Emerson XEV22D Installation And Operation Manual

Page 1
026-1206 Rev 3 13-DEC-2012
XEV22D Driver for Stepper
Electronic Expansion Valves Installation
and Operation Manual
Page 2
Page 3
Emerson Climate Technologies Retail Solutions
1065 Big Shanty Road NW, Suite 100
Kennesaw, GA 30144, USA
Fax: 770-425-9319
Page 4
Page 5
Table of Contents
1 INTRODUCTION.......................................................................................................................................................... 1
1.1. GENERAL WARNING ..................................................................................................................................................... 1
2 OVERVIEW................................................................................................................................................................... 1
2.1. GENERAL DESCRIPTION ................................................................................................................................................ 1
2.2. ORDERING CODE .......................................................................................................................................................... 1
3 WIRING CONNECTIONS........................................................................................................................................... 2
4 WIRING GUIDELINES................................................................................................................................................ 3
5 MOUNTING AND POWERING ................................................................................................................................. 4
5.1. INSTALLATION .............................................................................................................................................................. 4
5.2. P
OWERING THE XEV22D ............................................................................................................................................. 4
5.2.1. Choosing Transformer Sizes................................................................................................................................. 4
5.2.2. XEV22D Power Wiring......................................................................................................................................... 5
5.2.3. Wire Type and Maximum Distances ..................................................................................................................... 5
6 VALVE CONNECTIONS AND CONFIGURATION ............................................................................................... 6
7 ABSOLUTE MAXIMUM POWER............................................................................................................................. 8
8 FRONT PANEL............................................................................................................................................................. 9
8.1. KEYS AND FUNCTIONS ................................................................................................................................................. 9
8.2. XEV22D LEDS............................................................................................................................................................ 9
9 USER INTERFACE .................................................................................................................................................... 10
9.1. TO SEE THE READ-ONLY VALUES ............................................................................................................................. 10
9.2. TO SEE THE SETPOINT ................................................................................................................................................ 10
9.3. TO MODIFY THE SETPOINT ......................................................................................................................................... 10
9.4. TO ENTER PR1 PARAMETERS LIST ............................................................................................................................. 10
9.5. TO ENTER PR2 PARAMETERS LIST ............................................................................................................................. 10
9.6. TO MODIFY THE PARAMETERS VALUE ...................................................................................................................... 10
9.7. HOW TO ASSIGN A MODBUS ADDRESS.................................................................................................................... 11
10 PARAMETERS.......................................................................................................................................................... 12
11 DIGITAL INPUTS..................................................................................................................................................... 17
12 FORCED OPENING................................................................................................................................................. 17
13 ELECTRICAL CONNECTIONS ............................................................................................................................ 17
13.1. PROBES ..................................................................................................................................................................... 17
14 RS485 SERIAL LINE................................................................................................................................................ 17
15 HOW TO USE THE HOT KEY............................................................................................................................... 18
15.1. HOW TO PROGRAM A HOT KEY FROM THE CONTROLLER (UPLOAD)...................................................................... 18
15.2. HOW TO PROGRAM THE CONTROLLER USING A HOT KEY (DOWNLOAD) ............................................................... 18
16 DISPLAY MESSAGES ............................................................................................................................................. 19
16.1. ALARM RECOVERY ................................................................................................................................................... 19
Table of Contents • v
Page 6
17 SPECIFICATIONS ................................................................................................................................................... 20
18 E2 MODBUS NETWORK WIRING ....................................................................................................................... 21
19 ECT MODBUS NETWORKING TO E2S............................................................................................................... 22
19.1. COM PORT ASSOCIATIONS - E2 VERSIONS 3.XX AND BELOW ................................................................................ 22
19.2. COM PORT ASSOCIATIONS - E2 VERSIONS 4.2 AND ABOVE ................................................................................... 23
19.3. E2 SETUP OF DEVICES .............................................................................................................................................. 23
19.3.1. Set Up Network Ports........................................................................................................................................ 23
19.3.2. Add and Connect the Device............................................................................................................................. 23
19.4. WIRING TYPES .......................................................................................................................................................... 25
19.5. MODBUS TERMINATION BLOCKS ........................................................................................................................... 25
20 STANDARD VALUES .............................................................................................................................................. 26
vi • XEV22D I&O Manual 026-1206 Rev 3 13-DEC-2012
Page 7
1 Introduction
2 Overview
1.1. General Warning
Please read the following safety precautions and
warnings before using this manual:
CAUTION!
• This manual is part of the product and should be kept near the controller for easy
and quick reference.
• The controller should not be used for purposes different from those described in this manual. It can­not be used as a safety device.
• Check the application limits before proceeding.
SAFETY PRECAUTIONS AND WARNINGS!
• Check that the supply voltage is correct
before connecting the controller.
• Do not expose to water or moisture: use the con­troller only within the operating limits and avoid sud­den temperature changes with high atmospheric humidity to prevent condensation from forming.
• Warning! Disconnect all electrical connections before performing any kind of maintenance.
• Fit the probe where it is not accessible by the end user. The controller must not be opened.
• In case of failure or faulty operation, send the controller back to Retail Solutions (see address) with a detailed description of the fault.
• Verify the maximum current that can be applied to each relay (see Section 17, Specifications).
• Ensure that the wires for probes, loads, and the power supply are separated and far enough from each other, without crossing or intertwining.
• In case of applications in industrial environ­ments, the use of main filters (our mod. FT1) in paral­lel with inductive loads could be useful.
2.1. General Description
The XEV22D controller is capable of driving a wide variety of stepper electronic expansion valves. The controller regulates the superheat (SH) of the flu­id that runs into the refrigeration unit to obtain opti­mized performance and functioning of the evaporator independent of climate or load conditions.
XEV22D controllers are equipped with two (2) probe inputs, one for a 4 to 20mA (or 0 to 5V) pres­sure transducer and another one for a Pt1000 or NTC temperature probe.
The LAN connection transmits the pressure signal to the other XEVs; this allows the use of only one pressure transducer in multiplexed cabinet applica­tions. The controller can also have two (2) configu­rable digital inputs, the first one is free of voltage and the other one is at high voltage, to simplify connec­tions with cooling request signal.
With the integrated display, it is possible to see the superheat (SH) value, the degree of valve opening, or the probe values; the local keyboard enables the con­troller to be programmed without any other devices.
An RS485 serial link connects the controller to other Emerson monitoring and supervising systems.
2.2. Ordering Code
Device
Name
XEV22D
Table 2-1 - Product Ordering Code
Dixell Code
XEV22D-1C0F0B
X0JFGAESG3NA-000
Emerson
Code
318-5001
General Warning Introduction • 1
Page 8
3 Wiring Connections
The superheat regulation is performed only when the cooling digital input is enabled. Figure 3-1 shows how
the device takes the request of cooling:
Figure 3-1 - How XEV22D Acts on Cooling Request
See Figure 3-2 for wiring. The “First Level” indicates the connections on the floor of the 4-DIN module and
“Second Level” indicates the connections on the first floor that are only for the stepper motor of the valve and for the Hot Key.
