EMI CAHG09, CAHH12, CAHH24, CAHH09, CAHG12 Installation, Operation And Maintenance Manual

...
P/N 240008108, Rev. B [082509]
CACG/CAHG &
CACH/CAHH
High-Efciency Cassette Ductless Split System Air Handlers
Straight cool / Heat pump nominal capacities
CAHG09 CAHH09
CAHG24 CAHH24
Units
9,000 12,000 18,000 24,000 Btuh
2.6 3.5 5.3 7. 0 kW
Straight cooling only — circuit load — two circuits
CACG-36 & CACH-36
Units
30,000 36,000 Btuh
8.8 10.5 kW
Installation, Operation and
Maintenance Manual
ECR International LLC 2201 Dwyer Ave. Utica, NY 13504 www.enviromaster.com
An ISO 9001-2000 Certified Company
CAHH12
CACG/CAHG & CACH/CAHH
Air Handlers
Installation, Operation and Maintenance Manual
Comfort where it counts 2 P/N 240008108, Rev. B [082509]
Contents
To the Installer
Retain this manual and warranty for future reference. Before leaving the prem­ises, review this manual to be sure the unit has been installed correctly and run the unit for one complete cycle to make sure it functions properly.
To obtain technical service or warranty assistance during or aer the installation of this unit, contact your local representa­tive. For a local representative listing, visit our web site:
www.enviromaster.com
For further assistance call:
1-800-228-9364
When calling for assistance, please have the following information ready:
Model Number _____________ Serial Number _____________ Date of installation ___________
WARNING
Shipping damage MUST be reported to the carrier IMMEDIATELY.
Examine the exterior. Remove cover and examine compressor and piping for signs of damage.
NOTICE
e EMI Ductless Series of high e­ciency evaporators are backed by EMI and ECR International and are tested, rated, and certied in accordance with AHRI Standard 210/240-2008 and UL-1995.
Due to ongoing product development, product designs and specications may change without notice.
Please contact the factory for more information.
Contents . . . . . . . . . . . . . . . . . . . . . . . . . 2
Read Before Proceeding
. . . . . . . . . . . . . . . 3
Verify Unit Before Installing (continued)
. . . . . 6
Piston/Orifice Replacement (when required)
. . 7
Mounting the Unit
. . . . . . . . . . . . . . . . . . . 8
Condensate Piping
. . . . . . . . . . . . . . . . . . .13
Duct Connections
. . . . . . . . . . . . . . . . . . .14
Refrigerant Piping
. . . . . . . . . . . . . . . . . . .15
Refrigerant Processing
. . . . . . . . . . . . . . . .18
Final Assembly
. . . . . . . . . . . . . . . . . . . . .19
Final Assembly (continued)
. . . . . . . . . . . . .20
Remote Thermostat Selection (optional for CACH/ CAHH)
. . . . . . . . . . . . . . . . . . . . . . . . . . .21
Electrical Wiring
. . . . . . . . . . . . . . . . . . . . .22
Initial Start-Up — CACG/CAHG Units ONLY
. . .24
Initial Start-Up — CACH/CAHH Units ONLY
. . .28
CACH/CAHH Microprocessor Controller Overview 31
Setting the CACH/CAHH Controller . . . . . . . .35
CACH/CAHH Microprocessor Controller Operation
. . . . . . . . . . . . . . . . . . . . . . . .38
CACH/CAHH Remote Thermostat Operation
. .45
CACH/CAHH Controller Features
. . . . . . . . . .47
CACH/CAHH Controller Fault Conditions
. . . . .48
Maintenance
. . . . . . . . . . . . . . . . . . . . . . .49
Troubleshooting — General
. . . . . . . . . . . . .50
Troubleshooting — CACG/CAHG Units
. . . . . .52
Troubleshooting — CACH/CAHH Units
. . . . . .55
Frequently Asked Questions
. . . . . . . . . . . . .56
Dimensions
. . . . . . . . . . . . . . . . . . . . . . .58
Dimensions (continued)
. . . . . . . . . . . . . . .59
Specifications
. . . . . . . . . . . . . . . . . . . . . .60
System Options
. . . . . . . . . . . . . . . . . . . . .61
Test Unit Performance Data Sheet
. . . . . . . . .63
EMI’s Product Line
. . . . . . . . . . . . . . . . . . .64
CACG/CAHG & CACH/CAHH
Air Handlers
Installation, Operation and Maintenance Manual
P/N 240008108, Rev. B [082509] 3
Read Before Proceeding
Recognize this symbol as an indication of
important safety information.
