Emerson VSSG 291, VSSG 601, VSSG 341, VSSG 451, VSG 751 Software Manual

...
VSG & VSSG
Single Screw Compressor
Software Manual
Compact Logix PLC
1
2
Important Note
Before applying power to the control panel, all wiring to the panel shall be installed per NEC. Specifically check for proper voltage and that the neutral is grounded at the source. An equipment ground should also be run to the panel.
*See Wiring Instructions and Diagrams before proceeding.
NOTES:
• Before start-up you need to enter all system values and options, see section on Setpoint Values.
• Power circuits entry on left side of enclosure
• Instrument circuits entry on right side of enclosure
Electrical installation shall be completed by a licensed electrician qualified in field wiring
located in Class 1 Div 2 Hazardous Locations per the National Electric Code (NEC).
3
4
Table of Contents
Important Note .................................................................................................3
VSG STANDARD VILTER WARRANTY STATEMENT
............................................... 6
Operational Flow Charts ....................................................................................7
Main Screen
.....................................................................................................15
Log On Screen .................................................................................................16
Set Up Screen ..................................................................................................17
Vilter Only Screen
............................................................................................19
Menu Screen ...................................................................................................20
Compressor Alarm and Trip
............................................................................. 24
Compressor Control Setpoints ......................................................................... 27
Additional Compressor Controls ...................................................................... 32
Compressor Setpoints and Alarms Motor Speed Setpoints & Control Screen
................................................................... 34
.........................................................35
Diagnostics Force Output ................................................................................37
Instrument Calibration ....................................................................................38
Oil Mixing Valve ...............................................................................................43
Unit Start Screen (Start / Stop Logic) Device Names
..................................................................................................50
................................................................47
Calibration Procedure of Optical Actuators ...................................................... 51
Calibration Procedure of Optical Actuators ...................................................... 52
Calibration Procedure of Optical Actuators ...................................................... 53
Installation Instructions For Replacement Of Optical Actuator Slide Valve Actuator Theory of Operation
........................................................ 55
.........................54
Slide Valve Actuator Troubleshooting Guide ....................................................56
Slide Valve Actuator Troubleshooting Guide ....................................................57
Slide Valve Actuator Troubleshooting Guide ....................................................58
Command Shaft Rotation and Travel Safety Failure Message
....................................................................................60
................................................................ 59
Safety Failure Message .................................................................................... 61
Safety Failure Message .................................................................................... 62
Version Screen .................................................................................................63
Trend Charts
....................................................................................................64
Trend Charts .................................................................................................... 65
Captured Data at Shutdown
............................................................................ 67
Appendix A: Slide Valve Actuator Troubleshooting Guide Appendix B: Drawings and Parts Lists
5
VSG STANDARD VILTER WARRANTY STATEMENT
Seller warrants all new single screw gas compression units and bareshaft single screw compressors manufactured by it and supplied to Buyer to be free from defects in materials and workmanship for a period of (a) eighteen (18) months from the date of shipment or (b) twelve (12) months from the date of installation at the end user’s location, whichever occurs first.
If within such period any such product shall be proved to Seller’s satisfaction to be defective, such product shall be repaired or replaced at Seller’s option. Such repair or replacement shall be Seller’s sole obligation and Buyer’s exclusive remedy hereunder and shall be conditioned upon (a) Seller’s receiving written notice of any alleged defect within ten (10) days after its discovery, (b) payment in full of all amounts owed by Buyer to Seller and (c) at Seller’s option, Buyer shall have delivered such products to Seller, all expenses prepaid to its factory. Expenses incurred by Buyer in repairing or replacing any defective product (including, without limitation, labor, lost refrigerant or gas and freight costs) will not be allowed except by written permission of Seller. Further, Seller shall not be liable for any other direct, indirect, consequential, incidental, or special damages arising out of a breach of warranty.
