EMI KWHA12AO, KWC24DO, KWCA12AO, KWHA09AO, KWHA18DO Installation, Operating And Maintanance Manual

...
HIGH WALL COOLING
DUCTLESS
9,000, 12,000, 18(
24,000
...... :ii!¸I:::,I_(:
Enviromaster Internati( 5780 Success Dr,
www,enviromaster, com
mNSTALLATION, OPERATION AND MAINTENANCE MANUAL
P/N 240006537, Rev. 1.0 [01/07]
This manual is intended as an aid to a qualified service personnel for proper installation, operation, and maintenance of EMI EnviroAir high efficiency R-410A Ductless Split Systems. Carefully read these instructions before attempting installation or operation.
Failure to follow these instructions may result in improper installation, operation, or maintenance, possibly resulting in fire, electrical shock, property damage, personal
injury, or death.
(1) Retain this manual for future reference. (2) Before leaving the premises, review this
manual to be sure the unit has been installed correctly and run the unit for
one complete cycle to make sure it functions properly.
To obtain technical service or warranty assistance during or after the installation d this unit, check our website @ www. enviromaster.com or call your installing
contractor or distributor. Our technical service department may be contacted at
1-800-228-9364.
When calling for assistance, please have the following information ready:
Indoor Unit
Model Number
Indoor Unit
Serial Number
Outdoor Unit
Model Number
Outdoor Unit
Serial Number
Date of installation
Read all instructions before using
the EMI EnviroAir high efficiency system. Install or locate this sys- tem only in accordance with these
instructions. Use this system only
for its intended use as described in this manual.
Check rating plate for correct system
voltage before installing. Installa- tion and operation of a system with
the incorrect voltage may result in
malfunction or other issues and will void _he warranty.
The EMI EnviroAir system must be connected only to a properly grounded electrical supply. Do not
fail to properly ground this unit.
Turn off the electrical supply be- fore servicing the EMI EnviroAir system.
Do not use the EMI EnviroAir
system if it has damaged wiring, is not working properly, or has been
damaged or dropped.
[Save These/nstrucdons]
X,_ j
This symbol is an indicationof ,_"_
Important Safety Information.
TheEnviroAirsystemisanefficientduct- lesssplitairconditioningsystemwithcooF
ingcapacitiesfrom9,000-24,000Btuhand heatpumpcapacityof9,000-24,000Btuh. Designedforquietoperationandboasting compactdimensions,theEnviroAirsys-
temincludesadvancedfeatureslikeauto- restart,fullfeatureremotecontrol.
oMain System Breaker: Sized per unit
requirements, to be mounted adjacent to outdoor unit.
o Mounting Hardware: Wall anchors,
condenser pad.
oVacuum Pump oGauge Set: R-410 specific.
o High Vo#age interconnect Wiling:
14 AWG wiring from outdoor unit to in-
door unit for power and control. *
oRefrigerant : R-410A required for addi-
tional line sets beyond 16 ft=
Can be purchased through the factory asan
accessory, (partof the Tube Set Kit below)
Comprised of three standard components the indoor high wall evaporator, the out
door condensing unit, and an infrared handheld remote contro!. The EnviroAir
system is engineered to the highest per- formance and reliability standards. The evaporator is equipped with permanent
washable air filters as well as motorized air sweep for enhanced air circulation, and
the condensing unit is equipped as stan- dard with a high efficiency rotary compres-
sor.
Tube-Set Kit consisting of:
o Refrigerant Line Set - 25 feet of
suction and liquid line, both fully in- sulated, and flare fittings supplied
on both ends.
ointerconnecting High Vo#age Wiring
- 25 feet supplied.
oAdd#ional Condensate Tubing - 6feet
extra supplied.
EMI recommends the EnviroAir system for residential and light commercial cool- ing applications. The EnviroAir system will operate in standard cooling mode down to
60°F outdoor temperature.
o Matched System Consisting Of:
Evaporator section and condenser sec-
tion with remote control.
The EnviroAir system is backed with the standard limited warranty that applies to all EMI equipment. For a copy of this
limited warranty, please contact EMI cus- tomer service or refer to the website at
_,_Nw.enviromaster, com.
Application:
Check the application of the unit prior to
installation, certain applications require
additional components or installation pa- rameters, such as the need for external
condensate pump or if the system will need to perform low ambient cooling at outdoor temperatures below 6O°F.
