EMI DWPH365 User Manual

DWPH365 (WHP36-SHC36)
Rev. 1.1 [12/04]
JOB NAME: _____________________________________ LOCATION: _______________________________________
PURCHASER: _____________________________________________________________________________________
ENGINEER: _______________________________________________________________________________________
SUBMITTED TO: _________________________________ FOR: REFERENCE [ ] APPROVAL [ ] CONSTRUCTION [ ]
SUBMITTED BY: _________________________________ DATE: ___________________________________________
UNIT DESIGNATION: SCHEDULE #: _______________ MODEL #: ________________________________________
CAPACITIES:
Cooling 33,000 Btu Heating – High 31,000 Btu – Low 18,200 Btu
571/
2
Indoor Design Temp ºF DB/WB
Cooling 80/67 Heating 70/57
Outdoor Design Temp ºF DB/WB
Cooling 95/75 Heating – High 47/43 – Low 17/15
EER 10.0 SEER 10.0 HSPF 6.8
INDOOR UNIT:
Power Supply 208/230/1/60 Max. Fuse Size 15 Amps (w/o electric heat) Min. Ampacity .70 Amps (w/o electric heat) Max. Fuse Size 30 Amps (w/5kw electric heat) Min. Ampacity 27.9 Amps (w/5kw electric heat) Sound 54 dBa Weight 115 Lbs
OUTDOOR UNIT:
Power Supply 208/230/1/60 Max. Fuse Size 30 Amps Min. Ampacity 19.8 Amps Sound 67.2 dBa Weight 155 Lbs
REFRIGERANT PIPING:
Max. Lift 35 Ft Max. Length 100 Ft Liquid (OD) 3/8 In Suction (OD) 7/8 In
STANDARD FEATURES:
• Five-Year Compressor/One-Year Parts Warranty
• I/R Unit Mount Control (w/optional hand-held control)
• Dry Mode for humidity control (when optional electric heat is ordered) Restart following a power outage
• Auto
• Anti-Short Cycle protection
• Freeze Protection
• Test Operation
• Side Discharge/Low Profi le Condenser
• Fan Purge
• Manual Reset High Pressure Switch
17
1
11
/
4
Rome, New York, USAEnviromaster International LLC
EMI ENGINEERING SUBMITTAL DWPH365 (WHP36-SHC36)
PART ONE “GENERAL”
The Heat Pump air conditioning system shall be an EMI AmericaSeries split system. The system shall consist of a High Wall mounted packaged evaporator section Model WHP36 and matching AmericaSeries outdoor unit Model SHC36. The units shall be made within North America. The units shall be listed by Intertek Testing Service (ITS) and bear the ETL label. All wiring shall be in accordance with the National Electrical Code (N.E.C.). The units shall be rated in accordance with ARI Standard 210/240 and bear the ARI label. The units shall be manufactured in a facility certifi ed to ISO 9001, which is an international standard used to provide guidance in the development and implementation of an effective Quality Management System. The condensing unit shall contain an R-22 refrigerant charge for the evaporator section and condenser section. System SEER shall meet or exceed 1992 Federal Standards.
PART TWO “WARRANTY”
The units shall have a manufacturer’s warranty for a period of one (1) year from date of installation. The compressor shall have a warranty of fi ve (5) years from date of installation. If, during this period, any part should fail to function properly due to defects in workmanship or material, it shall be replaced or repaired at the discretion of Enviromaster International LLC. This warranty does not include labor. Manufacturer shall have fi fteen years experience in the U.S. market.
PART THREE “PERFORMANCE”
Each indoor unit shall provide a total minimum cooling capacity of 33,000 Btuh with an SEER of 10.0 and EER of
10.0 at ARI standard conditions. The system net minimum total cooling capacity shall be 33,000 Btuh and the net minimum sensible cooling capacity shall be 20,600 Btuh with a circulating air rate of 750 CFM at 80o F (DB)/67o F (WB) entering the indoor coil and 95o F (DB) air entering the outdoor coil. The total power consumption of the combined system shall not exceed 3,300 Watts at these conditions.
HEATING
The system shall provide a heating capacity of 31,000 Btuh with a HSPF of 6.8 at ARI standard conditions.
The heating capacity at 70º F indoor and17º F outdoor shall be 18,200 Btuh.
PART FOUR “INDOOR UNIT”
The indoor unit shall be factory assembled, wired and contain a low voltage transformer. The cabinet shall have a white paint fi nish. The evaporator fan shall be an assembly with line fl ow tangential fan direct driven by a single motor. The fan shall be statically and dynamically balanced and run on permanently lubricated bearings. An adjustable vane shall be provided with ability to change the airfl ow vertically. Return air shall be fi ltered by means of an easily removable electrostatic washable fi lter. The evaporator coil shall be of nonferrous construction with louvered fi ns bonded to rifl ed copper tubing. The tubing shall have inner grooves for high effi ciency heat exchange. All tube joints shall be brazed with phoscopper or silver alloy. The coil shall be pressure tested at the factory. A condensate pan and drain shall be provided under the coil. System refrigerant fl ow shall be controlled by means of an orifi ce piston in the indoor unit. The unit electrical power shall be 208/230 of satisfactory operation within voltage limits of 208/230 +/- 10% Volts.
PART FIVE- “CONTROL SYSTEM”
The control system shall consist of unit-mounted infrared compatible controls. Interconnect low-voltage Wiring shall run from indoor unit to outdoor unit direct. NO SPLICES. When running low voltage wiring a double insulated, 5-wire 18 gage cable is mandatory or use shielded 5-wire cable. The microprocessor shall be factory wired and located within the indoor unit. It shall have the capability of sensing return air temperature and indoor coil temperature; large ¾” LCD backlit display; operational range adjustable between 55º F and 95º F in one-degree increments; anti-short cycle compressor protection; minimum compressor run time; fan purge, fan remains on for 60 seconds after heat/cool call is dropped for improved effi ciency; freeze protection to prevent evaporator freeze ups; annunciation provides an audio feedback when the control settings are changed; universal control board allows the unit to operate with either a straight cool or heat pump condenser; two stage heating when optional electric heat and heat pump condenser
Volts, 1 phase, 60 Hertz. The system shall be capable