Emerson ZBH38KJE, ZBH30KJE, ZRH49KJE, ZBH45KJE, ZBHV45KJE Application Manuallines

...
Application Guidelines
Copeland Scroll™ Horizontal Compressors for Air-Conditioning Applications
ZRH49K* to ZRH72K*, ZBH30K* to ZBH45K* ZRHV45K* & ZRHV72K*
WARNING
This icon indicates instructions to avoid personal injury and material damage.
CAUTION This icon indicates instructions to avoid property damage and possible personal injury.
High voltage This icon indicates operations with a danger of electric shock.
IMPORTANT This icon indicates instructions to avoid malfunction of the compressor.
Danger of burning or frostbite This icon indicates operations with a danger of burning or frostbite.
NOTE
This word indicates a recommendation for easier operation.
Explosion hazard This icon indicates operations with a danger of explosion.
WARNING System breakdown! Personal injuries! Never install a system in the field
and leave it unattended when it has no charge, a holding charge, or with the service valves closed without electrically locking out the system. System breakdown! Personal injuries! Only approved refrigerants and refrigeration oils must be used.
WARNING High shell temperature! Burning! Do not touch the compressor until it has
cooled down. Ensure that other materials in the area of the compressor do not come into contact with it. Lock and mark accessible sections.
CAUTION Overheating! Bearing damage! Do not operate compressors without
refrigerant charge or without being connected to the system.
CAUTION Contact with POE! Material damage! POE lubricant must be handled
carefully and the proper protective equipment (gloves, eye protection, etc.) must be used at all times. POE must not come into contact with any surface or material that it might damage, including without limitation, certain polymers, eg, PVC/CPVC and polycarbonate.
IMPORTANT Transit damage! Compressor malfunction! Use original packaging. Avoid
collisions and tilting.
Compressor
Cooling capacity
[kW]
Displacement
[m³/h]
Motor
R407C
R134a
ZBH30KJE
10.0
7.0
11.7
TFD/TF5
ZBH38KJE
12.6
8.6
14.4
TFD/TF5
ZBH45KJE
14.8
10.2
17.1
TFD/TF5
ZBHV45KJE
14.8
10.2
17.1
TFD/TF5
ZRH49KJE
10.2
7.1
11.8
TFD/TF5
ZRH61KJE
13.0
8.9
14.5
TFD/TF5
ZRH72KJE
15.0
10.5
17.1
TFD/TF5
ZRHV72KJE
15.0
10.5
17.1
TFD/TF5
IMPORTANT
It is essential that the glide of refrigerant blends (primarily R407C) be carefully considered when adjusting pressure and superheat controls.
Qualified refrigerants
R407C & R134a
Copeland brand products standard oil
Emkarate RL 32 3MAF
Servicing oils
Emkarate RL 32 3MAF
Mobil EAL Arctic 22 CC
CAUTION Inadequate lubrication! Compressor breakdown! The superheat at the
compressor suction inlet must always be sufficient to ensure that no refrigerant droplets enter the compressor. For a typical evaporator-expansion valve configuration a minimum stable superheat of at least 5K is required.
Compressor
version
BOM 650
BOM 651
ZRH*
Brazing stub tubes
Electrical connection ready for
molded plug IP65
Without oil sight glass
Without oil service Schraeder valve
Rotalock connections
Electrical connection ready for molded
plug IP65
Without oil sight glass
Without oil service Schraeder valve
ZRHV*
Brazing stub tubes
Electrical connection ready for
molded plug IP65
Without oil sight glass
Without oil service Schraeder valve
Variable speed
Rotalock connections
Electrical connection ready for molded
plug IP65
Without oil sight glass
Without oil service Schraeder valve
Variable speed
ZBH*
Brazing stub tubes
Electrical connection ready for
molded plug IP65
Oil sight glass
Oil service Schraeder valve
Rotalock connections
Electrical connection ready for molded
plug IP65
Oil sight glass
Oil service Schraeder valve
ZBHV*
Brazing stub tubes
Electrical connection ready for
molded plug IP65
Oil sight glass
Oil service Schraeder valve
Variable speed
Rotalock connections
Electrical connection ready for molded
plug IP65
Oil sight glass
Oil service Schraeder valve
Variable speed
WARNING High pressure! Injury to skin and eyes possible! Be careful when opening
connections on a pressurized item.
WARNING Risk of collapse! Personal injuries! Move compressors only with
appropriate mechanical or handling equipment according to weight. Keep in the upright position. Respect stacking loads according to Figure 3. Check the tilting stability and if needed take action to ensure the stability of the stacked loads. Keep the packaging dry at all times.
IMPORTANT Handling damage! Compressor malfunction! Only use the lifting eyes
whenever the compressor requires positioning. Using discharge or suction connections for lifting may cause damage or leaks.
Soft rubber mounting parts
Hard rubber mounting parts
IMPORTANT Blockage! Compressor breakdown! Maintain a flow of oxygen-free nitrogen
through the system at very low pressure during brazing. Nitrogen displaces the air and prevents the formation of copper oxides in the system. If allowed to form, the copper oxide material can later be swept through the system and block screens such as those protecting capillary tubes, thermal expansion valves, and accumulator oil return holes.
