Emerson VSSG 451, VSSG 601, VSG 301, VSG361, VSG 401 Operation Manual

...
VSG/VSSG compact logix PLC
Operation manual
FOR UNITS BUILT BEFORE JULY 1, 2013
Important Note
Before applying power to the control panel, all wiring to the panel shall be installed per NEC. Specifically check for proper voltage and that the neutral is grounded at the source. An equipment ground should also be run to the panel.
*See Wiring Instructions and Diagrams before proceeding.
NOTES:
• Before start-up you need to enter all system values and options, see section on Setpoint Values.
• Power circuits entry on left side of enclosure
• Instrument circuits entry on right side of enclosure
Electrical installation shall be completed by a licensed electrician qualified in field wiring
located in Class 1 Div 2 Hazardous Locations per the National Electric Code (NEC).
VSG/VSSG • Compact Logix PLC Manual •Vilter/Emerson • 35391CL
3
4/Blank
VSG/VSSG • Compact Logix PLC Manual •Vilter/Emerson • 35391CL
Table of Contents
Important Note .................................................................................................3
VSG/VSSG STANDARD VILTER WARRANTY STATEMENT ...................................... 6
Operational Flow Charts .................................................................................... 7
Main Screen ..................................................................................................... 15
Log On Screen .................................................................................................16
Set Up Screen .................................................................................................. 17
Vilter Only Screen ............................................................................................19
Menu Screen ................................................................................................... 20
Compressor Alarm and Trip .............................................................................24
Compressor Timer Setpoints ...........................................................................26
Compressor Control Setpoints ......................................................................... 28
Additional Compressor Controls ...................................................................... 33
Compressor Setpoints and Alarms ................................................................... 34
Motor Speed Setpoints & Control Screen ......................................................... 36
Diagnostics Force Output ................................................................................ 38
Instrument Calibration ....................................................................................39
Oil Mixing Valve ............................................................................................... 45
Unit Start Screen (Start / Stop Logic) ................................................................ 48
Device Names ..................................................................................................51
Calibration Procedure of Optical Actuators ...................................................... 52
Calibration Procedure of Optical Actuators ...................................................... 53
Calibration Procedure of Optical Actuators ...................................................... 54
Installation Instructions For Replacement Of Optical Actuator ......................... 56
Slide Valve Actuator Theory of Operation ........................................................ 57
Slide Valve Actuator Troubleshooting Guide ....................................................58
Command Shaft Rotation and Travel ................................................................ 60
Safety Failure Message .................................................................................... 62
Version Screen .................................................................................................65
Trend Charts .................................................................................................... 66
Captured Data at Shutdown ............................................................................69
VSG/VSSG • Compact Logix PLC Manual •Vilter/Emerson • 35391CL
5
VSG/VSSG STANDARD VILTER WARRANTY STATEMENT
Seller warrants all new single screw gas compression units and bareshaft single screw compressors manufactured by it and supplied to Buyer to be free from defects in materials and workmanship for a period of (a) eighteen (18) months from the date of shipment or (b) twelve (12) months from the date of installation at the end user’s location, whichever occurs first.
If within such period any such product shall be proved to Seller’s satisfaction to be defective, such product shall be repaired or replaced at Seller’s option. Such repair or replacement shall be Seller’s sole obligation and Buyer’s exclusive remedy hereunder and shall be conditioned upon (a) Seller’s receiving written notice of any alleged defect within ten (10) days after its discovery, (b) payment in full of all amounts owed by Buyer to Seller and (c) at Seller’s option, Buyer shall have delivered such products to Seller, all expenses prepaid to its factory. Expenses incurred by Buyer in repairing or replacing any defective product (including, without limitation, labor, lost refrigerant or gas and freight costs) will not be allowed except by written permission of Seller. Further, Seller shall not be liable for any other direct, indirect, consequential, incidental, or special damages arising out of a breach of warranty.
