Emerson Vission Control Manual

Page 1
Vission Control Manual
Page 2
2
Page 3
Important Note
Before applying power to the VISSION MicroController panel, all wiring to the panel should be per NEC. Specifically check for proper voltage and that the neutral is grounded at the source. An equipment ground should also be run to the panel.
*See W iring Instructions and Diagrams before proceeding.
“Before powering the Vission control panel down”, it is a good idea to Backup Control Settings to insure that all previously changed setpoints have been properly saved. See section on saving changes. After back­ing up the setpoints DO NOT power down the V ission panel for at least 1 minute. This will allow adequate time for all setpoints to be properly saved.
Note: The screen shots depicted in this manual represent the screens corresponding to Vission program version # 2.4.41, the current version at time of printing. In our effort to continuously improve the functionality and ease-of-use of the Vission Micro-con­troller, the look of some screens may differ slightly than the representations shown here.
Equipment Indentification Numbers:
Vilter Order Number: __________________________Serial Number: _____________ Vilter Order Number: __________________________Serial Number: _____________ Vilter Order Number: __________________________Serial Number: _____________
3
Page 4
4
Page 5
Table of Contents
Important Note ............................................................................................................3
STANDARD VILTER WARRANTY STATEMENT .............................................6
Operational Flow Chart ............................................................................................. 8
Operational Flow Chart (cont.).................................................................................9
Wiring Instructions ...................................................................................................11
Wiring Instructions For Vission Only .....................................................................1 2
Wiring Diagram For Vission Only..........................................................................2 0
Main Screen...............................................................................................................22
Set Up Screen .............................................................................................................23
Version Screen ...........................................................................................................25
Maintenance Screen .................................................................................................26
Menu Screen ..............................................................................................................28
Common Buttons .......................................................................................................29
Compressor Control .................................................................................................30
Additional Compressor Controls ............................................................................32
Compressor Alarm and Trip....................................................................................35
Compressor Setpoints and Alarms ..........................................................................37
Miscellaneous Screens (Condenser Control) ........................................................41
Compressor Sequencing (Max 5 Compressors) .................................................... 4 3
Vilter Only Screen .....................................................................................................47
Diagnostics Force Output ........................................................................................48
Instrument Calibration .............................................................................................49
Calibration Procedure of Optical Actuators ..........................................................5 1
Installation Instructions For Replacement Of Optical Actuator .........................5 4
Slide Valve Actuator Troubleshooting Guide ......................................................... 5 5
Slide Wiring Diagram for Models Vission VSM-91 To VSS-601 ........................5 9
Slide Wiring Diagram for Models Vission VSS-751 To VSS-1801 .....................6 0
Command Shaft Rotation and Travel.....................................................................61
Calibration For Earlier Style Mechanical Gearmotor/Potentiometers ............. 6 2
Trend Chart ............................................................................................................... 6 4
Data Select Screen....................................................................................................65
Event List ...................................................................................................................66
Trouble Shooting Flowchart (Vission Only) ..........................................................6 8
5
Page 6
Safety Failure Message ............................................................................................70
Supressor Kit Installation ........................................................................................ 7 3
Flash Card Installation Instructions.......................................................................74
Back Light Installation Instructions .......................................................................76
System Setpoints Alarms and Trips Work Sheet .................................................. 8 0
System Control Limit Values Work Sheet ..............................................................8 1
System Timer Values ................................................................................................. 8 2
Spare Parts ................................................................................................................84
Modifications for Analog Board (Vission/Vantage after July 2003) ...................8 5
Danfoss Liquid Injection Valves ..............................................................................87
Who to Contact .........................................................................................................88
6
Page 7
STANDARD VILTER WARRANTY
STATEMENT
Seller warrants the products it manufactures to be free from defects in material and workmanship for a period of eighteen (18) months from the date of shipment from Seller s manufacturing plant or twelve (12) months from date of installation at the initial end users location, whichever occurs first. In addition, Seller provides the following extended warranties: (a) three (3) years from the date of shipment on single screw compressor internal rotating parts, (b) two (2) years from the date of shipment on reciprocating compressors and single screw and reciprocating compressor parts, and (c) two (2) years on all other parts on a single screw compressor unit. Such warranties do not apply to ordinary wear and tear. Seller does not warrant that the product complies with any particular law or regulation not explicitly set forth in the specifications, and Buyer is responsible for ensuring that the product contains all features necessary to safely perform in Buyers and its customers plants and operations. Buyer must notify Seller of any warranty claim within ten (10) days after such claim arises, otherwise Buyer waives all rights to such claim. Products supplied by Seller, which are manufac­tured by others, are not warranted by Seller, but rather Seller merely passes through the manufacturers warranty to Buyer.
SELLER EXPRESSL Y DISCLAIMS ALL OTHER W ARRANTIES, WHETHER EXPRESS OR IMPLIED, INCLUDING THE IMPLIED W ARRANTIES OF MERCHANT ABILITY AND FITNESS FOR A P ARTICULAR PURPOSE.
Unless otherwise agreed in writing, Buyers sole remedy for breach of warranty is, at Sellers option, the repair of the defect, the correction of the service, or the providing a replacement part FOB Sellers office. Seller will not be responsible for costs of dismantling, lost refrigerant, reassembling, or transporting the product. Further, Seller will not be liable for any other direct, indirect, consequential, incidental, or special damages arising out of a breach of warranty. THESE W ARRANTY REMEDIES ARE EXCLUSIVE AND ALL OTHER WARRANTY REMEDIES ARE EXCLUDED. Products or parts for which a warranty claim is made are to be returned transportation prepaid to Sellers factory. Any improper use, corrosion, neglect, accident, operation beyond rated capacity, substitution of parts not approved by Seller, or any alteration or repair by others which, in Sellers judgement, adversely affects the Product, shall void all warranties and warranty obligations. Further, Seller shall not be liable under the above warranties should Buyer be in default of its payment obligations to Seller under this Agreement or any credit agreement.
7
Page 8
Operational Flow Chart
8
Page 9
Operational Flow Chart (cont.)
9
Page 10
10
Page 11
Wiring Instructions
11
Page 12
Wiring Instructions For Vission Only
5-1= Main Power to Panel 5-2= Heater #1 power 5-5= Heater #2 Power
12
Page 13
Wiring Instructions For Vission Only
Mandatory Wiring
Step #2 Motor Starter Contactor Connection The contact to the pull in the motor starter contactor is a dry
contact, place a "HOT" wire from the starter circuit on 7-1. Place the wire to energize the starter contactor on 7-2.
