EMI S1CG, S2HG, S1HG, S2CG Installation, Operation And Maintenance Manual

S1CG/S1HG Single-Zone
S2CG/S2HG Dual-Zone
Side-Discharge Ductless Split-System
Condensing Units for R410 Refrigerant
Capacities — Single-Zone Applications
S1CG or S1HG S1CG only
9,000 12,000 18,000 24,000 28,000 33,600 Btuh
Capacities — Dual-Zone Applications
S2CG or S2HG
9,000 12,000 Btuh
2.6 3.5 kW
Installation, Operation and
Maintenance Manual
Units
Units
ECR International LLC 2201 Dwyer Ave Utica, NY 13504 www.enviromaster.com
S1CG S1HG
S2CG S2HG
An ISO 9001-2000 Certified Company
P/N 240007754, Rev. C [3/19/2010]
S1CG/S1HG
Sing
G
nstallation, Operation and Maintenance Manual •
le-Zone,
S2CG/S2H
Dual-Zone
Contents
Contents . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 2
Verify unit before installing . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 4
Mounting the Unit . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 6
Electrical Wiring . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 8
Refrigerant Piping . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 11
Refrigerant Processing . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 13
Operation Charts . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 17
Starting the Unit . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 30
Operation and Maintenance. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 30
Single-zone and Dual-zone Condenser Sequence of Operation . . . . . . . . . . . . . . . . . . . . . . . . . . 31
Single-zone and Dual-zone Condenser Sequence of Operation,
Testing Defrost Operation Using Test Pins . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 32
Specifi cation and Dimensions. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 33
Test Unit Performance Data Sheet . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 38
EMI’s Product Line . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 40
NOTICE
Shipping Damage
Shipping damage MUST be reported to the carrier IMMEDIATELY. Examine the exterior. Remove cover and examine compressor and piping for signs of damage.
Inspect each component for damage. Concealed damage must be reported to the carrier within 15 days of the receipt of the shipment.
 e carrier must make proper notation on the delivery receipt of all damage identi ed and complete a carrier inspec­tion report.
 e purchaser must notify ECR Inter­national’s Customer Service Depart­ment of all damage and is responsible for  ling any necessary claims with the carrier.
Customer Service : (800) 228-9364
To the Installer
Retain this manual and warranty for future reference. Before leaving the prem­ises, review this manual to be sure the unit has been installed correctly and run the unit for one complete cycle to make sure it functions properly.
To obtain technical service or warranty assistance during or a er the installation of this unit, contact your local representa­tive. For a local representative listing, visit our web site:
www.enviromaster.com
For further assistance call:
1-800-228-9364
When calling for assistance, please have the following information ready:
Model Number _____________ Serial Number _____________ Date of installation ___________
 e EMI series high e ciency condensing unit is backed by EMI and ECR International and is tested and rated in accordance with AHRI Standard 210/240-2008 and UL-1995. Due to ongoing product development, product designs and speci cations may change without notice. Please contact the factory for more information.
Comfort where it counts 2 P/N 240007754, Rev. C [3/19/2010]
NOTICE
S1CG/S1HG
Sing
G
nstallation, Operation and Maintenance Manual •
le-Zone,
S2CG/S2H
Dual-Zone
Read Before Proceeding
Recognize this symbol as an indication of
important safety information.
Completely read all instructions
prior to assembling, installing, oper-
ating, or repairing this product.
WARNING
Inspect all parts for damage prior to installation and start-up.  e EMI series high e ciency condensing unit must be installed ONLY by quali ed installation personnel.
Tampering with this unit is danger-
. Tampering voids all warranties. DO
ous
a empt to modify or change this
NOT
DANGER
unit in any way.
Safety Instructions
 is manual is intended as an aid to quali­ ed service personnel for proper installa­tion, operation, and maintenance of the EMI series high efficiency condensing unit. Read these instructions thoroughly and carefully before a empting installa­tion or operation. Failure to follow these instructions may result in improper instal­lation, operation, service, or maintenance, possibly resulting in  re, electrical shock, property damage, personal injury, or death.
Read all instructions before using this unit. Install or locate this unit only in ac­cordance with these instructions. Use this unit only for its intended use as described in this manual.
DANGER
 e EMI series must:
Be connected to a properly grounded • electrical supply with the proper voltage as stated on the rating plate.
Have proper over current protection • (i.e. time-delay fuse/HACR Breaker) as listed on the rating plate.
Failure to follow these instructions can result in a  re, explosion, or electrical shock causing property damage, personal injury, or death.