IMPORTANT Contamination or moisture! Bearing failure! Do not remove the plugs until
the compressor is set into the unit. This minimises any entry of contaminants and moisture.
CAUTION Leaking system! System breakdown! It is strongly recommended to
periodically re-torque all pipe and fixing connections to the original setting after the system has been put into operation.
Connection
Torque [Nm]
Rotalock 1" – 14 UNS
70 - 80
Rotalock 1 ¼" – 12 UNF
110 - 135
Rotalock 1 ¾" – 12 UNF
135 - 160
Figure 7: Suction tube brazing
CAUTION Inadequate lubrication! Bearing destruction! Minimise liquid refrigerant
returning to the compressor. Too much refrigerant dilutes the oil. Liquid refrigerant can wash the oil off the bearings leading to overheating and bearing failure.
CAUTION Screen blocking! Compressor breakdown! Use screens with at least
0.6 mm openings.
WARNING Conductor cables! Electrical shock! Shut off power supply before and
between each test.
WARNING Electric arc! Explosion hazard! Removing the molded plug cable while
under load or electrically energized will create arcing between the connection pins and the cable connectors. Always shut off power supply before attaching or removing the molded plug cable from the connection pins. The molded plug connector must be smoothly pushed by hand towards the connection pins of the compressor. Never use a tool to knock the molded plug connector on the terminal pins as this could damage the glass inserts of the pins. It is mandatory to secure the molded plug cable on the connection pins with a retainer. Any rework on the terminal pins is strictly prohibited.
WARNING Electrical shock hazard! Serious personal injuries and/or system breakdown! Use qualified molded plug cables with grounding connection
only. Make sure to connect the grounding first before attaching the molded plug cable to the connection pins of the compressor. When removing the molded plug cable from the connection pins, disconnect the grounding last.
L1
K1
K2
S1
P>
P<
F3
F4
B3
K2
R2
N
1 2 3
B1
K1
B1
F1
IMPORTANT Oil dilution! Bearing malfunction! Turn the crankcase heater on 12 hours
before starting the compressor.
25
30
35
40
45
50
55
60
65
70
-25 -20 -15 -10 -5 0 5 10 15
Condensing Temperature (
o
C)
Evaporating Temperature (oC)
R407C
45-75Hz
35-75Hz
15
20
25
30
35
40
45
50
55
60
65
70
75
-20 -15 -10 -5 0 5 10 15 20
Condensing Temperature (
o
C)
Evaporating Temperature (oC)
R134a
35-75Hz
45-75Hz
IMPORTANT Loss of system charge and lubrication! Bearing malfunction! Compressor breakdown! A low-pressure control is highly recommended. Do
not bridge or by-pass the low-pressure cut out.
IMPORTANT Inadequate lubrication! Scroll set damage! All ZRH* and ZBH* horizontal
Scroll compressors must be equipped with an external discharge gas temperature protection.
Install the discharge line thermostat on the
discharge tube 120 mm from top cap.
Snap the retainer clip over the tube and onto
the thermostat.
The thermostat should be placed on the
discharge tube so that its body is in upward position on a horizontal tube installation.
Ensure that the thermostat is not tilted.
The wire must not be in contact with the top
cap of the compressor or the discharge tube. Care should be taken to route wires so that they do not come into contact with sharp objects.
To avoid any impact on tripping temperature
by the ambient, the discharge line thermostat must be insulated.
Wrap thermal insulation around the pipe left
and right of the thermostat and secure it with plastic straps.
Wrap a second layer of insulation around the
first one and around the thermostat, and secure it with plastic straps.
WARNING Conductor cables! Electrical shock! Shut off power supply before high-
potential testing.
CAUTION Internal arcing! Motor destruction! Do not carry out high-voltage or
insulation tests if the compressor housing is under vacuum.
WARNING Diesel effect! Compressor destruction! The mixture of air and oil at high
temperature can lead to an explosion. Avoid operating with air.
IMPORTANT Oil dilution! Bearing malfunction! Turn the crankcase heater on 12 hours
before starting the compressor.
WARNING High pressure! Personal injuries! Consider personal safety requirements
and refer to test pressures prior to test.
WARNING System explosion! Personal injuries! DO NOT USE other industrial
gases.
CAUTION System contamination! Bearing malfunction! Use only dry nitrogen or dried
air for pressure testing.
CAUTION Low suction pressure operation! Compressor damage! Do not operate
with a restricted suction. Do not operate with the low-pressure cut-out bridged. Do not operate compressor without enough system charge to maintain at least
0.5 bar(g) suction pressure. Allowing pressure to drop below 0.5 bar(g) for more than a few seconds may overheat scrolls and cause early drive bearing damage.
CAUTION Oil dilution! Bearing malfunction! It is important to ensure that new
compressors are not subjected to liquid abuse. Turn the crankcase heater on 12 hours before starting the compressor.