CON 1
CON 2
CON 3
CON 4
CON 5
CON 6
CON 7
Lug
View Inside Of Vission Panel
CON 1
CON 2
CON 3
CON 4
CON 5
CON 6
CON 7
1-1 1-2 Safety 1-3 1-4 1-5 1-6 " 1-7 1-8 1-9 1-10
2-1 2-2 2-3 2-4 2-5 2-6 2-7 2-8 2-9 2-10
3-1 "N" 3-2 3-3 3-4 3-5 "N" 3-6 3-7 3-8 3-9 3-10
4-1 4-2 4-3 4-4 4-5 4-6 4-7 4-8 4-9 4-10
5-1 5-2 5-3 5-4 5-5 5-6 5-7 5-8 5-9 5-10
6-1 6-2 6-3 6-4 6-5 6-6 6-7 6-8 6-9 6-10
7-1 7-2 7-3 7-4 7-5 7-6 7-7 7-8 7-9 7-10
13
Page 14
Wiring Instructions For Vission Only
Mandatory Wiring
Step #3 Motor St a rter Auxila ry C o nt a c t "HOT" to 4-5
Wire to en e r g ize to 1-1
CON 1
CON 2
CON 3
CON 4
CON 5
CON 6
CON 7
View Inside Of Vission Panel
CON 1
CON 2
CON 3
CON 4
CON 5
CON 6
CON 7
1-1 1-2 Safety 1-3 1-4 1-5 1-6 " 1-7 1-8 1-9 1-10
2-1 2-2 2-3 2-4 2-5 2-6 2-7 2-8 2-9 2-10
3-1 "N" 3-2 3-3 3-4 3-5 "N" 3-6 3-7 3-8 3-9 3-10
4-1 4-2 4-3 4-4 4-5 4-6 4-7 4-8 4-9 4-10
5-1 5-2 5-3 5-4 5-5 5-6 5-7 5-8 5-9 5-10
6-1 6-2 6-3 6-4 6-5 6-6 6-7 6-8 6-9 6-10
7-1 7-2 7-3 7-4 7-5 7-6 7-7 7-8 7-9 7-10
14
Page 15
Wiring Instructions For Vission Only
Mandatory Wiring
Step #4 Oil Pump Starter Connection "HOT" to 6-1
Wire to energize on 6-2
CON 1
CON 2
CON 3
CON 4
CON 5
CON 6
CON 7
View Inside Of Vission Panel
CON 1
CON 2
CON 3
CON 4
CON 5
CON 6
CON 7
1-1 1-2 Safety 1-3 1-4 1-5 1-6 " 1-7 1-8 1-9 1-10
2-1 2-2 2-3 2-4 2-5 2-6 2-7 2-8 2-9 2-10
3-1 "N" 3-2 3-3 3-4 3-5 "N" 3-6 3-7 3-8 3-9 3-10
4-1 4-2 4-3 4-4 4-5 4-6 4-7 4-8 4-9 4-10
5-1 5-2 5-3 5-4 5-5 5-6 5-7 5-8 5-9 5-10
6-1 6-2 6-3 6-4 6-5 6-6 6-7 6-8 6-9 6-10
7-1 7-2 7-3 7-4 7-5 7-6 7-7 7-8 7-9 7-10
15
Page 16
Wiring Instructions For Vission Only
Optional Wiring
Step #5 Auxiliary / Safety Wiring
A determination by the user is to be made if this option will be used. If it is
not
used, insure that a jumper is insta l led between L 2-1 and 1-2 If this option is used, remove the jum per 2-1 to 1-2 and place the high level cutout (typically, other cutouts or an E-stop could be used) common wire on 2-1 and the normally closed wire to 1-2.
CON 1
CON 2
CON 3
CON 4
CON 5
CON 6
CON 7
Lug
View Inside Of Vission Panel
CON 1
CON 2
CON 3
CON 4
CON 5
CON 6
CON 7
1-1 1-2 Safet y 1-3 1-4 1-5 1-6 " 1-7 1-8 1-9 1-10
2-1 2-2 2-3 2-4 2-5 2-6 2-7 2-8 2-9 2-10 3-1 "N" 3-2 3-3 3-4 3-5 "N" 3-6 3-7 3-8 3-9 3-10
4-1 4-2 4-3 4-4 4-5 4-6 4-7 4-8 4-9 4-10 5-1 5-2 5-3 5-4 5-5 5-6 5-7 5-8 5-9 5-10
6-1 6-2 6-3 6-4 6-5 6-6 6-7 6-8 6-9 6-10
7-1 7-2 7-3 7-4 7-5 7-6 7-7 7-8 7-9 7-10
16
Page 17
Wiring Instructions For Vission Only
Optional Wiring
Step #6 Remote Start Wiri n g A determination by the user is to be made if this option will
be used. If it is
not
used, insure that a jumper is installed between L 2-1 and 1-5. If this option is used, remove the jum pe r 2-1 to 1-5 and place the dry remote start contact common wire on 2-1 and the normally open wire to 1-5.
CON 1
CON 2
CON 3
CON 4
CON 5
CON 6
CON 7
Lug
View Inside Of Vission Panel
CON 1
CON 2
CON 3
CON 4
CON 5
CON 6
CON 7
1-1 1-2 Safety 1-3 1-4 1-5 1-6 " 1-7 1-8 1-9 1-10
2-1 2-2 2-3 2-4 2-5 2-6 2-7 2-8 2-9 2-10 3-1 "N" 3-2 3-3 3-4 3-5 "N" 3-6 3-7 3-8 3-9 3-10
4-1 4-2 4-3 4-4 4-5 4-6 4-7 4-8 4-9 4-10 5-1 5-2 5-3 5-4 5-5 5-6 5-7 5-8 5-9 5-10
6-1 6-2 6-3 6-4 6-5 6-6 6-7 6-8 6-9 6-10
7-1 7-2 7-3 7-4 7-5 7-6 7-7 7-8 7-9 7-10
17
Page 18
Wiring Instructions For Vission Only
Optional Wiring
Step #7 Setpoint #1/#2 Selection W iring A determination by the user is to be made if this option will
be used. This optional input does not need to be closed for the compressor to run no jumper is required. If this option is to be used, Place the dry contact common wire on L 2-7 and normally open on 1-3
CON 1
CON 2
CON 3
CON 4
CON 5
CON 6
CON 7
Lug
View Inside Of Vission Panel
CON 1
CON 2
CON 3
CON 4
CON 5
CON 6
CON 7
1-1 1-2 Safety 1-3 1-4 1-5 1-6 " 1-7 1-8 1-9 1-10
2-1 2-2 2-3 2-4 2-5 2-6 2-7 2-8 2-9 2-10 3-1 "N" 3-2 3-3 3-4 3-5 "N" 3-6 3-7 3-8 3-9 3-10
4-1 4-2 4-3 4-4 4-5 4-6 4-7 4-8 4-9 4-10 5-1 5-2 5-3 5-4 5-5 5-6 5-7 5-8 5-9 5-10
6-1 6-2 6-3 6-4 6-5 6-6 6-7 6-8 6-9 6-10
7-1 7-2 7-3 7-4 7-5 7-6 7-7 7-8 7-9 7-10
18
Page 19
Note Page
19
Page 20
Wiring Diagram For
Vission Only
20
Page 21
Wiring Diagram For
Vission Only
21
Page 22
The Main Screen
Main Screen
This screen has been designed to give the operator an overall view of all operating parameters affecting the compressor pack­age. This screen should always be displayed
when maintenance items and setpoint items are not being performed. The date on the
screen is updated every ½ second. Status information such as Alarms and Trips are displayed on the screen.
This Screen contains buttons to navigate to setpoint, setup and maintenance screens.
Status information on the compressor, oil pump, oil heater and run mode.
Start/Stop buttons. Hour meter. Motor amperage. Refrigerant. Real time compressor
and package operating conditions. Volume and Capacity Slide locations.
22
Page 23
From the Main screen, touch the Setup but- ton. After entering an authorized user name password, the screen pictured below will ap­pear.
·Operator Name – This is the same list that appears in the login dialog. Names in this list can be selected for deletion. To change a name or password, you delete the name and enter a new name/password pair. The VILTER operator name cannot be deleted. Emergency passwords provided by a Vilter representative for the VILTER name are good only on the date for which they are issued. They are intended to permit navi­gation to this screen for setup or repair of this list.
Set Up Screen
·Language – The user screens can be seen in English, French, and Spanish, depend ing on the option selected. Some text will still display in English even when another language is selected.
