Emerson ZR16-29KC, ZR16-24K4, ZR16-34KA, ZR38-54KA, ZR18-48K3 Application Engineering Bulletin

...
AE4-1312 R2
AE4-1312 R2
Application Guidelines for 1.5 to 6.75 Ton Refrigerant
Introduction
The ZR*KA, ZR*KC, ZR*K3, & ZR*K4 Copeland Scroll® compressors include a wide range of capacities, electrical options, and features. Typical model numbers are ZR24K4-PFV and ZR81KC-TF5. This bulletin describes the operating characteristics, design features, and application requirements for these models. For additional information, please refer to the online product information accessible from the Emerson Climate Technologies website at www.emersonclimate. com. Operating principles of the Copeland Scroll are described in Figure 7 at the end of this bulletin.
The ZR*KA scroll compressors are designed for air conditioning systems only in the 12+ SEER range but may be applied to 10 SEER A/C systems if desired. They range in size from 16,000 to 54000 Btu/hr (4.7 to
15.8 kw-hr).
The ZR*K3 and K4 are models designed for 11+ SEER A/C and heat pump usage ranging in size from 16,000 to 61,000 Btu/hr (4.7 to 17.9 kw-hr).
The ZR*KC models are designed for 10 SEER A/C and heat pump usage ranging in size from 16,000 to 81,000 Btu/hr (4.7 to 23.7 kw-hr).
The models include a number of features outlined in the matrix below:
January, 2005
Reformatted November 2010
®
Compressors
IPR Valve-Internal Pressure Relief Valve
The internal pressure relief valve is located between the high side and the low side of the compressor. It is designed to open when the discharge to suction differential pressure exceeds 375 to 450 psid (26 – 32 kg/cm2). When the valve opens, hot discharge gas is routed back into the area of the motor protector to cause a trip.During developmental blocked fan testing, it is sometimes noted that the valve opens, but the compressor does not shut off while the discharge pressure continues to climb. This condition is normally
caused by refrigerant ood back and may be corrected
by using a more restrictive expansion device or reducing the refrigerant charge.
Internal Temperature Protection
®
The Therm-O-Disc snap disc device located between the high and low pressure side of the scroll. It is designed to open and route excessively hot discharge gas back to the motor protector. During a situation such as loss of charge, the compressor will be protected for some time while it trips on the protector. However, as refrigerant leaks
out, the mass ow and the amperage draw are reduced
and the scrolls will start to overheat. Normally, during air conditioning operation the problem is detected because of rising indoor temperatures before damage is done. This may not be the case during heat pump
or TOD is a temperature-sensitive
Motor
Frame Size*
ZR16-29KC 53 X X NO X X X X
ZR16-24K4 53 X X NO X X X X ZR16-34KA 53 X NO X X X X X ZR38-54KA 63 X NO X X X X X
ZR18-48K3 63 X X X X X X X ZR26-48KC 63 X X X X X X X
ZR54-61K3 70 X X X X X X X ZR54-81KC 70 X X X X X X X
* Approximate Shell Diameter (e.g. 53 = 5.5 Inches)
© 2010 Emerson Climate Technologies Printed in the U.S.A.
Application
AC HP
IPR TOD
1
Quiet Shut
Down
Discharge
Check Valve
Motor
Protector
AE4-1312 R2
operation since backup heat will make up the decit. A
low pressure control is recommended for loss of charge protection in heat pumps for the highest level of system protection. A cut out setting no lower than 25 psig (2 kg/cm2) for air conditioning and 7 psig (0.5 kg/cm2) for heat pumps is recommended. The low pressure cut-out, if installed in the suction line to the compressor, can provide additional protection against a TXV failed in the closed position, outdoor fan failure in heating, a closed liquid line or suction line service valve, or a blocked liquid
line screen, lter, orice, or TXV. All of these can starve
the compressor for refrigerant and result in compressor failure. The low pressure cut-out should have a manual reset feature for the highest level of system protection. If a compressor is allowed to cycle after a fault is detected, there is a high probability that the compressor will be damaged and the system contaminated with debris from the failed compressor and decomposed oil. If current monitoring to the compressor is available, the system controller can take advantage of the compressor TOD and internal protector operation. The controller can lock out the compressor if current draw is not coincident with the contactor energizing, implying that the compressor has shut off on its internal protector. This will prevent unnecessary compressor cycling on a fault condition until corrective action can be taken.
