Emerson Waffle Iron 3051N User Manual

Reference Manual
00809-0100-4808, Rev CA June 2008

Rosemount 3051N Smart Pressure Transmitter for Nuclear Service

www.rosemountnuclear.com
IMPOR TANT NOTICE -- ERRATA
No. Affected Pages Description of Change
1 5-8 Flange Bolts and Mounting Bolts - Carbon steel, per
ASTM A449 Type 1 or SAE J429 Grade 5
2 5-8 Electronics Housing – Low copper aluminum with
polyurethane paint, or CF-8M (cast version of 316 SST)...
3 5-8
Mounting Bracket – AISI 1010 steel or JIS G3131 SPHC P/O Steel with polyurethane paint (Option Code B2)...
Effect.
Date
12/3/07
11/18/08
1/24/11 12/5/07
Reference Manual
Rosemount Nuclear Instruments, Inc. 8200 Market Blvd. Chanhassen, Mn 55317 Tel 952-949-5210 Fax 952-949-5201
©Rosemount Nuclear Instruments, Inc. www.rosemountnuclear.com
Rosemount Nuclear Instruments, Inc. satisfies all obligations coming from legislation to harmonize product requirements in the European Union.
00809-0100-4808, Rev CA June 2008
Rosemount 3051N

Rosemount 3051N Smart Pressure Transmitter for Nuclear Service

Rosemount 3051 HART Universal Revision 5
NOTICE
Read this manual before working with the product. For personal and system safety, and for optimum product performance, make sure you thoroughly understand the contents before installing, using, or maintaining this product.
Within the United States, contact Rosemount Nuclear Instruments, Inc. at 1-952-949-5210 for assistance.
Outside of the United States, contact your local Emerson Process Management Sales Representative.
The Rosemount logotype, and SMART FAMILY are registered trademarks of Rosemount Inc. Coplanar is a trademark of Rosemount Inc. Teflon is a registered trademark of E.I. du Pont de Nemours & Co. D.C. 200 is a registered trademark of Dow Corning Corporation. HART is a registered trademark of the HART Communication Foundation.
www.rosemountnuclear.com
Reference Manual
00809-0100-4808, Rev CA
Rosemount 3051N
June 2008