·Pressure Units – Select units of measure for pressure readings. Choices are psi, kg cm2 and kPa. This section only, affects pressures displayed on main screen. On all other screens, units are displayed in psi. On the main screen with psi selected, negative gauge pressures will display as inches of mercury vacuum with the unit “Hg. On other screens, negative numbers are scaled as “psi”.
·Temperature Units – Select units of mea sure for temperature. Choices are Fahren heit or Celsius.
·Refrigerant – The choice R717 (Ammonia).
T ouch Here
23
Page 24
Set Up Screen
· Anti-Recycle – The operator can select from
the following AntiRecycle options: True, Ac­cumulative, Modified, or Hot Starts. These select the strategy used to prevent excessive start/stop cycles of the compressor. Timers and counters used to enforce anti-recycling are adjusted and monitored in the Compres­sor Timer Settings screen, reached from the Menu screen. Help for the Timer Settings screen explains how the different settings and strategies operate.
· Compressor Control Via – Operator can
choose the method or mode of compressor control. This determines which measured vari­able is used in making loading (capacity con­trol) decisions. The choice selected here de­termines which setpoints are made available for adjustment on the Compressor Control Setpoints screen.
· Delete Operator – Operator can choose to
delete operator names from the authorized op­erator listing. A name in the list is selected by touching it. The selected name will be deleted from the list when this button is pushed. If you delete all the names (besides VIL TER), be sure you add at least one before leaving this screen.
· Add Operator – The button opens a dialog
for entry of a new name/password pair. Noth­ing (leaving the password text box blank) is a legal password. The password is not ob­scured as it is typed in, so untrusted parties should not be permitted to view the screen during entry. The password is not confirmed with a repeat entry, so verify it visually before pressing okay. Up to 25 name/password pairs can be added. The Operator Name list box will acquire a scroll bar when it fills.
·
Slide Non-Movement – Alarm enable and dis­able buttons permit selecting whether an alarm should be generated when failure of slides to move is detected.
· Setpoint #1 Oil Pump #2 Oil Pump – For
single stage and high stage operation, part time or normal oil pump fuction are used. The oil pump shuts off after discharge pressure has risen sufficiently to drive oil injection. Oil pump operating mode is independently settable for setpoint groups # 1 and # 2.
· Modbus Slave Network Address – When mul-
tiple MicroControllers are connected on a Modbus Network, each controller must have a unique address from the other MicroControllers on the network. Duplicate node addresses are not allowed. The node address of each V ission is determined through the SETUP menu. The MicroController that will initiate all conversation on the network MUST be defined as node 100 (this is defined as the “master” node). All other node num­bers should be in the range of 101 through
174.
This must be set when the extra special port (Com4) is used to control or monitor the com­pressor via Modbus. It also must be set when the multi-compressor sequencing feature is used. Even though Ethernet is used for the comms, this address establishes the compressor’s identity and role in the sequenc­ing logic.
· Reset After Power Fail – When Auto is se-
lected, the compressor will attempt to restart on powering up if it was running in ‘Auto’ when powered down and enabling conditions are met. When ‘Manual’ is selected, the com­pressor powers up into the ‘Stop’ mode and an explicit command to run is required from an operator or comms channel.
· Min Run Capacity – When enabled, the Mini-
mum Run Capacity setting on the Addition Compressor Setpoints screen operates as de­scribed in the help for that screen. When multiple compressor sequencing is used, se­lecting Disable here does not interfere with use of the Min Run Capacity setting in the se­quencing logic.
24
Page 25
Log On, Off,or Save Changes
Set Up Screen
Press Log on/Save Button and the above screen will appear. When altering setpoints, log on is necessary. Select appropriate user name and enter password to change setpoints. This screen is also used to backup and save setpoints by pressing (Backup Settings).
After performing a “Back up Setting” operation, DO NOT power down the Vission/Vantage panel for atleast 1 minute. This will allow adequate time to insure all setpoints have been properly stored.
Version Screen
T o View if a customized program has been installed in your unit, go to the main screen and press VERSION, a screen will appear with the program version and the make model of the unit.
25
Page 26
Maintenance Screen
T ouch Here
From the Main screen touch the Maintenance button.
“Service Item Required” message indicates that the compressor runtime hours has accumulated to a value - or a point- where service Maintenance is required.
>From the main screen, press the “Maintenance” button. A chart will be shown to indicate what service is required
- based on the number of hours the compressor has run.
After the all required service work has been accomplished, press the “Service” button located on the Maintenance screen. A “Services Completed” screen will appear. Press on each service that has been completed. A “check” will appear next to each item that has been pressed. When all required services have been completed, and the appropriate box has been checked in the “Services Completed” screen, then the “Service Item Required” message will disappear on the main screen.
Note: All of the service items listed for that interval must be checked before the “Servicing Item Required” message will disappear.
26
Page 27
Maintenance Screen
This screen shows the chart of routine maintenance to be performed on the machine at hourly intervals from 200 hours to 120,000 hours.
The Service Button from the Maintenance Screen will bring you to this screen. When entering service items that were completed, make sure to check all items that are listed to be done at that
service interval.
27
Page 28
At the bottom of the Main screen touch the Menu button to bring up the screen shown in Figure below .
Use this screen to navigate to the other setpoint screens contained within the program. Each screen has a help button to describe the func-
tion of the screen.
T ouch Here
Menu Screen
28
Page 29
Common Buttons
A. Common Buttons
There are several buttons that are common for all menu screens:
· Return to Menu – This button always returns you to the Menu screen
· Logon To Edit – The user is allowed to view data at all screen levels but cannot edit data until a login has
occurred. In order to logon, press the arrow next to user name, select user then press the abc button, the key pad screen will appear. Enter your password and hit OK.
· Set – T o change a value, the operator must first press the SET button and then the text field of the value they want
to modify. A number pad will pop up for ease in entry.
· Help – This screen will provide more information to the user about the operation of the microprocessor .
29
Page 30
Compressor Control
Level 1 Access – Compr essor Control Setpoints
From the Menu screen , press the Compressor Control setpoints button. The compressor control setpoints screen will be shown.
These screens enable the operator to view and
adjust settings that affect compressor control. From the Setup screen, the operator can choose
the method or mode of compressor control:
Compressor Control V ia Suction Pressure Process T emperature Discharge Pressure
Once the method is chosen, the appropriate setpoints are then displayed on the Compres­sor Control Setpoints screen.
The compressor will decide when to increase or decrease capacity by comparing the con­trolled variable to the setpoints. The maxi­mum on time and minimum off time settings for slide actuator motors can be used to reduce hunting or improve response time. The de-
fault settings of 3 and 20 seconds respectively, pro­vide good operation over a wide range of condi­tions.
Also on this screen, the following buttons are dis­played:
· Event List – Provides a chronological event list-
ing.
· Chart – Provides a line graph showing process
values over a range of time.
· Auto – Places the capacity slides into automatic
mode. In automatic mode, the capacity slide moves according to control setpoint informa­tion.
· Manual – Places the capacity slides into manual
mode. In manual mode, the capacity slide moves based on input from the operator.
30
Page 31
Setpoints on this screen:
Compressor Control
· Suction Pressure On/Off – The compressor
will automatically cycle ON and OFF at the setpoints entered. Suction Pressure On/Off control is only active if the Compressor Con­trol Via Suction Pressure option is selected on the Setup screen. If a compressor shut­down is desired on a suction pressure drop and a manual reset is required, set the OFF value below the Low Suction Pressure Safety Trip value. This will shut down the unit and a reset will be required to restart it.