Figure 3-2 - XEV22D Wiring Connections
2 • XEV22D I&O Manual 026-1206 Rev 3 13-DEC-2012
Page 9
4 Wiring Guidelines
DEVICE TYPE RETAIL SOLUTIONS
ANALOG TEMP SENSOR DIGITAL INPUT
RS-485 NETWORK BELDEN #8761 #22-2 SHIELDED
PRESSURE TRANSDUCER **BELDEN #8771 #22-3 SHIELDED
*STEPPER VALVE Use valve manufacturer’s harness with a maximum length not
POWER LOADS AND VALVE
Table 4-1 - Wiring Guidelines
BELDEN #8761 #22-2 SHIELDED
Retail Solutions P/N 035-0002
Retail Solutions P/N 035-0002
BELDEN #8641 #24-2 SHIELDED
Retail Solutions P/N 135-8641
Retail Solutions P/N 135-8771
**#8771 for alternate 600v rated wire use BELDEN #8618 16 AWG
to exceed 30 feet (10 meters).
Allow a maximum wire size of 14 AWG (2 mm
2
).
Ordering Code Wiring Guidelines • 3
Page 10
5 Mounting and
Powering
The XEV22D is usually mounted by the Refriger­ation equipment manufacturer. Therefore, the install­er need only make the necessary connections between the boards and the site controller(s).
In some instances, an installer may be required to mount the XEV22D. There are no restrictions on the location of the XEV22D; however, the controller should be mounted in a location protected from mois­ture. Typically, mounting inside the electrical control panel of a package unit is acceptable.
5.1. Installation
The XEV22D uses a DIN mount installation.
Figure 5-1 - DIN Mounting
Mount: On a DIN rail (EN 50022,
DIN 43880) Fastened with screws via the removable plastic flaps
Material: PC-ABS Thermoplastic
Self-extinguishing: VO (UL94)
Comparative Tracking Index (CTI):
Color: Gray
Table 5-1- XEV22D Enclosure Specification
4 • XEV22D I&O Manual 026-1206 Rev 3 13-DEC-2012
300V
5.2. Powering the XEV22D
Retail Solutions supplies a wide variety of 24VAC transformers with varying sizes without center taps.
Table 5-2 shows the transformer sizes and are non
center-tapped.
5.2.1. Choosing Transformer Sizes
The transformer used to power the XEV22D
should have at least a 20VA rating. The XEV22D
should not share a transformer with any other de­vices.
Page 11
Transformer
Part Number
640-0040 50VA 110/208/220 VAC
640-0041 50VA 110 VAC
640-0042 50VA 220 VAC
Table 5-2- Transformer Compatible with XEV22D
VA Rating
Primary
Voltage
5.2.2. XEV22D Power Wiring
The XEV22D can be powered by one of the 50VA
non-center-tapped transformers listed in Table 5-2.
Neither side of the secondary should be connected to ground. Also, do not connect the center tap (if pro­vided on the transformer) to ground. The entire sec­ondary of the transformer should be isolated from any ground.
5.2.3. Wire Type and Maximum
Distances
Two-conductor non-shielded cables are the rec­ommended wire for connecting the transformer to the
XEV22D, see Table 5-3 for power wiring types.
Shielded cable should not be used for power wiring. The center tap should be left disconnected, if present on the transformer.
14AWG:
Feet = 1920/VA
18AWG:
Feet = 739/VA
(VA is the total VA rating of the controller)
For example, if you had an 18 VA load:
14 AWG: 24 ft.
18 AWG: 9ft. (rounded down)
Sensors requiring 24VAC should not be powered
from the same transformer powering the input board.
Any devices that will be connected to the XEV22D’s inputs or outputs must be powered with a separate 24VAC transformer.
Power Wiring Types 14 AWG Belden 9495 18 AWG Belden 9495
Table 5-3- Power Wiring Types
The wire length from the transformer determines the type wire gauge used. In most cases, the distance between the XEV22D and the transformer that sup­plies power to it is not enough to be of concern;
how­ever, it is very important NOT to exceed this maximum wire length or the controller will not oper­ate correctly.
Use these formulas to determine if the wire gauge
you are using fits within specification:
Powering the XEV22D Mounting and Powering • 5
Page 12
6 Valve Connections and Configuration
CAUTION! To avoid possible problems, before connecting the valve configure the driver by making the right changes on the parameters. Select the kind of motor (tEU parameter) and check if the valve is present in the tEP parameter table reported below:
tEP Model
0 Manual settings Par Par Par Par Par
1 Alco EX4-EX5-EX6 5 75 50 10 500
2 Alco EX7 10 160 75 25 500
3 Alco EX8 500 10 260 80 50 500
4 Danfoss ETS-25/50 7 262 10 10 300
5 Danfoss ETS-100 10 353 10 10 300
6 Danfoss ETS-250/400 11 381 10 10 300
7 Sporlan SEI 0.5-11 0 159 16 5 200
8 Sporlan SER 1.5-20 0 159 12 5 200
9 Sporlan SEI 30 0 319 16 5 200
10 Sporlan SER(I) G,J,K 0 250 12 5 200
11 Sporlan SEI 50 0 638 16 5 200
12 Sporlan SEH(I) 100 0 638 16 5 200
13 Sporlan SEH(I) 175 0 638 16 5 200
Table 6-1 - tEP Parameter Table
CAUTION! The maximum distance between an XEV22 controller and a valve must not exceed 30 feet (10 meters).
LSt
(steps*10)
uSt
(steps*10)
CPP
(mA*10)
CHd
(mA*10)
Sr
(step/s)
If you can locate your valve in the table, select the valve through the tEP parameter. This way, you can be
sure of the correct configuration (refer to Table 6-1).
Regarding connections, use Table 6-2 below for a quick reference on the connection mode for valves of dif-
ferent manufacturers. In any case, the unique and valid reference has to be considered the datasheet made by manufacturer of the valve:
Connection Numbering
4 BLUE WHITE BLACK
2 BROWN BLACK WHITE
3 BLACK RED RED
1 WHITE GREEN GREEN
Table 6-2 - 4-Wire Valves (Bipolar)
6 • XEV22D I&O Manual 026-1206 Rev 3 13-DEC-2012
ALCO EX*
SPORLAN
SEI-SEH
DANFOSS ETS
Page 13
Connection Numbering
4 ORANGE ORANGE
2 RED RED
3 YELLOW YELLOW
1 BLACK BLACK
5- Common GRAY GRAY
Table 6-3 - 5 to 6 Wire Valves (Unipolar)
NOTE: After making the connection, switch the XEV controller OFF and ON to make sure that the valve is positioned properly.
