EMI S1HA4000, S1HA9000, S1CA3000, S1CA2000, S1HA2000 Installation, Operation And Maintenance Manual

...
CACA/CAHA & CACB/CAHB CASSETTE
duCTlESS SpliT SySTEm Air HAndlErS
P/N 240006022 Rev. 1.5 [1/08]
Enviromaster International LLC 5780 Success Dr. Rome, NY 13440 www.enviromaster.com
An ISO 9001-2000 Certied Company
CAHB12
Model Shown
straight cool
Nominal Circuit Capacities:
30,000 - 36,000 Btuh
heat pUmp
Nominal Circuit Capacities:
9,000 - 12,000 - 18,000 - 24,000 Btuh
www.enviromaster.com
3
Cassette Air Handler
TO THE INSTALLER
INSTALLATION, OpERATION ANd mAINTENANCE mANUAL
CASSETTE HIgH EffICIENCy AIR HANdLERS
Shipping Damage MUST be Reported to the Carrier IMMEDIATELY!!! Exam­ine the exterior.
This manual is intended as an aid to a qualified service personnel for proper installation, operation, and maintenance of EMI AmericaSeries high efciency air handlers. Carefully read these instructions before attempting installation or operation. Failure to follow these instructions may result in improper installation, operation, service, or maintenance, possibly resulting in re, electrical shock, property damage, personal injury, or death.
SAfETy INSTRUCTIONS
This unit has been designed and manu­factured to meet international safety standards.
Read all instructions before installing
or using the EMI AmericaSeries high
efciency air handlers. Locate and
install this unit only in accordance
with these instructions. Use this unit
only for its intended purpose as de­scribed in this manual. Care must be
taken to obtain the best results.
Check the rating plate on the EMI
AmericaSeries air handlers before
installation to make certain the
voltage shown is the same as the
electric supply to the unit.
The EMI AmericaSeries air handlers
must be connected only to a properly grounded electrical supply. Do not fail to properly ground this unit.
Turn off the electrical supply before
servicing the EMI AmericaSeries
air handlers. Ensure that there is no
power to any part of the equipment and both the indoor and outdoor units are switched off.
Do not use the EMI AmericaSeries
air handlers if it has damaged wiring,
is not working properly, or has been damaged or dropped.
Follow all safety instructions in this
manual and on any tags or labels
on the unit.
[Save These instructions]
(1) Retain this manual and warranty for future
reference.
(2) Before leaving the premises, review this
manual to be sure the unit has been
installed correctly and run the unit for
one complete cycle to make sure it func-
tions properly.
To obtain technical service or warranty assistance during or after the installation
of this unit, check our web site @ www. enviromaster.com or call your installing
contractor or distributor. Our technical service department may be contacted at
1-800-228-9364.
When calling for assistance, please have the following information ready:
• Model Number___________________
• Serial Number___________________
• Date of installation________________
Ensure there are no power feeds to the
unit such as re alarm circuits, BMS cir-
cuits, etc.
EMI AmericaSeries Units are
Approved for R-22 Refrigerant ONLY.
! !
WARNING
www.enviromaster.com
Cassette Air Handler
4
STANdARd fEATURES
Continued
pROdUCT dESCRIpTION
The EMI AmericaSeries Cassette Air
handlers are available in three cabinet sizes with four output capacities from 9,000 ­24,000 Btuh, and two cooling only capacities from 30,000 - 36,000 Btuh. Key features include a condensate pump with safety switch and a 36” (0.9 m) lift*, electric heat is a
factory installed option ONLY (there are no
,
fresh air inlet and branch duct knockouts, and motorized air vanes (Cassette 24 & 36
only). The Cassette air handler accepts a
24 volt thermostat control (thermostat not
included). Designed for low noise levels, easy installation and maintenance and a
slim line fascia, all ensure minimum intrusion
into the conditioned environment. Due to ongoing product development, all designs and specications are subject
to change without notice.