CAUTION High discharge pressure operation! Compressor damage! Do not use
compressor to test opening setpoint of high-pressure cut-out. Bearings are susceptible to damage before they have had several hours of normal running in.
CAUTION Vacuum operation! Compressor damage! Scroll compressors should never
be used to evacuate a refrigeration or air-conditioning system.
CAUTION Inadequate lubrication! Bearing destruction! Exchange the accumulator
after replacing a compressor with a burned-out motor. The accumulator oil return orifice or screen may be plugged with debris or may become plugged. This will result in starvation of oil to the new compressor and a second failure.
CAUTION Chemical reaction! Compressor destruction! Do not mix up ester oils with
mineral oil and/or alkyl benzene when used with chlorine-free (HFC) refrigerants.
WARNING Explosive flame! Burning! Oil-refrigerant mixtures are highly flammable.
Remove all refrigerant before opening the system. Avoid working with an unshielded flame in a refrigerant charged system.
BENELUX
Josephinastraat 19 NL-6462 EL Kerkrade Tel: +31 45 535 06 73 Fax: +31 45 535 06 71 benelux.sales@emerson.com
UK & IRELAND
Unit 17, Theale Lakes Business Park Reading, Berkshire RG7 4GB Tel: +44 1189 83 80 00 Fax: +44 1189 83 80 01 uk.sales@emerson.com
GERMANY, AUSTRIA & SWITZERLAND
Theo-Mack Str. 3 DE-63477 Maintal Tel: +49 6109 605 90 Fax: +49 6109 60 59 40 ECTGermany.sales@emerson.com
FRANCE, GREECE & MAGHREB
8, Allée du Moulin Berger FR-69134 Ecully Cédex, Technoparc - CS 90220 Tel: +33 4 78 66 85 70 Fax: +33 4 78 66 85 71 mediterranean.sales@emerson.com
ITALY
Via Ramazzotti, 26 IT-21047 Saronno (VA) Tel: +39 02 96 17 81 Fax: +39 02 96 17 88 88 italy.sales@emerson.com
SPAIN & PORTUGAL
C/ Pujades, 51-55 Box 53 ES-08005 Barcelona Tel: +34 93 412 37 52 iberica.sales@emerson.com
CZECH REPUBLIC
Hajkova 22 CZ - 133 00 Prague Tel: +420 733 161 651 Fax: +420 271 035 655 Pavel.Sudek@emerson.com
SWEDEN, DENMARK, NORWAY & FINLAND
Pascalstr. 65 DE-52076 Aachen Tel: +49 2408 929 0 Fax: +49 2408 929 525 nordic.sales@emerson.com
EASTERN EUROPE & TURKEY
Pascalstr. 65 DE-52076 Aachen Tel: +49 2408 929 0 Fax: +49 2408 929 525 easterneurope.sales@emerson.com
POLAND
Szturmowa 2 PL-02678 Warsaw Tel. +48 22 458 92 05 Fax +48 22 458 92 55 poland.sales@emerson.com
RUSSIA & CIS
Dubininskaya 53, bld. 5 RU-115054, Moscow Tel: +7 - 495 - 995 95 59 Fax: +7 - 495 - 424 88 50 ECT.Holod@emerson.com
BALKAN
Selska cesta 93 HR-10 000 Zagreb Tel: +385 1 560 38 75 Fax: +385 1 560 38 79
ROMANIA & BULGARIA
Parcul Industrial Tetarom 2 Emerson Nr. 4 400641 Cluj-Napoca Tel: +40 374 13 23 50 Fax: +40 374 13 28 11 ro-bg.sales@emerson.com
MIDDLE EAST & AFRICA
PO Box 26382 Jebel Ali Free Zone - South, Dubai - UAE Tel: +971 4 811 81 00 Fax: +971 4 886 54 65 mea.sales@emerson.com
ASIA PACIFIC
Suite 2503-8, 25/F., Exchange Tower 33 Wang Chiu Road, Kowloon Bay Kowloon , Hong Kong Tel: +852 2866 3108 Fax: +852 2520 6227
For more details, see www.climate.emerson.com/en-gb
Connect with us: facebook.com/EmersonCommercialResidentialSolutions
C6.2.7/1007-0619/E
Emerson Commercial & Residential Solutions Emerson Climate Technologies GmbH - Pascalstrasse 65 - 52076 Aachen, Germany Tel. +49 (0) 2408 929 0 - Fax: +49 (0) 2408 929 570 - Internet: www.climate.emerson.com/en-gb
The Emerson logo is a trademark and service mark of Emerson Electric Co. Emerson Climate Technologies Inc. is a subsidiary of Emerson Electric Co. Copeland is a registered trademark and Copeland Scroll is a trademark of Emerson Climate Technologies Inc.. All other trademarks are property of their respective owners. Emerson Climate Technologies GmbH shall not be liable for errors in the stated capacities, dimensions, etc., as well as typographic errors. Products, specications, designs and technical data contained in this document are subject to modication by us without prior notice. Illustrations are not binding.
© 2019 Emerson Climate Technologies, Inc.