WARNING
Completely read all instructions prior to assembling, installing, oper­ating, or repairing this product.
Inspect all parts for damage prior to installation and start-up. e EMI Duct­less high eciency evaporator must be installed ONLY by qualied installation personnel.
DANGER
Tampering with this unit is danger-
ous
. Tampering voids all warranties.
DO NOT aempt to modify or change
this unit in any way.
DANGER
e EMI ductless unit must:
Be connected to a properly grounded • electrical supply with the proper voltage as stated on the rating plate.
Have proper overcurrent protection • (time-delay fuse/HACR Breaker) as listed on the rating plate.
Ensure there are no power feeds to the unit such as fire alarm circuits, BMS circuits, etc.
Failure to follow these instructions can result in a re, explosion, or electrical shock causing property damage, personal injury, or death.
Safety Instructions
is manual is intended as an aid to quali­ed service personnel for proper installa­tion, operation, and maintenance of the EMI Ductless high eciency evaporator. Read these instructions thoroughly and carefully before aempting installation or operation.
Failure to follow these instructions may result in improper installation, operation, service, or maintenance, possibly resulting in re, electrical shock, property damage, personal injury, or death.
Read all instructions before using this unit. Install or locate this unit only in ac­cordance with these instructions. Use this unit only for its intended use as described in this manual.
Check the rating plate on the unit before installation to make certain the voltage shown is the same as the electric supply to the unit. e rating plate is located on the top panel only.
This unit must be connected only to a properly grounded electrical supply. Do not fail to properly ground this unit.
Turn o the electrical supply before servic­ing the unit.
Do not use the unit if it has damaged wir­ing, is not working properly, or has been damaged or dropped.
CACG/CAHG & CACH/CAHH
Air Handlers
Installation, Operation and Maintenance Manual
Comfort where it counts 4 P/N 240008108, Rev. B [082509]
Product description
e EMI Ductless Cassee Air handlers • are available in three cabinet sizes with four output capacities from 9,000–24,000 Btuh, and two cooling only capacities from 30,000–36,000 Btuh.
Key features include a condensate pump • with safety switch and a 36” (0.9 m) li (measured from the base or boom of the unit), fresh air inlet and branch duct knockouts, and motorized air vanes mod­els 24 and 36 only).
Electric heat is a factory-installed option • ONLY (there are no eld installed electric heat kits available). (See NOTICE on next page.)
The cassette air handler accepts a 24 • volt thermostat control (thermostat not included).
Designed for low noise levels, easy instal-• lation and maintenance and a slim line fascia, all ensure minimum intrusion into the conditioned environment.
Due to ongoing product development, all • designs and specications are subject to change without notice.
These cassette air handlers produce • system SEER’s meeting or exceeding 13 when matched with EMI outdoor units:
Single-zone condensing units  – S1CG/S1HG 09–24 and S1CG 30–
36. Dual-zone condensing units 
S2CG/S2HG side discharge. Multi-zone, top discharge condens-
ing units  T2CG/T2HG, T3CG/ T3HG, or T4CG/T4HG.
Refer to specications contained in – this document.
All EMI air handlers are backed by En-• viromaster International LLC and are tested, rated, and certied in accordance with ARI standards 210/240-2008 and UL 1995.
Verify Unit Before Installing
Standard features
CACG/CAHG units
“G” units require a remote thermostat • for operation. They do not include an onboard controller.
External thermostat required.•
CACH/CAHH units
“H” units include an on-board micropro-• cessor controller with infrared remote.
e remote is required to adjust seings • and congure the controller.
Also included is a bank of DIP switches for • seing operating behavior. ese can be used to select operation by the on-board controller or by a remote thermostat.
When operated by remote thermostat, the • controller oers limited options.
Materials of Construction
Galvanized steel cabinet with re-resistant • thermal and acoustic foam insulation.
Light grey high-impact ABS fascia.• Expanded polystyrene drain pan with a •
tough, re-retardant thermoplastic liner.