Quiet Shut down
All scrolls in this size range have one of several types of “quiet” shutdown solutions. The ZR..KC/K3/ K4 Scrolls up to four tons use a cam-type device that separates the scrolls when they are driven backwards as high-pressure gas equalizes from the high side of the compressor to the low side during shutdown. Larger scrolls with 70 frame motors through ZR61 use a different type of cam that stops backward rotation during shut down. Models ZR68KC through ZR81KC
will continue to be built with the uid brake design,
so a momentary reverse rotation sound will be heard from these compressors. The newer ZR..KA scrolls incorporate a non dynamic discharge port check valve that prevents high pressure gas trapped in the dome from returning through the scroll set. All of these quiet shut down solutions allow the scroll compressor to restart immediately even if the system is not equalized eliminating the need for a time delay. Development testing should include a review of the shutdown sound for acceptability in a particular system. Also refer to section on “Brief Power Interruption”.
Discharge Check Valve
A low mass, disc-type check valve in the discharge tting
of the compressor prevents the high side, high pressure
discharge gas from owing rapidly back through the
compressor. This check valve was not designed to be
used with recycling pump down because it is not entirely leak-proof.
Motor Protector
Conventional internal line break motor protection is provided. The protector opens the common connection of a single-phase motor and the center of the Y connection on three-phase motors. The three-phase protector provides primary single-phase protection. Both types of protectors react to current and motor winding temperature.
Field Replacement of obsolete Single Phase ZR*K1 or ZR*K2 with Equivalent Capacity ZR*K3/K4/KA/ KC, Scroll Compressors
The discharge and suction tting sizes as well as the mounting foot pattern of the new models are identical to the ZR*K1 or ZR*K2. Tubing location is identical in
most cases for easy eld replacement. The ZR*K1
has an external top cap thermostat to limit discharge temperature. This feature has been replaced by the Therm-O-Disc® located inside the new scrolls. When replacing the ZR*K1, the top cap thermostat wires must be removed and the control circuit wires spliced together. See section on Compressor Replacement
after Motor Burn for further tips on eld replacement.
The replacement compressor will need a new run capacitor if the old capacitor is more than 5 microfarads different or the voltage rating of the old capacitor is lower than the new one. See compressor nameplate or Table 4 for recommended run capacitor. Note that the ZR*KA may only be used to replace compressors used for A/C, not heat pumps.
Application Considerations
The Copeland Scroll compressor has a number of application characteristics that are different from those of the traditional reciprocating compressor. These are detailed below.
Accumulators
The use of accumulators is very dependent on the application. The Copeland Scroll’s inherent ability to handle liquid refrigerant during occasional operating
ood back situations make the use of an accumulator
unnecessary in standard designs such as condensing
units. Applications, such as heat pumps with orice
refrigerant control, that allow large volumes of liquid
refrigerant to ood back to the compressor during
normal steady operation can dilute the oil to such an extent that bearings are inadequately lubricated and wear will occur. In such a case an accumulator must
be used to reduce ood back to a safe level that the compressor can handle. To test for ood back conditions
© 2010 Emerson Climate Technologies Printed in the U.S.A.
2
AE4-1312 R2
and determine if the accumulator design is adequate, please see the section entitled Excessive Liquid Flood back Tests at the end of this bulletin. The accumulator
oil return orice should be from .040 to .055 inches (1 –
1.4 mm) in diameter depending on compressor size and
compressor ood back results. A large-area protective screen no ner than 30 x 30 mesh (0.6 mm openings) is required to protect this small orice from plugging. Tests have shown that a small screen with a ne mesh
can easily become plugged causing oil starvation to the compressor bearings.