· Suction Pressure Capacity Increase – The
capacity of the compressor will increase when suction pressure is at or above the Increase ON setpoint, and the increase “off” timer has cycled. Capacity will continue to increase until the Suction Pressure Capacity Increase OFF setpoint is reached. If closer system control is desired, set the ON and OFF setpoints at the same values. This will es­sentially eliminate any differential between the ON and OFF setpoints.
· Suction Pressure Capacity Decrease – The
capacity of the compressor will decrease when suction pressure is at or below the ON setpoint, and the decrease “off” timer has cycled. Capacity will continue to decrease until the Suction Pressure Capacity Decrease OFF setpoint is reached. If closer system control is desired, set the ON and OFF setpoints at the same values. This will es­sentially eliminate any differential between the ON and OFF setpoints. While this set­ting is only available for adjustment on the Control Setpoints screen when the Compres­sor Control Via Suction Pressure option is selected on the Setup screen, it has an over­ride effect when control is via process tem­perature as described below .
· Capacity Control °F On/Off – The compres-
sor will automatically cycle ON and OFF at the setpoints entered. Capacity Control °F On/Off is only active if the Compressor Con­trol via Process Temperature option is se­lected on the Setup screen. If compressor shutdown is desired on a process tempera­ture drop and a manual reset is required, set the OFF value below the Low Control T em-
perature safety trip value. This will shut down the unit and a reset will be required to restart it.
· Capacity Control °F Increase – The capac-
ity of the compressor will increase when pro­cess temperature is at or above the ON setpoint, and the increase “off” timer has cycled. Capacity will continue to increase until the Capacity Control °F Increase OFF setpoint is reached. If closer system control is desired, set the ON and OFF setpoints at the same val­ues. This will essentially eliminate any differ­ential between the ON and OFF setpoints. Process temperature control of the capacity is active only if the Compressor Control V ia Pro­cess Temperature option is selected on the Setup screen.
· Process Temperature Control – Provides for
a Suction Pressure Override feature. If the suction pressure should drop below the Suc­tion Pressure Capacity Decrease OFF setpoint, the Suction Pressure Capacity Decrease OFF setpoint will override the Capacity Control °F Increase and prevent the compressor capac­ity from increasing (loading). If the suction pressure should continue to decrease below the Suction Pressure Capacity Decrease ON setpoint, the compressor capacity will be forced to decrease until the suction pressure is just above the Suction Pressure Capacity Decrease ON setpoint. This will help stabilize the suction pressure, allowing for the process temperature to be gradually pulled down. The Suction Pressure Capacity Decrease ON and OFF setpoints can be viewed or adjusted by temporarily selecting “Processor Control V ia Suction Pressure” on the Setup screen.
· Capacity Control °F Decrease – The capac-
ity of the compressor will decrease when the process temperature is at or below the ON setpoint and the decrease “off” timer has cycled. Capacity will continue to decrease until the Capacity Control °F Decrease OFF setpoint is reached. If closer system control is desired, set the ON and OFF setpoints at the same values. This will essentially elimi­nate any differential between the ON and OFF
31
Page 32
Additional Compressor Controls
· High Discharge Pressure Unloading Setpoints 1&2 – Active in Suction Pressure or
Process T emperature Capacity Control mode. These setpoints limit the compressor from loading at high discharge pressure conditions. They override the Suction Pressure or Process T emperature Capacity Control setpoints. The capacity of the compressor will decrease when the discharge pressure is at or above the ON set point. When the OFF setpoint is reached, the compressor will stop from unloading any further.
· Motor Amp. Load Limit Setpoints 1&2 – This control limit is the motor full load current draw and the maximum current draw. This control
32
limit will only prevent the compressor from loading and does not shut down the compres­sor if the maximum current draw setpoint is exceeded. The actual values entered may depend on particular circumstances. The function of the setpoint is as follows:
If the motor is operating at the full load am­perage (FLA) setting, the compressor is pre­vented from loading. If the motor amps ex­ceed the MAX setpoint, the compressor is forced to unload until the current is at 1.0625 times above the FLA setting. If the motor being used has a service factor below 1.0625, use a value for the FLA that is 10% lower than the MAX value.
Page 33
Compressor Control
· Oil Separator Heater T emperature – This con-
trol limit determines when the oil separator heater is energized. A decrease in oil separator temperature below the ONsetpoint energizes the oil separator heater. On an increase in oil sepa­rator temperature above the OFF setpoint, the oil heater is de-energized.
· Oil Pump Restart – To determine the ON and
OFF values for the pressure ratios, take the ab­solute discharge pressure (PSIA), and divide it by the absolute suction pressure (PSIA). If the pressure ratio is below the ON setpoint value, the oil pump will restart and stay on until the pressure ratio increases above the OFF setpoint. This enables a high stage compressor with a part time oil pump to temporarily operate under con­ditions requiring a full time oil pump.
EXAMPLE: To calculate the OFF value, if the absolute discharge pr essure is 200 PSIA and the desired absolute suction pr essure of the cut­out point is 67 PSIA, the discharge pr essure is divided by the suction pressur e. The result is a OFF value of approximately 3.0. This would then be entered for the OFF pressure. Now determine the ON value, take the absolute dis­charge pressure (200 PSIA) and divide this by the desired absolute suction pr essure (71 PSIA). This results in a ON valve of 2.8.
· Capacity Slide Adjustment Range – This con-
trol limit determines the capacity range the Ca­pacity Slide Adjustment factor will be active. The factor will be active from 0% capacity and will be deactivated when the OFFsetpoint is reached. On a decrease in capacity below the ON set point, the factor will be active.
Capacity setpoint. On a call for unloading, the compressor will unload until it reaches the Mini­mum Run Capacity control setpoint. It will re­main there until the suction pressure reduces and the compressor cycles off on the Suction Pres­sure On/Off control setpoint.
Volume Slide Adjustment Factor – This value is normally zero (0) and will not require changing. However, if the system operating conditions show the volume ratio is not at the optimum value for the system, this value can be adjusted up or down to permit the most efficient positioning of the vol­ume slide valves. T o determine the value to enter , first ensure that the system is in a steady operating state and place the volume side in manual. NOTE: The volume position setting and increase the vol­ume side position slowly until the lowest amper­age level is achieved. If the amperage level rises instead of falls, decrease the volume slide posi­tion until the lowest amperage is achieved. Record the differential from the original position. This will then be adjustment factor to enter for our system. NOTE: Negative numbers can be used for this setting. This setpoint is active on a drop in capac­ity below the Capacity Slide Adjustment Range cut-in (ON) setting. The adjustment is disabled when capacity rises above the Adjustment Range OFF setting. Normally, the “ON-Off” set points should both be set at 100%, so the volume side adjustment factor will be applied over the full range of 0 to 100%
· Economizer Solenoid – This control limit deter-
mines when the economizer solenoid is energized. When the percentage of compressor capacity re­duces below the Economizer Solenoid OFFset point, the solenoid is energized.
· Minimum Run Capacity – The Minimum Run
Capacity is the minimum capacity the compres­sor will be allowed to run at. When the com­pressor is started, it will be loaded to the Mini­mum Run Capacity control setpoint minus 5%. This is done to prevent the capacity control from hunting if the load is not great enough to keep the compressor capacity at the Minimum Run
· Current Transformer Ratio – The value entered
must agree with the Current Transformer Ratio on the current transformer being used. The cur­rent transformer is mounted in the compressor mo­tor conduit box. The ratio is stated as the ratio of measured current to a nominal full scale current in the secondary of 5 amps; only the first of these is entered. For example, if the ratio reads 250/5, enter 250.