Air Systems
Fans are backward-curved impeller • centrifugal design; dynamically and stati­cally balanced; and mounted on integral mounting rails.
Single-fan models 9, 12 & 24 are – designed with re-retardant plastic or aluminum impellers.
Twin-fan model 36 is designed with – re-retardant plastic impellers.
Motors are multispeed, enclosed type – with thermal protection and sealed lifetime bearings.
Permanent, washable lter (user acces-• sible).
Branch duct knockouts on three sides • for remote discharge locations (using no more than two non-adjacent sides).
Fresh air intake capability on three sides of • cabinet (only two on models 9–12).
CACG/CAHG & CACH/CAHH
Air Handlers
Installation, Operation and Maintenance Manual
P/N 240008108, Rev. B [082509] 5
Verify Unit Before Installing (continued)
Four plastic air vanes, motor driven with • auto sweep or xed position stop seing on models 24 and 36. Models 9–12 are equipped with manually-adjusted air vanes.
Coil
Coil is seamless, copper tubing, arranged • in staggered conguration, with enhanced aluminum ns, tested to 600 psig.
e tubes are mechanically expanded for • secure bonding to n shoulder.
Refrigeration Circuit
Units are equipped with a serviceable • fixed orifice expansion device and use R410A refrigerant only.
Controls and Components (factory installed or supplied)
Connections for 24V remote thermo-• stat.
Custom control board featuring program-• mability, configuration, and multiple modes of operation. (CACH/CAHH only)
Controls also feature anti-short-cycle • timer, post purge fan relay, and an on­board 30-amp electric heat relay.
Condensate pump with 36” (0.9 m) li • (measured from base of unit).
24V Transformer.•
System options
24V remote thermostat.• Electric Heat (@ 230V) •
1.5 kW  models 9–12 – 3 kW  model 24 – 5 kW  model 36.
Heat pump applications
NOTICE
Electric heat option  EMI heat pumps are intended to operate with an indoor air handler, with electric heat. If an in­door air handler without electric heat is matched with a heat pump condenser, the system will deliver cold air during defrost.
CACG/CAHG & CACH/CAHH
Air Handlers
Installation, Operation and Maintenance Manual
Comfort where it counts 6 P/N 240008108, Rev. B [082509]
Remote thermostat applications
CACG/CAHG units require a remote • thermostat for operation. CACH/ CAHH units can be operated by a remote thermostat by conguring the unit’s DIP switches.
A thermostat can be obtained through • EMI or your local distributor.
NOTICE
Make sure the thermostat is suitable for unit operation (i.e., cooling only, cool­ing/electric heat, heat pump.) See ther­mostat requirements in this manual.
Mechanical characteristics
Filters
Metal framed lters are ed. ese are • reusable and may be vacuum cleaned.
Condensate pump
A condensate pump is designed to carry • water out of the unit. e pump is xed to a mounting bracket which can be withdrawn from the side of the chassis and incorporates an inspection hole to allow a visual check of the pump during operation. A oat switch stops the cool­ing action (shuts off the compressor) should the pump become blocked or fail. (Important: Total li for this pump is 36” (0.9 m) or less.)
Air vanes
Air outlet vanes are manually adjustable • on the models 9 and 12 or driven by an electric motor on the models 24 and 36.
Where ed, the motorized air vanes can • be set to auto sweep or can be stopped in a xed position.
Heating
e cassee may be ed with electric • heaters which are equipped with over­temperature limit switches. Consult factory for available models with electric heat.
Fresh air connection
Fresh air may be introduced to the unit • by the addition of ducts connected to the fresh air knockouts on the cassee case.
Recommended maximum length is 10’ • (3m) of 4” (0.1m) diameter duct. e fresh air volume is approximately 7–10% of the unit’s published maximum air ow (if more than 10% make up air is needed, a fresh air booster fan is required).
Refer to Performance Data section of this • manual for further information.
e cassee is best installed in new con-• struction or existing construction with a suspended or false ceiling with enough clearance to accommodate concealing the piping and electrical connections to the unit.