This warranty is only applicable to products properly maintained and used according to Seller’s instructions. This warranty does not apply (i) to ordinary wear and tear, damage caused by corrosion, misuse, overloading, neglect, improper use or operation (including, without limitation, operation beyond rated capacity), substitution of parts not approved by Seller, accident or alteration, as determined by Seller or (ii) if the product is operated on a gas with an H2S level above 100 PPM. In addition, Seller does not warrant that any equipment and features meet the requirements of any local, state or federal laws or regulations. Products supplied by Seller hereunder which are manufactured by someone else are not warranted by Seller in any way, but Seller agrees to assign to Buyer any warranty rights in such products that Seller may have from the original manufacturer. Labor and expenses for repair are not covered by warranty.
THE WARRANTY CONTAINED HEREIN IS EXCLUSIVE AND IN LIEU OF ALL OTHER REPRESENTATIONS AND WARRANTIES, EXPRESS OR IMPLIED, AND SELLER EXPRESSLY DISCLAIMS AND EXCLUDES ANY IMPLIED WARRANTY OF MERCHANTABILITY OR IMPLIED WARRANTY OF FITNESS FOR A PARTICULAR PURPOSE.
Any description of the products, whether in writing or made orally by Seller or Seller’s agents, specifications, samples, models, bulletins, drawings, diagrams, engineering sheets or similar materials used in connection with Buyer’s order are for the sole purpose of identifying the products and shall not be construed as an express warranty. Any suggestions by Seller or Seller’s agents regarding use, application or suitability of the products shall not be construed as an express warranty unless confirmed to be such in writing by Seller.
6
VSG/VSSG • Compact Logix PLC Manual •Vilter/Emerson • 35391CL
Requirements to Start Compressor
Operational Flow Charts
Volume and
Capacity slides are
less than 5 %.
Oil Separator Temp > Oil Sep Start
Trip
Setpt.
Oil Pump On: Prelub Oil Press is > Prelub Oil Press Reset Setpt for “Min Compressor Prelub Timer” setting (Default 7 Seconds)
Critical Compressor Run Logic @ Compressor Start
Start
Compressor
Compressor
Start Mode
Prelube 5
Seconds
Satified Oil
Pressure
Filter Diff Press <
Filter Diff
Start Trip Setpt
Is Run Oil Press >
Run Oil Press setpt?
Yes
Yes
Start Compressor
Is
Run Oil Press >
Run Oil Press
setpt?
Reset
(Default 40 PSI)
No
Run Oil Press Failure
“Filter Diff Press Safety
Changeover” timer expires
(60 sec after start).
Compressor Amperage Load Limiting
Is
Motor Amps >
FLA (ON
)
Setpt?
Yes
No
Capacity INC Disabled
No
Is
Motor Amps >
Max (OFF
Setpt?
Yes
)
Is
Filter Diff < Hi Filter
Diff Press Run Trip
setpt?
No
Oil Separator Temp Safety Changeover
Yes Yes
Timer expires. (5 min after start)
Is
Oil Sep Temp > Lo
Oil Sep Run Reset
setpt:?
No
Run Filter Diff Press Failure Lo Run Oil Sep Temp Failure
High Disch Pressure Load Limit
Is Normal Loading & Unloading
Disch Press >
Cutin (ON
)
Normal Loading &
No
Unloading
Setpt?
Yes
Capacity INC Disabled
No
Capacity Decrease until Amps < FLA x
1.0625
Is
Disch Press >
Cutout (OFF
Setpt?
)
Capacity Decrease until
Yes
DischPress < ON Setpt x
1.0625
Yes
Run
VSG/VSSG • Compact Logix PLC Manual •Vilter/Emerson • 35391CL
7
Suction Pressure Control
Operational Flow Charts
Is
Suction Press >
Suct Press Cap Inc
Setpt?
No
No
Is
Suction Press <
Suct Press Cap
Dec Setpt?