Rosemount Nuclear Instruments, Inc. Warranty and Limitations of Remedy

The warranty and limitations of remedy applicable to this Rosemount equipment are as stated on the reverse of the current Rosemount quotation and customer acknowledgment forms.
RETURN OF MATERIAL
Authorization for return is required from Rosemount Nuclear Instruments, Inc. prior to shipment. Contact Rosemount Nuclear Instruments, Inc. (1-952-949-5210) for details on obtaining Return Material Authorization (RMA). Rosemount Nuclear Instruments will not accept any returned material without a Returned Material Authorization. Material returned without authorization is subject to return to customer.
Material returned for repair, whether in or out of warranty, should be shipped prepaid to:
Rosemount Nuclear Instruments, Inc. 8200 Market Blvd. Chanhassen, MN 55317 USA
IMPORTANT
The Rosemount 3051N Pressure Transmitter is qualified for nuclear use per IEEE Std 344-1987 and IEEE Std 323-1983 (mild environment) as documented in Rosemount Report D2001019, and is supplied in accordance with 10CFR50 Appendix B and ISO 9001:2000 quality assurance programs. To ensure compliance with 10CFR Part 21, the transmitter must comply with the requirements herein and in Report D2001019 throughout its installation, operation, and maintenance. It is incumbent upon the user to ensure that the Rosemount Nuclear Instruments, Inc. component traceability program where applicable is continued throughout the life of the transmitter.
Where the manual uses the terms requirements, mandatory, must, or required, the instructions so referenced must be carefully followed. Rosemount Nuclear Instruments, Inc. expressly disclaims all responsibility and liability for transmitters for which the foregoing has not been complied with by the user.
ii
Reference Manual
00809-0100-4808, Rev CA June 2008
Rosemount 3051N
Revision Status
Changes from June 2006 to June 2008
Page (Old) Page (New) Changes
Cover,
throughout
TOC-1 Page i, back
- Page iii Add Revision Status page
TOC-1 to TOC-8 i to iv and TOC-1
Throughout Throughout Manual number corrected to 00809-0100-4808 3-6 and 3-8 3-6 and 3-8 Changed significant digits to conform to standard
3-12 3-12 Removed word ‘process’ from sentences indicating user responsibility for qualifying the connection
5-7 5-8 Reworded flange bolt description to reflect qualification configuration
NOTE
The above Revision Status list summarizes the changes made. Please refer to both manuals for complete comparison details.
Cover,
throughout
cover
to TOC-4
Document revision date change from June 2006 to June 2008, rev from BA to CA
CE mark added with Rosemount Nuclear Instruments, Inc.
Page numbers changed
interface
www.rosemountnuclear.com
Rosemount 3051N
Reference Manual
00809-0100-4808, Rev CA
June 2008
iv
Reference Manual
00809-0100-4808, Rev CA June 2008
Rosemount 3051N
Table of Contents
SECTION 1 Introduction
SECTION 2 Transmitter Functions
Using This Manual . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 1-1
Overview . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 2-1
Safety Messages . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 2-1
Warnings . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 2-1
Failure Mode Alarm . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 2-2
Alarm Level Verification . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 2-2
Transmitter Security. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 2-2
Security Jumper (Write Protect) . . . . . . . . . . . . . . . . . . . . . . . . . . . 2-3
Local Zero and Span (Local Keys) Software Lock Out. . . . . . . . . . 2-3
Physical Removal of Local Zero and Span (Local Keys) . . . . . . . . 2-3
Configuring Transmitter Alarm
and Security Jumper Procedure . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 2-3
Commissioning the Rosemount 3051N with a
HART-Based Communicator . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 2-4
Setting the Loop to Manual. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 2-5
Wiring Diagrams (Bench Hook-up). . . . . . . . . . . . . . . . . . . . . . . . . 2-5
Wiring Diagrams (Field Hook-up) . . . . . . . . . . . . . . . . . . . . . . . . . . 2-6
Review Configuration Data . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 2-7
Check Output. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 2-7
Process Variables. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 2-7
Sensor Temperature. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 2-8
Basic Setup . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 2-8
Set Process Variable Units. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 2-8
Set Output . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 2-8
Rerange . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 2-9
Rerange with a Communicator Only. . . . . . . . . . . . . . . . . . . . . . . . 2-9
Rerange with a Pressure Input Source and a Communicator . . . 2-10
Rerange with a Pressure Input Source and
the Local Zero and Span Buttons . . . . . . . . . . . . . . . . . . . . . . . . . 2-10
Damping . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 2-12
LCD Meter Options. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 2-12
Detailed Setup . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 2-12
Local Span and Zero Control (Local Keys). . . . . . . . . . . . . . . . . . 2-12
Sensor Temperature Output Unit Selection . . . . . . . . . . . . . . . . . 2-12
Diagnostics and Service . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 2-12
Transmitter Test . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 2-13
Loop Test . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 2-13
Calibration . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 2-13
Calibration Overview . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 2-15
Deciding Which Trim Procedure to Use . . . . . . . . . . . . . . . . . . . . 2-16
Sensor Trim . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 2-16
www.rosemountnuclear.com
Rosemount 3051N
Reference Manual
00809-0100-4808, Rev CA
June 2008
Zero Trim . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 2-17
Full Trim . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 2-18
Recall Factory Trim . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 2-19
Recall Factory Trim— Sensor Trim . . . . . . . . . . . . . . . . . . . . . . . 2-19
Recall Factory Trim— Analog Output. . . . . . . . . . . . . . . . . . . . . . 2-19
Analog Output Trim . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 2-19
Digital-to-Analog Trim. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 2-19
Digital-to-Analog Trim Using Other Scale. . . . . . . . . . . . . . . . . . . 2-19
Compensating Rosemount 3051N Range 4 and
5 Differential Transmitters for Line Pressure . . . . . . . . . . . . . . . . 2-20
SECTION 3 Installation
SECTION 4 Troubleshooting
SECTION 5 Specifications and Reference Data
Overview . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 3-1
Safety Messages . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 3-1
Warnings . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 3-1
General Considerations . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 3-4
Special Draft Range Considerations . . . . . . . . . . . . . . . . . . . . . . . 3-4
Mechanical Considerations . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 3-4
Mounting. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 3-9
Process Connections . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 3-12
Housing Rotation . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 3-12
Electrical Considerations . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 3-12
Power Supply . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 3-12
Wiring . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 3-13
Grounding the Transmitter Case . . . . . . . . . . . . . . . . . . . . . . . . . 3-14
Environmental Considerations. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 3-14
Access Requirements. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 3-14
Cover Installation . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 3-14
Overview . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 4-1
Safety Messages . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 4-1
Warnings . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 4-1
Returning Rosemount Products and Materials. . . . . . . . . . . . . . . . 4-2
Nuclear Specifications . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 5-1
Seismic . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 5-1
Environmental. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 5-2
Quality Assurance Program . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 5-2
Nuclear Cleaning . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 5-2
Hydrostatic Testing. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 5-2
Performance Specifications . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 5-3
Reference Accuracy . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 5-3
Drift . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 5-3
Ambient Temperature Effect. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 5-3
Overpressure Effect . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 5-4
Static Pressure Effect . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 5-4
Power Supply Effect . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 5-4
Load Effect . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 5-4
Mounting Position Effect. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 5-4
Functional Specifications . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 5-5
Service . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 5-5
Output. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 5-5
Power Supply . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 5-5
TOC-2
Reference Manual
00809-0100-4808, Rev CA June 2008
Rosemount 3051N
Temperature Limits. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 5-5
Span and Zero, Zero Elevation, and Suppression . . . . . . . . . . . . . 5-6
Humidity Limits . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 5-6
Volumetric Displacement . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 5-6
Turn-on Time . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 5-6
Response Time . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 5-6
Maximum Working Pressure . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 5-7
Static Pressure Limits. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 5-7
Overpressure Limits . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 5-7
Burst Pressure . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 5-7
Physical Specifications . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 5-8
Materials of Construction . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 5-8
Ordering Information . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 5-10
Configuration Information . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 5-11
Rosemount 3051N 4-20 mA/HART Output Smart
Pressure Transmitters Typical Configuration Data Worksheet . . . . . 5-12
SECTION 6 Options
APPENDIX A HART Communicator
Overview . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 6-1
Safety Messages . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 6-1
Warnings . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 6-1
LCD Meter . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 6-1
Custom Meter Configuration. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 6-2
Installing the Meter . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 6-3
Diagnostic Messages . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 6-5
Error . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 6-5
Warnings . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 6-6
Operation . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 6-7
Mounting Brackets . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 6-7
Traditional Flange (H2). . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 6-8
Transient Protection Terminal Block (T1) . . . . . . . . . . . . . . . . . . . . . . 6-8
Introduction . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . A-1
Safety Messages . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . A-1
Warnings . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .A-2
Connections and Hardware . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . A-5
Rosemount 275 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .A-7
Communicator Keys . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . A-7
Action Keys. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . A-7
Function Keys. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . A-8
Alphanumeric and Shift Keys . . . . . . . . . . . . . . . . . . . . . . . . . . . . .A-8
Data Entry. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . A-8
Fast Key Sequences . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .A-9
Fast Key Sequence Conventions . . . . . . . . . . . . . . . . . . . . . . . . . . A-9
Fast Key Sequence Example . . . . . . . . . . . . . . . . . . . . . . . . . . . . . A-9
Menus and Functions . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .A-9
Main Menu . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . A-9
Online Menu . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . A-10
Rosemount 375 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .A-11
Communicator Keys . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . A-11
Action Keys. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . A-11
Alphanumeric Keys. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . A-12
Function Key. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . A-12
TOC-3
Rosemount 3051N
Glossary
Index
Reference Manual
00809-0100-4808, Rev CA
June 2008
Multifunction LED . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .A-12
Touch Screen . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . A-12
Using the Soft Input Panel (SIP) keyboard. . . . . . . . . . . . . . . . . . A-13
Menus and Functions . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . A-13
HART Application Startup. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . A-13
Main Menu . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . A-13
Fast Key Sequences . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .A-14
Hot Key options . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . A-14
Diagnostic Messages. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . A-14
TOC-4
Reference Manual
00809-0100-4808, Rev CA June 2008
Rosemount 3051N