Verify Unit Before Installing (continued)
CACG/CAHG & CACH/CAHH
Air Handlers
Installation, Operation and Maintenance Manual
P/N 240008108, Rev. B [082509] 7
Piston/Orifice Replacement (when required)
NOTICE — model 24 with T2, T3 or T4 condenser
Piston/orifice replacement  e factory-installed piston/orice must be replaced
when a model 24 air handler is matched with a T2CG/T2HG4400, T2CG/T2HG2400 or T2C/T3CG/T3H2240 condenser that has a 24,000 Btuh compressor (designated by a “4” in the capacity decoding eld). e piston will need replacement only on the 24,000 Btuh zone.
All other applications use the factory-installed orice.
Follow these instructions to replace the orice BEFORE mounting the unit.
Replacing the piston/orifice
Disassemble the orice joint, remove the 1. factory-installed orice, and replace with the orice listed in Figure 1 (supplied in the Kit Bag).
Piston/orifice replacementFigure 1
Model Condenser Factory-installed orifice size
(Inches)
Replacement orifice size
(Inches)
CAHG/
CAHH
24
T2C/T2H4400 T2C/T2H2400 T3C/T3H2240
0.054 0.047
CACG/
CACH
36
S1CG3000
.070 .063
Make sure the o-ring is in good condition 2. and properly installed.
18 Piston Change
CACG/CAHG & CACH/CAHH
Air Handlers
Installation, Operation and Maintenance Manual
Comfort where it counts 8 P/N 240008108, Rev. B [082509]
Mounting the Unit
Before installing, consider:
Determine the best location for mounting • the unit for room air circulation.
Locate outdoor and indoor units as close • together as possible.
Determine how power wire (high and • low-voltage) condensate drainage, and refrigerant piping may be run to and from the unit.
Ensure that interconnect tubing is within • the limits given in Table 1.
Tubing specificationsTable 1
S1CG
or
S2CG
Model
Max.
Length
Equivalent
feet
Max.
Lift
Max. Trap
Height
Liquid
Line
Suction
Line
“H” “P” O.D. O.D.
09
50’
(15 m)
20’
(6 m)
15’
(5 m)
1/4" 1/2"
12 1/4" 1/2"
18
100’
(30 m)
35’
(11 m)
20’
(6 m)
3/8" 5/8"
24 3/8" 3/4"
30 3/8" 3/4"
36 3/8" 3/4"
NOTICE
Piping may be roughed in before wall­board or panels are placed in new con­struction. PVC pipe (3” or 4” I.D.) may be used as a pipe chase.
Unpacking
e Cassee fascia and main chassis are pack­aged together for increased protection.
Remove the banding straps and li the 1. cardboard lid.
Fascia is packed in bubble wrap and on 2. top of the chassis (fascia is not aached to the chassis for shipping).
Cardboard template is between the chas-3. sis and the fascia.
NOTICE
Do not throw template away with pack­aging
Li the fascia and template from the box
4. and set aside.
Remove the cassette chassis from the
5. box utilizing the four corner brackets for liing.
WARNING
Do not use the drain or refrigerant con­nections for liing.
In order to protect the fascia from dirt and 6. damage, it should be returned to the box until it is ready to be installed.
NOTICE
Do not throw away the two polystyrene blanking-o pieces with packaging
CACG/CAHG & CACH/CAHH
Air Handlers
Installation, Operation and Maintenance Manual
P/N 240008108, Rev. B [082509] 9
Mounting the Unit (continued)
Blanking off
e fascia discharge slot(s) will need blank­ing o when ducts are used to channel the conditioned air to other areas.
Position the two polystyrene blanking o • strips (provided) in the fascia discharge slots to direct the air to the ducts.
Up to two non-adjacent sides may be • blanked o.
If the fascia discharge slot needs blanking off —
Remove the inlet grilles and lters (see 1. Figure 2, Page 9) and (Figure 3, Page 9).
Once the grilles and lters are removed, 2. turn the fascia over so the polystyrene insulation is exposed (Figure 4, Page 9).
Push one of the polystyrene blanking-o 3. pieces into the recess in the polystyrene fascia insulation.