KWCA09A0 KWCA12A0 KWCA18D0 KWCA24D0 KWHA09A0 KWHA12A0 KWHA18D0 KWHA24D0
K1CA9000A00 K1CA2000A00 K1CA8000D00 K1CA4000D00 K1HA9000A00 K1HA2000A00 K1HA8000D00 K1HA4000D00
Cooling Only Cooling Only Cooling Only Cooling Only
Heat Pump Heat Pump Heat Pump Heat Pump
9,000 12,000 18,000
24,000
9,000
12,000 18,000
24,000
115zlz60
115zl-60 208/230-1-60 208/230-1z60
115-1-60
115-1-60 208/230zl-60 208/230-1-60
Example
EnviroAir Unit
Unit Style
W = High Waft Unit
Duty
C = Cooling Only H = Heat Pump
Design Revision
A =R-4'10A
Capacity
09 = 9,000 Btuh 12 = 12,000 Btuh
18 = I8,000 Btuh 24 = 24,000 Btuh
Voltage
A = "115-I-60
(09 and "12only)
D = 208/230-"1-60
(18 and24 only)
Not Used
Example
EnviroAir Unit
Number of Zones
I = Single Zone
Duty
C = Cooling Only
H = Heat Pump
Design Revision
A = R-410A
Zone I Capacity
9 = 9,000 Btuh 2 = 12,000 Btuh
8 = 18,000 Btuh 4 = 24,000 Btuh
Not Used
Not Used
Not Used
Voltage
A = 115-1-60
(9 and 2 only)
D = 208/230-I-60
(8 and 4 only)
Controls
0 = Standard
Condenser Coil
0 = StandardAI/Cu
Determine the best location for mounting the indoor unit, it must be located a mini-
mum of 4ft (6 ft or more recomended) from the floor and no less than 6" from ceiling.
Pay attention to the air circulation in the room, 9,000 & 12,000 Btuh units throw air
15ft, 18,000 & 24,000 Btuh units throw air 25ft, ensure no obstacles to airflow exist.
Locate the indoor and outdoor units as close together as possible, maximum line set run
and lift MUST NOT BE EXCEEDED. Deter- mine how the interconnect piping, wiring
and condensate hose are to be run.
Units are supplied with a wireless remote control, which communicates with the unit
microprocessor control. The return air temperature sensor mounted in the in- door unit provides input to the control for system operation.
Several modes of operation are available to the end user depending on the type of comfort required. All unit operating func-
tions are controlled via the remote con- trol. Refer to "_System Operation" section
of this manual.
KWCA/K 1CA 09/12 KWCA/K1 CA 18/24
KWHA/K1HA 09/12 KWHA/K1 HA 18/24
35 Feet 50 Feet
35 Feet 50 Feet
17 Feet 17 Feet
17 Feet 17 Feet
Ensure that all panels can be removed for service as required.
Cerdffeadon:
All EnviroAir Ductless Splits are certified by UL under UL Standard 1995. Per- formance is varified by CSA under ARI
210/240 test standard.
Low Ambient Contro#
Please consult the factory for availability of approved method of low ambient cooling
operation.
Condensate Pump: It is recommended to use the supplied
condensate drain hose in a gravity fed method whenever possible. If this can not be done then a field installed pump that is external to the evaporator would be required.
structions,failureto followI
s maycausepossiblemat=I
ndvoidanywarranty. J
J
Remove indoor and outdoor units from the carton/box, indoor unit carton con-
tains, remote controt and batteries, en- sure these are kept in a safe place during
installation.
Locate area to install indoor unit the unit should be located a minimum of 6 ft.
from the floor and 6" from the ceiling.
Choose an area where the watt is plumb and determine how to best to run the unit interconnects.
CEIMNG
ceiling minimum
6" from
from wall
minimum
4R from floor (minimum)
6R plus from floor (optimum)
FLOOR
Ensure no obstacles to airflow are directly in front of the unit, for a minimum of 12 ft
for 9,000/12,000 Btuh units and 16 ft for 18,000t24,000 Btuh units.
Do not install the Indoor unit units in areas exposed to high humidity (Relative Hu=
midity of 80% or more), direct sunlight and direct heat from stoves or other devices.
Prepare the evaporator for moundng
by removing the mounting bracket from the rear of the indoor unit. Use a Phillips head screwdriver to remove the unit pipe
strap. If the unit is a heat pump the de- frost sensor also must be undone from its
retainer.
If mounting the unit on an outside wall measure from the edges of the unit to the center of the line set 90° bend to locate the
the center of the wall penetration. Drill a 3" e hole through the wall. Angle the wall penetration slightly down towards the out-
side to assist in draining the condensate away from the unit.
If mounting the unit on an inside walt, use the knockouts provided on the left and
right sides d the unit to route the piping and wiring connections through.
The indoor unit weighs a maximum of 20 Lbs. Use watt anchors to secure the
mounting bracket to a watt stud and en- sure that the wall is capable of holding the
weight of the unit.
Be sure mounting bracket is level, so that the condensate can drain properly.
knockout remove mounting
knockout
mounting bracket
on wall
_are unit fine set connections
Rotate refrigerant line stubs gently to 90° (if mounting on an outside wall). For oth- er line set configurations align the stubs as required.
ieP:Use Duct tape to tape the Con-_
nsate hose (make sure it is below I
I the Line set stubs) and the defrost I I sensor (heat pump only). This makes I I it easier to guide them through the I
f
i !!!