SPORLAN SAGINOMIYA
It is highly recommended that the maximum dis­tance of the stepper valve harness length between the valve and the XEV22D controller must not exceed 30 feet (10 meters).
If the valve harness length must be extended be­yond 30 feet (10 meters), Emerson Retail Solutions
provides an Inductor Extender (P/N 335-3500) for use
with Sporlan Valves ONLY.
The Inductor Extender (P/N 335-3500) is ONLY
for use with Sporlan Bipolar 4-wire stepper valves with 100 ohm or 75 ohm phase resistance.
When using the Inductor Extender, the XEV22D controller “CPP” parameter setting MUST be less than 20; otherwise the Valve, Controller, and/or In­ductor Extender will be damaged or have its life ex­pectancy drastically shortened.
Refer to Table 6-1 for the list of the XEV series
controller supported Sporlan Stepper valves. The In­ductor Extender can ONLY be used with Sporlan Bi­polar Stepper valves that have a setting of 16 or 12 in the “CPP” column.
The recommended CPP parameter should NOT be increased to create AC voltage at the valve, if the valve harness length is over 30 feet, an Inductor Ex­tender MUST be added into the 4-wire valve harness.
When using the Inductor Extender
(P/N 335-3500), any stepper valve harness extensions
MUST not exceed 170 feet total length.
Use 14 AWG wire for valve harness extensions in conduit. If the valve harness extension is not in con­duit, use 16 AWG or 14 AWG shielded cable with the shield terminated to an earth grounded chassis. For valve harness extensions over 100 feet, 14 AWG shielded cable is recommended.
Using an AC volt meter to measure voltage at the Valve will not produce accurate results with a voltage chopper constant current stepper valve drivers as used in XEV22D controllers.
Instead, an AC current meter can be used to mea­sure valve milliamps as a field verification method.
If the current measurement using the method de­scribed below is less than the recommended value by more than 20%, the CPP parameter may be increased by up to 2 (12 to 14 or 16 to 18). The CPP parameter MUST be less than 20 when using the Inductor Ex-
tender (P/N 335-3500).
For a CPP parameter of 12, the measured current should be near 120 mA AC, for a CPP setting of 16, the measured current should be near 160 mA AC.
Below is a description of using an AC current me­ter to test a stepper valve:
Using an AC Volt meter to measure the voltage across a stepper valve will not produce accurate re­sults if the valve is driven by a voltage chopper con­stant current valve driver. XEV controllers use a voltage chopper constant current stepper valve driver.
The stepper valve voltage can be checked by using an in-line True RMS AC current meter. The AC cur­rent meter will produce a more accurate reading than AC voltage due to the valve drive switching the volt­age to the valve on and off at a frequency much higher than a voltmeter can read. The voltage chopper con­stant current valve driver maintains a constant AC current through the valve while the valve is moving, which makes an AC mA meter ideal to test the valve. The current can be read in each of the stepper valves two windings/phases. Due to the fact that current un­like voltage is the same at any point in a wire, the cur­rent test can be performed at the XEV22D controller or at the valve, and will have the same results. It is no longer necessary to take apart the case or get on a lift to access the valve, the in-line current test can be per­formed at the most convenient location.
An AC clamp meter will not have enough resolu­tion to read the stepper valve milliamps.
If the current meter used is not a True RMS meter, the readings will be approximately10% higher due to the stepper drive producing square waves and not sin waves.
1. Power down the XEV22D controller.
2. Disconnect the Sporlan valve white wire from the XEV22D controller.
3. Connect the meter red lead from the meter 10A ter­minal to the Sporlan valve white wire.
4. Connect the meter black lead from the meter COM terminal to the XEV22D controller where the Spor­lan white wire was removed.
5. Change the meter dial selector to AC amps (~A).
Powering the XEV22D Valve Connections and Configuration • 7
Page 14
6. Note the mA terminal on the meter. It should be la­beled 400 mA or 300 mA.
7. Power up the XEV22D controller.
8. Cycle the valve and verify the meter AC amp read­ing is less than 0.3A.
7 Absolute
Maximum Power
CAUTION: 0.3A is 300mA; if the AC amp reading in step 8 was above your meters mA terminal label: STOP and check. DO NOT proceed or your meter will be damaged.
9. If step 8 reading was less than 0.3A, power down
the XEV22D and move the meter red lead from the meter 10A terminal to the meter 400 mA or 300mA terminal.
10. If the meter dial selector has an AC mA selection (~mA), change to the AC mA selection.
11. Power up the XEV22D controller.
12. Cycle the valve and record the maximum constant meter AC mA reading.
13. The mA reading should be within 20% of the Phase current CPP setting.
14. The valve voltage can be calculated by multiplying the mA reading by the valve coil resistance. For ex­ample: 102 mA x 100 ohm valve coil = 10.2V. 150mA x 75 ohm valve coil = 11.25V.
The 2nd valve coil current/voltage can be tested by repeating the above procedure on the Sporlan valve Green wire and XEV22D controller.
The in-line AC mA meter is also compatible with the constant voltage stepper valve drivers used in the MultiFlex ESR, CC100, and CCB.
The XEV22D controller is capable of driving a
wide range of stepper valves; listed in Table 7-1 are
the maximum values of current that the actuator can supply to the stepper wiring. Use the TF20D trans­former.
NOTE: The electrical power absorption of the valve can be unrelated to refrigeration power that the valve has. Before using the actuator,
read the technical manual of the valve sup­plied by the manufacturer and check the maximum cur­rent used to drive the valve to verify that they are lower than indicated below in Table 7-1.
Bipolar Valves
VALVE
TYPE
Table 7-1 - Maximum Allowable Valve Current
(4 Wires)
Uni-polar Valves
(5 to 6 Wires)
Maximum Current
0.9A
Maximum Current
0.33A
8 • XEV22D I&O Manual 026-1206 Rev 3 13-DEC-2012
Page 15
8 Front Panel
Key Function
To lock and unlock the keyboard.
To enter programming mode.
Table 8-1- XEV22D Front Panel Keys and Functions
8.2. XEV22D LEDS
Each LED function is described in Table 8-2:
LED Mode Function
ON Low pressure alarm
Figure 8-1 - XEV22D Front Panel
8.1. Keys and Functions
Table 8-1 shows the keys found on the front panel
of the XEV22D and their corresponding functions:
Key Function
To display and to modify the set point. In programming mode, it selects a parame­ter or confirms a value.
By pressing and releasing this key, it is possible to see the values of the probes. In programming mode, it slides the codes of the parameters or increases their val­ues.