Section 1 Introduction

USING THIS MANUAL The sections in this manual provide information on installing, operating, and

maintaining devices from the Rosemount 3051N Smart Pressure Transmitter Family. The sections are organized as follows:
Section 2: Transmitter Functions
Provides instruction on commissioning and operating Rosemount 3051N Pressure Transmitters. Information on software functions, configuration parameters, and on-line variables is also included.
Section 3: Installation
Contains mechanical and electrical installation instructions.
Section 4: Troubleshooting
Provides troubleshooting techniques for the most common Rosemount 3051N transmitter operating problems.
Section 5: Specifications and Reference Data
Supplies reference and specification data for the Rosemount 3051N Smart Pressure Transmitter Family.
Section 6: Options
Describes the mounting and configuration options available for Rosemount 3051N transmitters.
Appendix A: HART Communicator
Gives an overview of the HART Communicator, defines its partial command menu tree for the Rosemount 3051N family, and provides a table of typical fast key sequences. A table of typical diagnostic messages is also included.
www.rosemountnuclear.com
Rosemount 3051N
Reference Manual
00809-0100-4808, Rev CA
June 2008
1-2
Reference Manual
00809-0100-4808, Rev CA June 2008
Rosemount 3051N

Section 2 Transmitter Functions

Overview . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . page 2-1
Safety Messages . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . page 2-1
Failure Mode Alarm . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . page 2-2
Review Configuration Data . . . . . . . . . . . . . . . . . . . . . . . . page 2-7
Check Output . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . page 2-7
Basic Setup . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . page 2-8
Detailed Setup . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . page 2-12
Diagnostics and Service . . . . . . . . . . . . . . . . . . . . . . . . . . page 2-12
Calibration . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . page 2-13

OVERVIEW This section contains information on commissioning and operating

Rosemount 3051N Smart Pressure Transmitters. Tasks that should be performed on the bench prior to installation are explained in this section.
When the HART Communicator is referenced, it refers to either the Rosemount 275 or Rosemount 375 as documented in Rosemount Report D2001019.
For your convenience, typical HART Communicator fast key sequences are listed for most software functions. These fast key sequences are the same for both the Rosemount 275 and Rosemount 375 Communicators. If you are unfamiliar with the communicator or how to follow fast key sequences, please refer to Appendix A for communicator operations.
A typical transmitter software configuration data worksheet is provided in Section 5.

SAFETY MESSAGES Procedures and instructions in this section may require special precautions to

ensure the safety of the personnel performing the operations. Information that raises potential safety issues is indicated by a warning symbol ( ). Refer to the following safety messages before performing an operation preceded by this symbol.

Warnings

Explosions can result in death or serious injury.
• Do not remove the transmitter covers in explosive environments when the circuit is alive.
www.rosemountnuclear.com
Reference Manual
00809-0100-4808, Rev CA
Rosemount 3051N
Electrical shock can result in death or serious injury.
• Avoid contact with the leads and terminals. High voltage that may be present on leads can cause electrical shock.
June 2008

FAILURE MODE ALARM Rosemount 3051N transmitters automatically and continuously perform

self-diagnostic routines. If the self-diagnostic routines detect a failure, the transmitter drives its output outside of the normal saturation values. The transmitter will drive its output low or high based on the position of the failure mode alarm jumper. See Table 2-1 for failure mode and saturation output levels. To select alarm position, see “Configuring Transmitter Alarm and Security Jumper Procedure” in Section 2.
Table 2-1. Standard Alarm and Saturation Values.
Level
4–20 mA Saturation
4–20 mA Alarm
Low 3.9 mA 3.75 mA
High 20.8 mA 21.75 mA
NOTE
You can alter the actual transmitter mA output values by performing an analog output trim.
NOTE
When a transmitter is in an alarm condition, the hand-held HART Communicator indicates the analog output the transmitter would drive if the alarm condition did not exist. The transmitter will alarm high in the event of failure if the alarm jumper is removed.