P/N 240007754, Rev. C [3/19/2010] 3 Made in the USA
Check the rating plate on the unit before installation to make certain the voltage shown is the same as the electric supply to the unit.  e rating plate is located on the front panel only.
This unit must be connected only to a properly grounded electrical supply. Do not fail to properly ground this unit.
Turn o the electrical supply before servic­ing the unit.
Do not use the unit if it has damaged wir­ing, is not working properly, or has been damaged or dropped.
S1CG/S1HG
Sing
G
nstallation, Operation and Maintenance Manual •
le-Zone,
S2CG/S2H
Verify unit before installing
Dual-Zone
Product description
 e EMI Series S1CG/S1HG and S2CG/ S2HG condensing units are air-cooled, verti­cally-arranged side-discharge, high-e ciency units designed speci cally to meet or exceed a 13 SEER rating.
 e S1CG Models 09–36 and S1HG Models 09–24 condensing units will provide cooling and heating for a single air handler, as identi­ ed on page 34 and page 35 .
 e S2CG/S2HG 18,000 (99), 21,000 (92) and 24,000 (22) Btuh capacity condensing units will provide cooling and heating for two air handlers, as identi ed on page 36 .
The S1CG/S1HG and S2CG/S2HG are quiet units that can be recommended for both commercial and residential applications.
Features
Installation of the S1CG/S1HG and • S2CG/S2HG condensing units is sim­pli ed by a 24v control interconnection from the air handler.
Multiple units can be lined up in close • proximity to an exterior wall.
Service valves are recessed to reduce • tampering.
All 9,000-12,000 Btuh units are equipped • with a Duratec Performance Package that includes an oversized suction accumula­tor with surge ba es and enhanced oil management and a factory-installed solid core  lter drier.
A factory-installed crankcase heater is • standard on S1HG 09 &12 (thermostati­cally controlled) and S2HG models, and is available as optional equipment on other models.
Controls and components (Factory-installed or supplied)
Compressor and fan motor contactor• Run capacitor• Low voltage terminal connections• H.P.S. (High pressure switch) with
manual external reset Heat pump hard start• Cooling operation down to 32°F standard
on all units Models 09–12 only:
Large capacity suction accumulator – Solid-core  lter drier – Thermostatically-controlled crank-
case heater (heat pump only)
Thermostatically-controlled crankcase heater
This feature energizes the crankcase • heater only when needed, saving unnec­essary power usage and increasing overall system e ciency.
Comfort where it counts 4 P/N 240007754, Rev. C [3/19/2010]
S1CG/S1HG
Sing
G
nstallation, Operation and Maintenance Manual •
le-Zone,
S2CG/S2H
Verify unit before installing (continued)
Dual-Zone
System options
Corrosion-resistant coil options (sea • coast and harsh environment usage):
Copper  n/copper tube condenser – coil
Coated aluminum fin/copper tube – condenser coil
Low Ambient controls for cooling opera-• tion down to 0°F (standard equipment can operate down to 32°F)
Optional field-installed kit, when – speci ed, for cooling operation down to 0°F — kit includes control, louvers and wind baffle plus installation instructions
Low Ambient controls for operation • down to 0°F (consult factory for avail­ability)
Models 09–12 only:
115v (single-zone only — S1CG or – S1HG)
Field-installed thermostatically-con- – trolled crankcase heater for straight cool units (S1CG or S2CG) Recom­mended for operation below 60°F.
Installer-supplied items
Power wiring• Low Volt wiring (18 awg minimum)• Secure mounting pad or foundation• Refrigerant piping (if not purchased from
EMI) High Volt Disconnect• Refrigerant for charging interconnect pip-
ing (see charge table on page 15 )
NOTICE
Low Ambient controls are required
when the system is asked to cool at outdoor temperatures below 32°F, this may cause damage to the compressor and coil, and may void the warranty. A field-installed low-ambient kit allows operation down to 0°F.
This is accomplished by cycling the condenser fan on and off. This will, in turn, maintain a constant low-side pressure, providing a steady cooling e ect and keeping the air handler from frosting-up.
 e optional kits include louvers/wind baffle, crankcase heater, outdoor fan cycling switch, and installation instruc­tions.
P/N 240007754, Rev. C [3/19/2010] 5 Made in the USA
S1CG/S1HG
Sing
G
nstallation, Operation and Maintenance Manual •
le-Zone,
S2CG/S2H
Mounting the Unit
Dual-Zone
Before installing, consider:
Locate the unit as close to the indoor sec-• tion as possible. (see page 11 .)
S1CG/S2CG — If the unit is used for low • ambient cooling down to 32°F, S1CG/ S2CG require CCH.