* Condensate pump lift measured from
the base or bottom of the unit.
These American made Cassette Air
Handlers produce system SEER’s meeting or exceeding 13, when matched with EMI’s S1CA/S1HA single zone, S2CA/S2HA dual zone side discharge condensing units,
T2CA/T2HA, T3CA/T3HA, or T4CA/T4HA
top discharge multi-zone condensing units. Refer to specications contained in this document.
All EMI Air Handlers are backed by
Enviromaster International LLC and are tested, rated, and certied in accordance with ARI standards 210/240 and UL 1995.
STANdARd fEATURES
Materials of Construction - Galvanized
steel cabinet with re-resistant thermal and acoustic foam insulation and light grey high-impact ABS fascia, and an expanded polystyrene drain pan with a tough re retardant thermoplastic liner.
Air Systems:
• Fans are backward curved impeller centrifugal design; dynamically and
statically balanced; and mounted on
integral mounting rails.
• Single Fan models, Cassette 12 & 24, are designed with re retardant plastic or aluminum impellers.
• Twin Fan models, Cassette 36, are designed with fire retardant plastic impellers.
• Motors are multispeed, enclosed type with thermal protection and sealed
lifetime bearings.
• Permanent, washable lter (user ac­cessible).
• Branch duct knockouts on three sides for remote discharge locations (using no more than two non-adjacent sides).
• Fresh air intake capability on three sides of cabinet (only two on the Cassette 12’s).
• Four plastic air vanes; motor driven with auto sweep or xed position stop setting
on the Cassette 24 and 36 models (Cas-
sette 12’s are equipped with manually adjusted air vanes).
Coil - Coil is seamless, copper tubing,
arranged in staggered conguration, with enhanced aluminum ns, tested to 600 psig. The tubes are mechanically expanded for secure bonding to n shoulder.
Refrigeration Circuit - Units are equipped
with a serviceable xed orice expansion de-
vice and use R22 refrigerant only.
Controls and Components (factory
installed or supplied):
• Connections for 24V remote wall ther­mostat.
• Custom control board featuring program-
mability, conguration, and multiple modes of operation. (CACB/CAHB only)
• Controls also feature anti-short cycle timer, post purge fan relay, and an on board 30 amp electric heat relay.
• Condensate Pump with 36” (0.9 m) lift
measured from base of unit.
• 24V Transformer.
www.enviromaster.com
5
Cassette Air Handler
STANdARd fEATURES
Continued
CASSETTE CONTROLS ANd COmpONENTS
Continued
Fresh air connection: fresh air may
be introduced to the unit by the addition
of ducts connected to the fresh air knock­outs on the Cassette case. Recommend-
ed maximum length 10’ (3m) of 4” (0.1m)
diameter duct. The fresh air volume is ap-
proximately 7-10% of the unit’s published maximum air ow (if more than 10% make up air is needed, a fresh air booster fan is
required). Refer to Performance Data sec-
tion of this manual for further information. The Cassette is best installed in new con-
struction or existing construction with a sus-
pended or false ceiling with enough clear-
ance to accommodate concealing the piping and electrical connections to the unit.
pREpARATION fOR INSTALLATION
U The Cassette fascia and
main chassis are packaged together for increased protection.
• Remove the banding straps and lift the cardboard lid.
• Fascia is packed in bubble wrap and on top of the chassis (fascia is not attached to the chassis for shipping).
Cardboard template is between the chassis and the fascia (DO NOT throw
template away with packaging!).
• Lift the fascia and template from the box and set aside.
• Remove the Cassette chassis from the box utilizing the four corner brackets
for lifting. DO NOT use the drain or re­frigerant connections for lifting.
• In order to protect the fascia from dirt and damage, it should be returned to the box until it is ready to be installed.
  When branch ducting is to be used, two polystyrene pieces for blanking off fascia openings are Included with the fascia packing. Up to two non­adjacent sides may be blanked off.