ON
OFF Valve is completely closed
BLINKING Valve is moving
ON Valve is completely opened
BLINKING
OFF
ON Superheat alarm
Table 8-2 - XEV22D LEDs
Maximum operating pres­sure alarm
Serial communication present
Serial communication absent
In programming mode, it slides the codes of parameters or decreases their values.
Key Combinations
Table 8-1- XEV22D Front Panel Keys and Functions
Keys and Functions Front Panel • 9
Page 16
9 User Interface
2. The device will display the first parameter in Pr1
menu.
9.5. To Enter Pr2
9.1. To See the Read-Only Values
1. Press and release the UP arrow key.
2. The first read-only label is displayed.
3. Slide labels using the UP or DOWN arrow keys.
4. Press the SET key to see the read-only value. To
change and view the parameter, press SET.
5. To exit the fast access menu, press and release the SET + UP arrow keys or wait for the device time­out for 3 minutes.
9.2. To See the Setpoint
1. Press the SET key until the setpoint is displayed.
2. To return and view the temperature, wait for 5 sec­onds or press the SET key again.
9.3. To Modify the Setpoint
Parameters List
To enter to Pr2 parameters list:
1. Enter the Pr1 level menu.
2. Select Pr2 parameter and press SET.
3. The PAS label will be displayed followed by a blinking 0.
4. Insert 321 password using the UP and DOWN ar-
row keys.
To change the setpoint value, operate as follows:
1. Press the SET key until the set point is displayed.
2. Use the UP or DOWN arrow keys to change its val­ue.
3. Press SET to store the new value.
9.4. To Enter Pr1 Parameters List
To enter in Pr1 level menu:
1. Press the SET + DOWN arrow keys for about 3 sec­onds.
9.6. To Modify the Parameters Value
To change the parameter’s value operate as fol-
lows:
1. Enter the programming mode by pressing the SET and DOWN arrow keys for about 3 seconds.
2. Select the required parameter.
3. Press the SET key to display its value.
4. Use the UP or DOWN arrow keys to change its val­ue.
5. Press the SET key to store the new value and move to the next parameter.
6. To exit, press SET + UP or wait 30 seconds without
pressing a key.
NOTE: The set value is stored even when the time-out expires and ends the procedure.
10 • XEV22D I&O Manual 026-1206 Rev 3 13-DEC-2012
Page 17
9.7. How to Assign a MODBUS Address
1. To enter the programming mode, press and hold the SET and DOWN arrow keys together for about three (3) seconds or until the dots at the top of the display start flashing.
2. Arrow down to PR2 and press SET to select.
3. PAS for password will display and flash.
4. Use the arrow keys to set the 321 password. Press
SET to save.
NOTE: If a time-out occurs while setting the password (PR2 flashes), press SET to resume entering the password.
5. Use the arrow keys to scroll through and locate
nod. Press SET. Use the arrow keys to scroll
through and locate Std. Press SET.
6. Use the arrow keys to scroll through and locate
Adr. Press SET. Use the arrow keys to choose the
address number of the device. Press SET to save.
7. To exit, press the SET and UP arrow keys together or wait 15 seconds without pressing a key.
How to Assign a MODBUS Address User Interface • 11
Page 18
10 Parameters
NOTE: All pressure parameters are relatives or absolutes depending on the PrM parameter.
Code Description Function
REGULATION
Fty Kind of gas (R22, 134, 404, 407, 410, 507, CO2)
Type of gas used by plant.
ing of all systems.
PEo Probe error opening percentage (0 to 100%)
If a temporary probe error occurs, valve opening percentage is PEo until PEd time is elapsed. If PEo is different from 0, it ensures cooling also
with probe error, because even if the device cannot calculate superheat,
the valve can work at PEo percentage.
PEd Probe error delay before stop-
ping regulation
tEU Type of stepper motor (uP- bP)
tEP Predefined valve selection (0 to 13)
HFS Kind of motor movement: (HAF; FUL)
LSt Minimum number of steps (0 to Ust)
(0 to 239 sec – 240 = On = unlimited)
If the probe error duration is bigger than PEd, valve closes completely. The Pf message is displayed. If PEd = On, valve opening is PEo until
probe error finishes.
Selects the kind of valve.
uP = 5 to 6 wires unipolar valves bP = 4 wires bipolar valves
CAUTION! By changing this parameter, the valve has to be re-initial­ized.
If tEP = 0, the user has to modify all the parameters of configuration in order to use the valve. If tEP is different from 0, the controller performs a fast configuration of the following parameters: LSt, Ust, Sr, CPP, and CHd. To select the correct value, refer to Table 6-1.
If tEP is different from 0, previous configuration of LSt, Ust, Sr, CPP, and CHd are overwritten.
• HAF = half step. Use this setting for the unipolar valve.
• FUL = half step. Use this setting for the bipolar valve.
Selects the minimum number of steps. At this number of steps, the valve should be closed. Read the manufacturer datasheet to set this parameter correctly. The number of steps should be set within the advised range of functioning.
CAUTION! When this parameter is changed, the valve must be re-ini­tialized. The controller performs this procedure automatically and re­starts its normal functioning when the programming mode ends.
Fundamental parameter for correct function-
Table 10-1 - List of Parameters
12 • XEV22D I&O Manual 026-1206 Rev 3 13-DEC-2012
Page 19
Code Description Function
Ust Maximum number of steps (LSt to 800*10)
Selects the maximum number of steps. At this number of steps, the valve should be opened completely. Read the datasheet provided by the valve manufacturer to set this parameter correctly. The maximum number of steps should be set within the advised range of functioning.
CAUTION! When this parameter is changed, the valve must be re-ini­tialized. The controller performs this procedure automatically and re­starts its normal functioning when the programming mode ends.
Sr Step rate (10 to 600 step/sec)
Maximum speed to change a step without losing precision (= losing steps). Set parameter under the maximum speed.
CPP Current per phase (Only bipolar
valves)
CHd Holding current per phase
(Only bipolar valves)
(0 to 100 * 10mA) Maximum current per phase used to drive valve.
(0 to 100 * 10mA) The current per phase when the valve is stopped for more than 4 minutes.
oPE Start opening percentage (0 to 100%)
Opening valve percentage when the start function is active and during
post defrost phase. This phase duration is SFd time.
SFd Start function duration (0.0 to 42.0 min: tens of seconds)
It sets start function duration and post-defrost duration. During this
phase, the alarms are neglected.
Sti Stop regulation interval (0.0 to 24.0 hours: tens of minutes)
After regulating continuously for Sti time, the valve closes for Std time
to prevent ice from forming.
Std Stop duration (0 to 60 min)
Defines the stop regulation time after Sti. During this stop, display shows
StP message.
MnF Maximum opening percentage
at normal functioning
(0 to 100%) During regulation, it sets the maximum valve opening percentage.