Avoid high traffic areas and prevailing • wind locations.
Surface must be  at and level.• Mount unit above typical snow fall level.
This is particularly important for heat pump applications (S1HG/S2HG).
NOTICE
Ensure free  ow of air through the • unit.
Air must not recirculate from dis-• charge to intake — air is drawn through the coil and side discharged through the fan grille.
A minimum 48” clearance is neces-• sary for the condenser discharge.
Rear intake (coil side) clearance is • 12” minimum.
Consider how power will be run to • the unit from the power source.
Refrigerant piping should be a direct • line to the indoor unit.
In areas of heavy snowfall, condensers 2. should be set above the maximum antici­pated snow line (12" is usually adequate for most locations).
Unit Mounting Instructions
Model S1CG is shown for example in the following sequence.
 e side-discharge unit allows for permanent mounting through the feet. This is highly recommended due to the vertical design of the unit.
1. Figure 1, Page 7 : Bullet 1 — Loosen the screws on le
and right sides of the front panel. (Do not remove these screws.)
Bullet 2 — Remove the screws on the – front of the panel.
2. Figure 2, Page 7 :
Slide front panel forward to clear side screws and remove.
3. Figure 3, Page 7 :
Insert lag bolts through the holes in the bo om of the unit and tighten to secure.
4. Figure 4, Page 7 :
Insert lag bolts through the holes in the feet on the back of the unit and tighten to secure.
Site preparation
Place the unit on a  at concrete surface 1. or pad if on the ground. Roof mounting should use a built up platform to avoid intake of hot air from the roof.
Comfort where it counts 6 P/N 240007754, Rev. C [3/19/2010]
Replace the front panel, do not tighten 5. the side screws at this time.
S1CG/S1HG
Sing
G
A
A
B
C
DDE
S1CG
Shown
S1CG
Shown
nstallation, Operation and Maintenance Manual •
le-Zone,
S2CG/S2H
Mounting the Unit (continued)
Dual-Zone
Remove front panel screwsFigure 1
1 2
Bottom lag hole locationsFigure 3
C
A
Lag boltsA Filter drierB CompressorC AccumulatorD CapacitorE
S1CG
Shown
B
E
A
Lag holes in feetFigure 4
S1CG
Shown
Remove front panelFigure 2
P/N 240007754, Rev. C [3/19/2010] 7 Made in the USA
S1CG/S1HG
Sing
G
Rating
plate
nstallation, Operation and Maintenance Manual •
le-Zone,
S2CG/S2H
Electrical Wiring
Dual-Zone
NOTICE
All electrical wiring must be run accord­ing to NEC and local codes.
1. Figure 5, Page 8 — Refer to the unit rat­ing plate for voltage, minimum circuit ampacity and over current protection requirements.
Use only HACR type breakers or time 2. delay fuses. Select the wire size according to the ampacity rating.
To access electrical connections and wir-3. ing diagram:
a. Figure 6, Page 8 — Remove the screws on the side panel that covers the electrical box.  e box is adjacent to the back panel and denoted with electrical connections.
 e screws adjacent to the front panel b. should already be loose (don’t remove them).
Slide the side panel out to access the c. high/low electrical connections and wire diagram.
d. Figure 7, Page 9 — Add water-tight strain relief   ing to the high volt side before wiring, a split grommet   ing has been factory installed in the low volt side.
Rating plate locationFigure 5
Rating
plate
Remove side panel screwsFigure 6
Power should be run to a weather proof 4. disconnect box usually within 3 feet of the unit.
Comfort where it counts 8 P/N 240007754, Rev. C [3/19/2010]
S1CG/S1HG
Sing
G
S1CG
Shown
High volt
Plastic edge guards
Low volt
S1CG
Shown
S1CG
Shown
nstallation, Operation and Maintenance Manual •
le-Zone,
Electrical Wiring (continued)
S2CG/S2H
Dual-Zone
5. Figure 8, Page 9 — From the disconnect box, run the power through the 7/8” hole on the side of the unit and into the electrical box. Anchor with the strain relief   ing.
Run wires to the high volt pigtail in the 6. control box and a ach L1 and L2 con­nections. Also run green wire to ground wire.
Check wiring diagram for the required 7. number of low voltage wires to be run between indoor and outdoor sections.
8. Figure 9, Page 9 — Connect the 24 volt wiring matching color to color. Refer to the wiring diagram on the inside panel of the condenser, and also refer to the wir­ing diagram on the indoor unit. Low volt interconnect should be at least 18 awg.