33
Page 34
· Low Suction Pressure Load Limit – Active in Dis-
charge Pressure Capacity Control mode only . These setpoints limit the compressor from loading at low suction pressure conditions. They override the dis­charge pressure capacity control setpoints. When the OFF setpoint is reached (at or below setpoint), the compressor will not be allowed to load any fur­ther. If the suction pressure continues to fall, the capacity of the compressor will decrease when the suction pressure is at or below the ON set point. It will stop decreasing when the suction pressure rises to a point that is just below the ON set point.
34
Page 35
Compressor Alarm and Trip
· Low Suction Pressure Setpoints 1&2 – This
is the low suction pressure safety . This safety is active in both temperature and pressure control modes. An alarm or trip will be ac­tive on a drop in suction pressure below the setpoint value.
· High Discharge Pressure Setpoints 1&2
This is the high discharge pressure safety. The alarm or trip will be active on a rise in discharge pressure above the setpoint value.
Low Oil Separator Temperature – This is the lowest allowable oil separator tempera­ture. The compressor will not be allowed to run if the Oil Separator Temperature is be­low the trip setting. After the compressor starts, the alarm or trip will be active if the oil temperature in the separator drops below the setpoint value.
· High Discharge Temperature – This is the
high discharge temperature safety . The alarm or trip will be active if the discharge tempera­ture should rise above the setpoint value.
· Low Oil Separator Start Temperature – This
is the starting low oil separator temperature safety. The compressor is prevented from starting or running if the oil in the separator is below the trip value. After a time delay (Oil Separator Temperature Safety Changeover), this safety is deactivated and the Lo Oil Sepa­rator Run Temperature is the active setpoint.
· Low Oil Separator Run Temperature – This
is the running low oil separator temperature safety. After a time delay (Oil Separator T em­perature Safety Changeover), the Lo Oil Sepa­rator Start Temperature is bypassed and Lo Oil Separator Run Temperature is the active
35
Page 36
Compressor Alarm and Trip
setpoint. The alarm or trip will be active if the oil temperature of the separator drops be­low the setpoint value.
· Low Oil Injection Temperature – This is the
low oil injection safety. The alarm or trip will be active if oil injection temperature drops below setpoint value after a time delay (Oil Injection T emperature Safety Changeover).
· High Oil Injection T emperature – This is the
high oil injection temperature safety. The alarm or trip will be active on a rise in oil in­jection temperature above the setpoint value.
· Low Control Temperature – This is the low
control temperature safety. This safety is ac­tive when process temperature control has been selected in the Setup screen. An alarm or trip will be active on a drop in process tem­perature below the setpoint value.
· High Control T emperature – This is the high
control temperature safety. This safety is ac­tive when the temperature control has been selected in the Setup screen. An alarm will be active on an increase in process tempera­ture above the setpoint value.
36
Page 37
Compressor Setpoints and Alarms
· Prelube Oil Pressure – If the oil pressure does
not rise above the reset setting for a time exceed­ing the Minimum Compressor Prelube Time and the pump runs longer than the Prelube Pump Time Limit, an alarm or trip will occur. These time limits are set on the Compressor Timer Setpoints screen. Prelube oil pressure is defined as the amount that the oil pump drives manifold pres­sure above the discharge pressure.
· Low Oil Pressure – This is the running oil pres-
sure safety. An alarm or trip will be active if the oil pressure should drop below the setpoint value. This occurs once the Oil Pressure Bypass timer has expired. The time limit is set on the Com­pressor Timer Setpoints screen. For the single screw compressor, oil pressure is defined as mani­fold pressure minus suction pressure.
· High Filter Differential Pressure Start – This
safety setpoint is active when the compressor is in the start cycle. An alarm or trip will be active if the filter inlet pressure exceeds the filter out­let pressure by the setpoint value.
· High Filter Differential Pressure Run – This
safety setpoint is active when the compressor is in the run cycle. An alarm or trip will be active if the filter inlet pressure exceeds the filter out­let pressure by the setpoint value.
· High Motor Amps – This safety setpoint is ac-
tive after the Volume Decrease At Start Timer expires. This timer is not user settable, and in standard applications, is 15 seconds. A trip will occur if the motor amperage exceeds the safety setpoint value. The setpoint should be set at 125% of the motor full load amperage.
37
Page 38
Compressor Timer Setpoints
To change a timer setting,
you must “Logon to Edit”
first. Push the “Set”
button then push on the
timer setpoint value you wish to change. After the setpoint is changed, press
the “Refresh” button.
This will refresh the
“Current” window, which
shows the elapsed time of
the timers.
· Capacity Decrease At S tart – At compressor startup,
the capacity motor is held at minimum position for this time period. After the timer expires, the slide is free to move in accordance to the system demands.
· Compressor Starter Auxiliary Contact Bypass – This
timer is used to bypass the motor amperage input at start. After the timer times out, the program deter­mines if the motor starter has pulled in by testing the amperage channel. If the program determines that the starter did not “pull in”, then the compressor will fail on “Motor Starter Fail” message.
38
· Volume Slide Adjustment Timer – This timer de-
termines the intervals the volume slide is adjusted. If the volume slide is between 2½% & 7% away from the desired volume ratio, the motor is pulsed once toward the desired volume. If the volume slide is more than 7% away from the desired value, the volume slide motor is continuously energized until the valve is within 2½% of the desired value. If the actual position is within 2½% of the desired value, no adjustment will be made.
Page 39
Compressor Timer Setpoints
· Minimum Compressor Prelube Timer – This is the
length of time the oil pump will run after establish­ing the Prelube Oil Pressure, to prime oil circuit before starting the compressor.
· Oil Pressure Bypass At Compressor Start – This
timer bypasses the Low Oil Pressure limits. The timer starts when the compressor starts. After the timer has cycled, the Low Oil Pressure setpoint is active.
· Prelube Oil Pump Time Limit – This timer puts a
limit on how long the prelube oil pump is allowed to run without establishing the Prelube Oil Pres­sure.
· Filter Differential Pressure Safety Changeover
This timer bypasses the Hi Run Filter Differential Pressure setting during start, to allow the Hi Start Filter Differential Pressure to protect against High Filter Differential during start. After the timer has cycled, the Hi Run Differential Pressure Safety is active.
· Low Oil Separator Level Bypass Timer – This timer
bypasses the low oil level switch for momentary drops in the oil level. If the switch is still open after the Low Oil Separator Level Bypass Timer has timed out, the compressor will be shut down and an alarm will be displayed. This timer is avail­able if the unit is equipped with a low oil separator float switch. The oil level switch is standard on all liquid injection units and optional on all others.
· Oil Separator T emperature Safety Changeover
– This timer allows Low Oil Separator Start T emperature Safety setpoint to protect the com­pressor against cold oil during starting. After the timer has cycled, the Low Oil Separator Run T emperature is then active.
· Low Oil Injection T emperature Bypass – This
timer bypasses the Low Oil Injection T empera­ture Safety Setpoint during start-up. After the timer cycles, the Low Oil Injection Tempera­ture Safety is set.
· Hot Start s / Hr Counter – This counter counts
compressor starts. After every start, a one-hour timer is reset and starts timing. If the timer times out, the hot starts counter is reset. When the counter reaches it’s preset value, it will not al­low another compressor start until the one-hour timer times out and resets the counter. In other words, the hot starts counter will be reset when the time between compressor starts total one hour. This counter allows repetitive compres­sor starts, but once the counter has reached its set point, it requires a one-hour window between compressor starts in order for the counter to be reset.