Suction Pressure Safety
Capacity Inc
No No
Yes Yes Yes
Is Cap Inc ON Timer
Timed Out?
No
WAIT
Is Cap Inc OFF Timer
Timed Out?
Capacity Dec
Is Cap Dec. ON Timer
Yes Yes Yes
Timed Out?
Is Cap Dec. OFF Timer
Timed Out?
No
Reset Cap Inc Timers
Reset Cap Dec Timers
Suct Press Alarm
No
Is
Suction Press <
Setpt?
No
Is
Suction Press <
Suct Press Trip
Setpt?
Yes
Yes
Lo Suction Press
Alarm
Lo Suction Press
Failure
8
VSG/VSSG • Compact Logix PLC Manual •Vilter/Emerson • 35391CL
Operational Flow Charts
Oil Cooler Fan Control
(Selectable Control Optional)
Oil Cooler
Unit Start
outlet temp >
set pt?
Oil Cooler
outlet temp <
set pt?
Oil Temperature Control Valve
PID Control
30 sec
delay
Yes
NoNo
Yes
Increase Speed
Decrease Speed
PID Control
Unit Start
Oil injection
temp > set pt?
No No
Oil injection
temp < set pt?
Yes
Yes
30 sec
delay
Modulate valve
Modulate valve
VSG/VSSG • Compact Logix PLC Manual •Vilter/Emerson • 35391CL
9
Operational Flow Charts
Delayed Lockout Timers
WARNING: FOR THE FOLLOWING SHUTDOWNS, A DELAYED RESTART MAY OCCUR:
High Discharge Pressure Failure High Compressor Discharge Temp Failure High Package Outlet Temp Failure High Oil Injection Temp Failure
Shutdown due to
Operational
Failure
1 min Delay
Auto Restart if All Other Values
Are In Range
WARNING: INCASE OF A POWER FAILURE A DELAYED RESTART MAY OCCUR:
Shutdown Due
to Power Failure
Power Re-
establishing
Is
Shutdown Value
Below Reset
Value?
No
Yes
No
No
Lockout
Requires
Manual Restart
Yes Yes
No
Has It been *H1 Hours Since
Shutdown?
Have
There Been 3 Shutdowns of “Any
of the Above Failure Conditions”
in H2 Hours
Yes
Has It been *H3 Hours Since
Shutdown?
H1= Timer Set Between .5-6 Hours. Default Value= .5 Hours
Yes
H2= Timer Set Between 4-100 Hours. Minimum and Default Value= 4 Hours H2 must be equal to or greater than 4 x H1
H3= Timer Set Between .5-6 Hours. Default Value= .5 Hours
Auto Restart if All Other Values
Are In Range
Yes
10
1 min Delay
Was Compressor
Running During Power
Failure?
No
VSG/VSSG • Compact Logix PLC Manual •Vilter/Emerson • 35391CL
No
No
Lockout
Requires
Manual Restart
Have
There Been 3 Shutdowns
of This Same Condition
in H4 Hours
H4= Timer Set Between 4-100 Hours. Minimum and Default Value= 4 Hours H4 must be equal to or greater than 4 x H3
Yes
Operational Flow Charts
Capacity Control Using Suction Pressure Control Setpoints
Start
Has
Decrease at Start
(Expired 15
sec.)
No
Wait
Are Motor
Amps >
Motor Amps Load
Yes No No Yes Yes
Motor Amp Load Limit
Setpt?
Limit ON
(Time Delay
10 sec)
Yes
Disable Cap Inc
Are Motor
Amps >
Setpt?
OFF
Yes
Dec Cap
(Timer)
No Change No Change
Is Disch
Press > High Disch
Press Unload
OFF
Setpt?
Yes
Disable Cap Inc
Is Disch
Press > High Disch
Press Unload
Setpt?
ON
Yes
Dec Cap
(Timer)
Is Capacity
> Min Run Cap
OFF
Setpt?
No
Increase Cap
(Timer)
Is Suct
Press > Cap Inc
ON
Setpt?