Models 9–12 — one grille & one Figure 2 filter
Model 24 — two hinged grilles Figure 3 and two filters (Model 36, not shown has three grilles and three filters)
hinge
Applying blanking-off piecesFigure 4
blanking-off
Pieces
CACG/CAHG & CACH/CAHH
Air Handlers
Installation, Operation and Maintenance Manual
Comfort where it counts 10 P/N 240008108, Rev. B [082509]
Mounting the Unit (continued)
Positioning
e cassee installation position should be selected with the following in mind:
Pipe work, electrical connections, control 1. box and condensate pump access panels should be readily accessible. Refer to the cassee dimensions in the back of this manual.
e unit should be positioned at least 5 2. . (1.5m) from a wall or similar obstruc­tion.
Position the unit as close to the center 3. of the room as possible to ensure air is distributed evenly.
Position the unit so that the discharge 4. air does not blow directly on the remote thermostat, if used.
e unit should not be positioned directly 5. above any obstructions.
e condensate drain should have suf-6. cient fall  1” per 10’ (8 mm/m) in any horizontal run between cassee and drain.
Maximum condensate pump li is 36” 7. (0.9m).
ere should be a minimum 1” (25.4mm) 8. clearance above the depth of the cassee and the false ceiling for proper installa­tion. See (Figure 5, Page 10). (See the cassee dimensions in the back of this manual for cabinet sizing).
Spacing requirementsFigure 5
Dimension A + 1” = minimum space above the false ceiling for installation
A
A +1”
Model Dimension A
9 & 12 11.84” (0.3 m) min.
24 12.55” (0.32 m) min.
36 14.51” (0.37 m) min.
Remote thermostat
A remote thermostat can be obtained through EMI or your local distributor. e remote thermostat is required for CACG/CAHG units, optional for CACH/CAHH units.
In addition to positioning the cassee cor­rectly, it is very important to locate the wall mounted thermostat in the optimum position to ensure good temperature control. The installation should be selected with the fol­lowing points in mind:
Position the thermostat approximately 5
1. . (1.5m) above oor level.
Avoid external walls and dras from win-
2. dows and doors.
Avoid positioning near shelves and cur-
3. tains as these restrict air movement.
Avoid heat sources (direct sunlight, heat-
4. ers, dimmer switches, etc.)
Seal wiring holes in the wall behind the
5. thermostat to avoid dras.
CACG/CAHG & CACH/CAHH
Air Handlers
Installation, Operation and Maintenance Manual
P/N 240008108, Rev. B [082509] 11
Mounting the Unit (continued)
Mounting method
In existing construction, remove enough • ceiling panels to provide clearance space for mounting unit to ceiling joists.
Before beginning the installation, inspect • the unit location, test the strength of the ceiling joists to insure they will support the weight of the unit.
Determine mounting method: •
On wooden beams use threaded rods, – washers, and nuts to suspend support brackets.
With metal structures, secure thread- – ed rods on an existing angle or install a new support angle.
On newly built concrete slabs secure – threaded rods with inserts and em­bedded bolts.
For previously built concrete slabs – install hanging bolts with an expan­sion anchor.
Follow local building codes for required • safety cables, braces, etc.
Ceiling opening
NOTICE
Make sure the ceiling grid is supported separately from the Cassee. e ceiling must not be supported by any part of the Cassee unit, fascia or any associated wiring or pipe work.
Cut an opening in the false ceiling with the size shown in (Table 2, Page 11).
Ceiling opening sizesTable 2
Model Dimensions
9 & 12 23¼” x 23¼” (591 x 591 mm)
24 33/” x 33/” (860 x 860 mm)
36 46” x 33/” (1168 x 860 mm)
Ceiling cutout/rod placement Figure 6 template (shipped with unit)
(51mm x 45°)
2.000 x 45° TYP
rod
Positions
1.500 TYP
rod
Positions
(38mm TYP)
Ceiling rod positionsTable 3
A
A
B
Model Dimension A Dimension B
9 & 12 19.50” (495mm) 22.87” (581mm)
24 29.19” (740mm) 30.80” (782mm)
36 29.19” (740mm) 43.06” (1094mm)
Mounting bracketsFigure 7
Fold
bracket along
perforations
CACG/CAHG & CACH/CAHH
Air Handlers
Installation, Operation and Maintenance Manual
Comfort where it counts 12 P/N 240008108, Rev. B [082509]
Mounting the Unit (continued)
Mounting
Use the template (see 1. Figure 6, Page 11) to cut the ceiling opening and determin­ing the rod positions.