This warranty is only applicable to products properly maintained and used according to Seller’s instructions. This warranty does not apply (i) to ordinary wear and tear, damage caused by corrosion, misuse, overloading, neglect, improper use or operation (including, without limitation, operation beyond rated capacity), substitution of parts not approved by Seller, accident or alteration, as determined by Seller or (ii) if the product is operated on a gas with an H2S level above 100 PPM. In addition, Seller does not warrant that any equipment and features meet the requirements of any local, state or federal laws or regulations. Products supplied by Seller hereunder which are manufactured by someone else are not warranted by Seller in any way, but Seller agrees to assign to Buyer any warranty rights in such products that Seller may have from the original manufacturer. Labor and expenses for repair are not covered by warranty.
THE WARRANTY CONTAINED HEREIN IS EXCLUSIVE AND IN LIEU OF ALL OTHER REPRESENTATIONS AND WARRANTIES, EXPRESS OR IMPLIED, AND SELLER EXPRESSLY DISCLAIMS AND EXCLUDES ANY IMPLIED WARRANTY OF MERCHANTABILITY OR IMPLIED WARRANTY OF FITNESS FOR A PARTICULAR PURPOSE.
Any description of the products, whether in writing or made orally by Seller or Seller’s agents, specifications, samples, models, bulletins, drawings, diagrams, engineering sheets or similar materials used in connection with Buyer’s order are for the sole purpose of identifying the products and shall not be construed as an express warranty. Any suggestions by Seller or Seller’s agents regarding use, application or suitability of the products shall not be construed as an express warranty unless confirmed to be such in writing by Seller.
6
Requirements to Start Compressor
Operational Flow Charts
Volume and
Capacity slides are
less than 5 %.
Oil Separator Temp > Oil Sep Start
Trip
Setpt.
Oil Pump On: Prelub Oil Press is > Prelub Oil Press Reset Setpt for “Min Compressor Prelub Timer” setting (Default 7 Seconds)
Critical Compressor Run Logic @ Compressor Start
Start
Compressor
Compressor
Start Mode
Prelube 5
Seconds
Satified Oil
Pressure
Filter Diff Press <
Filter Diff
Start Trip Setpt
Is Run Oil Press >
Run Oil Press setpt?
Yes
Yes
Start Compressor
Is
Run Oil Press >
Run Oil Press
setpt?
Reset
(Default 40 PSI)
No
Run Oil Press Failure
“Filter Diff Press Safety
Changeover” timer expires
(60 sec after start).
Compressor Amperage Load Limiting
Is
Motor Amps >
FLA (ON
)
Setpt?
Yes
No
Capacity INC Disabled
No
Is
Motor Amps >
Max (OFF
)
Setpt?
Yes
Is
Filter Diff < Hi Filter
Diff Press Run Trip
setpt?
No
Oil Separator Temp Safety Changeover
Yes Yes
Timer expires. (5 min after start)
Is
Oil Sep Temp > Lo
Oil Sep Run Reset
setpt:?
No
Run Filter Diff Press Failure Lo Run Oil Sep Temp Failure
High Disch Pressure Load Limit
Is Normal Loading & Unloading
Disch Press >
Cutin (ON
)
Normal Loading &
No
Unloading
Setpt?
Yes
Capacity INC Disabled
No
Capacity Decrease until Amps < FLA x
1.0625
Is
Disch Press >
Cutout (OFF
Setpt?
)
Capacity Decrease until
Yes
DischPress < ON Setpt x
1.0625
Yes
Run
7
Suction Pressure Control
Is
Suction Press >
Suct Press Cap Inc
Setpt?
No
No
Is
Suction Press <
Suct Press Cap
Dec Setpt?
Suction Pressure Safety
Capacity Inc
No No
Yes Yes Yes
Is Cap Inc ON Timer
Timed Out?
No
WAIT
Is Cap Inc OFF Timer
Timed Out?
Capacity Dec
Is Cap Dec. ON Timer
Yes Yes Yes
Timed Out?
Is Cap Dec. OFF Timer
Timed Out?
No
Reset Cap Inc Timers
Reset Cap Dec Timers
Suct Press Alarm
No
Is
Suction Press <
Setpt?
No
Is
Suction Press <
Suct Press Trip
Setpt?
Yes
Yes
Lo Suction Press
Alarm
Lo Suction Press
Failure
8
Oil Cooler Fan Control
(Selectable Control Optional)
Unit Start
Oil Cooler
outlet temp >
set pt?