No
Is Suct Press< Cap
Setpt?
Dec ON
Yes
Dec Cap
(Timer)
No
Inc Cap (Timer)
VSG/VSSG • Compact Logix PLC Manual •Vilter/Emerson • 35391CL
11
Operational Flow Charts
Capacity Control Using Discharge Pressure Control Setpoints
Start
Are Motor
Has Decrease at Start (Expired 15 sec.)
Yes
Amps >
Motor Amps Load
Limit ON
Setpt?
(Time Delay
10 sec)
No
Is Disch Press > Cap
Dec ON
Setpt?
Yes
Dec Cap
(Timer)
No
Wait
Yes
Disable Cap Inc
Are Motor
Amps >
Motor Amp Load Limit
OFF
Setpt?
Yes
Dec Cap
(Timer)
No
No
Change)
No
Is Disch Press < Cap
Inc ON
Setpt
No
Yes
Inc Cap (Timer)
No
change
12
VSG/VSSG • Compact Logix PLC Manual •Vilter/Emerson • 35391CL
Operational Flow Charts
Compressor Operation with VFD Drive
Start
Compressor
Start VFD at
Minimum Speed
(30 Hz Typ.)
Is Control Press.
Within Setpt
Deadbands?
Yes
Check/Adjust VFD
Is Control Press @
Setpoint?
Yes
Is Motor Speed @
Min?
Check/Adjust Capacity Slide
No
Increase or Decrease the
Compressor Capacity Slides to
No
No
No
Match Setpoints
Increase or Decrease the
Compressor Capacity Slides to
Match Setpoints
Increase or Decrease Motor Speed
@ Rate Defined by VFD PID
Parameters
Is Capslide @
100%
Yes
VSG/VSSG • Compact Logix PLC Manual •Vilter/Emerson • 35391CL
13
14/Blank
VSG/VSSG • Compact Logix PLC Manual •Vilter/Emerson • 35391CL
Main Screen
Main Screen
This screen has been designed to give the operator an overall view of all operating parameters affect­ing the compressor package. This screen should
always be displayed when maintenance items and setpoint items are not being performed.
Status information such as Alarms and Trips are displayed on the screen.
This screen contains buttons to navigate to setpoint setup screens.
Status information on the compressor, oil pump, oil heater and run mode.
Start/Stop buttons.
Hour meter.
Motor amperage.
Compressor operating conditions.
VSG/VSSG • Compact Logix PLC Manual •Vilter/Emerson • 35391CL
15
Log On or Off
Log On Screen
Press Log on Button and the below screen will ap­pear. When altering setpoints, log on is necessary. Select appropriate user name and enter password to change/access setpoints.
To Log On: Enter your User Name (case sensitive) and Password (case sensitive) then touch the <_| enter key.
To Log Off: Touch the Log Off button. This will return to the DEFAULT low-level user. The DEFAULT user may navigate to most screens but cannot change settings.
Note: An operator will be automatically logged off after 10 minutes of inactivity.
Note: The machine can be run and moni­tored without logging on. To change the setup or parameters of the machine, the operator must log on.
16
VSG/VSSG • Compact Logix PLC Manual •Vilter/Emerson • 35391CL
Set Up Screen
From the Main screen, touch the Setup button. After entering an authorized user name and password, the screen pictured below will appear.
Pressure units,Temperature units and Suction/ Discharge Pressure control configurations are list selectable.
To choose a configuration from a list: 1.) Touch the list. 2.) Touch the Up or Down Arrow to move the green cursor “>” along side of the desired configura­tion. 3.) Touch the Enter button. This will highlight­green the chosen configuration.
Touch Here
VSG/VSSG • Compact Logix PLC Manual •Vilter/Emerson • 35391CL
17
Set Up Screen
· Setpoint #1/#2 Select – The operator can select
the compressor to run with setpoint #1 or #2 settings.