· True Anti-Recycle Timer – Once the compres-
sor turns off, the timer will keep the compres­sor off for the setting of True Anti-Recycle Timer. This timer is used to prevent short cy­cling of the compressor.
· Auto Restart After Power Failure – This timer
forces the microprocessor to wait for the set time period after a power failure before starting the com­pressor unit. By staggering the time settings, the compressors can be allowed to start automatically, one at a time, after a power failure. This prevents excessive loads on the power system that could be caused by all of the equipment coming online at the same time. The Power-Up Auto Start operator op­tion must be selected on the Setup screen for this option to be active.
· Accumulative Anti-Recycle Timer – This timer
also forces a specified time between compres­sor starts. When the compressor starts, the timer resets then starts timing and accumulates run­ning time. Once the compressor shuts down, it will not be allowed to restart for the remainder of the time left on the Accumulative Anti-Re­cycle Timer. Unlike the True Anti-Recycle Timer , if the compressor has run for a time pe­riod that exceeds the setpoint of the Accumula­tive Anti-Recycle Timer, then when the com­pressor shuts down, it will be allowed to restart immediately.
39
Page 40
Compressor Timer Setpoints
The compressor restart options (Hot Starts or Anti-Recycle Timers) are selected from the Setup screen. One additional Anti-Recycle Timer that can be selected from the Setup screen is the Modified Anti-Recycle T imer.
· Modified Anti-Recycle Timer – Normally, this
anti-recycle timer will function as a True Anti­Recycle Timer . However , if the operator presses the stop button, or if a failure occurs, the anti­recycle timer switches functions and acts as an accumulative type anti-recycle timer. It will al­low the compressor to restart when the accumu­lated runtime and the present off time meets or exceeds the setting of this timer.
40
Page 41
Miscellaneous Screens (Condenser Control)
This screen is designed for customized functions only, thus maybe placed as a view only screen.
Note: Changing variables on this screen will not have any effect unless you have a customized program for your unit.
To View if a customized program has been installed in your unit, go to the main screen and press VERSION, a screen will appear with the program version and the make model of the unit.
41
Page 42
Miscellaneous Screens (Motor Speed)
This screen is designed for customized functions only, thus maybe placed as a view only screen.
Note: Changing variables on this screen will not have any effect unless you have a customized program for your unit.
To View if a customized program has been installed in your unit, go to the main screen and press VERSION, a screen will appear with the program version and the make model of the unit.
42
Page 43
Compressor Sequencing (Max 5 Compressors)
From the Main Menu (press sequencing), this screen will appear.
Y ou must clear the IP Address before entering a new one.
43
Page 44
Compressor Sequencing (Max 5 Compressors)
Note: Sequencing and Remote/Start-Stop can NOT fuction at the same time- Sequencing will over-ride remote start/stop!
This screen allows the operator to setup a sequenc­ing network. Currently, the MicroController is ca­pable of sequencing 5 compressors. In order for a MicroController to participate on the network, it must have a unique address from the other Controllers on the network. Duplicate node addresses are not al­lowed. The node address of each is done through the Setup menu.
The MicroController which will initiate all conver­sation on the network MUST be defined as node 100. This is defined as the “master” node. All other node numbers should be in the range of 101 through 174.
Ethernet Peer To Peer – In addition to having unique node addresses, all compressors on the Ethernet network must have unique IP addresses and unique names. These are entered from the IP Address/Name screen, accessed from the VILTER ONLY screen. The Ethernet IP ad­dresses of each of the five compressors listed are required to be:
Equipment: Ethernet IP Address
Cmp#1: 10.8.0.73 Cmp#2: 10.8.0.74 Cmp#3: 10.8.0.75 Cmp#4: 10.8.0.76 Cmp#5: 10.8.0.77
Note: IP addresses must be set prior to themicrocontrollers being connected together.
The Compressor Sequencing screen only needs to be setup on the “Master” node. The elements of this screen are:
· Equipment – Allows the operator to select the
size of each compressor. This information is used to make sequencing decisions based on the CFM of the compressor. A valid size MUST be chosen for a compressor to participate in se­quencing. This field also allows the operator to change the name of each of the five compres­sors listed.
44
Page 45
Compressor Sequencing (Max 5 Compressors)
· Node – These node address fields tell the se-
quencing algorithm which the MicroController will be participating in the sequencing net­work. Input the node addresses of each Con­troller, participating on the network, in these fields.
NOTE:
The node addresses for each panel are defined and entered under the Setup screen at each individual panel.
· Central Off/On Buttons – These buttons in-
dicate whether the compressor has been se­lected to operate under Central Control. If the button reads “On”, the compressor will be included in the Central Control System. If the button reads “Off”, the compressor will not be included in the Central Control system. Pushing once on the button will toggle the button between “Off” and “On”.
· Priority – The Priority fields are used to as-
sign the compressor priority for Central Con­trol. The lower the priority number, the greater the priority of the compressor. Priority #1 compressor is the highest priority compres­sor. Compressors with higher priority num­bers will be lag compressors. A compressor with a priority of 1 will be considered the “lead” compressor. The suction pressure of priority #1 compressor is used to control the system pressure.
·
Step – This field sets the amount of capacity change that will occur when a compressor is loading or unloading.
NOTE:
Because of the method used to position the slide valve, and the method used to determine when the slide valve position is “close enough” to the target value, the step value should never be less than 5%.
· Min Cap – The Minimum Capacity is the lowest
capacity , in percentages, that this compressor is allowed to reach during operation. If the system needs to remove additional system capacity, it may shut a compressor off.
·
Max Cap – The Maximum Capacity is the high­est capacity , in percentage, that this compressor is allowed to reach during operation. If the sys­tem needs to increase capacity after this com­pressor has reached its maximum, it may turn on another compressor.
·
Stop Tmr – The Stop Timer (in seconds) is the amount of time the system must hold a compres­sor at minimum capacity before the compressor can be shut off.
PRESSURE SETPOINTS:
The 7 pressure setpoints are used to control the system pressure. W ith the exception of the Start #1 and Start Lag setpoints, all other setpoints must be in decreasing pressures from the previous value.
·
Start #1 – The Start #1 pressure setpoint is the system pressure at which the Priority 1 compres­sor will be started.
·
Start Lag – The Start Lag pressure setpoint will only start the lag compressor, and only after the lead compressor has reached the Max Cap value, and the Machine Start Timer has timed out. The Lead compressor is normally priority , unless it is not available to start due to waiting hot starts, safety trips, etc.
·
Load Rate 2 – If the system pressure exceeds the Load Rate 2 pressure setpoint for the time specified in the Load Rate 2 Timer , Central Con­trol will attempt to increase the capacity of the system.
·
Load Rate 1 – If the system pressure exceeds the Load Rate 1 pressure setpoint for the time specified in the Load Rate 1 Timer , Central Con­trol will attempt to increase the capacity of the system.
45
Page 46
Compressor Sequencing (Max 5 Compressors)
· Unload Rate 1 – If the system pressure falls be-
low the Unload Rate 1 pressure setpoint for the time specified in the Unload Rate 1 Timer , Central Control will attempt to decrease the capacity of the system.
·
Unload Rate 2 – If the system pressure fails be­low the Unload Rate 2 pressure setpoint for the time specified in the Unload Rate 2 Timer , Central Control will attempt to decrease the capacity of the system.