Screens
The use of screens ner than 30 x 30 mesh (0.6mm
openings) anywhere in the system should not be used with these compressors. Field experience has
shown that ner mesh screens used to protect thermal
expansion valves, capillary tubes, or accumulators can become temporarily or permanently plugged with
normal system debris and block the ow of either oil or
refrigerant to the compressor. Such blockage can result in compressor failure.
Crankcase Heat - Single Phase
Crankcase heaters are not required on single phase compressors when the system charge is not over the 120% limit shown in Table 5. A crankcase heater is required for systems containing more than 120% of the compressor refrigerant charge limit listed in Table 5. This includes long line length systems where the extra charge will increase the standard factory charge above the 120% limit.
Experience has shown that compressors may ll with
liquid refrigerant under certain circumstances and
system congurations, notably after longer off cycles
when the compressor has cooled. This may cause excessive start up clearing noise or the compressor may lock up and trip on protector several times before starting. The addition of a crankcase heater will reduce customer noise and dimming light complaints since the compressor will no longer have to clear out liquid during start. Table 6 lists the crankcase heaters recommended for the various models and voltages.
Crankcase Heat – Three-Phase
A crankcase heater is required for three-phase compressors when the system charge exceeds the compressor charge limit listed in Table 5 and an accumulator cannot be piped to provide free liquid drainage during the off cycle (See Figure 2 and Table
6).
Pump down Cycle
A pump down cycle for control of refrigerant migration is not recommended for scroll compressors of this size.
If a pump down cycle is used, a separate external check valve must be added. The scroll discharge
check valve is designed to stop extended reverse rotation and prevent high-pressure gas from leaking rapidly into the low side after shut off. The check valve will in some cases leak more than reciprocating compressor discharge reeds, normally used with pump down, causing the scroll compressor to recycle more frequently. Repeated short-cycling of this nature can result in a low oil situation and consequent damage to the compressor. The low-pressure control differential has to be reviewed since a relatively large volume of gas will re-expand from the high side of the compressor into the low side on shut down.
Minimum Run Time
There is no set answer to how often scroll compressors can be started and stopped in an hour, since it is highly dependent on system configuration. Other than the considerations in the section on Brief Power Interruptions, there is no minimum off time because scroll compressors start unloaded, even if the system has unbalanced pressures. The most critical consideration is the minimum run time required to return oil to the compressor after startup. To establish the minimum run time obtain a sample compressor equipped with a sight tube (available from Emerson Climate Technologies) and install it in a system with the longest connecting lines that are approved for the system. The minimum on time becomes the time required for oil lost during compressor startup to return to the compressor sump and restore a minimal oil level that will assure oil pick up through the crankshaft. Cycling the compressor for a shorter period than this, for instance to maintain very tight temperature control, will result in progressive loss of oil and damage to the compressor. See Application Engineering Bulletin 17­1262 for more information on preventing compressor short cycling.
Reversing Valves
Since Copeland Scroll compressors have very high
volumetric efciency, their displacements are lower
than those of comparable capacity reciprocating compressors. As a result, Emerson recommends that the capacity rating on reversing valves be no more than 2 times the nominal capacity of the compressor with which it will be used in order to ensure proper operation of the reversing valve under all operating conditions.
© 2010 Emerson Climate Technologies Printed in the U.S.A.
3
AE4-1312 R2
The reversing valve solenoid should be wired so that the valve does not reverse when the system is shut off by the operating thermostat in the heating or cooling mode. If the valve is allowed to reverse at system shutoff, suction and discharge pressures are reversed to the compressor. This results in pressures equalizing through the compressor which can cause the compressor to slowly rotate until the pressures equalize. This condition does not affect compressor durability but can cause unexpected sound after the compressor is turned off.