NoNo
Oil Cooler
outlet temp <
set pt?
Yes
Yes
PID Control
30 sec
delay
Increase Speed
Decrease Speed
Oil Temperature Control Valve
Unit Start
No No
Oil injection
temp > set pt?
Oil injection
temp < set pt?
Yes
Yes
PID Control
30 sec
delay
Modulate valve
Modulate valve
9
Delayed Lockout Timers WARNING: FOR THE FOLLOWING SHUTDOWNS, A DELAYED RESTART MAY OCCUR:
High Discharge Pressure Failure High Compressor Discharge Temp Failure High Package Outlet Temp Failure High Oil Injection Temp Failure
Shutdown due to
Operational
Failure
1 min Delay
Auto Restart if All Other Values
Are In Range
WARNING: INCASE OF A POWER FAILURE A DELAYED RESTART MAY OCCUR:
Shutdown Due
to Power Failure
Power Re-
establishing
Is
Shutdown Value
Below Reset
Value?
No
Yes
No
No
Lockout
Requires
Manual Restart
Yes Yes
No
Has It been *H1 Hours Since
Shutdown?
Have
There Been 3 Shutdowns of “Any
of the Above Failure Conditions”
in H2 Hours
Yes
Has It been *H3 Hours Since
Shutdown?
H1= Timer Set Between .5-6 Hours. Default Value= .5 Hours
Yes
H2= Timer Set Between 4-100 Hours. Minimum and Default Value= 4 Hours H2 must be equal to or greater than 4 x H1
H3= Timer Set Between .5-6 Hours. Default Value= .5 Hours
Auto Restart if All Other Values
Are In Range
Yes
10
1 min Delay
Was Compressor
Running During Power
Failure?
No
No
No
Lockout
Requires
Manual Restart
Have
There Been 3 Shutdowns
of This Same Condition
in H4 Hours
H4= Timer Set Between 4-100 Hours. Minimum and Default Value= 4 Hours H4 must be equal to or greater than 4 x H3
Yes
Capacity Control Using Suction Pressure Control Setpoints
Start
Are Motor
Has
Decrease at Start
(Expired 15
sec.)
Yes No No Yes Yes
Amps >
Motor Amps Load
Setpt?
Limit ON
(Time Delay
10 sec)
Press > High Disch
Is Disch
Press Unload
OFF
Setpt?
Is Capacity
> Min Run Cap
OFF
Setpt?
Is Suct
Press > Cap Inc
ON
Setpt?
Inc Cap (Timer)
No
Wait
Yes
Disable Cap Inc
Are Motor
Amps >
Motor Amp Load Limit
OFF
Setpt?
Yes
Dec Cap
(Timer)
Yes
Disable Cap Inc
Is Disch
Press > High Disch
Press Unload
ON
Setpt?
Yes
No Change No Change
Dec Cap (Timer)
No
Increase Cap
(Timer)
No
Is Suct Press< Cap
Dec ON
Setpt?
Yes
Dec Cap
(Timer)
No
11
Capacity Control Using Discharge Pressure Control Setpoints
Start
Are Motor
Has Decrease at Start (Expired 15 sec.)
Yes Yes
Amps >
Motor Amps Load
Limit ON
Setpt?
(Time Delay
10 sec)
No
Is Disch Press > Cap
Dec ON
Setpt?
Dec Cap
(Timer)
No
Wait
Yes
Disable Cap Inc
Are Motor
Amps >
Motor Amp Load Limit
OFF
Setpt?
Yes
Dec Cap
(Timer)
No
No
Change)
No
Is Disch Press < Cap
Inc ON
Setpt
No
Yes
Inc Cap (Timer)
No
change
12
Compressor Operation with VFD Drive
Start
Compressor
Check/Adjust Capacity Slide
No
Start VFD at
Minimum Speed
(30 Hz Typ.)
Is Control Press.
Within Setpt
Deadbands?
Yes
Check/Adjust VFD
Is Control Press @
Setpoint?
Yes
Is Motor Speed @
Min?