·
Stop – If the system pressure falls below the S top setpoint, Central Control will immediately try to shut down the lowest priority lag compressor. If there is only one compressor running, Central Con­trol will shut down.
·
CAP Load Timers – These timers are directly re­lated to the setpoint values described above. The timers are the minutes and seconds that theCentral Control algorithm will hold before deciding on an action. The CAP Load Rate Timers are related to the appropriate Load 1 and 2 increase setpoints described above.
·
CAP Unload T imers – The Capacity Unload Rate Timers are similar to the timers described above, however, they work to decrease system capacity. The CAP Unload Rate Timers are related to the appropriate Unload Rate 1 and 2 decrease setpoints described previously .
·
Machine Start Time – This timer is the time the system will wait until another compressor is started in an attempt to increase capacity .
·
Force Priority 1 Compressor On Checkbox ­When checked this will override other sequencing logic and priority 1 compressor will always run. Pressing the box alternating checks and unchecks it.
46
Page 47
Vilter Only Screen
WARNING: Settings on these screens should be used only by Vilter represen­tatives or persons acting under their direction. Improper setting may result in loss of vital data and require service NOT covered under warranty.
47
Page 48
Diagnostics Force Output
· On/Off – This will turn the force outputs option On/Off. The force outputs that can be modified are as follows:
Main Motor Starter, Oil Pump, Economizer Solenoid, Remote Alarm/T rip, Liquid Injection Solenoid, Capacity Increase Motor, Capacity Decrease Motor, Volume Increase Motor and Volume Decrease Motor. You can choose the forced output by pressing the down arrow in the control labeled Available Outputs.
48
Page 49
Instrument Calibration
The current values reflect the values presently maintained by the system. The user can perform a one-point calibration by entering an offset value into the respective column. This will automatically adjust the current value and zero out the offset value. Giving max and min values for a respective current value can perform a two-point calibration. The program will automatically adjust the calibration line to meet those values.
The following items can be calibrated at this screen: Discharge Pressure Transducer, Suction Pressure Transducer, Manifold Pressure, 0-10v Input, Oil Filter Inlet Pressure Transducer , Discharge Temperature RTD, Suction Temperature
RTD, Oil Injection T emperature R TD, Oil Separator R TD, Process T emperature R TD and Motor Amperage.
49
Page 50
Instrument Calibration
Instrument calibration menu displays the Input channels that can be calibrated to represent the actual values at the
sampling points.
The current values reflect the values presently maintained by the system. The user can perform a one point calibration by entering an offset value into the respective column. This will automatically adjust the current value and zero out the offset value.
The following items can be calibrated at this screen: three (3) spare RTDs and two (2) 0-10 volt input.
50
Page 51
Calibration Procedure of Optical Actuators
* If you are replacing or reinstalling a new optical actuator see: page 63 first.
ACTUATOR MOTOR CONTROL MODULE CALIBRA TION PROCEDURE
1. Disable the Slide Non-Movement Alarm by going to the “Setup” menu on the Vission/ Vantage and choosing “Alarm Disable” for the Slide Non Movement Option.
2. Open the plastic cover of the capacity motor by
removing the four #10 screws. Caution: there
are wires attached to the connector on the plastic cover. Handling the cover too aggres­sively could break the wires.
3. Gently lift the cover and tilt it toward the Turck connectors. Raise the cover enough to be able to press the blue calibrate button and be able to see the red LED on the top of assembly.
4. Press “Menu” on the main screen and then press the “Slide Calibration” button, to enter the slide calibration screen. If you are re-installing a new optical actuator re-connect the yellow and gray cables.
5. Press INC and DEC to move the slide valve and check for the correct rotation. See Table 1 for Actuator/command shaft rotation specifications.
6. Note: If the increase and decrease buttons do not correspond to increase or decrease shaft rotation, swap the blue and brown wires of the “yellow power cable”. This will reverse the rotation of the actuator/command shaft.
51
Page 52
Calibration Procedure of Optical Actuators
7. Quickly press and release the blue push button on the actuator one time. This places the actuator in calibration mode. The red LED will begin flashing rapidly.
8. Note: When the actuator is in calibration mode, it outputs 0V when the actuator is running and 5V when it is still. Thus, as stated earlier, the actuator voltage will fluctuate during calibration. After the actuator has been calibrated, 0V output will correspond to the minimum position and 5V to the maximum position.
9. Note: The “Slide calibration” screen on the V ission/Vantage has a “Current” window, which displays twice the actuator output voltage. This value, (the % volume and the % capacity) displayed in the “Current Vol” and Current Cap” Windows are meaningless until calibration has been completed.
10. Use the DEC button on the Vission/Vantage panel to drive the slide valve to its minimum “mechanical stop” position. Do not
continue to run the actuator in this direction after the slide valve has reached the stop. Doing so may cause damage to the actuator or the slide valve.
Remove Cover Press Down On Photochoppe r
Press down on the photochopper shaft to disengage the brake, releasing tension from the motor mount. Use the INC button to pulse the actuator to where the slide is just off of the mechanical stop and there is no tension on the motor shaft.
11. Quickly press and release the blue button on the actuator again. The red LED will now flash at a slower rate, indication that the minimum slide valve position (zero position) has been set.
12. Use the INC button on the Vission/ Vantage panel to drive the slide to its maximum “mechanical stop” position.
Do not continue to run the actuator in this direction after the slide valve has reached the stop. Doing so may cause damage to the actuator or the slide valve. Press down on the photochopper
shaft to disengage the brake, releasing tension from the motor mount. Use the DEC button to pulse the actuator to where the slide is just off of its mechani­cal stop and there is no tension on the motor shaft.
13. Quickly press and release the blue button on the actuator one more time. The red LED will stop flashing. The actuator is now calibrated and knows the minimum and maximum positions of the slide valve it controls. Now the capacity or volume channel of the Vission/ Vantage can be calibrated.
Do not touch wires, may cause an
electrical shock!
52
14. Use the Dec button to move the actuator towards its minimum position while watching the millivolt readout on the V ission/Vantage screen. Discontinue pressing the DEC button when the millivolt reading the “Current” window above the “Set Min” button is approxi­mately 500 millivolts.
Page 53
Calibration Procedure of Optical Actuators
15. Now use the DEC and INC buttons to position the slide valve until a value close to 300 millivolts is on the screen. Then, press the “Set Min” button in the capacity or volume slide valve window to tell the controller that this is the minimum millivolt position. Note: The value in the “Current Cap” or “Current Vol” window has no meaning right now.
16. Use the INC button to rotate the actuator towards its maximum position while watching the millivolt readout on the controller screen. Discontinue pressing the INC button when the millivolt reading in the “Current” window is approximately 9200 millivolts (7900 millivolts for the 2783J qualified analog boards applies to only VISSION). You are nearing the mechani­cal stop position.
17. Pulse the INC button to carefully move the slide valve until the millivolt readout “satu­rates”, or stops increasing. This is around 9500 millivolts (8400 millivolts for 2783 qualified
analog boards applies to only VISSION).
Record millivolt maximum reading.
22. Gently lower the plastic cover over the top of the actuator to where it contacts the base and o-ring seal. After making sure the cover is seated properly , gently tighten the four #10 screws. Caution:
The plastic cover will crack if the screws are over tightened.
23. Enable the “Slide Non-Movement Alarm” by going to the “Setup” menu and choosing “Alarm Enable” for the “Slide Non-Movement Option”.
