EMI SCC, SHC, MC4, MH4, MC2 Installation, Operation And Maintenance Manual

...
EMI AMERICASERIES
STRAIGHT COOL/HEAT PUMPS
Nominal Capacities:
9,000, 12,000, 15,000, 18,000,
24,000, 30,000, 36,000 Btuh
SCC/SHC SINGLE-ZONE
Enviromaster International LLC 5780 Success Dr. Rome, NY 13440 Phone: 1-800-228-9364 Fax: 1-800-232-9364 Email: emi@enviromaster.com
INSTALLATION, OPERATION AND MAINTENANCE MANUAL
MC4/MH4 MULTI-ZONE
MC2/MH2 DUAL-ZONE
An ISO 9001-2000 Certified Company
P/N# 240004514, Rev. 1.5 [05/05]
EMI AMERICASERIES CONDENSING UNIT CONDENSING UNITS
INSTALLATION, OPERATION AND MAINTENANCE MANUAL
P/N# 240004514, Rev. 1.5 [05/05]
Shipping Damage MUST be Reported to the Carrier IMMEDIATELY!!!
Examine the exterior. Remove cover and examine compressor and piping for signs of damage.
TABLE OF CONTENTS
To the Installer and Safety Instructions ........................ 2
Warnings, Controls and Components, ........................ 3
System Options, Installer Supplied Items ....................3
Low Ambient Option, Site Preparation ....................... 3
Electrical Wiring ..........................................................3
Refrigerant Piping, P-Trap Installation ........................
Refrigerant Processing, General Recom. ....................4
Complete Piping Connections, Starting the Unit .......... 4
Operation and Maintenance, Specific Changes .......... 5
Field Charging .............................................................. 6
SCC/SHC Single-Zone Installation ..........................7-9
MC/MH4 Multi-Zone Installation ............................ 10-11
MC/MH2 Multi-Zone Installation ............................12-13
Test Unit Performance Data Sheet ............................ 14
Warranty .................................................................... 15
This manual is intended as an aid to a qualified service personnel for proper installation, operation, and maintenance of these EMI AmericaSeries high efficiency condensing units. Read the instructions thoroughly and carefully before attempting installation or operation. Failure to follow these instructions may result in improper installation, operation, service, or maintenance, possibly resulting in fire, electrical shock, property damage, personal injury, or death.
4
TO THE INSTALLER
(1) Retain this manual and warranty for future reference.
(2) Before leaving the premises, review this manual to be sure
the unit has been installed correctly and run the unit for one complete cycle to make sure it functions properly.
To obtain technical service or warranty assistance during or after the installation of an EMI unit, check our website @ www.enviromaster.com or call your installing contractor or distributor. Our technical service department may be contacted at 1-800-228-9364.
When calling for assistance, please have the following information ready:
• Model Number_________________________
• Serial Number_________________________
• Date of installation______________________
SAFETY INSTRUCTIONS
DANGER
!
Tampering with the EMI AmericaSeries condensing unit is dangerous and may result in serious injury or death. Tampering voids all warranties. Do not attempt to modify or change this unit in any way.
!
Recognize this symbol as an indication
!
of important safety information
Made in Rome, New York, USA
!
• Read all instructions before using the EMI AmericaSeries high efficiency condensing unit. Install or locate this unit only in accordance with these instructions. Use this unit only for its intended use as described in this manual.
• Check the rating plate on the EMI AmericaSeries con densing unit before installation to make certain the voltage shown is the same as the electric supply to the unit.
• The EMI AmericaSeries condensing unit must be con nected only to a properly grounded electrical supply. Do not fail to properly ground this unit.
• Turn off the electrical supply before servicing the EMI AmericaSeries condensing unit.
• Do not use the EMI AmericaSeries condensing unit if it has damaged wiring, is not working properly, or has been damaged or dropped.
[Save These Instructions]
2
E-mail: emi@enviromaster.com
-
-
EMI AMERICASERIES CONDENSING UNIT - COMMON SECTION
CONTROLS AND COMPONENTS
(FACTORY INSTALLED OR SUPPLIED)
• Compressor and Fan Motor Contactor
• Capacitor
• Loss of Charge Switch (09 - 15 only)
• Defrost Control Board and Sensor (SHC only)
• Low Voltage Connections
• Large Capacity Suction Accumulator (09 - 15 only)
• High Pressure Control (SCC 18 - 36 and all Heat Pumps)
• Solid Core Filter Drier (09 - 15 only)
• Crankcase Heater (09-15K Heat Pump)
SYSTEM OPTIONS
• Low Ambient Option (Specify this option if system will oper­ate in cooling mode at outside temperatures below 60º F down to 0o F)
• Sea Coast Style Coated Coils
• 115
V (09-12 only)
• 265V (all models)
• Hard Start - Straight Cool only (standard on Heat Pumps)
INSTALLER SUPPLIED ITEMS
• Power wiring
• Low Volt wiring - 18 AWG minimum
• Secure mounting pad or foundation
• Refrigerant piping (if not supplied)
• Disconnect switch
Heat pump units produce condensate in the heat pump mode. Water will drain from the unit at the base. Place the unit so as not to create a hazard for pedestrians.