No
No
Increase or Decrease the
Compressor Capacity Slides to
Match Setpoints
Increase or Decrease the
Compressor Capacity Slides to
Match Setpoints
Increase or Decrease Motor Speed
@ Rate Defined by VFD PID
Parameters
No
Is Capslide @
100%
Yes
13
14
Main Screen
Main Screen
This screen has been designed to give the operator an overall view of all operating parameters affect­ing the compressor package. This screen should
always be displayed when maintenance items and setpoint items are not being performed.
Status information such as Alarms and Trips are displayed on the screen.
This screen contains buttons to navigate to setpoint setup screens.
Status information on the compressor, oil pump, oil heater and run mode.
Start/Stop buttons.
Hour meter.
Motor amperage.
Compressor operating conditions.
15
Log On or Off
Log On Screen
Note: An operator will be automatically logged off after 10 minutes of inactivity.
Note: The machine can be run and moni­tored without logging on. To change the setup or parameters of the machine, the operator must log on.
Press Log on Button and the above screen will ap­pear. When altering setpoints, log on is necessary. Select appropriate user name and enter password to change/access setpoints.
To Log On: Touch the current User Name in the white User Name box to display the keypad. Enter your User Name (case sensitive) and Password (case sensitive) then touch the <_| enter key.
Some Users are configured such that their passwords may be changed. To change a User’s password, touch the Password box or the “abc” button then enter the old password, new password and confirm the new password.
To Log Off: Touch the Log Off button. This will return to the DEFAULT low-level user. The DEFAULT user may navigate to most screens but cannot change settings.
16
Set Up Screen
From the Main screen, touch the Setup button. After entering an authorized user name and password, the screen pictured below will appear.
Pressure units,Temperature units and Suction/ Discharge Pressure control configurations are list selectable.
To choose a configuration from a list: 1.) Touch the list. 2.) Touch the Up or Down Arrow to move the green cursor “>” along side of the desired configura­tion. 3.) Touch the Enter button. This will highlight­green the chosen configuration.
Touch Here
17
· Pressure Units – Select units of measure for pres- sure readings. Choices are psi, kg cm2 and kPa.
· Temperature Units – Select units of measure for temperature. Choices are Fahrenheit or Cel­sius.
· Anti-Recycle – The operator can select from the following Anti-Recycle options: True, Accumula­tive, Modified, or Hot Starts. These select the strategy used to prevent excessive start/stop cycles of the compressor. Timers and counters used to enforce anti-recycling are adjusted and monitored in the Compressor Timer Settings screen, reached from the Menu screen. Help for the Timer Settings screen explains how the different settings and strategies operate.
· Compressor Control Via – Operator can choose the method or mode of compressor control. This determines which measured variable is used in making loading (capacity control) decisions. The choice selected here determines which setpoints are made available for adjustment on the Compressor Control Setpoints screen.
· Slide Non-Movement – Alarm enable and dis- able buttons permit selecting whether an alarm should be generated when failure of slides to move is detected.
· Reset After Power Fail – When Auto is selected, the compressor will attempt to restart on pow­ering up if it was running in ‘Auto’ when powered down and enabling conditions are met. When ‘Manual’ is selected, the compressor powers up into the ‘Stop’ mode and an explicit command to run is required from an operator or comms channel.
· Min Run Capacity – When enabled, the Minimum Run Capacity setting on the Addition Compres­sor Setpoints screen operates as described in the help for that screen. When multiple compressor sequencing is used, selecting Disable here does not interfere with use of the Min Run Capacity setting in the sequencing logic.
18
Vilter Only Screen
To set and synchronize the date and time for the HMI and ControlLogix or CompactLogix processor, first con­figure the PanelView date and time then, move the PanelView’s date and time to the processor
To set the date, time and regional settings in the PanelView Plus HMI:
1. Display the Vilter Only Screen (This screen has restricted access).
2. Touch the PanelView Configuration button.
3. Wait approximately 30 seconds while the PanelView application shuts down then loads.
4. Touch the Thermal Settings button.
5. Scroll to or touch the Time/Date/ Regional Settings field then touch the Enter button.
6. Set the Date, Regional Settings. Time and Time Zone as applicable. Touch OK after setting each screens’ values to accept the new values.