Alarm Level Verification Transmitters allow verification testing of alarm current levels. If you replace

the LCD meter, reconfigure or make any changes to the transmitter, verify the transmitter alarm level before you return the transmitter to service. This feature is also useful in testing the reaction of your control system to a transmitter in an alarm state. To verify the transmitter alarm values, perform a loop test and set the transmitter output to the alarm value (see Table 2-1 and “Loop Test” in Section 2).
TRANSMITTER
There are three security methods with the Rosemount 3051N transmitter:
SECURITY
2-2
Reference Manual
00809-0100-4808, Rev CA June 2008
Rosemount 3051N
1. Security Jumper: prevents all writes to transmitter configuration.
2. Local Keys (Local Zero and Span) Software Lock Out: prevents changes to transmitter range points via local zero and span adjustment keys. With local keys security enabled, changes to configuration are possible via HART.
3. Physical Removal of Local Keys (Local Zero and Span) Magnetic Buttons: removes ability to use local keys to make transmitter range point adjustments. With local keys security enabled, changes to configuration are possible via HART.
NOTE
If the security jumper is not installed, the transmitter will continue to operate in the security OFF configuration.

Security Jumper (Write Protect)

Local Zero and Span (Local Keys) Software Lock Out

Physical Removal of Local Zero and Span (Local Keys)

CONFIGURING TRANSMITTER ALARM AND SECURITY JUMPER PROCEDURE

You can prevent changes to the transmitter configuration data with the write protection jumper. Security is controlled by the security (write protect) jumper located on the electronics board or meter face. Position the jumper on the transmitter circuit board in the “ON” position to prevent accidental or deliberate change of configuration data.
If the transmitter write protection jumper is in the “ON” position, the transmitter will not accept any “writes” to its memory. Configuration changes, such as digital trim and reranging, cannot take place when the transmitter security is on.
To enable this feature, see “Local Span and Zero Control (Local Keys)” in Section 2.
To remove the magnetic buttons used to activate the local zero and span, use a small slotted head screwdriver and pry off the small, plastic cap located under the approval tag. Remove button assemblies and discard.
To reposition the jumpers, follow the procedure described below.
1. If the transmitter is installed, secure the loop and remove power.
2. Remove the housing cover opposite the field terminal side. Do not remove the transmitter covers in explosive atmospheres when the circuit is alive.
3. Reposition the jumpers as desired.
Figure 2-1 shows the jumper positions for Electronics Boards.
Figure 2-2 shows transmitters with an optional LCD meter.
4. Reattach the transmitter cover. Transmitter covers must be fully engaged to meet explosionproof requirements.
2-3
Rosemount 3051N
ELECTRONICS BOARD
Alarm
Security
HI LO
OFF ON
NOTE
Security jumper not installed = Not Write Protected. Alarm jumper not installed = High Alarm.
FIGURE 2-1. Electronics Board.
Reference Manual
00809-0100-4808, Rev CA
June 2008
FIGURE 2-2. Rosemount 3051N with Optional LCD Meter.

COMMISSIONING THE ROSEMOUNT 3051N WITH A HART-BASED COMMUNICATOR

Commissioning consists of testing the transmitter and verifying transmitter configuration data. You may commission Rosemount 3051N transmitters either before or after installation. Commissioning the transmitter on the bench before installation using a HART-based Communicator ensures that all transmitter components are in good working order and acquaints you with the operation of the device.
2-4
Reference Manual
See “Safety Messages” on page 2-1 for warning information.
24 V dc Supply
R
L
250Ω
Current Meter
00809-0100-4808, Rev CA June 2008
Rosemount 3051N
To commission on the bench, connect the transmitter and the communicator as shown in Figure 2-3. Make sure the instruments in the loop are installed in accordance with intrinsically safe or nonincendive field wiring practices before connecting a communicator in an explosive atmosphere. Connect the communicator leads at any termination point in the signal loop. It is most convenient to connect them to the terminals labeled “COMM” on the terminal block. Connecting across the “TEST” terminals will prevent successful communication. To avoid exposing the transmitter electronics to the plant environment after installation, set all transmitter jumpers during the commissioning stage on the bench.
For 4–20 mA transmitters, you will need a power supply capable of providing
10.5 to 55 V dc at the transmitter, and a meter to measure output current. To enable communication, a resistance of at least 250 ohms, but within the transmitter load limitations (see Figure 3-7 “Power Supply Load Limitations.” in Section 3) must be present between the communicator loop connection and the power supply. Do not use inductive-based transient protectors with the Rosemount 3051N.

Setting the Loop to Manual

Wiring Diagrams (Bench Hook-up)

FIGURE 2-3. Bench Hook-up (4–20 mA Transmitters).
Whenever you are preparing to send or request data that would disrupt the loop or change the output of the transmitter, you must set your process application loop to manual. The HART Communicator will prompt you to set the loop to manual when necessary. Keep in mind that acknowledging this prompt does not set the loop to manual. The prompt is only a reminder; you have to set the loop to manual yourself as a separate operation.
Connect the bench equipment as shown in Figure 2-3 and turn on the HART-based Communicator by pressing the ON/OFF key. The communicator will search for a HART-compatible device and will indicate when the connection is made. If the communicator fails to connect, it will indicate that no device was found. If this occurs, refer to Section 4: Troubleshooting.
2-5
Rosemount 3051N
Power Supply
R
L
250Ω
Current Meter
Signal point may be grounded at any point or left ungrounded.
CAUTION Do not use inductive-based transient protectors.
Reference Manual
00809-0100-4808, Rev CA
June 2008

Wiring Diagrams (Field Hook-up)

