EMI High Wall Air Handler WCP User Manual

WCP
HigH Wall air Handler
P/N# 240003248 Rev. A [06/08]
Materials of Construction:
• Cabinet (available in designer white with grey discharge
vanes) fabricated of cold roll steel with structural stiff-
eners
• Air inlet panel made from high impact polystyrene with
perforated steel grille
• Discharge grille constructed of high temperature Noryl
• Condensate drain pan made from galvanized steel (G90U) with anti-corrosion coating
oPtIonaL EquIPmEnt
• Hand held infra-red remote controller (a separate hand
held remote controller used to command the on-board
controls).
2 PiPe CHilled Water Fan Coil
Nominal Capacities: 9000, 12000,
15000, 18000, 24000, 30000 Btuh
ProduCt dEsCrIPtIon
The WCP is a contemporary design, chilled water air handler that combines attractive appearance in any decor, with the
highly efcient conditioning of small to mid size commercial
or residential spaces. Equipped with unit mounted infrared compatible controls, optional hand held remote also available.
Units provide up to a nominal 30,000 Btuh of cooling. Electric heat options are available for up to 5KW of supplemental heat. It can be paired with a matching capacity chilled water supply. This all American made unit offers ease of installation, operation and service.
aIr HandLEr standard FEaturEs
Factory Installed Controls/Components:
• Relays and connections for chilled water supply
• Unit mounted digital controls as standard:
– Large ¾” LCD display – Anti-short cycle protection – Fan purge (fan remains on for 60 seconds after
heat/cool call dropped for improved efciency)
• Auto/high/low fan operation
• Low Volt transformer
notE: Auto fan operation automatically selects fan speed according to heating or cooling demand.
SpecificationS and performance
Constant fan operation is manually selected high or low speed.
notE: Unit mounted controls are fully functional without the remote controller.
• Field installed condensate pump
• 24V remote thermostat with controls & relays
• Chilled water control valve (N/C 24V ac, 20VA max. or 8 VA max. on units with condensate pumps)
• Electric heat with automatic reset high temperature
cutout and redundant high temperature fuse link.
InstaLLEr suPPLIEd ItEms
• Power wiring & low voltage wiring
• Mounting screws and fasteners
• Chilled water & condensate piping
WCP CaPaCItIEs
model
09/12
15 /18
24/30
nominal
Capacaties
9,000
12,000
15,000
18,000
24,000
30,000
total
Capacity
7,375 6,732 45 1 0.8 10,801 8,272 45 2 3.8 13,270 9,279 45 3 8.0
8,387 7,189 40 1 0.8 12,481 8,950 40 2 3.9 15,643 10,304 40 3 8.1
15,624 13,477 45 2 4.4
19,761 15,367 45 3 9.1
17,724 14,379 40 2 4.5
23,073 16,763 40 3 9.3 20,563 17,564 45 3 2.3 29,031 21,178 45 6 8.3 32,320 22,539 45 9 17.7 23,600 18,887 40 3 2.4 34,400 23,423 40 6 8.4 38,790 25,351 40 9 17.9
sensible
Capacity
Fluid
temp.
Fluid Flow
Pd
Ft. H
0
2
Web: http://www.enviromaster.comEnviromaster International LLC
WCP Dimensions and Specications
notE: Due to EMI’s ongoing development programs, design and specications may change without notice.
dIsCHarGE aIr sPEEd and FLoW
(230V High speed Fan)
model CFm Coil FPm throw/Ft.
9/12 310 Dry 960 16 15/18 600 Dry 1412 26 24/30 750 Dry 1400 25
36 750 Dry 1400 25
WCP PHYsICaL dImEnsIons
model Width “a” Height “B” depth “C” Width “d” Width “E” Width “F” Width “G” Width “H” Width “I”
09/12 36½” 14½” 10¾” 32” 9” 24½” 8” 18” 16” 85 15/18 47½” 14½” 10¾” 32” 10” 34½” 8” 18” 27” 115 24/30 57½” 14½” 10¾” 42” 10” 44½” 8” 27” 28” 115
36 57½” 17” 11¼” 42” 10” 44½” 10½” 25” 28½” 115
WCP ELECtrICaL sPECIFICatIons
model #
09A, 12A 115/60/1 0.64 0.03 0.64 104 0.8 15
09D, 12D 208/230/60/1 0.34 0.02 0.34 197 0.43 15 15A, 18A 115/60/1 1.2 0.083 1.2 104 1.5 15 15D, 18D 208/230/60/1 0.56 0.07 0.56 197 0.7 15 24A, 30A 115/60/1 1.2 0.083 1.2 104 1.5 15 24D, 30D 208/230/60/1 0.56 0.07 0.56 197 0.7 15
(1) If electric heaters are installed, use Min Amp and Max Fuse from Heater Options Chart.
Volts/HZ/
Phase
Fan
FLa HP
total
amps
WCP oBsErVEd
(230V High speed Fan)
model dba
9/12 48
15/18 51
24/30 54
min.
Volt
sound VaLuEs
36 54
min.
ampacity
(1)
max
Fuse (1)
ConnECtIons
WCP
Chilled Line
size
1/2” I.D. 1/2” I.D. 5/8” I.D. 1/2” I.D. 5/8” I.D. 1/2” I.D.
3/4” I.D. 1/2” I.D.
drain size
WCP ELECtrIC HEat oPtIons
model Voltage KW
9/12 230 3 13.1 13.5 16.8 20 15/18 230 3 13.1 13.6 17 20 24/30 230 5 21.7 22.3 27.9 30
36 230 5 21.7 22.3 27.9 30
5780 Success Drive, Rome, NY 13440
shipping
Wt.
Heater
amps
total
amps
min. Cir.
amps
max
Fuse
Enviromaster International LLC
www.enviromaster.com
made in rome, new York, usaWCP Chilled Water air Handler