the condenser discharge. Intake
(coil side) clearance is 12” minimum.
Consider how power will be run to the unit
from the power source. Refrigerant piping
must be a direct line to the indoor unit.
Heat pump units produce condensate in the
heat pump mode. Water will drain from the
unit at the base. Place the unit so as not to
create a hazard for pedestrians.
SiTe PreP araTion
Place the unit on a flat concrete surface or
pad if on the ground. Roof mounting should
use a build up platform. Piping is through
the wall or roof directly to the unit. In areas
of heavy snowfall, condensers should be
set above the level of maximum anticipated
snowfall (12” is usually adequate).
multi-zone Heat Pump Condensing units
3
www.enviromaster.com
S2HB InStAllAtIon InStructIonS SEctIon
noTe: For T2HB, T3HB, & T4HB installation refer to the T2HB, T3HB, & T4HB
Installation Instruction section in this manual.
S2HB uniT mounTing SeCTion
Side discharge unit allows for permanent mounting through the feet. This is highly
recommended due to the vertical design of the unit.
1. Loosen the screws on left and right sides
of the front panel. (Do not remove these
Accumulator
Compressor Capacitor
screws.)
Filter Driers
Lag Bolts
5. Insert lag bolts through the holes in
the bottom of the unit and tighten to
secure.
2. Remove the screws on the front of the
panel.
3. To remove front panel:
4. Slide front panel forward to clear side
screws and remove.
multi-zone Heat Pump Condensing units
6. Insert lag bolts through the holes in the
feet on the back of the unit and tighten
to secure.
7. Replace the front panel, do not tighten
the side screws at this time.
4
www.enviromaster.com
S2HB ElEctrIcAl WIrIng InStAllAtIon SEctIon
dAngEr
! !
The EMI America Series condensing
unit must:
• Be connected to a properly grounded
electrical supply with the proper voltage
as stated on the rating plate.
• Have proper over current protection (i.e.
time- delay fuse/HACR-Breaker) as listed
on the Rating Plate.
Failure to follow these instructions can result in a re, explosion, or electrical shock
causing property damage, personal injury,
or death.
dAngEr
! !
Do not use the EMI America Series
condensing unit with any electrical supply
voltage other than the one listed on the
rating plate.
Check the rating plate on the unit for the
correct voltage rating. Failure to use the
correct voltage may result in death, serious
bodily injury or property damage. If you have
any questions or doubts, consult the factory
before installing this unit.
1. All electrical wiring must be run according
to NEC and local codes.
2. Refer to the unit rating plate for voltage,
minimum circuit ampacity and over current protection requirements.
Rating
Plate
3. Use only HACR type breakers or time
delay fuses. Select the wire size according to the ampacity rating.
4. To access electrical connections and
wiring diagram:
a) Remove the screws on the side panel
adjacent to the back panel.
b) The screws adjacent to the front
panel should already be loose (don't
remove them).
c. Slide the side panel out to access the
high/low electrical connections and
wire diagram.
Note: Remove the plastic edge guards
from the holes and replace with a watertight strain relief tting (High V) and a
split grommet tting (low V)
5. Power should be run to a weather proof
disconnect box usually within 3 feet of
the unit.
6. From the disconnect box, run the power
through the 7/8" hole on the side of the
unit and into the electrical box and anchor with the strain relief tting.
multi-zone Heat Pump Condensing units
7. Run wires to the high Volt pigtail in the control box and attach L1 and L2 connections.
Also run green wire to ground wire.
5
www.enviromaster.com
S2HB ElEctrIcAl WIrIng InStAllAtIon SEctIon
Note: Refer to the
units’ wiring diagram
for all wiring.
Inside electrical
access panel.
8. Check wiring diagram for the required number of low voltage wires
to be run between indoor and out-
door sections.
low Volt Connection
Completed
electrical Connections
Wire diagram
Low Volt
Plastic edge guards
9. Connect the 24 Volt wiring matching color
to color. Refer to the wiring diagram on the
inside panel of the condenser, and also
refer to the wiring diagram on the indoor
unit. Low Volt interconnect should be at
least 18 AWG.
10. To replace side panel slide the slotted
holes of the panel onto the loosened
sc r e w s of th e fr o n t
panel so thatthe
edge of the front
panel c o v e r s
the edge of the
side panel.
High Volt
multi-zone Heat Pump Condensing units
11. Tighten all remaining loose screws.
6
www.enviromaster.com
t2HB, t3HB, And t4HB InStAllAtIon InStructIonS SEctIon
noTe: For S2HB installation refer to the S2HB Installation Instruction in this manual.
After the T2HB, T3HB, or T4HB unit is positioned on the concrete slab or platform (refer
to the Site Preparation in the front of this manual) the T2HB, T3HB, or T4HB is ready
for installation:
1. Remove the screw on the back panel.
2. Remove panel to expose eletrical
wiring.