Power entrancesFigure 7
Plastic edge guards
High voltage connectionsFigure 8
S1CG
Shown
Low volt
High volt
S1CG
Shown
See 9. Figure 10, Page 10 and Figure 11, Page 10 for completed wiring of S1CG and S2CG examples.
To replace side panel slide the slotted 10. holes of the panel onto the loosened screws of the front panel so that the edge of the front panel covers the edge of the side panel.
Fasten all remaining loose screws.11.
Low voltage connectionsFigure 9
S1CG
Shown
Continued on next page
P/N 240007754, Rev. C [3/19/2010] 9 Made in the USA
S1CG/S1HG
Sing
G
S1CG
Shown
nstallation, Operation and Maintenance Manual •
le-Zone,
Electrical Wiring (continued)
S2CG/S2H
Dual-Zone
Completed wiring, S1CGFigure 10
S1CG
Shown
Completed wiring, S2CGFigure 11
Replacing side panelFigure 12
Fasten loose screwsFigure 13
Comfort where it counts 10 P/N 240007754, Rev. C [3/19/2010]
S1CG/S1HG
Sing
G
nstallation, Operation and Maintenance Manual •
le-Zone,
S2CG/S2H
Refrigerant Piping
Dual-Zone
Tubing specifi cations
 e system will support refrigerant runs to the inside unit as listed in
Table 1, Page 11 .
 e units are furnished with sweat connec­tions and are equipped with refrigerant valves and Schrader   ings for charging and taking pressure readings.
CAUTION
It is recommended that a fi lter drier be installed in the liquid line, at the indoor unit on models without a factory-in­stalled  lter drier (i.e. 18K and larger).
S1CG/S2CG tubing specifi ca-Table 1 tions (see Table 14, Page 11 )
P-trap installation
A P-trap is recommended when the • suction riser is equal to or greater than show in Figure 14, Page 11 and Table 1, Page 11.
When the condenser is installed above the • air handler, the P-trap will help the return of oil back to the compressor.
P-trap placement (see Figure 14 Table 1, Page 11 for dimensions H & P)
Model Max.
Length
Equivalent
Feet
09
12 1/4" 1/2"
18
24 3/8" 3/4"
30 3/8" 3/4"
36 3/8" 3/4"
50’
(15 m)
100’
(30 m)
Max.
Lift
“H” “P” O.D. O.D.
20’
(6 m)
35’
(11 m)
Max.
Trap
Height
15’
(5 m)
20’
(6 m)
Liquid
Suction
Line
1/4" 1/2"
3/8" 5/8"
Line
A P-trap may be fabricated using (2) street • elbows and (2) regular elbow.
A prefabricated trap may be purchased • from a wholesaler or distributor however the trap should be shallow as with the (3) elbow con guration.
Each elbow is approximately 2 equivalent • feet.
One P-trap is equal to approximately • 12 equivalent feet.
P-traps are not required at the foot of the • hot gas risers due to increased oil  ow at higher temperatures.
P/N 240007754, Rev. C [3/19/2010] 11 Made in the USA
S1CG/S1HG
Sing
G
S2CG
S1CG Shown
S1CG Shown
S2CG Shown
nstallation, Operation and Maintenance Manual •
le-Zone,
S2CG/S2H
Refrigerant Piping (continued)
Dual-Zone
CAUTION
Avoid piping on wet and rainy days.• Use only clean, refrigeration-grade
copper tubing. Use tubing benders to guard against
kinking. Be certain no burrs remain on the
  ings. Cap ends of lines until ready for con-
nections. Be certain that plastic end caps remain
in place when inserting through wall openings.
Insulate the suction line.• Isolate tubing from transmi ing vibra-
tion to the building or unit and avoid contact with sharp edges.
Wrap refrigeration valves with a wet • rag “heat sink” to protect valves while brazing. (See Figure 16, Page 12 .)
Clean ends of tubingFigure 15
Wet rag “heat shield over valvesFigure 16
S1CG Shown
S2CG
Refrigerant piping
Clean the ends of tubing and insert into 1.   ings ( Figure 15 ).
Protect valves by wrapping with a wet rag 2. “heat sink” before brazing ( Figure 16 ).
Use a shield to protect the paint as shown 3. in Figure 17 . ( e shield can be made from scrap metal.)
Braze tubing into   ings.4. Install all panels removed to this point. 5.
Panels are required for proper air  ow.
Make a shield to protect paintFigure 17
S1CG Shown
S2CG Shown
Comfort where it counts 12 P/N 240007754, Rev. C [3/19/2010]
Loading...
+ 28 hidden pages