DO NOT throw the two polystyrene blanking off pieces out with packaging!
Electromechanical Operation (Stan-
 An optional thermostat can be ob­tained through EMI or your local distributor.
NOTE: make sure the thermostat is suitable for unit operation (i.e., cooling only, cooling/electric heat, heat pump.)
Filters: Metal framed lters are tted. These
are reusable and may be vacuum cleaned.
Condensate pump: A condensate
pump is designed to carry water out of the unit. The pump is xed to a mounting bracket which can be withdrawn from the side of the chassis and incorporates an inspection hole to allow a visual check of the pump during operation. A oat switch is tted to stop the cooling action (shut off the compressor) should the pump become blocked or fail.
IMpORTANT: Total lift for this pump is 36”
(0.9 m) or less.
Air vanes: Air outlet vanes are manual-
ly adjustable on the Cassette 12’s or driv-
en by an electric motor on the Cassette 24’s and 36’s. Where tted, the motorized air vanes can be set to auto sweep or can be stopped in a xed position.
Heating: The Cassette may be tted with
electric heaters which are equipped with
over-temperature limit switches. Consult fac-
tory for available models with electric heat.
System Options:
• Infrared Hand Held Controller (CACB/CAHB only)
• 24V remote wall thermostat
• Electric Heat (@ 230V)
1.5 kW (Cassette 12’s) 3 kW (Cassette 24’s) 5 kW (Cassette 36’s)
www.enviromaster.com
Cassette Air Handler
6
The Cassette 12 unit has is one grille and one
lter.
BLANkINg Off
Cassette 24 units have two hinged grills that
open in the middle and two lters.
hinge
The fascia discharge slot(s) will need
blanking off when ducts are used to chan-
nel the conditioned air to other areas. The
two polystyrene blanking off strips (pro-
vided) will need to be positioned in the fascia discharge slots to direct the air to the ducts.
blanking-off
Pieces
Cassette 12 Unit Shown
The Cassette 36 units have three hinged grills
and three lters.
Cassette 24 Unit
Shown
Cassette 36 Unit Not Shown
If the fascia discharge slot needs blanking off:
1. Remove the inlet grille(s) and lter(s).
2. Once the grille(s) and lter(s) are removed
turn the fascia over so the polystyrene in-
sulation is exposed.
3. Take one of the polystyrene blanking off
pieces and push it into the recess in the polystyrene fascia insulation.
NOTE: Up to two non-adjacent sides can be blanked off.
www.enviromaster.com
7
Cassette Air Handler
Important - Replace the existing
piston (before installing the unit) with
the piston supplied in the Kit bag: when a
Cassette 24 air handler is matched with a
T2CA/
T2hA4400, T2CA/T2hA2400, T2CA/T2hA8400, T3CA/
T3hA9240, T3CA/T3hA2240, or T3CA/T3hA9940
condenser which
has a 24,000 Btuh compressor (“4” in the capacity decoding eld) the
piston will need replacement only on the 24,000 btuh zone. *
EMi air handlers units contain the appropriate piston for the model. Refer to this docu-
ment to determine if a change is required based on the condenser rating. if the match is
not listed below no piston change is required. (See chart)
CASSETTE pREpARATION ANd pOSITIONINg
pOSITIONINg
The Cassette installation position should be selected with the following points in mind:
1. Pipe work, electrical connections, con-
trol box and condensate pump access panels should be readily accessible.
Refer to the “Cassette Dimensions”
section in the back of this manual for dimensional drawings.
2. The unit should be positioned at least
5 ft. (1.5m) from a wall or similar ob­struction. Position the unit as close to
the center of the room as possible to insure air is distributed evenly.
3. Position the unit so that the discharge air does not blow directly on the thermostat.
4. The unit should not be positioned direct-
ly above any obstructions.
5. The condensate drain should have suf-
cient fall 1” per 10’ (8mm/m) in any horizontal run between Cassette and drain. Maximum condensate pump lift is 36” (0.9m).