SITE PREPARATION
Place the unit on a flat concrete surface or pad if on the ground. Roof mounting should use a build up platform. Piping is through the wall or roof directly to the unit. In areas of heavy snowfall,
condensers should be set above the level of maximum an ticipated snowfall (12" is usually adequate).
ELECTRICAL WIRING
DANGER
!
The EMI AmericaSeries condensing unit must:
• Be connected to a properly grounded electrical supply with the proper voltage as stated on the rating plate.
• Have proper over current protection (i.e. time­delay fuse/HACR-Breaker) as listed on the Rating Plate.
Failure to follow these instructions can result in a fire, explosion, or electrical shock causing property damage, personal injury, or death.
!
-
LOW AMBIENT OPTION
MUST BE SPECIFIED IF: The system will be asked to cool at
outdoor temperatures below 60º F, this may cause damage to the compressor and coil, and could result in freezing that may void the warranty. We accomplish the low-ambient operation on our condensers by cycling the condenser fan. When in low-ambient operation the system high side pressure will cycle (fairly rapidly) between 275 psi and 210 psi. This will in turn maintain a constant low side pressure and keep the air handler from frosting-up.
NOTE: If this option is not specified and system runs under low-ambient conditions and experiences any failures (com­pressor, motor, etc.), warranty on these components may not be honored.
ITEMS FOR CONSIDERATION
• Locate the unit as close to the indoor section as possible. Maximum length allowed is 100'.
• Avoid high traffic areas and prevailing wind locations.
• Surface must be level.
• Mount unit above typical snow levels.
Ensure free flow of air through the unit. Air must not recirculate from discharge to intake. Air is drawn through the coil with side, or top discharged through the fan grille. A minimum 48" clear
ance is necessary for the condenser discharge. Intake (coil side) clearance is 12" minimum. Consider how power will be
run to the unit from the power source. Refrigerant piping must be a direct line to the indoor unit.
DANGER
!
Do not use the EMI AmericaSeries condensing unit with any electrical supply voltage other than the one listed on the rating plate.
Check the rating plate on the unit for the correct voltage rating. Failure to use the correct voltage may result in death, serious bodily injury or property damage. If you have any questions or doubts, consult the factory before installing this unit.
Note: Refer to the units' wiring diagram for all wiring.
All electrical wiring must be run according to NEC and local codes. Refer to the unit rating plate for voltage, ampacity and fuse size requirements. Use only HACR type breakers. Select the size wire according to the ampacity rating. Power should be run to a weather proof disconnect box usually within 3 feet of the unit. From the disconnect box, run the power through the 7/8" hole and into the electrical box and anchor with a strain relief fitting. Run wires to the high wire to ground lug.
Check wiring diagrams for the required number of low voltage
-
wires to be run between indoor and outdoor sections. Connect
Volt wiring matching color to color. Refer to the wiring
the 24 diagram inside the unit for more details.
should be at least 18 AWG.
Volt L1 and L2 connections. Also run green
!
Low Volt interconnect
High Efficiency Condensing Units
3
www.enviromaster.com
EMI AMERICASERIES CONDENSING UNIT - COMMON SECTION
REFRIGERANT PIPING
The standard system will support refrigerant runs to the inside unit of 100' equivalent feet with a 35' rise included.
Units are furnished with sweat connections and are equipped with service valves and schrader fittings for charging and taking pressure readings. The following precautions should be made:
• Be certain no burrs remain on the fittings.
• Use only clean refrigeration tubing.
• Use tube benders to guard against kinking.
• Avoid piping on wet and rainy days and insulate suction line. Be certain that plastic end caps remain in place when insert­ing through wall openings. Isolate tubing from transmitting vibration to the building or unit and avoid contact with sharp edges. Refrigeration valves should be wrapped with a wet
rag "heat sink" to protect valves while brazing.
NOTE: It is recommended that a filter dryer be installed in
liquid line, at the air handler.