Mounting
Screw
Low Volt
High Volt
3. Location of electrical and tubing connec-
tions on back of unit.
Common
Suction
Pressure
Access
Point
Vapor
(Suction)
Liquid
High
Pressure
Reset
(18 & 24)
eleCTriCal Wiring
1. All electrical wiring must be run according
to NEC and local codes.
2. Refer to the unit rating plate for voltage,
minimum circuit ampacity and over current protection requirements.
3. Use only HACR type breakers or time
delay fuses. Select the wire size according to the ampacity rating.
Remove the
four screws
on the front
panel
4. To access wiring diagram:
a) Remove the four screws on the front
panel of the unit and slide the panel
down until
th e up p er
edge is free,
then remove
the panel.
b) The wiring
di agr am is
located on
the inside
of the front
panel.
wiring
Diagram
multi-zone Heat Pump Condensing units
7
www.enviromaster.com
t2HB, t3HB, And t4HB InStAllAtIon InStructIonS SEctIon
eleCTriCal Wiring
5. with a screw-
drive r p u n c h
out and remove
Mounting
Screw
the knock-outs
in the low &
high Volt elec-
trical connec-
tion box.
Knock-out
High VoltLow Volt
Note: Po wer should be ru n to a
weather proof disconnect box usually
within 3 feet of the unit.
6. From the disconnect box feed the high
Volt wires through a weather proof con-
duit and run the power through the 7/8"
hole (from knock-out) in the unit’s electrical box. Anchor with a strain relief tting.
Refer to the wiring diagram.
7. Following the wiring diagram, run wires
to the High Volt pigtail in the control box
and attach L1 and L2 connections. Also
run green wire to ground lug.
9. Connect the 24 Volt wiring matching color
to terminal block designation for each zone
as labeled. Refer to the wiring diagram on
the inside front panel of the condenser,
and also refer to the wiring diagram on the
indoor unit. Low Volt interconnect should
be at least 18 AWG.
When connecting to the rear terminal strip
there are two approaches.
a) Using a long straight screw driver over
the top of the front terminal strip while
holding the wire with needle nose pliers
from below.
b) Remove the mounting screw (stubby
screwdriver), then pull the entire front
terminal strip forward, disengaging the
tab on left from slot. When nished,
reinsert terminal strip tab into slot and
reinstall mounting screw.
CauTion
!
!
Make sure that Low Volt wiring for each
circuit is connected to the matching
Low Volt wiring.
8. Check wiring diagram for the required number of low voltage wires to be run between
is 3/4” O.D. and must bush down to 5/8” for 18,000
Btuh circuits at the indoor unit.
Maximum
Lift
Liquid
Line
OD
Suction
Line
OD
Schrader ttings for charging and taking
pressure readings. The following precautions should be made:
• Be certain no burrs remain on the
ttings.
• Use only clean refrigeration tubing.
• Use tube benders to guard against
kinking.
• Avoid piping on wet and rainy days
and insulate suction line. Be certain
that plastic end caps remain in place
when inserting through wall openings.
Isolate tubing from transmitting vibra-
The system will support refrigerant runs
to the inside unit of up to 100' equivalent
feet with a 35' rise included. The units
are furnished with sweat connections and
are equipped with refrigerant valves and
tion to the building or unit and avoid
contact with sharp edges. refrigera-
tion valves should be wrapped with
a wet rag "heat sink" to protect
valves while brazing.
PiSTon/oriFiCe CHange KiT inSTallaTion
When a WLH24 or UNH24 air handler is matched with a T2HB or T3HB containing a 24,000 Btuh nominal capacity circuit, the air handler must have it’s stock
piston changed from 0.059 to 0.063.
Air Handler
A 24,000 Btuh nominal circuit
can be identied by the “4” in
Note: This kit is only supplied with the above Heat Pump models.
multi-zone Heat Pump Condensing units
Factory installed
Piston/Orice Size
.059”.063”
9
Field Changeover
Piston/Orice Size
www.enviromaster.com
P-trAP InStAllAtIon
Condenser
Evaporator
• A P-trap is recommended when the suction riser is equal to or greater than 20
feet in height.
• When the condenser is installed above
the evaporator, the P-trap will help the
return of oil back to the compressor.
• The placement of the P-trap should be at
the halfway mark of the suction riser. For
example if the suction riser is 30 feet tall
then a P-trap is recommended at the 15 foot
mark of the suction riser (see Figure #1).
Figure #1
• A P-trap may be fabricated using;
(2) street elbows and (2) regular elbows.
A prefabricated trap may be purchased
from a Wholesaler or Distributor however the trap should be shallow as the:
(4) elbow conguration. Each elbow is
approximately 2 equivalent feet. One Ptrap is equal to approximately 8 equivalent feet.
multi-zone Heat Pump Condensing units
10
www.enviromaster.com
Loading...
+ 22 hidden pages
You need points to download manuals.
1 point = 1 manual.
You can buy points or you can get point for every manual you upload.