FOP Forced opening percentage (0 to 100 - not used; nU)
If FOP = not used; nU, valve works with regulation algorithm. If FOP is different from not used; nU, the valve stays at FOP opening percent-
age. This function could be useful during plant starting or during service operations.
PI PARAMETERS (For use of trained staff only)
Pb Proportional band
(0.1 to 50.0 / 1 to 90°F)
PI proportional band. A value
bigger than 5°C is advised.
Table 10-1 - List of Parameters
How to Assign a MODBUS Address Parameters • 13
Page 20
Code Description Function
rS Band offset
(-12.0 to 12.0°C / -21to21°F) PI band offset. It moves the pro-
portional band of the PI. With rS = 0, the band is between Set to Set + Pb.
InC Integration time (0 to 255 sec)
PI integration time
PROBE PARAMETERS
tPP Type of pressure transducer (420 – 5V – LAn)
Sets the type of pressure transducer to use: 420 = 4 to 20mA pressure transducer; 5V = 0 to 5V ratiometric transducer; LAn = the pressure sig-
nal comes from another XEV module.
LPP Enable pressure probe sending
in LAN
(n to Y) If LPP = Y, the value of pressure read by device is sent in LAN. Only
one device of the LAN can have LPP = Y.
PA4 Probe value At 4mA or At 0V (-1.0 to P20 bar/ -14 to PSI)
Pressure value measured by probe at 4mA or at 0V (related to PrM pa-
rameter).
P20 Probe value 20mA or At 5V (PA4 to 50.0 bar/ 725 psi)
Pressure value measured by probe at 20mA or at 5V (related to PrM pa-
rameter).
OPr Pressure probe calibration (-12.0 to 12.0 bar/ -174 to 174 psi)
ttE Type of temperature probe (PtM to ntC)
Sets the kind of probe used by the controller: PtM = Pt1000, ntC = NTC
probe.
otE Temperature probe calibration (-12.0 to 12.0°C/ -21 to 21°F)
DIGITAL INPUTS
i1P Digital input 1 (free of voltage)
digital input polarity
i1F Digital input 1 (free of voltage)
digital input function
d1d Digital input 1 (free of voltage)
activation delay
i2P Digital input 2 (high voltage)
digital input polarity
i2F Digital input 2 (high voltage)
digital input function
d2d Digital input 2 (high voltage)
activation delay
(CL, OP) CL = activated when closed; OP = activated when opened
(CCL
, rL)
CCL = cooling call; rL = digital input activates relay
(0 to 255 min)
This activation delay is used only if digital input is configured as rL. (CL,OP)
CL = activated when closed; OP = activated when opened (CCL, rL)
CCL = cooling call; rL = digital input activates relay
(0 to 255 min)
This activation delay is used only if digital input is configured as rL.
ALARM
dAo Alarm delay after restarting reg-
ulation
(0.0 to 42.0 min: tens of seconds)
Time between digital input activation (configured as CCL) and alarm signaling. The LSH alarm is always signaled also during this time.
Table 10-1 - List of Parameters
14 • XEV22D I&O Manual 026-1206 Rev 3 13-DEC-2012
Page 21
Code Description Function
tdA Type of alarm signaled by relay (ALL, SH, PrE, di)
ALL = all alarm; SH = superheat alarm; PrE = pressure alarm; di = ac- tivation only when digital input configured as rL is activated.
LPL Lower pressure limit for super-
heat regulation
(PA4 to P20 bar/ psi) When the suction pressure comes down to LPL, the regulation is per-
formed with a LPL fixed value for pressure; when the pressure comes back to LPL, the normal pressure value is used. (related to PrM param-
eter).
MOP Maximum operating pressure
threshold
(PA4 to P20 bar/ psi)
If the suction pressure exceeds the maximum operating pressure value, the controller signals a condition with a High Pressure alarm LED (relat-
ed to PrM parameter).
LOP Lowest operating pressure (PA4 to P20 bar/ psi)
If the suction pressure comes down to this value, a low pressure alarm is
signaled with Low Pressure alarm LED (related to PrM parameter).
PHY Pressure alarm hysteresis (0.1 to 5.0 bar/ 1 to 72 PSI)
Alarm hysteresis to disable alarm signaling.
dML delta MOP-LOP (0 to 100%)
When a MOP alarm occurs, the valve will close at the dML percentage every one second until the MOP alarm is active. When LOP occurs, the valve will open at the dML percentage every one second until LOP
alarm is active.
MSH Maximum superheat alarm (LSH to 32.0°C/ LSH to 176°F)
When the superheat exceeds this value, a high superheat alarm is sig-
naled after interval SHd.
LSH Lowest superheat alarm (0.0 to MSH
°C/ 32 to MSH°F)
When the superheat goes down to this value, a low superheat alarm is
signaled after interval SHd.
SHy Superheat alarm hysteresis (0.0 to 25.5°C/ 1 to 77°F)
Hysteresis for superheat alarm deactivation.
SHd Superheat alarm activation de-
lay
(0 to 255 sec)
When a superheat alarm occurs, the time SHd has to pass before signal-
ing alarm.
FrC Fast-recovery constant (0 to 100 sec)
Increases the integral time when SH is below the setpoint. If FrC = 0,
fast-recovery function is disabled.
DISPLAY
Lod Local display Display: (SH, PEr, P1, P2)
SH = superheat; PEr = valve opening percentage; P1 = value of temper- ature measured; P2 = pressure measured by P2 probe;
CF Temperature measurement
units
(°C to °F)
°C = Celsius degree; °F = Fahrenheit degree
CAUTION! By changing the measurement unit, the regulation parame­ters have to be changed correctly.
PMU Pressure measurement units (bAr, PSI)
bAr = bar; PSI = psi
CAUTION! By changing the measurement unit, the regulation parame­ters have to be changed correctly.
rES Resolution (only °C) (dE to in)
Whether a whole number or decimal point is used in temperature reading
Table 10-1 - List of Parameters
How to Assign a MODBUS Address Parameters • 15
Page 22
Code Description Function
PrM Pressure visualization mode (rEL to AbS)
rEL = relative pressure; AbS = absolute pressure
All pressure parameters depend on this parameter.
CLP Cooling percentage (Read only)
Displays the percentage of time during which the cooling call was active
in the time interval defined by parameter CLt.
tP1 Temperature probe value (Read only)
Shows the temperature probe value from P1.
PPr Pressure probe value (Read only)
Shows the pressure probe value. The value depends on PrM.
tP2 Temperature from P2 Shows the temperature obtained from conversion of pressure value.
OPP Opening percentage Shows the actual opening percentage of the valve.
d1S Free of voltage digital input
state
(Read only) Shows the free of voltage digital input.
d2S High voltage digital input state (Read only)
Shows the high voltage digital input state.