6. There should be a minimum 1” (25.4mm) clearance above the depth of the Cassette and the false ceiling for proper installation, shown below
Figure #1 (see the “Cassette Dimen­sions” section in the back of this IOM
for cabinet sizing):
Dimension A + 1” = minimum space above the false ceiling for installation
A
A +1”
Figure #1
model #
Air handlers
Condenser Btuh
factory Installed
Piston-Orice Size
field Changeover
Piston-Orice Size
CAHA / CAHB24
T2CA/T2HA4400 T2CA/T2HA2400 T2CA/T2HA8400
.059” .063”
CAHA / CAHB24
T3CA/T3HA9240 T3CA/T3HA2240 T3CA/T4HA9940
.059” .063”
* “4” in the capacity decoding eld = 24,000 Btuh
Air handlers
pISTON/ORIfICE INSTALLATION INSTRUCTION
Cabinet dimension A
Cassette 12 11.84” (0.3 m) min. Cassette 24 12.55” (0.32 m) min. Cassette 36 14.51” (0.37 m) min.
www.enviromaster.com
Cassette Air Handler
8
CASSETTE CHASSIS pOSITIONINg ANd INSTALLATION
Ceiling opening:
In existing construction, remove enough
ceiling panels to provide clearance space for mounting unit to ceiling joists.
• Before beginning the installation, inspect
the unit location, test the strength of the
ceiling joists to insure they will support
the weight of the unit.
• Determine mounting method:
- On wooden beams use threaded rods, washers, and nuts to suspend support brackets.
- With metal structures, secure threaded
rods on an existing angle or install a new support angle.
- On newly built concrete slabs secure threaded rods with inserts and em-
bedded bolts.
- For previously built concrete slabs install
hanging bolts with an expansion anchor.
A template for ceiling cut-out and rod posi-
tions can be found with the Cassette unit.
- Follow local building codes for required
safety cables, braces, etc.
An opening in the false ceiling will have to be cut to the following sizes:
NOTE: Make sure the ceiling grid is sup- ported separately from the Cassette. The ceiling must not be supported by any part of the Cassette unit, fascia or any associated wiring or pipe work.
A
A
B
Cabinet A B
Cassette 12
19.50”
(495mm)
22.87”
(581mm)
Cassette 24
29.19”
(740mm)
30.80”
(782mm)
Cassette 36
29.19”
(740mm)
43.06”
(1094mm)
Figure #2
mOUNTINg THE CASSETTE
CEILINg AIR HANdLERS
ELECTROmECHANICAL
THERmOSTAT
An optional thermostat can be obtained through EMI or your local distributor. In
addition to positioning the Cassette cor-
rectly, it is very important to locate the wall
mounted thermostat in the optimum posi-
tion to ensure good temperature control. The installation should be selected with the following points in mind:
1. Position the thermostat approximately 5 ft. (1.5m) above oor level.
2. Avoid external walls and drafts from windows and doors.
3. Avoid positioning near shelves and cur-
tains as these restrict air movement.
4. Avoid heat sources (direct sunlight, heaters, dimmer switches, etc.)
5. Seal wiring holes in the wall behind the thermostat to avoid drafts.
Cabinet Opening Size
Cassette 12
23¼” x 23¼” (591 x 591mm)
Cassette 24
33⅞” x 33⅞” (860 x 860mm)
Cassette 36
46” x 33⅞” (1168 x 860mm)
(51mm x 45°)
2.000 x 45° Typ
Rod
Positions
1.500 Typ
Rod
Positions
(38mm Typ)
www.enviromaster.com
9
Cassette Air Handler
1. Use the template (provided) to cut the
ceiling opening and determining the rod positions.
2. Install hanger bolts using 3/8” (10mm)
all thread rod at the centers shown in
Figure #2.
3. Prepare the installation guides by fold-
ing the metal bracket by hand along the
perforations, see Figure #3.