Low Ambient Cut-Out
A low ambient cut-out is not required to limit air-to-air heat pump operation. Air-to-water heat pumps must
be reviewed since this conguration could possibly run
outside of the approved operating envelope (Figure 5) causing overheating or excessive wear.
Oil Type
Several types of compatible mineral oils are used in the R-22 compressors. A standard 3GS oil may be
used if the addition of oil in the eld is required. See
the compressor nameplate for original oil charge. See Application Engineering bulletin 17-1248 for more information about oil types Emerson uses. A complete
recharge should be four uid ounces (118 ml) less than
the nameplate value. Some models have been released for use with R407C or 134a and use polyol ester oil,
identied as POE, along with the charge quantity on
the nameplate. These models have an “E” in the 7th place of the model number. An example would be the ZR24K3E-PFJ compressor. Copeland® Ultra 22 CC
should be used if additional oil is needed in the eld.
Mobil Arctic EAL22CC or ICI Emkarate RL32CF oil may be used to recharge these compressors if Ultra 22 is not available. Compressors charged with POE may be used with R-22 but compressors charged with mineral oil may not be used with HFC refrigerants such as 407C or 134a because they are not miscible.
Discharge Mufers
Flow through Copeland Scroll compressors is semi­continuous with relatively low pulsation. External
mufers, where they are normally applied to piston
compressors today, may not be required for Copeland Scroll. Because of variability between systems, however, individual system tests should be performed to verify acceptability of sound performance. When no testing is
performed, mufers are recommended in heat pumps. A hollow shell mufer such as the Alco APD-1 or APD- 054 will work quite well. The mufer should be located
a minimum of six inches (15 cm) to a maximum of 18 inches (46 cm) from the compressor for most effective
operation. The further the mufer is placed from the
compressor within these ranges the more effective it may be. If adequate attenuation is not achieved, use a
mufer with a larger cross-sectional area to inlet-area
ratio. The ratio should be a minimum of 20 to 1 with a
30 to 1 ratio recommended. The mufer should be from
four to six inches (10-15 cm) long.
Air Conditioning System Suction Line Noise and Vibration
Copeland Scroll compressors inherently have low sound and vibration characteristics. However, the sound and vibration characteristics differ in some respects from those of reciprocating compressors. In rare instances, these could result in unexpected sound complaints.
One difference is that the vibration characteristic of the scroll compressor, although low, includes two very close frequencies, one of which is normally isolated from the shell by the suspension of an internally suspended compressor. These frequencies, which are present in all compressors, may result in a low level “beat” frequency that may be detected as noise coming along the suction line into a house under some conditions. Elimination of the “beat” can be achieved by attenuating either of the contributing frequencies. The most important frequencies to avoid are line and twice-line frequencies for single-phase compressors and line frequency for three phase compressors. This is easily done by using one of the common combinations of design congurations described in Table 3. The scroll compressor makes both a rocking and torsional motion,
and enough exibility must be provided in the line to
prevent vibration transmission into any lines attached to the unit. In a split system the most important goal is to ensure minimal vibration in all directions at the service valve to avoid transmitting vibrations to the structure to which the lines are fastened.
A second difference of the Copeland Scroll is that under some conditions the normal rotational starting motion of the compressor can transmit an “impact” noise along the suction line. This may be particularly pronounced in three-phase models due to their inherently higher starting torque. This phenomenon, like the one described previously, also results from the lack of internal suspension, and can be easily avoided by using standard suction line isolation techniques as described in Table 3.
The sound phenomena described above are not usually associated with heat pump systems because of the isolation and attenuation provided by the reversing valve and tubing bends.
© 2010 Emerson Climate Technologies Printed in the U.S.A.