Adr RS485 serial address (1 to 247)
Identifies the controller address when connected to a MODBUS compat­ible monitoring system.
Mod MODBUS (AdU to StD)
AdU = (Only for XWEB systems) In this case, the XEV and the thermo-
static controller are considered standalone controller (it requires a cus-
tom library for XWEB); StD = to use XEV in standalone mode, in this
case normal MODBUS-RTU protocol is used.
Ptb Parameters map (Read only)
It identifies the parameters map written by factory.
rEL Release firmware (Read only)
It shows the firmware release.
Pr2 Second level menu
Table 10-1 - List of Parameters
16 • XEV22D I&O Manual 026-1206 Rev 3 13-DEC-2012
Page 23
11 Digital Inputs
The XEV22D comes with two (2) digital inputs: a voltage-free input and a high voltage input; both can be configured as cooling call. In this way the cooling signal can come from the controllers with direct load outputs or via the controllers with voltage-free out­puts. One of these inputs must be configured as the cooling call.
12 Forced Opening
13.1.Probes
The recommended temperature probe placement is
illustrated in Figure 13-1, between 0 and 180 degrees
of inclination with respect to the horizontal pipe sec­tion. For suction pressure probes, there is no particu­lar recommendation.
If necessary, change the FOP parameter to force the valve to open. For example, if FOP is set to 50 (FOP = 50), the valve will be opened at half of full
scale.
To disable this function, set the FOP to default
value (FOP = not used). The valve opening is en-
abled only when CCL digital input is enabled.
13 Electrical
Connections
The controller comes with a screw terminal block to connect cables with a cross section up to 2.5 mm Heat-resistant cables have to be used. Before connect­ing the cables, verify that the power supply complies with the controller’s requirements. Separate the probe cables from the power supply cables, from the outputs and the power connections.
mum current allowed on each relay, in case of heavier loads, use a suitable external relay.
Do not exceed the maxi-
2
Figure 13-1 - Recommended Temperature Probe Placement
14 RS485 Serial Line
All models can be connected to the monitoring and
supervising system XWEB3000. If Mod = StD, the standard MODBUS-RTU protocol is used; if Mod = AdU,
the custom XWEB library is required. This last
configuration makes it possible to use the same serial address of the thermostat that gives the cooling re­quest to XEV. In this way, it is possible to reduce the number of addresses used.
.
Probes Digital Inputs • 17
Page 24
15 How to Use the
Hot Key
15.1.How to Program a Hot Key From the Controller (Upload)
1. Program one controller using the front keypad.
2. When the controller is ON, insert the Hot Key and
press the UP arrow key; the uPL message will ap­pear followed by a flashing End LED.
3. Push the SET key and the End LED will stop flash-
ing.
4. Turn OFF the controller, remove the Hot Key, then turn it ON again.
NOTE: The Err message is displayed in case an error or failure in programming occurs. In this case, push the UP arrow key again if you want to restart the upload or remove the Hot
Key to abort the operation.
NOTE: The Err message is displayed in case an error or failure in programming occurs. In this case, turn the unit OFF and then ON if you want to restart the download or remove the
Hot Key to abort the operation.
15.2.How to Program the Controller Using a Hot Key (Download)
1. Turn OFF the controller.
2. Insert a programmed Hot Key into the 5-pin con­nector and then turn the controller ON.
3. Automatically the parameter list of the Hot Key is downloaded into the controller memory, the doL message will blink followed by a flashing End
LED.
4. After 10 seconds, the controller will restart work with the new parameters.
5. Remove the Hot Key.
18 • XEV22D I&O Manual 026-1206 Rev 3 13-DEC-2012
Page 25
16 Display Messages
Message Cause Outputs
nA None of the digital in-
puts configured as
CCL are activated
Pf The PEd time is
elapsed and the regu­lation is stopped.
P1 Temperature probe
fault
P2 Pressure transducer
fault
HSH High superheat alarm By PI LSH Low superheat alarm Valve closed
LPL Low pressure limit See LPL parame-
MoP Maximum Operating
Pressure
LoP Lowest Operating
Pressure
StF Start Function en-
abled
StP Regulation stop
caused by Std and Sti
EE Memory anomaly
Valve closed
Valve closed after
PEd. There is a
probe error.
According to PEo and PEd
According to PEo and PEd
ter
See dML parame-
ter
See dML parame-
ter
See SFd parameter
Valve closed
16.1.Alarm Recovery
Probe alarms P1 and P2 start a few seconds after
the fault in the probe; they automatically stop few sec­onds after the probe restarts normal operation. Check the connections before replacing the probe. Maxi-
mum and minimum alarms HSH, LSH, MoP, and LoP automatically stop as soon as the variable returns
to normal values.
The controller is provided with an internal check
to verify memory integrity. Alarm EE flashes when a
failure in the internal memory is detected. In this case, call for service.
Table 16-1 - Alarm Signals
Alarm Recovery Display Messages • 19
Page 26
17 Specifications
Housing Self extinguishing ABS Dimensions Case:
Front: 4 DIN modules, 70 mm x 135 mm with male and female connectors Depth: 60 mm
Mounting: DIN RAIL mounted in a omega (3) din rail
Protection IP20 Connections
Power Supply 24VAC/DC ±10% Power Absorption
(depending on the valve) Display Three (3) digits with icons, red LEDs, height 14.2 mm Inputs 1 temperature probe Pt1000 or NTC
Digital Inputs 1 free of voltage
Outputs for Valve Bipolar or unipolar valves Data Storage On the non-volatile memory (EEPROM) Kind of Action 1B Pollution Grade Normal Software Class A Temperature Operating: 0 to 60°C
Relative Humidity
Resolution 0.1°C or 1°F Precision at 25°C ±0.7°C ±1 digit
Detachable screw terminal block 2.5 mm2 wiring
20VA max
1 pressure transducer 4 to 20mA or 0 to 5V
1 at high voltage
Storage: -25 to 60 °C
20 to 85% (no condensing)
Table 17-1 - XEV22D Specifications
20 • XEV22D I&O Manual 026-1206 Rev 3 13-DEC-2012
Page 27
18 E2 MODBUS Network Wiring
• Connect MODBUS Network to the RS485 Connector on the E2 PIB board (Belden 8641 recommended).
• Note to wire the RS485 +/- polarity at the E2 in the
• Position the three termination jumpers to the UP (terminated) position to provide RS485 termination at the E2.
• Do not connect the shield of the MODBUS network to the E2 PIB center terminal. Instead, use a 100 ohm 1/2 watt resistor to connect the MODBUS cable shield to earth ground.
• At each XEV22D device, wire the MODBUS cable to the RS485 +/- terminals and connect the MODBUS shield to
the pin 16 terminal.