FIGURE 2-4. Field Hook-up (4–20 mA Transmitters).
The following diagrams illustrate wiring loops for a field hook-up with a HART-based Communicator.
2-6
Reference Manual
00809-0100-4808, Rev CA June 2008
Rosemount 3051N

REVIEW CONFIGURATION DATA

HART Comm 1, 5
NOTE
Information and procedures in this section that make use of HART Communicator fast key sequences assume that the transmitter and communicator are connected, powered, and operating correctly. If you are not familiar with the HART Communicator or fast-key sequences, refer to Appendix A: HART Communicator.
Before you place the transmitter into operation, it is recommended that you review the transmitter configuration data that was set at the factory. You should review the following configuration data:
Transmitter Model Type
Tag Range
Date Descriptor
Message Minimum and Maximum
Sensor Limits
Minimum Span Units
4 and 20 mA points Output (linear or sq. root)
Damping Alarm Setting (high, low)
Security Setting (on, off) Local Zero/Span Keys
(enabled, disabled)
Integral Meter Sensor Fill
Isolator Material Flange (type, material)
O-Ring Material Drain/Vent
Remote Seal (type, fill fluid, isolator material, number)
Address Sensor S/N
Transmitter S/N

CHECK OUTPUT Before performing other transmitter on-line operations, review the digital

output parameters to ensure that the transmitter is operating properly and is configured to the appropriate process variables.

Process Variables The process variables for the Rosemount 3051N provide the transmitter

HART Comm. 2
output, and are continuously updated. The process variable menu displays the following process variables:
Pressure
Percent of Range
Analog Output
The pressure reading in both Engineering Units and Percent of Range will continue to track with pressures outside of the defined range from the lower to the upper range limit of the sensor module.
2-7
Reference Manual
00809-0100-4808, Rev CA
Rosemount 3051N
June 2008
NOTE
Regardless of the range points, the Rosemount 3051N will measure and report all readings within the digital limits of the sensor. For example, if the 4 and 20 mA points are set to 0 and 10 in H 3051N, and the transmitter detects a pressure of 25 inH the 25 inH
O reading and a 250% of span reading. However, there may be up
2
O on a range code 1 Rosemount
2
O, it digitally outputs
2
to ±5.0% error associated with output outside of the range points.

Sensor Temperature The Rosemount 3051N contains a temperature sensor just above its pressure

HART Comm. 1, 1, 4
sensor in the sensor module. When reading this temperature, keep in mind that this is not a process temperature reading.

BASIC SETUP

Set Process Variable Units

HART Comm. 1, 3, 2
The PV Unit command sets the process variable units to allow you to monitor your process using the appropriate units of measure. Select from the following engineering units:
•inH2O•bar
inHg mbar
•ftH
O g/cm
2
•mmH2O kg/cm
2
2
•mmHg •Pa
•psi •kPa
torr atm
•inH
O at 4 °C mmH2O at 4 °C
2

Set Output Activate the transmitter square root output option to make the analog output

HART Comm. 1, 3, 5
proportional to flow. As the input approaches zero, the Rosemount 3051N automatically switches to a linear output in order to ensure a more smooth, stable output near zero. See Figure 2-5.
The transition from linear to square root is not adjustable. It occurs at 0.8% of ranged pressure input or 8.9% of full-scale flow output.
From 0 percent to 0.6 percent of the ranged pressure input, the slope of the curve is unity (y = x). This allows accurate calibration near zero. Greater slopes would cause large changes in output for small changes at input. From
0.6 percent to 0.8 percent, the slope of the curve equals 42 (y = 42x) to achieve continuous transition from linear to square root at the transition point.
2-8
Reference Manual
Sq. Root Curve
Transition Point
Linear Section
Slope=1
Slope=42
Transition Point
Sq. Root Curve
Full Scale
Flow (%)
Full Scale Output
(mA dc)
00809-0100-4808, Rev CA June 2008
FIGURE 2-5. Square Root Output Transition Point.
Rosemount 3051N

Rerange The Range Values command sets the 4 and 20 mA points (lower and upper

range values). Setting the range values to the limits of expected readings maximizes transmitter performance. In practice, you may reset the transmitter

Rerange with a Communicator Only

HART Comm. 1, 2, 3, 1, 1
range values as often as necessary to reflect changing process conditions.
You may use one of three methods to rerange the transmitter. Each method is unique; examine all three closely before deciding which method to use.
Reranging using only the communicator changes the values of the analog 4 and 20 mA points independently without a pressure input.
NOTE
Changing the lower or upper range point results in similar changes to the span.
To rerange using only the communicator, enter the fast-key sequence above, select 1 Keypad input, and follow the on-line instructions. Or enter the values
directly from the ONLINE screen.
2-9
Rosemount 3051N
Reference Manual
00809-0100-4808, Rev CA
June 2008
NOTE
If the transmitter security jumper is in the ON position, you will not be able to
make adjustments to the zero and span. Refer to Figure 2-1 for the appropriate placement of the transmitter security jumper.