4
AE4-1312 R2
Single Phase Starting Characteristics
Start assist devices are usually not required, even if a system utilizes non-bleed expansion valves. Due to the inherent design of the Copeland Scroll, the internal compression components always start unloaded even if system pressures are not balanced. In addition, since internal compressor pressures are always balanced at startup, low voltage starting characteristics are excellent for Copeland Scroll compressors. Starting current on
any compressor may result in a signicant “sag” in
voltage where a poor power supply is encountered. The low starting voltage reduces the starting torque of the compressor and subsequently increases the start time. This could cause light dimming or a buzzing noise where wire is pulled through conduit. The start components listed in Table 7 will substantially reduce start time and consequently the magnitude and duration of both light dimming and conduit buzzing.
PTC Start Components
For less severe voltage drops or as a start boost, solid
state Positive Temperature Coefcient devices rated
from 10 to 25 ohms may be used to facilitate starting for any of these compressors.
Electrical Connection
The orientation of the electrical connections on the Copeland Scroll compressors is shown in Figure 4. Three electrical connection options are available for these compressors. These include the “Molded Plug” one piece push-on connection, available in certain
markets, and “Quick Connect” ag termination available
on all scrolls of this size. Some four-ton and larger models also offer “T-block Screw Connection” for ring termination.
Deep Vacuum Operation
Scrolls incorporate internal low vacuum protection and will stop pumping (unload) when the pressure ratio exceeds approximately 10:1. There is an audible increase in sound when the scrolls start unloading.
Copeland Scroll compressors (as with any refrigerant compressor) should never be used to evacuate a refrigeration or air conditioning system. The scroll compressor can be used to pump down refrigerant in a unit as long as the pressures remain within the operating envelope shown in Figure 5. Prolonged operation at low suction pressures will result in overheating of the scrolls and permanent damage to the scroll tips, drive bearings and internal seal. (See AE24-1105 for proper system evacuation procedures.)
Nomenclature
The model numbers of the Copeland Scroll compressors include the approximate nominal 60 HZ capacity at standard operating conditions. An example would be the ZR24K3-TFD, which has 24,500 Btu/hr (7 kw) cooling capacity at the ARI high temperature air conditioning rating point when operated on 60 Hz. Note that the same compressor will have approximately 5/6 of this capacity or 20,200 Btu/hr (5.9 kw) when operated on 50 Hz current. Please refer to Online Product Information at www.emersonclimate.com for details.
Shell Temperature
Certain types of system failures, such as condenser or evaporator fan blockage or loss of charge, may
cause the top shell and discharge line to briey but
repeatedly reach temperatures above 350ºF (177ºC) as the compressor cycles on its internal protection devices. Care must be taken to ensure that wiring or other materials, which could be damaged by these temperatures, do not come in contact with these potentially hot areas.
Suction and Discharge Fittings
Copeland Scroll compressors have copper plated steel
suction and discharge ttings. These ttings are far more rugged and less prone to leaks than copper ttings
used on other compressors. Due to the different thermal properties of steel and copper, brazing procedures may have to be changed from those commonly used. See
Figure 6 for assembly line and eld brazing procedures.
Three Phase Scroll Compressors
Scroll compressors, like several other types of compressors, will only compress in one rotational direction. Direction of rotation is not an issue with single phase compressors since they will always start and run in the proper direction (except as described in the section “Brief Power Interruptions”). Three phase compressors will rotate in either direction depending upon phasing of the power. Since there is a 50-50 chance of connecting power in such a way as to cause rotation in the reverse direction, it is important to
include notices and instructions in appropriate locations on the equipment to ensure proper rotation direction is achieved when the system is installed and operated. Verification of proper
rotation direction is made by observing that suction pressure drops and discharge pressure rises when the compressor is energized. Reverse rotation will result in substantially-reduced current draw compared to normal values.
© 2010 Emerson Climate Technologies Printed in the U.S.A.