• Terminate the end of the MODBUS network at the last XEV22D device on the daisy chain with the MODBUS ter-
mination block (P/N 535-2711), or by connecting a 150 ohm resistor between the MODBUS +/- terminals.
reverse of the XEV22D devices.
Figure 18-1 - XEV22D to E2 Wiring Diagram (E2 PIB version 3.xx and below shown in this example)
CAUTION! For the XR, XM, and XEV series of controllers, the shield wire must not come into contact with any other wire or ground source. If contact with other wires or devices does occur, the 485 MODBUS net­work will malfunction or connected devices will be damaged. This applies to all installations where the
shield is tied to ground through a 100 ohm ½ Watt resistor.
Alarm Recovery E2 MODBUS Network Wiring • 21
Page 28
19 ECT MODBUS
Networking to E2s
19.1.COM Port Associations
- E2 Versions 3.xx and
Connect the MODBUS network cable to the three­terminal connector on the COM port you wish to as­sign as MODBUS. Reverse polarity of +/- on RS485 cable from E2 to the device.
Below
Figure 19-2 - MODBUS Networking
COM ports can only be used for one function; in other words, if COM2 is set up as the I/O network, you cannot connect MODBUS devices to COM2. En­sure your E2 is equipped with an RS485 COM Card
(P/N 637-4890) and configured in E2 General Servic­es (, Serial tab) to enable COM4 or an
E2 Expansion COM Card (P/N 637-4871) to enable
COM6.
Connect the MODBUS network cable to the three­terminal connector on the COM port you wish to as­sign as MODBUS. Reverse polarity of +/- on RS485 cable from E2 to the device.
Figure 19-1 - Location of E2 COM Ports (E2 Versions 3.xx and Below)
Connecting an XEV22D controller to an E2 re­quires the E2 to be version 2.84 or above. Contact Re­tail Solutions for upgrade information if the controller is a version before 2.84.
An E2 has up to three COM ports that can be as­signed for MODBUS communication: COM2, an RS485 port on the E2 power interface board, and COM4 and COM6, which are optional ports requiring expansion cards.
BUS connection of Emerson units.
22 • XEV22D I&O Manual 026-1206 Rev 3 13-DEC-2012
COM4 is recommended for MOD-
Page 29
19.2.COM Port Associations
- E2 Versions 4.2 and Above
Figure 19-3 - Location of E2 COM Ports - E2 PIB Board (E2 version 4.2 and above)
An E2 has three COM ports that can be assigned for MODBUS communication (COM2). COM ports can only be used for one function; in other words, if COM2 is set up as the I/O network, you cannot con­nect MODBUS devices to COM2. Ensure your E2 is
configured in E2 General Services (
Serial tab)
to enable COM4 or COM6.
,
3. Press + to open the Serial tab of the General
Controller Info setup screens:
Figure 19-4 - Serial Communications Manager Screen
4. This screen will have a “Connection” field for all COM ports on the E2. Highlight the COM port con­nection field that will be used for the device, and
press  - LOOK UP. From the list of network types, select MODBUS.
5. Four fields will become visible underneath the COM port connection field, which pertain to the way the device communicates:
Baud - Default setting is 19.2k. The baud rate
setting should be set to match the baud rate of
the device (9600). (All devices connected to the
same COM port should be set to the same baud rate.)
Data Size - Leave this field at the default value (8).
Parity - Leave this field at the default value (None).
Stop Bits - Leave this field at the default value (1).
6. Press to save changes and exit.
19.3.E2 Setup of Devices
19.3.1.Set Up Network Ports
Before setting up device, the port on the E2 that has the MODBUS cable connected must be set up as a MODBUS port.
1. Log in to the E2 with Level 4 access.
2. Press followed by  - General
Controller Info.
COM Port Associations - E2 Versions 4.2 and Above ECT MODBUS Networking to E2s • 23
19.3.2.Add and Connect the Device
To enable communications between E2 and the
units, the devices must be added and addressed in E2.
1. Log in to the E2 with Level 4 access.
2. Press  - Connected I/O Boards
Page 30
and Controllers.
Figure 19-5 - Num Network Ctrls: NetSetup Screen
3. In the Num Network Ctrls: NetSetup screen, under
the ECT tab, enter the number of devices in the Quantity field. (Max shows the maximum number
of devices allowed on the network.)
through the front display, and press to select
it. A window will open where you can specify the address of the controller. If a network ID has al­ready been selected, its name will be shown next to the network ID in this list. If the network ID you are trying to assign has already been used, you must set the address on this device to a different number that is not being used.
4. Press to return to the Network Setup menu, then select - Network Summary.
5. Locate the units you added to the network list (press
and to scroll through the list). If desired, en-
ter a new name for each device in the Name field.
Figure 19-6 - Network Summary Screen
6. By default, each device in the network list has a board number of 0. To set the address and begin communication, choose the device and press
. In the list of MODBUS devices, choose the
address number corresponding to the address set up
Figure 19-7 - List of MODBUS Devices
7. Repeat Steps 5 and 6 until each device has a name
and address.
8. When finished, press to return to the Net-
work Setup menu, then press - Network Sum- mary (Figure 19-8). Locate the devices you set up,
and look at each device’s status in the Status field.
You will see one of the following messages:
Online - The device is communicating normal-
ly.
Offline - The device is not communicating, has
not been commissioned, is not functional, or is not powered up. Verify the device is powered up, wired correctly, and has the proper network address, baud rate, and parity.
Unknown - The device is not communicating or
has not been commissioned. Verify the device is powered up, wired correctly, and has the proper network address, baud rate, and parity.
No Port - No port is set up in the E2 Serial Con-
figuration Manager to be a MODBUS port.
Wrong FW Rev - This message is likely caused
by the device having a firmware version older than the minimum revision required by E2 for communication. Replace the device with a new one or a device that has the latest version of
24 • XEV22D I&O Manual 026-1206 Rev 3 13-DEC-2012
Page 31
firmware on it.
Figure 19-8 - Network Summary Screen
19.4.Wiring Types
Retail Solutions specifies Belden #8761 shielded twisted pair cables for use as MODBUS wiring (or Belden #82761 and Belden #88761 for plenum instal­lations).
For MODBUS network wiring of XEV series of
controllers to E2, Belden #8641 (P/N 135-8641) is the
recommended wire type to use.
19.5.MODBUS Termination Blocks
Because the XEV22D device has no on-board
means of termination, use the MODBUS termination
block (P/N 535-2711) for termination that can be
wired to the end of the cable segment using the three­pin connector. Wire the two signal wires to the out-
side terminals, and connect the shield to pin 16, keep-
ing the exposed shield wire length as short as possible (3 inches ideal maximum length).