Rerange with a Pressure Input Source and a Communicator

HART Comm. 1, 2, 3, 1, 2

Rerange with a Pressure Input Source and the Local Zero and Span Buttons

Reranging using the communicator and a pressure source or process pressure is a way of reranging the transmitter with a pressure input. When specific 4 and 20 mA points are not known process input can be used. This method changes the values of the analog 4 and 20 mA points.
NOTE
When you set the 4 mA point the span is maintained; when you set the 20 mA point the span changes. If you set the lower range point to a value that causes the upper range point to exceed the sensor limit, the upper range point is automatically set to the sensor limit, and the span is adjusted accordingly.
To rerange using the communicator and a pressure source or process pressure, enter the fast-key sequence above, select 2 Apply values, and follow the on-line instructions.
NOTE
If the transmitter security jumper is in the ON position, you will not be able to
make adjustments to the zero and span. Refer to Figure 2-1 for the appropriate placement of the transmitter security jumper.
Reranging using the local zero and span adjustments (see Figure 2-6) and a pressure source or process pressure is a way of reranging the transmitter with a pressure input and when a communicator is not available. When specific 4 and 20 mA points are not known process input can be used.
2-10
NOTE
When you set the 4 mA point the span is maintained; when you set the 20 mA point the span changes. If you set the lower range point to a value that causes the upper range point to exceed the sensor limit, the upper range point is automatically set to the sensor limit, and the span is adjusted accordingly.
Reference Manual
Span and Zero Adjustment Buttons
00809-0100-4808, Rev CA June 2008
Rosemount 3051N
To rerange the transmitter using the span and zero buttons, perform the following procedure:
1. Loosen the screw holding the label on top of the transmitter housing, and rotate the label to expose the zero and span buttons (see Figure 2-6).
2. Using a pressure source with an accuracy three to ten times the desired calibrated accuracy, apply a pressure equivalent to the lower range value to the high side of the transmitter.
3. To set the 4 mA point, press and hold the zero button for at least two seconds, then verify that the output is 4 mA. If a meter is installed, it will display ZERO PASS.
4. Apply a pressure equivalent to the upper range value to the high side of the transmitter.
5. To set the 20 mA point, press and hold the span button for at least two seconds, then verify that the output is 20 mA. If a meter is installed, it will display SPAN PASS.
NOTE
If the transmitter security jumper is in the ON position, or if the local zero and
span adjustments are disabled through the software, you will not be able to make adjustments to the zero and span using the local buttons. Refer to Figure 2-1 for the proper placement of the transmitter security jumper. Or refer to “Local Span and Zero Control (Local Keys)” in Section 2 for instructions on how to enable the span and zero buttons.
FIGURE 2-6. Local Zero and Span Adjustments.
After you rerange the transmitter using the span and zero adjustments, it is possible to disable the adjustments to prevent further reranging. Refer to “Local Span and Zero Control (Local Keys)” below for more information.
2-11
Reference Manual
00809-0100-4808, Rev CA
Rosemount 3051N
June 2008

Damping The process variable (PV) Damp command changes the response time of the

HART Comm. 1, 3, 6
transmitter to smooth variations in output readings caused by rapid changes in input. Determine the appropriate damping setting based on the necessary response time, signal stability, and other requirements of the of loop dynamics of your system. The default damping value is 0.4 seconds, to any of eleven pre-configured, nominal damping values between 0 and 25.6 seconds.
(1)
and can be reset

LCD Meter Options The Meter Options command allows you to customize the LCD meter for use

HART Comm. 1, 4, 3, 4
in your application. You can configure the meter to display the following information:
Engineering Units
Percent of Range
User-Configurable LCD Scale
Alternating between any two of the above
The user-configurable scale is a feature that enables you to configure the LCD meter to a custom scale using a HART Communicator. With this feature you can define the decimal point position, the upper range value, the lower range value, the engineering units, and the transfer function. Refer to “Custom Meter Configuration” in Section 6 for complete configuration information.

DETAILED SETUP

Local Span and Zero Control (Local Keys)

HART Comm. 1, 4, 4, 1, 7

Sensor Temperature Output Unit Selection

HART Comm. 1, 4, 1, 2, 2

DIAGNOSTICS AND SERVICE

The Local keys command allows software control over the use of the local span and zero adjustments. To enable or disable the span and zero adjustment buttons on your transmitter, perform the fast key sequence at left.
NOTE
Disabling the local keys does not disable all transmitter configuration changes. With the local keys disabled, you can still make changes to the transmitter configuration—including range values—using a HART Communicator.
The Sensor Temperature Output Unit Selection command selects between Celsius and Fahrenheit units for output of the sensor temperature. The sensor temperature output is accessible via HART only.
The diagnostics and service functions listed here are primarily for use after you install the transmitter in the field. The transmitter test feature is designed to verify that the transmitter is operating properly, and can be performed either on the bench or in the field. The loop test feature is designed to verify proper loop wiring and transmitter output, and should only be performed after you install the transmitter.
2-12
(1) Rosemount 3051ND0 default damping is 3.2 seconds. Rosemount 3051ND1, with calibra-
tions below 2.5 inH
O (0,62 kPa), have damping set at 3.2 seconds.
2
Reference Manual
00809-0100-4808, Rev CA June 2008
Rosemount 3051N

Transmitter Test The transmitter Self Test command initiates a more extensive diagnostics

HART Comm. 1, 2, 1, 1
routine than that performed continuously by the transmitter. The transmitter test routine can quickly identify potential electronics problems. If the transmitter test detects a problem, messages to indicate the source of the problem are displayed on the communicator screen.

