Emerson Yarway TempLowHT Installation And Maintenance Instructions Manual

YARWAY TempLowHT DESUPERHEATER
InstallatIon and MaIntenance InstructIons
Before installation these instructions must be fully read and understood
MODEL 59/69/79
ATTENTION WHEN PUTTING INTO OPERATION
Readjust ‘Stuffing box’ immediately as required (see separate section). Leakage is out of guarantee.
INSTALLATION OF THE TempLowHT DESUPERHEATER
Before installation, check the TempLowHT Desuperheater, actuator and accessories for any visible damage. Check that the information on the documentation, identification plate and tag number complies with the order specification. Remove the TempLowHT Desuperheater carefully from its packaging, liftingby means of straps around the body. Do not use the water inlet connection, yoke, actuator or any of its accessories for lifting. Leave the flange covers until ready to install in the pipework.
WARNING
The hoisting lug is for the actuator only, NOT for a total assembly!
When installing the TempLowHT Desuperheater use gaskets and bolting material in accordance with the relevant piping code, for example ASME B31.1 or AD 2000/EN. Place the gasket onto the mounting flange and carefully insert the nozzle into the branch pipe. Ensure that the spray cylinder is pointed with the direction of the steam flow before tightening the mounting bolts (see figure 3).
in place during transportation,
RECOMMENDATIONS (acid cleaning ofsteam boilers)
Remove TempLowHT Desuperheaters from thepiping prior to acid cleaning!
UNPACKING
The Yarway TempLowHT Desuperheater is packed with the greatest of care in wooden boxes or cartons for protection during handling and transit to site. After hydrostatic testing, the TempLowHT Desuperhater is flushed through with a high grade of preservative to protect machined and internal surfaces from corrosion. If it is found, however, that damage has occurred during shipment, then this should be reported immediately to your forwarder or Yarway representative. Particular care should be taken when removing the TempLowHT Desuperheater from its packing and your special attention is required to check carefully that no damage has occurred to flange faces, threading, actuators, connecting pipes, etc. (See figure 1).
NOTE
The TempLowHT Desuperheaters should be installed free of ‘forces, moments and torques’.
The TempLowHT Desuperheater is provided with a standard lower body length, as specified in the contract drawing and the mounting branch for the steam pipework must be manufactured to suit. The length of this branch should be such, that the centerline of the spray cylinder is located on the centerline of the steam pipe (± 5 mm).
The mounting branch should be 3” (DN 80) for Model 59, 4” (DN 100) for Model 69 and 5” (DN125) for Model 79 nominal bore, maximum pipe schedule 160 for clearance purposes (check the applicable power piping code). Check the certified drawing for flange details.
© 2017 Emerson. All Rights Reserved.Emerson.com/FinalControl VCIOM-03239-EN 18/04
YARWAY TempLowHT DESUPERHEATER
InstallatIon and MaIntenance InstructIons
The minimum pipe run, required downstream of the TempLowHT Desuperheater, varies with each individual application and would be specified by Yarway at the enquiry stage. This straight run is needed to prevent erosion due to impingement of water droplets against pipewalls, valves and fittings and is normally
FIGURE 1 - MODEL 59/69/79
Check for damages
Identification plate
FIGURE 3
Water flange positions
Steam line
inthe order of 4 to 6 meters, as a minimum (no upstream straight length is normally required). The distance from the TempLowHT Desuperheater to the temperature sensor is nominally 12to 15meters, although the distance specific to theapplication would be advised by Yarway at the enquirystage. Longerdistances will ensure
Check for damages
Check for damages
Steam flow
that full evaporation of the water will take place at lowersteam velocities. The temperature sensor should be located in the upper half of the pipe, avoid branching of the steam pipework between the TempLowHT Desuperheater and the sensor (see figure 4).
Steam line
FIGURE 4
Water
Steam
FP9 FP12 FP3 FP6
Handwheel positions
HWW HWN HWE HWS
Air
Air
Steam flow
Item Description
1 Temperature sensor 2 Temperature transmitter 3 Temperature controller 4 TempLowHT Desuperheater 5 Air filter regulator 6 Safety relief valve 7 Strainer 8 Check valve 9 Flange 10 E/P-positioner
2
YARWAY TempLowHT DESUPERHEATER
InstallatIon and MaIntenance InstructIons
Pipe bends should always be of the long radius type to assist in keeping the water droplets in suspension, until complete evaporation has taken place. Installation may be in vertical or horizontal piping, but the direction of water injection should always be with the steam flow. The TempLowHT Desuperheater may be mounted at 90° to the steam pipe, for all steam flow orientations, but avoid installation in the vertically downwards position, wherever possible (see figure 5).
Yarway supplies the TempLowHT Desuperheater as follows: Identification number: xx. 59. xxxxx - Forged type with 3” (DN 80)
mounting flange
xx. 69. xxxxx - Forged type with 4” (DN 100)
mounting flange
xx. 79. xxxxx - Forged type with 5” (DN 125)
mounting flange
NOTE
Horizontal orientated TempLowHT Desuperheater has to be installed with a support for weightcompensation.
The water supply should be of a good quality; clean and filtered, for example boiler feed water and should have a constant pressure as specified in the order documents. Each water supply line should be protected with its own individual strainer with a maximum element perforation size of 0.1 mm (0.4 mm acceptable for nozzles ‘E’ size and up). Where there are positive shut-off components in the water supply (including electric actuators) then a safety relief valve of an approved type should be fitted. As in the case of thesteam pipework, accordance with the relevant piping code. Flushout the water line before connecting to the TempLowHT Desuperheater mounting flange (see figure 6).
use gasketing and bolting in
START-UP
Ensure that all components are installed correctly. Connection of electrical supplies and instrument air piping should be in accordance with the manufacturer’s instruction manual. Verify and adjust, ifnecessary, set points for filter regulators and valve positioners, following the manufacturer’s recommendations. Similarly, calibrate thetemperature transmitter/controller, verifying automatic response to temperature changes.
Warm the steam main and open the valve in the water supply. Check the water pressure at the TempLowHT Desuperheater. Verifytheoperation of the temperature transmitter and controller by manually increasing and decreasing the output signal and observing indicated and recordedtemperatures. When satisfactory coordination between instrument signals and temperature are attained, adjustment of the set point can be made and the system transferred to automaticoperation. It is recommended to record the various steam coordinates, over a sustained period, to verify operation, adjusting where necessary.
FIGURE 5
FIGURE 6
Check valve
Strainer
Safety valve
TC TT
3
Loading...
+ 7 hidden pages