P-TRAP INSTALLATION
• A P-trap is recommended when the suction riser is equal to or greater than 20 feet in height.
• When the evaporator is installed above the compressor, the P-trap will prevent the flow of liquid back to the compressor in the off cycle.
• The placement of the P-trap should be at the halfway mark of the suction riser. For example if the suction riser is 30 feet tall then a P-trap is recommended at the 15 foot mark of the suction riser (see Figure 1).
• A P-trap may be fabricated using (2) street elbows and (1) regular elbow. A prefabricated trap may be purchased from a Wholesaler or Distributor however the trap should be shallow as the (3) elbow configuration. Each elbow is approximately 5 equivalent feet. One P-trap is equal to approximately 15 equivalent feet.
• Whether the outdoor unit is above or below the indoor unit a P-trap is recommended if the suction riser is 20 feet or higher.
Figure 1
NOTE: Avoid excessive oil buildup. The P-trap should have a shallow depth and a short horizontal section.
• P-traps are not required at the foot of the hot gas risers due to increased oil flow at higher temperatures.
REFRIGERANT PROCESSING
WARNING!! It is illegal to discharge refrigerant into the atmosphere after July 1, 1992. Use proper reclaiming methods & equipment when installing or servicing this unit.
The unit is delivered with precharged refrigerant for the condenser coil and the evaporator. Charging of the field installed piping is required. Refer to the refrigerant charge table for the proper amount to be added for the applications interconnect pipping. Unit service valves are solid brass.
IMPORTANT: All systems require field charge adjustments. Refer to the attached "Charge Adjustment Table" for proper weight charge and to the supplied "Operational Charts" for proper system pressures and temperature at different outdoor conditions. Superheat and subcooling method should be used for final system charge (see page 6).
When charging and checking pressures/temperatures on system supplied with Low Ambient Option, the fan cycle switch should be jumped out of the circuit temporarily to obtain accurate data.
COMPLETE PIPING CONNECTIONS
Pressure test all field installed piping with nitrogen. Using a suit­able vacuum pump, evacuate the tubing and indoor unit to 300 microns, with service values remaining front seated (closed).
Before releasing the refrigerant from the condenser, be sure the manifold gauge set is closed so as not to lose vacuum when shutting down the pump.
Release refrigerant from the condensing unit by back seating the service value. Allen wrenches are used to open the valve. Replace valve caps. Be Careful to not back seat the valves past the snap flanges that hold the valve core in place.
Made in Rome, New York, USA
4
E-mail: emi@enviromaster.com
EMI AMERICASERIES CONDENSING UNIT - COMMON SECTION
STARTING THE UNIT
• Before starting the unit in cool weather, power the system 24 hours before attempting to start if a crankcase heater is installed.
• Do a final system check using the superheat/subcooling method. Record results on Test Unit Data Sheet.
• Remove gauge set. Mount all access panels and make sure they are properly secured.
• Make final visual inspection and repair any deficiencies.
NOTE: A hard start kit may be required for units in low volt- age/frequent cycle applications.
OPERATION AND MAINTENANCE
The EMI AmericaSeries outdoor section is the compressor bearing unit of the system. It operates at the command of the indoor sec tion or room thermostat. Therefore, the operation will be described in the manual pertaining to the indoor section.
EMI units are designed and constructed for reliability and long life with minimal maintenance. You can assure peak operating efficiency by regularly inspecting for free air passage into and through the coil. If debris collect on the air coil, it should be cleaned by "back-flushing" with a spray of water or vacuuming. OFF POWER SUPPLY FIRST. Outdoor units may be cleaned or waxed if desired. Use a non-abrasive car wax.
TURN
SPECIFIC CHANGES
All EMI products are subject to ongoing development programs so design and specifications may change without notice. Please
consult the factory for more information.
GENERAL RECOMMENDATIONS
Do not charge the straight cool units on cold days unless weigh- ing in the charge. The heat pump systems may be charged in heat cycle at any temperature. These units uses a heat cycle
TXV and cannot be charged to superheat; use weight or subcooling method only.
Charging should be done with a dial-a-charge or weighed in with a scale.
-
NOTE: For more information, please visit our web-site
at www.enviromaster.com or call 1-800-228-9364.
See Field Charging on following page.
This unit is equipped with a permanently lubricated motor. Al though oiling is not necessary, adding a few drops through the oiling ports twice yearly will extend the life of the motor. Do not over oil.
Panels should remain on the unit at all times. Service should be performed by a QUALIFIED service agency only.
-
High Efficiency Condensing Units
5
www.enviromaster.com
Loading...
+ 11 hidden pages