7. When finished, touch the Close button to exit the Time/Date/Regional Settings screen.
8. IMPORTANT: Clear the log files of the PanelView after changing the PanelView Date and/or time. a. Touch or scroll to the File Management field then touch the Enter Button. b. Touch or scroll to the Delete Files field then touch the Enter button. c. Touch or scroll to the Delete Log Files field then touch the Enter button. DO NOT DELETE APPLICATIONS! DO NOT DELETE FONTS! d. Touch “Yes” to delete the log files. e. Touch the Close button twice to return to the Terminal Settings screen.
9. Touch the Close button twice again to return to the Terminal Settings screen.
10. Touch the Reset button then “Yes” button to reset the PanelView.
To synchronize the ControlLogix or CompactLogix date and time to the PanelView date and time:
1. Display the Vilter Only Screen (This screen has restricted access).
2. Touch the “Touch to Synchronize CLX Clock to HMI” button.
19
Touch Here
Menu Screen
At the bottom of the Main screen touch the Menu button to bring up the screen shown in Figures below.
Use this screen to navigate to the other setpoint screens contained within the program. Each screen has a help button to describe the function of the screen.
There are several buttons that are common for all menu screens:
Return to Menu – This button always returns you to the Menu screen
Logon To Edit – The user is allowed to view data at all screen levels but cannot edit data until a login has occurred.
Refer to the Logon Instructions on page 21.
Set – To change a value, the operator must first press the SET button and then the text field of the value they
want to modify. A number pad will pop up for ease in entry.
Help – This screen will provide more information to the user about the operation of the microprocessor.
Event List – provides a chronological event listing.
Chart – Provides a line graph showing process values over a range of time.
Auto – Places the capacity slides into automatic mode. In automatic mode, the capacity slide moves according
to control setpoint information.
Manual – Places the capacity slides into manual mode. In manual mode, the capacity slide moves moves based
on input from the operator.
20
There are three options for the Compressor Control Setpoints:
Discharge Pressure Control
21
22
Suction Pressure Control
Process Temperature Control
23
Compressor Alarm and Trip
· Low Suction Pressure Setpoints 1&2 – This is the low suction pressure safety. This safety is active in both temperature and pressure control modes. An alarm or trip will be active on a drop in suction pressure below the setpoint value.
· High Discharge Pressure Setpoints 1&2 This is the high discharge pressure safety. The alarm or trip will be active on a rise in discharge pressure above the setpoint value.
· Low Suction Temperature – This is the lowest allowable Suction temperature. The compres­sor will not be allowed to run if the Suction Temperature is below the trip setting.
· High Discharge Temperature – This is the high discharge temperature safety. The alarm or trip will be active if the discharge temperature should rise above the setpoint value.
· Low Oil Separator Start Temperature – This is the starting low oil separator temperature safety. The compressor is prevented from starting or running if the oil in the separator is below the trip value. After a time delay (Oil Separator
Temperature Safety Changeover), this safety is deactivated and the Lo Oil Separator Run Tem­perature is the active setpoint.
· Low Oil Separator Run Temperature – This is the running low oil separator temperature safety. After a time delay (Oil Separator Temperature Safety Changeover), the Lo Oil Separator Start Temperature is bypassed and Lo Oil Separator Run Temperature is the active setpoint. The alarm or trip will be active if the oil temperature of the separator drops below the setpoint value.
· Low Oil Injection Temperature – This is the low oil injection safety. The alarm or trip will be active if oil injection temperature drops below setpoint value after a time delay (Oil Injection Temperature Safety Changeover).
· High Oil Injection Temperature – This is the high oil injection temperature safety. The alarm or trip will be active on a rise in oil injection tem­perature above the setpoint value.
24
Compressor Timer Setpoints
To change a timer set­ting, a user with high access level must be logged on.
· Capacity Decrease At Start – At compressor startup, the capacity motor is held at minimum position for this time period. After the timer expires, the slide is free to move in accordance to the system demands.
· Compressor Starter Auxiliary Contact Bypass – This timer is used to bypass the motor amperage input at start. After the timer times out, the program determines if the motor starter has pulled in by testing the amperage channel. If the program determines that the starter did not “pull in”, then the compressor will fail on “Motor Starter Fail” message.