Loop Test The Loop Test command verifies the output of the transmitter, the integrity of

HART Comm. 1, 2, 2
the loop, and the operations of any recorders or similar devices installed in the loop. To initiate a loop test, perform the following procedure:
1. Connect a reference meter to the transmitter. To do so, either connect the meter to the test terminals on the transmitter terminal block, or shunt the power to the transmitter through the meter at some point in the loop.
2. From the ONLINE screen, select 1 Device Setup, 2 Diagnostics and
Service, 2 Loop Test, to prepare to perform a loop test.
3. Select OK after you set the control loop to manual (see “Setting the
loop to Manual”). The communicator displays the loop test menu.
4. Select a discreet milliamp level for the transmitter to output. At the
CHOOSE ANALOG OUTPUT prompt, select 1 4mA, 2 20mA, or
select 3 other to manually input a value. IF test to verify the output of a transmitter, THEN 4 and 20 mA. IF transmitter alarm levels, THEN an alarm state (see Table 2-1).
5. Check the electrical current meter installed in the test loop to verify that it reads the value you commanded the transmitter to output. IF the readings match, THEN configured and functioning properly. IF
THEN
you may have the current meter attached to the wrong loop, there may be a fault in the wiring or elsewhere in the loop, the transmitter may require an output trim, or the electrical current meter may be malfunctioning.
you are performing a loop test to verify the
enter the milliamp value representing
the transmitter and the loop are
you are performing a loop
enter a value between
the readings do not match,
After completing the test procedure, the display returns to the loop test screen and allows you to choose another output value or to exit loop testing.
NOTE
If the HART Communicator is disconnected from the process loop or loses power prior to exiting loop testing, output will remain fixed at the loop test value.

CALIBRATION Calibrating a smart transmitter is different from calibrating an analog

transmitter. The one-step calibration process of an analog transmitter is done in three steps with a smart transmitter:
Rerange—sets the 4 and 20 mA points at the desired pressures;
Sensor T rim—Adjusts the position of the factory characterization curve
to optimize the transmitter performance over a specified pressure range or to adjust for mounting effects
Analog Output Trim—Adjusts the analog output to match the plant
standard or the control loop.
2-13
Rosemount 3051N
Reference Manual
00809-0100-4808, Rev CA
June 2008
Smart transmitters operate differently than analog transmitters. A smart transmitter uses a microprocessor and sensor memory that contains information about the sensor’s specific characteristics in response to pressure and temperature inputs. A smart transmitter compensates for these sensor variations. The process of generating the sensor performance profile is called factory characterization. Factory characterization also provides the ability to readjust the 4 and 20 mA points without applying pressure to the transmitter.
The trim and rerange functions also differ. Reranging sets the transmitter analog output to the selected upper and lower range points and can be done with or without an applied pressure. Reranging does not change the factory characterization curve stored in the microprocessor. Sensor trimming requires an accurate pressure input and adds additional compensation that adjusts the position of the factory characterization curve to optimize transmitter performance over a specific pressure range.
NOTE
Sensor trimming adjusts the position of the factory characterization curve. It is possible to degrade the performance of the transmitter if the sensor trim is done improperly or with inaccurate equipment. Contact Rosemount Nuclear Instruments, Inc. at 952-949-5210 if you have questions.
Table 2-2. Recommended Calibration Tasks.
Transmitter Bench Calibration Tasks Field Calibration Tasks
3051ND 3051NG
3051NA
1. Set output configuration parameters: a. Set the process variable units. b. Set the output type. c. Set the range points. d. Set the damping value.
2. Optional: Perform a full sensor trim. (Accurate multimeter required.)
3. Optional: Perform an analog output trim. (Accurate multimeter required.)
1. Set output configuration parameters: a. Set the process variable units. b. Set the output type. c. Set the range points. d. Set the damping value.
2. Optional: Perform a full sensor trim if equipment available (accurate absolute pressure source required), otherwise perform the low trim value section of the full sensor trim procedure.
3. Optional: Perform an analog output trim (accurate multimeter required).
1. Reconfigure parameters if necessary.
2. Zero trim the transmitter to compensate for mounting effects or static pressure effects.
1. Reconfigure parameters if necessary.
2. Perform low trim value section of the full sensor trim procedure to correct for mounting position effects.
Notes:
A HART Communicator is required for all sensor and output trim procedures.
Rosemount 3051N Range 4 and Range 5 transmitters require a special calibration procedure when used in differential pressure applications under high static line pressure (see “Compensating Rosemount 3051N Range 4 and 5 Differential Transmitters for Line Pressure” on page 2-20).
2-14
Reference Manual
00809-0100-4808, Rev CA June 2008
Rosemount 3051N

Calibration Overview Complete calibration of the Rosemount 3051N Pressure Transmitter involves

the following tasks:
Configure the Analog Output Parameters
Set Process Variable Units (page 2-8)
Set Output Type – Linear or Square Root (page 2-8)
Set the Range Points (page 2-9)
Set Damping (page 2-12)
Calibrate the Sensor
Full Trim (page 2-18)
Zero Trim (page 2-17)
Calibrate the 4–20 mA Output (Digital-to-Analog [D/A] Signal Conversion)
4–20 mA Output Trim (page 2-19) or
4–20 mA Output Trim Using Other Scale (page 2-19)
Figure 2-7 illustrates the Rosemount 3051N transmitter data flow. This data flow can be summarized in four major steps:
1. A change in pressure is measured by a change in the sensor output (Sensor Signal).
2. The sensor signal is converted to a digital format that can be understood by the microprocessor (Analog-to-Digital Signal Conversion).
3. Corrections are performed in the microprocessor to obtain a digital representation of the process input (Digital PV).
4. The Digital PV is converted to an analog value (Digital-to-Analog Signal Conversion).
Figure 2-7 also identifies the approximate transmitter location for each calibration task. Note that the data flows from left to right, and a parameter change affects all values to the right of the changed parameter.
Not all calibration procedures should be performed for each Rosemount 3051N transmitter. In addition, some procedures are appropriate for bench calibration but should not be performed during field calibration. Table 2-2 identifies the recommended calibration procedures for each type of Rosemount 3051N transmitter for both bench and field calibration.
2-15
Rosemount 3051N
Transmitter Electronics Module
Microprocessor
Digital PV
Sensor
Input Device
Output Device
20.00 mA
3051:PT-4001
1 Device Setup
Online 2 PV 100.00 inH2O
3 AO 20.00 mA 4 LRV 0.00 inH2O 5 URV 100.00 inH2O
Transmitter Ranged 0 to 100 inH2O
Input
Pressure
Sensor
Signal
Analog Output
HART
Communicator
NOTE Value on PV line should equal the input pressure. Value on AO line should equal the output device reading.
FIGURE 2-7. Transmitter Data Flow with Calibration Options.
Reference Manual
00809-0100-4808, Rev CA
June 2008