Install hanger bolts using 3/8” (10mm) 2. all-thread rod at the centers shown in (Table 3, Page 11).
Prepare the installation guides by fold-3. ing the metal bracket by hand along the perforations (Figure 7, Page 11).
Li the cassee onto the hanging rods. 4. Level at the correct distance from the ceil-5.
ing with the aid of the installation guides as shown in (Figure 8, Page 12).
Secure the unit in position with locknuts 6. and washers on either side of the cassee bracket.
Ensure threaded rod does not protrude 7. more than 2” (51mm) below the mount­ing bracket see (Figure 9, Page 12).
NOTICE
If the ceiling is not level or even, it is important that the cassee is installed level to ensure correct pump operation and to maintain fan clearances.
Place a carpenter’s level on the unit. A maximum slope of 1/8” (3mm) over
the length of the chassis toward the con­densate drain is allowed.
Any slight discrepancy between the cas­see and ceiling will be taken up by the fascia foam seal.
Positioning installation guidesFigure 8
Inner CAse InsulAtIon
CAssette CAse
Threaded rods must not pro-Figure 9 trude more than 2 inches below the mounting brackets
mAx
2”
(51mm)
CACG/CAHG & CACH/CAHH
Air Handlers
Installation, Operation and Maintenance Manual
P/N 240008108, Rev. B [082509] 13
Condensate Piping
e unit can now be piped up in accordance with good refrigeration and/or plumbing practices.
The Cassette is supplied with a 1/2” I.D. exible PVC hose for connection to copper or plastic drain piping.
When installing the cassette, consider the following:
Maximum pump li is 36” (0.9m).1. The highest point in the condensate 2.
piping should be as close to the unit as possible. is prevents a large volume of water draining back into the unit when it is switched o.
NOTICE
ere is a check valve at the pump dis­charge to prevent water from draining back into the unit. is piping technique will minimize any issues should the check valve become stuck open from airborne debris.
Condensate pipe-work should slope 3. downwards in the direction of water ow with a minimum gradient of 1” per 10’ (8mm/1m). There must be no uphill gradients other than in the rst 36” (0.9m) of pipe-work from the cassee.
When multiple cassees are connected to 4. a common condensate drain, ensure the drain is large enough to handle the total volume of condensate.
NOTICE
A drain line vent may be required to pre­vent siphoning of water from the drain pan and associated noise.
The highest point of the con-Figure 10 densate piping should be as close to unit as possible
Correct
Incorrect
Condensate drainFigure 11
Condensate Drain Connection
CACG/CAHG & CACH/CAHH
Air Handlers
Installation, Operation and Maintenance Manual
Comfort where it counts 14 P/N 240008108, Rev. B [082509]
Duct Connections
Branch duct and fresh air duct collars can be aached to the cassee chassis by following the steps below.
NOTICE
Recommendation  no more than 10 feet (3m) of branch duct or fresh air duct should be installed.
Locate the knock-out holes (1. Figure 12, Page 14).
NOTICE
e number of knockouts varies with unit size.
Branch duct knock-outs are 5¼” (133mm) round.
Fresh air knockouts are:
1¼” x 2½” (32 x 64mm) rectangular • on models 9 & 12.
3” (76mm) square on models 24 • and 36.
Cut the black insulation around the 2. knock-out (Figure 13, Page 14).
Snip the tabs holding the knock-out in 3. place (Figure 13, Page 14).
Remove the metal knock-out and the 4. black insulation behind it.
Aach the duct collars (eld supplied) to 5. the chassis using self-drilling screws.
Repeat steps above for remaining duct 6. work.
KnockoutsFigure 12
fresh air knockout
branch Duct knockout
Cassette 12
CAssette 24 & 36
Cut insulation and snip out Figure 13 knockouts
CACG/CAHG & CACH/CAHH
Air Handlers
Installation, Operation and Maintenance Manual
P/N 240008108, Rev. B [082509] 15
Refrigerant Piping
CAUTION
Avoid piping on wet and rainy days.• Use only clean, refrigeration-grade •
copper tubing. Use tubing benders to guard against •
kinking. Be certain no burrs remain on the •
ings. Cap ends of lines until ready for con-•
nections. Be certain that plastic end caps remain in place when inserting through wall openings.