Figure 19-9 - MODBUS Termination Block (P/N 535-2711)
If the recommended cable is not available in your area, be sure the wiring meets or exceeds the follow­ing specs:
Shielded? Yes Conductor Type Twisted Pair Gauge 18 - 24 AWG Capacitance between
signal wires Capacitance between
signal and shield Maximum Length 4000 ft/18 to 22 AWG
Nominal Impedance 120±50
31 pF/ft or less (9.45 m) or less
59 pF/ft or less (17.98 m) or less
(1219.2 m) 2500 ft/24 AWG (762 m)
The maximum distance between an XEV22 con­troller and a valve must not exceed 10 meters (32 feet). Use only shielded cables with a cross section greater than or equal to 0.325 mm
2
(AWG22).
Wiring Types ECT MODBUS Networking to E2s • 25
Page 32
20 Standard Values
NOTE: For viewing and adjusting setpoints, refer to: Section 9.2., To See the Setpoint and Section 9.3., To Modify the Setpoint.
Label Description Range Default Level
Fty Kind of gas R22, 134, 404, 407, 410, 507, CO2 404 Pr2
PEo Probe error opening percentage 0 to 100% 50 Pr2
PEd Probe error delay before stopping regulation 0 to 239 sec - On On Pr2
tEU Type of stepper motor uP – bP bP Pr2 tEP Automatic valve configuration 0 to 10 1 Pr2 LSt Minimum number of steps 0 – Ust See tEP Pr2
Ust Maximum number of steps LSt – 800 * 10 See tEP Pr2
Sr Step rate 10 to 600 step/s See tEP Pr2 CPP Current per phase (only bipolar valves) 0 to 100 * 10mA See tEP Pr2 CHd Holding current per phase (only bipolar valves) 0 to 100 * 10mA See tEP Pr2
oPE Start opening percentage 0 to 100% 85 Pr2 SFd Start function duration 0.0 to 42.0 min: tens of seconds 1.3 Pr2
Sti Stop regulation interval 0.0 to 24.0 hr: tens of minutes 0 Pr2
Std Stop duration 0 to 60 min 0 Pr2 MnF Maximum opening percentage 0 to 100% 100 Pr2 FOP Forced opening time-out 0 to 100% - not used not used Pr2
PI PARAMETERS (For trained staff use only)
Pb Proportional band 0.1 to 50.0°C/ 1 to 90°F 10.0 Pr2
rS Band offset -12.0 to 12.0°C/ -21 to 21°F 0.0 Pr2
inC Integration time 0 to 255 sec 120 Pr2
PROBE PARAMETERS
tPP Type of pressure transducer 420 - 5V- LAn 420 Pr2 LPP Enable pressure probe sending in LAN n to YnPr2 PA4 Probe value at 4mA or at 0V
(related to PrM parameter)
P20 Probe value at 20mA or at 5V
(related to PrM parameter)
OPr Pressure probe calibration -12.0 to 12.0 bar/ -174 to 174 psi 0 Pr2
ttE Type of temperature probe PtM to ntC PtM Pr2 otE Temperature probe calibration -12.0 to 12.0°C/ -21 to 21°F 0 Pr2
DIGITAL INPUTS
-1.0 bar/ -14 PSI -0.5 Pr2
PA4 to 50.0 bar/ 725 PSI 11.0 Pr2
Table 20-1 - XEV22D Standard Parameter Values
26 • XEV22D I&O Manual 026-1206 Rev 3 13-DEC-2012
Page 33
Label Description Range Default Level
i1P Free of voltage digital input polarity CL – OP CL Pr2
d1d Digital input 1 (free of voltage) activation de-
0 to 255 min 0 Pr2
lay
i2P Main voltage digital input polarity CL – OP CL Pr2 i2F Main voltage digital input function CCL, rL CCL Pr2
d2d Digital input 2 (Main voltage) activation delay 0 to 255 min 0 Pr2
ALARMS
dAo Alarm delay after restarting regulation 0.0 to 42.0 min: tens of seconds 10.0 Pr2
tdA Type of alarm signaled by relay ALL, SH, PrE, di ALL Pr2
LPL Lower pressure limit for superheat regulation
PA4 to P20 bar/ PSI -0.5 Pr2
(related to PrM parameter)
MOP Maximum operating pressure threshold
PA4 to P20 bar/ PSI 11.0 Pr2
(related to PrM parameter)
LOP Minimum suction pressure limit
PA4 to P20 bar/ PSI -0.5 Pr2
(related to PrM parameter) PHY Pressure alarm hysteresis 0.1 to 5.0 bar/ 1to 72 PSI 0.1 Pr2 dML delta MOP-LOP 0 to 100% 30 Pr2
MSH Maximum superheat alarm LSH to 32.0 °C/ LSH to 176 °F 80.0 Pr1
LSH Lowest superheat alarm 0.0 to MSH°C/ 32 to MSH°F 2.5 Pr1
SHy Superheat hysteresis 0.1 to 25.5°C/ 1 to 77°F 0.1 Pr2 SHd Superheat alarm activation delay 0 to 255 sec 120 Pr1 FrC Fast-recovery constant 0 to 100 sec 50 Pr2
DISPLAY
Lod Local display SH - PEr – P1 - P2 SH Pr1
CF Temperature measurement units °C - °F °C Pr2
PMU Pressure measurement unit bAr – PSI bAr Pr2
rES Resolution (only °C) dE – in dE Pr2 PrM Type of pressure (absolute/ relative) rEL – AbS rEL Pr2 CLP Cooling call percentage Read only --- Pr2
tP1 Temperature probe value Read only --- Pr1
PPr Pressure probe value Read only --- Pr1
tP2 Temperature converted from pressure probe Read only --- Pr1
OPP Actual opening percentage Read only --- Pr1
d1S Free of voltage digital input state Read only --- Pr1
d2S Main voltage digital input state Read only --- Pr1
Adr Serial address 1 to 247 1 Pr2
Mod MODBUS type StD – AdU StD Pr2
Ptb Parameters map --- --- Pr2
rEL Release software --- --- Pr2
Pr2 Second level menu --- --- Pr1
Table 20-1 - XEV22D Standard Parameter Values
MODBUS Termination Blocks Standard Values • 27
Page 34
Page 35
Page 36
The contents of this publication are presented for informational purposes only and they are not to be construed as warranties or guarantees, express or implied, regarding the products or services described herein or their use or applicability. Emerson Climate Technologies Retail Solutions, Inc. and/or its affiliates (collectively “Emerson”), reserves the right to modify the designs or specifications of such products at any time without notice. Emerson does not assume responsibility for the selection, use or maintenance of any product. Responsibility for proper selection, use and maintenance of any product remains solely with the purchaser and end-user.
026-1206 13-DEC-2012 Emerson is a trademark of Emerson Electric Co. ©2012 Emerson Climate Technologies Retail Solutions, Inc. All rights reserved.
Loading...