· Oil Pump Selection – The operator can select the compressor to use either oil pump #1 or #2 when compressor has a second oil pump.
· Pressure Units – Select units of measure for pres- sure readings. Choices are PSIG, PSIA, kPa [A], kPa [G], kg/cm² [A], kg/cm² [G], Hg (vac) [G], WC [A], WC [G], Bar [A], Bar [G], Torr [A], Torr [G].
· Temperature Units – Select units of measure for temperature. Choices are Fahrenheit or Cel­sius, Kelvin and Rankine.
· Anti-Recycle – The operator can select from the following Anti-Recycle options: True, Accumula­tive, Modified, or Hot Starts. These select the strategy used to prevent excessive start/stop cycles of the compressor. Timers and counters used to enforce anti-recycling are adjusted and monitored in the Compressor Timer Settings screen, reached from the Menu screen. Help for the Timer Settings screen explains how the different settings and strategies operate.
channel.
· Min Run Capacity – When enabled, the Minimum Run Capacity setting on the Addition Compres­sor Setpoints screen operates as described in the help for that screen. When multiple compressor sequencing is used, selecting Disable here does not interfere with use of the Min Run Capacity setting in the sequencing logic.
· Oil Pump Option #1 – The operator can choose the method the compressor oil pump operates.
· Suction Pressure Sensor Mode – The operator can select local or remote sensor mode. Remote sensor mode is typically used when compressors are installed in parallel.
· Compressor Control Via – Operator can choose the method or mode of compressor control. This determines which measured variable is used in making loading (capacity control) decisions. The choice selected here determines which setpoints are made available for adjustment on the Compressor Control Setpoints screen.
· Capacity & Volume Slide Non-Movement – Alarm enable and disable buttons permit selecting whether an alarm should be generated when failure of slides to move is detected.
· Reset After Power Fail – When Auto is selected, the compressor will attempt to restart on pow­ering up if it was running in ‘Auto’ when powered down and enabling conditions are met. When ‘Manual’ is selected, the compressor powers up into the ‘Stop’ mode and an explicit command to run is required from an operator or comms
18
VSG/VSSG • Compact Logix PLC Manual •Vilter/Emerson • 35391CL
Vilter Only Screen
To synchronize the PanelView date and time to the Conrol Logix date and time:
1. Display the Vilter Only Screen (This screen has restricted access).
2. Touch the “Touch to Synchronize HMI Clock to PLC” button.
VSG/VSSG • Compact Logix PLC Manual •Vilter/Emerson • 35391CL
19
Menu Screen
Touch Here
At the bottom of the Main screen touch the Menu button to bring up the screen shown in Figures below.
Use this screen to navigate to the other setpoint screens contained within the program. Each screen has a help button to describe the function of the screen.
There are several buttons that are common for all menu screens:
Return to Menu – This button always returns you to the Menu screen
Log On – The user is allowed to view data at all screen levels but cannot edit data until a login has occurred.
Refer to the Log on/off Instructions on page 16.
Set – To change a value, the operator must first press the SET button and then the text field of the value they
want to modify. A number pad will pop up for ease in entry.
Help – This screen will provide more information to the user about the operation of the microprocessor.
Event List – provides a chronological event listing.
Chart – Provides a line graph showing process values over a range of time.
Auto – Places the capacity slides into automatic mode. In automatic mode, the capacity slide moves according
to control setpoint information.
Manual – Places the capacity slides into manual mode. In manual mode, the capacity slide moves moves based
on input from the operator.
20
VSG/VSSG • Compact Logix PLC Manual •Vilter/Emerson • 35391CL
Menu Screen
There are three options for the Compressor Control Setpoints:
VSG/VSSG • Compact Logix PLC Manual •Vilter/Emerson • 35391CL
Discharge Pressure Control
21
Menu Screen
22
Suction Pressure Control
VSG/VSSG • Compact Logix PLC Manual •Vilter/Emerson • 35391CL
Loading...
+ 50 hidden pages