Insulate the suction and condensate • lines all the way to the cassee.
Isolate tubing from transmiing vibra-• tion to the building or unit and avoid contact with sharp edges.
Wrap refrigeration valves with a wet • rag “heat sink” to protect valves while brazing. (See Figure 16, Page 16.)
DO NOT use a suction line size larger • than the condenser service valve con­nection. is can harm the compres­sor. Install a reducer, when used, only on the inside connection.
NOTICE
e cassee is equipped with a Flo Rater piston expansion device. Connections are sweat type.
Piping connections at unitFigure 14
suction line liquid line
(When a reducing bushing is required, install only at the indoor suction-line connection.)
Line sizing
Size lines per (1. Table 11, Page 60). e suction line size must match the con-2.
denser service valve connection.
When matching the model 24 with an a. 18,000-Btuh condenser, you must use a 5/8-inch suction line, with a reducer installed as shown in (Figure 14, Page 15).
CACG/CAHG & CACH/CAHH
Air Handlers
Installation, Operation and Maintenance Manual
Comfort where it counts 16 P/N 240008108, Rev. B [082509]
Refrigerant Piping (continued)
Clean ends of tubingFigure 15
Place wet rag “heat shield over Figure 16 valves plus a sheet metal shield to protect paint
Wet rag heat sink
shield
Refrigerant piping
Clean the ends of tubing and insert into 1. ings (Figure 15).
Before brazing (2. Figure 16):
Protect valves by wrapping with a wet a. rag “heat sink” before brazing. Use a shield to protect the paint as b. shown. (e shield can be made from scrap metal.)
Braze tubing into ings, using a continu-3. ous nitrogen purge.
e suction line must be insulated the 4. entire length with closed cell, foam tube insulation.
Do not insulate the liquid line.5. Connect the outdoor unit according to 6.
the instructions supplied with unit.
NOTICE
Maximum equivalent pipe run should 1. comply with (Table 1, Page 8).
Horizontal pipe runs should be 2. slightly inclined, so as to encourage oil to flow in the direction of the compressor, for beer oil return.
Good refrigeration practices must be 3. employed to ensure the correct pres­sure drop and good oil return.
CAUTION
Pressure test all eld installed piping with nitrogen. Using a suitable vacuum pump,
evacuate the tubing and indoor unit to 500 microns or less, with service valves remaining front seated (closed).
CACG/CAHG & CACH/CAHH
Air Handlers
Installation, Operation and Maintenance Manual
P/N 240008108, Rev. B [082509] 17
Refrigerant Piping (continued)
Refrigerant processing
Aach manifold set (1. Figure 17). Evacuate line to 500 microns or less to 2.
ensure all moisture has been removed and there are no leaks.
Once certain of a good evacuation and 3. leak free joints, back-seat the valves (counter-clockwise) to open and allow factory charge to ll lines and indoor unit (Figure 18, Page 17).
NOTICE
Refer to refrigerant charge table for speci­ed charge.
Use only R410A refrigerant. Add and
4. remove only liquid, never vapor.
Charge to proper weight, charge based on 5. feet of interconnect (Figure 19, Page 17). See tables on page 18.
CAUTION
Refer to the charts in the condenser manual to “fine tune” the refrigerant charge.
CAUTION
Charging should be done with a dial-a­charge or weighed in with a scale.
WARNING
It is illegal to discharge refrigerant into the atmosphere. Use proper reclaiming methods & equipment when installing or servicing this unit.