INNER CASE INSULATIoN
CASSETTE CASE
Figure #4
5. Secure unit in position with locknuts and washers on either side of the Cassette bracket.
6. Ensure threaded rod does not protrude
more than 2” (51mm) below the mount-
ing bracket.
4. Lift the Cassette onto the hanging rods. Level at the correct distance from the ceiling with the aid of the installation
guides as shown Figure #4.
CASSETTE CHASSIS pOSITIONINg ANd INSTALLATION
Fold
bracket along
perforations
Figure #3
mAx
2”
(51mm)
NOTE: If the ceiling is not level or even, it is important that the Cassette is installed level to ensure correct pump operation and to maintain fan clearances. Place a carpenter’s level on the unit. A maximum slope of 1/8” (3mm) over the length of the chassis toward the condensate drain is allowed. Any slight discrepancy be­tween the Cassette and ceiling will be taken up by the fascia foam seal.
www.enviromaster.com
Cassette Air Handler
10
fresh Air Knockout
branch Duct Knockout
Cassette 12
CASSETTE 24 & 36
NOTES: The number of knock-outs varies de-
pending on unit size.
• Branch duct knock-outs are 5¼” (133mm) round
fresh air knock-outs are
1¼” x 2½” (32 x 64mm)
rectangular on
Cassette 12
and 3” (76mm) square
on
Cassette 24 & 36.
Recommendation: no more than 10’ (3m) of branch duct or fresh air duct should be installed.
CONdENSATE pIpINg ANd dUCT CONNECTIONS
The unit can now be piped up in ac-
cordance with good refrigeration and/or plumbing practices.
The Cassette is supplied with a 1/2”
I.D. exible PVC hose for connection to copper or plastic drain pipework. When installing the Cassette the following points should be noted:
1. Maximum pump lift is 36” (0.9m).
2. The highest point in the condensate pipework should be as close to the unit
as possible. This prevents a large vol-
ume of water draining back into the unit when it is switched off.
NOTE: There is a check valve at the pump discharge to prevent water from draining back into the unit. This piping technique will mini­mize any issues should the check valve be­come stuck open from airborne debris.
Correct
Incorrect
Condensate Drain Connection
3. Condensate pipe-work should slope downwards in the direction of water ow with a minimum gradient of 1” per 10’
(8mm/1m). There must not be any up-
hill gradients other than in the rst 36” (0.9m) of pipe-work from the Cassette.
4. When multiple Cassettes are connected to a common condensate drain, ensure the drain is large enough to handle the volume of condensate from several Cassettes. It is also recommended to have an air vent in the condensate pipe work to prevent any air locks.
Duct collars: Branch duct and fresh air
duct collars can be attached to the Cas-
sette chassis by following the steps below:
1. Locating the knock-out holes.
NOTE: A drain line vent may be required to prevent siphoning of water from the drain pan and associated noise.
www.enviromaster.com
11
Cassette Air Handler
pIpINg dO’S ANd dON’TS
• Avoid piping on a rainy day.
• Use refrigerant grade copper tubing.
• Use a tubing bender and avoid unneces-
sary bending.
• Cap ends of lines until ready for nal
connections.
Once the unit is mounted and level the Cassette piping connections can be made.
Any change in the diameter of the tubing MUST be made at the indoor connection. Line-set diam-
eter is determined by the condenser valve size.
Use of a larger line can harm
the compressor!
When matching a the Cassette 24 with an
18,000 Btuh condenser, the interconnecting suction line needs to be 5/8” O.D. to match the condenser service valve connection. Therefore the 3/4” O.D. suction connection of the Cassette 24 unit needs to be reduced to 5/8” at the Cassette 24 unit connection to match the 5/8” line of the condenser.
5/8” bushing goes on suction line
(Only when matched to an 18,000 btuh condenser)
NOTE: Refrigerant and condensate pipes should be insulated right up to the Cassette chassis.