Deciding Which Trim Procedure to Use

Sensor Trim You can trim the sensor using either the full trim or the zero trim function. The

2-16
To decide which trim procedure to use, you must first determine whether the analog-to-digital section or the digital-to-analog section of the transmitter electronics is in need of calibration. To do so, refer to Figure 2-7 and perform the following procedure:
trim functions vary in complexity, and their use is application-dependent. Both trim functions alter the transmitter’s interpretation of the input signal.
A zero trim is a single-point adjustment. It is useful for compensating for mounting position effects and is most effective when performed with the transmitter installed in its final mounting position. Since this correction maintains the slope of the characterization curve, it should not be used in place of a full trim over the full sensor range.
1. Connect a pressure source, a HART Communicator, and a digital readout device to the transmitter.
2. Establish communication between the transmitter and the communicator.
3. Apply pressure equal to the upper range point pressure (100 inH
0,
2
for example).
4. Compare the applied pressure to the Process Variable (PV) line on the Communicator On-line Menu. IF communicator does not match the applied pressure, and you are confident that your test equipment is accurate, THEN
the PV reading on the
perform a
sensor trim.
5. Compare the Analog Output (AO) line on the communicator on-line menu to the digital readout device. IF
the AO reading on the communicator does not match the digital readout device, and you are confident that your test equipment is accurate, THEN
perform an
output trim.
Reference Manual
ZERO-BASED FLOW
APPLICATION
ZERO-BASED LEVEL
APPLICATION
NONZERO-BASED
LEVEL APPLICATION
20 mA Point 4 mA Point
20 mA Point 4 mA Point
00809-0100-4808, Rev CA June 2008
FIGURE 2-8. Typical Zero vs. Non-zero-Based Application Illustrations.
Rosemount 3051N
When performing a zero trim, ensure that the equalizing valve is open and all wet legs are filled to the correct levels.
NOTE
Do not perform a zero trim on Rosemount 3051N Absolute pressure transmitters. A zero trim is zero-based, and absolute pressure transmitters
reference absolute zero. To correct mounting position effects on a Rosemount 3051N Absolute Pressure Transmitter, perform a low trim within the full sensor trim function. The low trim function provides a “zero” correction similar to the zero trim function but it does not require the input to be zero-based.
A full trim is a two-point sensor calibration where two end-point pressures are applied, and all output is linearized between them. You should always adjust the low trim value first to establish the correct offset. Adjustment of the high trim value provides a slope correction to the characterization curve based on the low trim value. The factory-established characterization curve is not changed by this procedure. The trim values allow you to optimize performance over your specified measuring range at the calibration temperature.

Zero Trim To calibrate the sensor with a HART Communicator using the Zero Trim

HART Comm. 1, 2, 3, 3, 1
function, perform the following procedure.
1. Vent the transmitter and attach a communicator to the measurement loop.
2. From the communicator menu select 1 Device setup, 2 Diagnostics and service, 3 Calibration, 3Sensor trim, 1 Zero trim to prepare to adjust the zero trim.
NOTE
The transmitter must be within 3% of true zero (zero-based) in order to calibrate it using the zero trim function.
3. Follow the commands provided by the communicator to complete the adjustment of the zero trim.
2-17
Reference Manual
250 Ω Minimum Loop Resistance
Rosemount 3051N Transmitter
Precision Meter
24 V dc Power Supply
HART-Based
Communicator
Rosemount 275 or
Rosemount 375
Dead Weight Tester
Calibration Standard for
Sensor Trim Only
00809-0100-4808, Rev CA
Rosemount 3051N
June 2008

Full Trim To calibrate the sensor with a HART Communicator using the full trim

HART Comm. 1, 2, 3, 3
function, perform the following procedure:
1. Assemble and power the entire calibration system including a transmitter, HART Communicator, power supply, pressure input source, and readout device (see Figure 2-9).
NOTE
Use a pressure input source with sufficient accuracy and allow the input pressure to stabilize for 10 seconds before entering any values.
2. From the communicator menu select 1 Device setup, 2 Diagnostics and service, 3 Calibration, 3Sensor trim, 2 Lower sensor trim to prepare to adjust the lower trim point.
NOTE
Select pressure input values so that the low and high values are equal to or outside the 4 and 20 mA points. Do not attempt to obtain reverse output by reversing the high and low points. The transmitter allows approximately a 5% URL deviation from the characterized curve established at the factory.
FIGURE 2-9. Digital Trim Connection Drawing (4–20 mA Transmitters).
3. Follow the commands provided by the communicator to complete the adjustment of the lower value.
4. Repeat the procedure for the upper value, replacing 2 Lower sensor trim with 3 Upper sensor trim in Step 2.
2-18
Loading...
+ 70 hidden pages