Manifold set connections at unitFigure 17
s1CG shown
Manifold set up for evacuationFigure 18
A C
B
s1CG
shown
ManifoldA Vacuum pumpB Micron gageC
Charging the unitFigure 19
s2CGs1CG
Refrigerant
s1CG
shown
CACG/CAHG & CACH/CAHH
Air Handlers
Installation, Operation and Maintenance Manual
Comfort where it counts 18 P/N 240008108, Rev. B [082509]
S1CG/S1HG and top discharge R410A refrigerant charge table
Table 4
(CAC_ refers to CACG/CACH; CAH_ refers to CAHG/CAHH)
Condenser
Evaporator
pairing
Line charge
per foot
Factory charge
Top discharge, Multi-zone
S1CG9 S1HG9
CAH_9
.25 oz/ft
(23 g/m)
39.50
51.25
Circuit capacity
Line charge
per foot
Factory
charge
S1CG2 S1HG2
CAH_12
.25 oz/ft
(23 g/m)
33.75
45.75
S1CG8 S1HG8
CAH_24
.64 oz/ft
(59 g/m)
62.25
63.00
09 (9,000 Btuh)
.25 oz/ft
(23 g/m)
41
S1CG4 S1HG4
CAH_24
.64 oz/ft
(59 g/m)
63.00
74.00
12 (12,000 Btuh)
.25 oz/ft
(23 g/m)
35
S1CG3 CAC_36
.64 oz/ft
(59 g/m)
97.50 18 (18,000 Btuh)
.25 oz/ft
(23 g/m)
65
S1CG6 CAC_36
.64 oz/ft
(59 g/m)
110.00 24 (24,000 Btuh)
.25 oz/ft
(23 g/m)
63
S2CG/S2HG R410A refrigerant charge table
Table 5
Condenser
Evaporator
pairing
Line charge
per foot
Factory
charge
Condenser
Evaporator
pairing
Line charge
per foot
Factory
charge
S2CG99
S2HG99
(2)
CAH_09
.25 oz/ft
(23 g/m)
40/40 51/51
S2CG92 S2HG92
(1) CAH_09 +
(1)CAH_12
.25 oz/ft
(23 g/m)
40/34 51/46
S2CG22
S2HG22
(2)
CAH_12
.25 oz/ft
(23 g/m)
34/34 46/46
Refrigerant Processing
NOTICE – to find charge adjustment
To nd the charge adjustment and system charge for any evaporator and tubing 1. length:
Line Adjustment = (Line Charge/FT) x Line Length System Total = Factory Charge + Line Adjustment
Round to the nearest ounce and allow for gauges and hoses.2.
CACG/CAHG & CACH/CAHH
Air Handlers
Installation, Operation and Maintenance Manual
P/N 240008108, Rev. B [082509] 19
Final Assembly
Assembly instructions
To install the four fascia mounting bolts:1.
Remove the bolts and washers from a. the supplied kit bag. Put washers onto the bolts. b. Screw the mounting bolt with washer c. into the chassis leaving approximately 1” (25mm) to hang the fascia.
Ensure the white panel fasteners holding 2. the fascia polystyrene are pushed rmly in (fasteners may have loosened in transit).
Li the fascia onto the chassis mounting 3. bolts. Align the key hole brackets with the mounting bolts and slide the fascia forward to lock into position.
On Cassee 24 and 36 units connect the 4. vane motor plug by plugging it into the socket connection on the chassis.
Ensure that the polarized connector a. (2 position) is in the proper orienta­tion and connected. Route the wires in a way that ensures b. they won’t become trapped, cut, bro­ken or chaed.
ONLY Cassette “H” models (CACH/5. CAHH) contain a second cable connec­tion to the control box for the Infrared Unit Mount Control.
Ensure that the polarized (10 position) 6. connector is in the proper orientation and connected.
Route the wires in a way that ensures that 7. they won’t become trapped, cut, broken, or chaed (Figure 22, Page 19).
e fascia can now be tightened up to the 8. Cassee chassis. make sure a good seal is obtained between fascia and chassis, this is necessary to prevent recirculation.
With lter(s) in place, the inlet grille(s) 9. can now be installed onto the fascia.
Mounting boltsFigure 20
White panel fasteners must be Figure 21 pushed in
Wire routingFigure 22
CACG/CAHG & CACH/CAHH
Air Handlers
Installation, Operation and Maintenance Manual
Comfort where it counts 20 P/N 240008108, Rev. B [082509]
Final Assembly (continued)
Connect vane motor plug into Figure 23 socket on chassis
female vane motor plug on chassis
Male vane motor plug on fascia
Connect infrared unit cable (“H” Figure 24 units only)
red stripe is
Conductor #1
Polarized
10 Position
Connector
Secure fascia to chassisFigure 25
CAUTION
DO NOT over-tight-
en the bolts  is
could cause damage
to the fascia and drain
pan.
Adjust louver position to 30°
Figure 26
from plumb
Loading...
+ 44 hidden pages