The Cassette is equipped with a Flo-
Rater/Piston Expansion device. Connec-
tions are sweat type. The suction line (large) must be insulated the entire length with closed cell, foam tube insulation. Do not insulate the liquid line (small). Connect the outdoor unit according to the instructions supplied with unit. All horizontal piping runs should be without dips to trap the oil and slightly inclined, so as to encourage oil ow in the direction of the compressor.
Suction line liquid line
REfRIgERA TION pIpINg
pIpE INSTALLATION NOTES
1. Maximum equivalent pipe run should be no more than 100’ (30.5m), with a maximum rise of 35’ (10.7m).
2. Horizontal pipe runs should be slightly inclined,
so as to encourage oil to ow in the direction
of the compressor, for better oil return.
3. Good refrigeration practices must be em­ployed to ensure the correct pressure drop and good oil return.
2. Cut the black insulation around the knock-out.
3. Snip the tabs holding the knock-out in place.
4. Remove the metal knock-out and the black insulation behind it.
5. Attach the duct collars (eld sup­plied) to the chassis using self tap­ping screws. (Repeat steps 1-5 for
remaining duct work.)
CAHB24
CONdENSATE pIpINg ANd dUCT CONNECTIONS
www.enviromaster.com
Cassette Air Handler
12
Assembly Instructions
2. Ensure the white panel fasteners hold-
ing the fascia polystyrene are pushed rmly in (fasteners may have loosened in
transit).
3. Lift the fascia onto the chassis mounting
bolts. Align the key hole brackets with the mounting bolts and slide the fascia forward to lock into position.
1. To install the four fascia mounting bolts: a) Remove the bolts and washers
from the supplied kit bag.
b) Put washers onto the bolts. c) Screw the mounting bolt with
washer into the chassis leav-
ing approximately 1” (25mm) to
hang the fascia.
4. On Cassette 24 and 36 units connect the vane motor plug by plugging it into the socket connection on the chassis.
a) Ensure that the polarized connector
(2 position) is in the proper orienta-
tion and connected.
b) Route the wires in a way that en-
sures they won’t become trapped, cut, broken or chaffed.
female vane motor plug on chassis
Male vane motor plug on fascia
5. ONLY Cassette “B” models (CACB/
CAHB) contain a second cable con-
nection to the control box for the Infra-
red Unit Mount Control.
NOTE: The fascia only ts correctly one way.
Position the fascia so that the AmericaSeries logo is on the control box end of the chassis.
CASSETTE AIR HANdLER INSTALLATION INSTRUCTIONS
www.enviromaster.com
13
Cassette Air Handler
To complete the installation adjust the louver position to 30° from plumb, this is recom-
mended for “optimum” system performance.
NOTE: All wiring should be in accordance with the National Electrical Code (NEC) and the local building codes.
1.
2. Inspect the existing wiring for any de-
ciencies such as cut or frayed wires. Replace if any such wiring if found.
The standard unit voltage is 208/230V
(60Hz, 1Ph). Check the unit’s rating plate for your models’ electrical requirements.
• The wires should be capable of carry-
ing the maximum load current under non-fault conditions at the stipulated
voltages.
• Avoid large voltage drops on cable runs, particularly in low voltage wiring.
• The correct cable size must be used to ensure a voltage drop of less than 1
Volt in the control wiring.
• Once the refrigeration pipe work is complete, the electrical supply can be connected.
• Low volt wiring must be at least 18 AWg.
Electrical Wiring
CASSETTE AIR HANdLER INSTALLATION INSTRUCTIONS
a) Ensure that the polarized (10 posi-
tion) connector is in the proper orien-
tation and connected.
6. The fascia can now be tightened up
to the Cassette chassis. M  good seal is obtained between fas­cia and chassis, this is necessary to prevent recirculation.
NOTE: Do not over
tighten the bolts. To do so may cause damage to the fascia and drain pan.
With lter(s) in place,
the inlet grille(s) can
now be installed onto the
fascia.
b) Route the wires in a way that ensures
that they won’t become trapped, cut, broken, or chaffed.