· Volume Slide Adjustment Timer – This timer determines the intervals the volume slide is adjusted. If the volume slide is between 2½% & 7% away from the desired volume ratio, the mo­tor is pulsed once toward the desired volume.
If the volume slide is more than 7% away from the desired value, the volume slide motor is continuously energized until the valve is within 2½% of the desired value. If the actual position is within 2½% of the desired value, no adjust­ment will be made.
· Minimum Compressor Prelube Timer – This is the length of time the oil pump will run after establishing the Prelube Oil Pressure, to prime oil circuit before starting the compressor.
· Oil Pressure Bypass At Compressor Start – This timer bypasses the Low Oil Pressure limits. The timer starts when the compressor starts. After the timer has cycled, the Low Oil Pressure setpoint is active.
· Prelube Oil Pump Time Limit – This timer puts a limit on how long the prelube oil pump is al­lowed to run without establishing the Prelube Oil Pressure.
25
· Filter Differential Pressure Safety Changeover – This timer bypasses the Hi Run Filter Differen­tial Pressure setting during start, to allow the Hi Start Filter Differential Pressure to protect against High Filter Differential during start. Af­ter the timer has cycled, the Hi Run Differential Pressure Safety is active.
· Low Oil Separator Level Bypass Timer – This timer bypasses the low oil level switch for mo­mentary drops in the oil level. If the switch is still open after the Low Oil Separator Level Bypass Timer has timed out, the compressor will be shut down and an alarm will be displayed. This timer is available if the unit is equipped with a low oil separator float switch. The oil level switch is standard on all liquid injection units and optional on all others.
· Auto Restart After Power Failure – This timer forces the microprocessor to wait for the set time period after a power failure before start­ing the compressor unit. By staggering the time settings, the compressors can be allowed to start automatically, one at a time, after a power failure. This prevents excessive loads on the power system that could be caused by all of the equipment coming online at the same time. The Power-Up Auto Start operator option must be selected on the Setup screen for this option to be active.
· Oil Separator Temperature Safety Changeover – This timer allows Low Oil Separator Start Temperature Safety setpoint to protect the compressor against cold oil during starting. After the timer has cycled, the Low Oil Separator Run Temperature is then active.
· Low Oil Injection Temperature Bypass – This timer bypasses the Low Oil Injection Tempera­ture Safety Setpoint during start-up. After the timer cycles, the Low Oil Injection Temperature Safety is set.
· Hot Starts / Hr Counter – This counter counts compressor starts. After every start, a one-hour timer is reset and starts timing. If the timer times out, the hot starts counter is reset. When the counter reaches it’s preset value, it will not allow another compressor start until the one­hour timer times out and resets the counter. In other words, the hot starts counter will be reset when the time between compressor starts total one hour. This counter allows repetitive compressor starts, but once the counter has reached its set point, it requires a one-hour window between compressor starts in order for the counter to be reset. Note: if this option
is chosen an arrow will appear alongside its current value. When active a point will appear.
· True Anti-Recycle Timer – Once the compressor turns off, the timer will keep the compressor off for the setting of True Anti-Recycle Timer. This timer is used to prevent short cycling of the compressor. Note: if this option is chosen an
arrow will appear alongside its current value. When active a point will appear.
· Accumulative Anti-Recycle Timer – This timer also forces a specified time between compres­sor starts. When the compressor starts, the timer resets then starts timing and accumulates running time. Once the compressor shuts down, it will not be allowed to restart for the remainder of the time left on the Accumula­tive Anti-Recycle Timer. Unlike the True Anti­Recycle Timer, if the compressor has run for a time period that exceeds the setpoint of the Accumulative Anti-Recycle Timer, then when the compressor shuts down, it will be allowed to restart immediately. The compressor restart options (Hot Starts or Anti-Recycle Timers) are selected from the Setup screen. One additional Anti-Recycle Timer that can be selected from the Setup screen is the Modified Anti-Recycle Timer. Note: if this option is chosen an arrow
will appear alongside its current value. When active a point will appear.
26
Loading...
+ 60 hidden pages