Feed the 14 AWG interconnect wiring between indoor and outdoor through
the unit electrical connection (maxi-
mum number of 6 wires is required) (if required by local codes an electrica/
connector can be attached to the rear of the unit). Tape the loose wire to the
line set stubs. (See Electrica/Wiring In- staff section.) These two tips save time
and prevent damage to the stubs when mounting the indoor unit.
HEAT PUMP SYSTEMS
Install unit on mounting bracket
Feed the line set stubs/condensate hose/
wiring connections through a o 3" hole in the walt.
Position the evaporator so that the "key"
slots on the back of the unit slide onto the tabs on top of the mounting bracket. Then
push the lower portion of the evaporator against the bracket until it latches into the mounting bracket.
indoor unit is now installed, it should be ptumb, level and flush with the wait. in- sure that the line set stubs are completely
through the watt penetration, also check that the watt is plumb. The unit must be
level and plumb for proper condensate removal.
Locate Outdoor unit Select a location with proper ventilation,
minimizing recircutation possibility. Do not install the outdoor unit in a location ex-
posed to high winds (field fabricated and installed wind baffle may be required).
Clearances for the Outdoor unit:
Ensure location does not impede access
around unit and pose a disturbance to neighboring areas.
Install the outdoor unit on a condenser
service pad. If unit is a heat pump ex- tend feet to raise 6" to allow for defrost
to drain away.
8" Minimum
Ote: Consult factory if"_
inimum clearances can't I
maintained. )
Airflow
40" Minimum
12" Minimum
Re_nt Line Set Pi in
interconnectingline set between the outdoor unit and the indoor unit, must have both re- frigerant lines insulated as the expansion
device is located in the outdoor unit.
Gently bend the tine set stubs from the in- door unit to the desired location. Using 2
x 10"/12" Crescent wrenches remove the flare nuts from the indoor unit tine stubs.
The indoor unit is filled with a dry gas, check for retease of this to ensure that no
leaks are present. Use a smatt amount of vacuum pump oil on the male flare threads to ease installation.
Outdoor
Unit
Connect the line set to the stubs. Using the 2 wrenches, 1 on the male and 1 on the female tighten the flare nuts. Run the tine set to the outdoor unit, avoid tight
bends and kinking the lines.
If line set length is in excess of that re- quired, cut line set and re-flare or coil ex- cess vertically to facilitate oit return to the compressor
Service port
Gas line service vahe
Line set connections
under the GRAY caps.
set cover
Indoor Unit
Install the line set on the
indoor unit stubs.
Evacuation
Gauges can now be attached to the service ports - SERVICE PORTS HAVE A 5/16"
CONNECTION TO GAUGES, which is dif- ferent from the norm for R-22. You will need
specific hoses or an adaptor for the 5/16" connection.
Once the gauges are attached the line set can be leak checked using Nitrogen
at 300 psig. Evacuate the unit and inter- connect down to a minimum of 400-500
Microns, break vacuum with Nitrogen to further leak check.
Re-evacuate the system down to 300-400 Microns or lower for a period of one hour.
This is an R-410A System it is essential that a deep vacuum be pulled on the sys-
tem to remove all traces of moisture. See
"System Start-Up" section to fine-tune the
refrigerant charge.
Main Power Wirin_
Electrical wiring should be done in ac- cordance with all National Electrical Code
(NEC) and local state!city building codes.
_Note: A small screwdriver is required_
Breaker size and wiring must be sized for the rating plate amperage, MCA and HACR. Use only HACR type breakers, each system installed must have a sep-
arate branch circuit with an individual breaker/fuse.
9,000
2,000 8,000
!4,000
9,000
2,000 8,000
!4,000
115/80/1 115/80/1 220/60/!
208/230/80/!
7,2 9,6 6,4 8,1
7,2 9,6 6,4 8,1
A local disconnect should be installed ad-
jacent to the outdoor unit in accordance
with National and Local Codes. The out- door unit provides power for the indoor
unit, no disconnect is required between the outdoor and indoor units.
Line voltage from the disconnect should be wired to:
N - L (115V Unit), + G LI - L2 (208/230V Unit), + G
Remove right side knockout on the termi- nal access panel for whip/wiring connec-
tion. Ground connection must be made to the terminal plate.
Heat Pump (208,/230V) unit terminals:
LI - L2 : Power from breaker + G L3 - L4 : Power to indoor unit + G
1- 2 - 3 : Control signals
These are just examples of typical wiring connections. Alway_ refer to Wire Diagram
on unit for actuamwiring connections.
: Foreasieraccessto the terminalsinthe_
oorunitremovethe loweraccesspaneltoJ
Loading...
+ 25 hidden pages