5
AE4-1312 R2
There is no negative impact on durability caused by operating three phase Copeland Scroll compressors in the reversed direction for a short period of time (under one hour) but oil may be lost. After several minutes of reverse operation, the compressor’s internal protector will trip. If allowed to repeatedly restart and run in reverse without correcting the situation, the compressor will be permanently damaged because of oil loss to the system. Oil loss can be prevented during reverse rotation if the tubing is routed at least six inches (15 cm) above the compressor. All three-phase scroll compressors are wired identically internally. As a result,
once the correct phasing is determined for a specic
system or installation, connecting properly phased
power leads to the identied compressor electrical
(Fusite) terminals will maintain proper rotation direction. See Fig 4. It should be noted that all three phase scrolls will continue to run in reverse until the protector opens or the phasing is corrected.
Brief Power Interruptions
Brief power interruptions (less than 1/2 second) may result in powered reverse rotation of single-phase Copeland Scroll compressors. This occurs because high-pressure discharge gas expands backward through the scrolls during power interruption, causing the scroll to orbit in the reverse direction. When power is reapplied while reverse rotation is occurring, the compressor may continue to run in the reverse direction for some time before the compressor’s internal protector trips. This has no effect on durability. When the protector resets, the compressor will start and run normally.
To avoid disruption of operation, an electronic control that can sense brief power interruptions may be used to lock out the compressor for a short time. This control could be incorporated in other system controls (such as defrost or thermostat), or be a stand-alone control.
Functional specications for this control as well as a
suggested wiring diagram are shown in Figure 3.
Because three-phase models have high enough torque to prevent reverse rotation after power interruptions no time delay is necessary.
ASSEMBLY LINE PROCEDURES
Installing the compressor
Scroll compressors leave the factory dehydrated with a positive dry air charge. Plugs should not be removed from the compressor until the compressor has had
sufcient time to warm up if stored outside and is ready
for assembly to the unit. It is suggested that the larger
suction plug be removed rst to relieve the internal
pressure. Removing the smaller discharge plug could
result in a spray of oil out of this tting since some oil
would accumulate in the head of the compressor after Emerson test runs the compressor. The inside of both
ttings should we wiped with a lint free wipe to remove
residual oil prior to brazing. A compressor containing mineral oil should never be left open longer than 15 minutes or 5 minutes if it contains POE oil.
Assembly Line Brazing Procedure Figure 6 discusses the proper procedures for brazing
the suction and discharge lines to a scroll compressor.
It is important to ow nitrogen through the system
while brazing all joints during the system assembly process. Nitrogen displaces the air and prevents the
formation of copper oxides in the system. If allowed
to form, the copper oxide akes can later be swept
through the system and block screens such as those protecting capillary tubes, thermal expansion valves, and accumulator oil return holes. The resulting blockage of oil or refrigerant may do damage resulting in compressor failure.
Pressure Testing
The pressure used on the line to meet the UL burst pressure requirement can not be higher than 400 psig. Higher pressure might result in permanent deformation of the compressor shell and possibly cause rotor slip.
Assembly Line System Charging Procedure
Systems should be charged on both the high and low sides simultaneously. The majority of the charge should be placed in the high side of the system to prevent low
volt start difculties, Hipot failures, and bearing washout during rst-time start on the assembly line. It is best to
charge only vapor into the low side of the system. Do not operate compressor without enough system charge to maintain at least 7 psig (0.5kg/cm2) suction pressure. Do not operate with a restricted suction. Do not operate with the low pressure cut­out disabled. Allowing pressure to drop below 7 psig
(0.5 kg/cm2) for more than a few seconds may overheat scrolls and cause early drive bearing damage. Do not use compressor to test opening set point of a high pressure cutout. Bearings are susceptible to damage before they have had several hours of normal running for proper break in.
“Hipot” (AC High Potential) Testing
Copeland Scroll compressors are congured with the
motor down and the pumping components at the top of the shell. As a result, the motor can be immersed in refrigerant to a greater extent than hermetic reciprocating compressors when liquid refrigerant is present in the shell. In this respect, the scroll is more like
© 2010 Emerson Climate Technologies Printed in the U.S.A.
6
Loading...
+ 12 hidden pages