Red stripe is
Conductor #1
Polarized
10 Position
Connector
www.enviromaster.com
Cassette Air Handler
14
High Volt Electrical Wiring
2. Secure the cable.
3. Refer to the wiring diagram (see follow-
ing page) to connect the ground wire to the ground lug.
1. Route the cable through the appropriate hole in the control box for the High Volt
electrical wiring.
high Volt Electric Cable
low Volt Electrical
Connections
CASSETTE AIR HANdLER INSTALLATION INSTRUCTIONS
Electrical Wiring- Continued
4. Slide cover up and out to remove.
5. The rating plate is located on the outside
of control box cover (see low Volt inter­connecting Wiring section for location of
wiring diagram).
6. Check the unit rating plate for circuit
ampacity and breaker or fuse size. Use
only HACR type breakers. Select the
proper wire for the ampacity rating.
7. Each unit must have a separate branch circuit protected by a fuse or breaker. Refer to the unit rating plate for the proper wire and breaker or fuse size.
8. It is also recommended that a local dis-
connect switch be connected within 3’ of the unit. In some areas this may be a code requirement.
3. Remove the 4 screws
securing the
control box
cover.
www.enviromaster.com
15
Cassette Air Handler
High Volt Electrical Wiring - Continued
Low Volt Interconnect Wiring
Refer to the wiring diagram to connect the low Volt wiring to the
appropriate terminals. The wiring diagram located on
the inside of the control
box cover.
once the connections
are made replace control
box cover with the wiring
diagram facing in and se-
cure with the four screws.
low Volt Connections
Wiring Diagram
The 24V control transformer is located in the air handler unit. This provides low volt
control power to both the air handler and condenser. Depending on the models selected,
the low volt interconnect control wiring may be different.
NOTE: All low volt interconnect wiring must be at least 18 Awg.
(l1)
(l2)
ground Wire
ground lug
4. Then refer to the wiring diagram to connect the power wire to (L1) and the other wire to (L2) at the power connector location (terminal block).
(See “Electrical Specifications” Sec­tion in the back of this manual for more information.)
Depending on the thermostat required or selected, cooling only air handlers may
utilize three to ve low voltage intercon-
necting wires between the indoor unit, thermostat and the outdoor unit. Some thermostats do not require the use of the
“C” (brown) connection. In this case, en-
sure that any unused wires are insulated to prevent them from making contact with the junction box or other metal surfaces.
If the indoor unit has electric heat then a “W” connection is required between the thermostat and the indoor unit.
CASSETTE AIR HANdLER INSTALLATION INSTRUCTIONS
www.enviromaster.com
Cassette Air Handler
16
REfRIgERANT pROCESSINg
Finish all pipe connecting before proceeding to charging the system.
Follow the instructions in the outdoor unit for line evacuation, opening service
valves, and nal charge adjustments. Op-
eration charts and charge tables can be found in the EMI Condenser IOMs.
IMpORTANT: It is illegal to discharge refrigerant into the atmosphere. Use proper reclaiming methods and equipment when installing or servicing this unit.
1. Clean the ends of tubing and insert into ttings.
2. Protect the valves by wrapping with a wet rag "heat sink" before brazing.
3. The use of a heat shield is recommend-
ed to protect the paint. (A heat shield can be made from scrap metal.)
4. Braze tubing into ttings.
5. Attach manifold set.
Refer to Charts in condenser manual to
“ne tune” the refrigerant charge.
heat sink
Shield
S1CA Shown
Manifold
Vacuum Pump Micron Gage
S1CA Shown
6. Evacuate line to 500 microns or less to
ensure all moisture has been removed and there are no leaks.
7. Once certain of a good evacuation and leak free joints, back-seat the valves
(counter-clockwise) to open and allow fac-
tory charge to ll lines and indoor unit.
Loading...
+ 36 hidden pages