24. This completes the calibration for this channel either capacity or volume. Repeat the same procedure to the other channel.
18. Pulse the DEC button until the millivolts just start to decrease. (This is the point where the channel drops out of saturation). Adjust millivolt value to 300 millivolts below recorded maximum millivolts in step #17.
19. Press the “Set Max” button.
20. Press the “Main” button to complete calibra­tion and exit the “Slide Calibration” screen. The controller will automatically energize the actuator and drive it back to its minimum position (below 5%) for pre-start-up.
21. Note: Now the “Current Cap” or the “Current Vol” value will be displayed in the window on the “Main” screen and the “Slide Calibration” screen.
53
Page 54
Installation Instructions For Replacement Of Optical Actuator
CAUTION: WHEN INSTALLING THE OPTICAL SLIDE MOTOR, LOOSEN LOCKING COLLAR BEFORE SLIDING THE COLLAR DOWN THE SHAFT . DO NOT USE A SCREWDRIVER TO PRY LOCKING COLLAR INTO POSITION.
OVERVIEW
Calibration of an optical slide valve actuator is a two step process that must be down for each actua­tor installed on the compressor. The steps are as fol­lows.
1. The actuator motor control module, located inside the actuator housing, is calibrated so that it knows the minimum and maximum rotational positions of the slide valve it controls. The calibrated act uator will output 0 VDC at the minimum position and 5 VDC at maximum position.
2. After the actuator motor control module has been calibrated for 0-5 Volts, the controll ing channel corresponding to the actuator motor ( either the capacity or volume) has to be calibrated. This instructs the V ission/ V antage control panel to learn the rotational 0% position & rotation 100% position of the slide valve travel.
Please Note:
Because there is an optical sensor on this motor, DO NOT attempt to calibration in direct sunlight.
3. Before appling power to the V ission/Van tage disconnect the gray and yellow cable.
4. Power the V ission/Vantage back on.
5. Refer to Calibration Procedure of Optical Actuators (page 60-62).
54
Page 55
Slide Valve Actuator Troubleshooting Guide
Slide Valve Actuator Theory of Operation
The slide valve actuator is a gear-motor with a posi­tion sensor. The motor is powered in the forward and reverse directions from the main computer in the con­trol panel. The position sensor tells the main com­puter the position of the slide valve. The main com­puter uses the position and process information to de­cide where to move the slide valve next.
The position sensors works by optically counting mo­tor turns. On the shaft of the motor is a small alumi­num “photochopper”. It has a 180 degree fence that passes through the slots of two slotted optocouplers. The optocouplers have an infrared light emitting di­ode (LED) on one side of the slot and a phototransistor on the other. The phototransistor behaves as a light controlled switch. When the photochopper fence is blocking the slot, light from the LED is prevented from reaching the phototransistor and the switch is open. When photochopper fence is not blocking the slot, the switch is closed.
As the motor turns, the photochopper fence alternately blocks and opens the optocoupler slots, generating a sequence that the position sensor microcontroller can use to determine motor position by counting. Because the motor is connected to the slide valve by gears, knowing the motor position means knowing the slide valve position.
manually while the power is off or the motor brake has failed, allowing the motor to free wheel for too long after the position sensor looses power, the actuator will become lost.
A brake failure can sometimes be detected by the posi­tion sensor. If the motor never stops turning after a power loss, the position sensor detects this, knows it will be lost, and goes immediately into calibrate mode when power is restored.
During calibration, the position sensor records the high and low count of motor turns. The operator tells the position sensor when the actuator is at the high or low position with the push button. Refer to the calibration instructions for the detailed calibration procedure.
The position sensor can get “lost” if the motor is moved while the position sensor is not powered. To prevent this, the motor can only be moved electrically while the position sensor is powered. When the position sen­sor loses power, power is cut to the motor . A capacitor stores enough energy to keep the position sensor cir­cuitry alive long enough for the motor to come to a complete stop and then save the motor position to non­volatile EEPROM memory. When power is restored, the saved motor position is read from EEPROM memory and the actuators resumes normal function
This scheme is not foolproof. If the motor is moved
55
Page 56
Slide Valve Actuator Troubleshooting Guide
The actuator cannot be cali­brated
Dirt or debris is blocking one or both optocoupler slots
The photochopper fence extends less than about half way into the optocoupler slots
The white calibrate wire in the grey Turck cable is grounded
Dirt and/or condensation on the po­sition sensor boards are causing it to malfunction
The calibrate button is stuck down
The position sensor has failed
Push button is being held down for more that ¾ second when going through the calibration procedure
Clean the optocoupler slots with a Q-Tip and rubbing alcohol.
Adjust the photochopper so that the fence extends further into the optocoupler slots. Make sure the motor brake operates freely and the photochopper will not contact the optocouplers when the shaft is pressed down.
T ape the end of the white wire in the panel and make sure that it cannot touch metal
Clean the boards with an elec­tronics cleaner or compressed air.
Try to free the stuck button.
Replace the actuator.
Depress the button quickly and then let go. Each ¾ second the button is held down counts as another press.
The actuator goes into calibra­tion mode spontaneously
The actuator goes into calibra­tion mode every time power is restored after a power loss
56
The white calibrate wire in the grey Turck cable is grounding intermit­tently
A very strong source of electromag­netic interference (EMI), such as a contactor, is in the vicinity of the ac­tuator or grey cable
There is an intermittent failure of the position sensor
The motor brake is not working prop­erly (see theory section above.)
T ape the end of the white wire in the panel and make sure that it cannot touch metal.
Increase the distance between the EMI source and the actuator.
Install additional metal shielding material between the EMI source and the actuator or cable.
Replace the actuator.
Get the motor brake to where it operates freely and recalibrate.
Replace the actuator
Page 57
Slide Valve Actuator Troubleshooting Guide
The actuator does not transmit the correct position after a power loss
There is a rapid clicking noise when the motor is operating
The motor operates in one direc­tion only
The motor was manually moved while the position sensor was not powered.
The motor brake is not working properly
The position sensor’s EEPROM memory has failed
The photochopper is misaligned with the slotted optocouplers
The photochopper is positioned too low on the motor shaft.
A motor bearing has failed
There is a loose connection in the screw terminal blocks
There is a loose or dirty connection in the yellow Turck cable
Recalibrate.
Get the motor brake to where it op­erates freely and then recalibrate.
Replace the actuator.
Try to realign or replace the actua­tor.
Adjust the photochopper so that the fence extends further into the optocoupler slots.
Replace the actuator.
Tighten.
Clean and tighten.
The motor will not move in ei­ther direction
The motor runs intermittently, several minutes on, several min­utes off
The position sensor has failed
There is a broken motor lead or winding
The thermal switch has tripped be­cause the motor is overheated
Any of the reasons listed in “The motor operates in one direction only”
The command shaft is jammed
Broken gears in the gearmotor
Motor is overheating and the ther­mal switch is tripping
Replace the actuator.
Replace the actuator.
The motor will resume operation when it cools. This could be caused by a malfunctioning control panel. Consult the factory .
See above.
Free the command shaft.
Replace the actuator.
This could be caused by a malfunc­tioning control panel. Consult the factory.
57
Page 58
Slide Valve Actuator Troubleshooting Guide
The motor runs sporadically
The motor runs but output shaft will not turn
Bad thermal switch
Any of the reasons listed in “The mo­tor will not move in either direction”
Stripped gears inside the gear motor or the armature has come un-pressed from the armature shaft
Replace the actuator.
See above.
Replace the actuator.
58
Page 59
Slide Wiring Diagram for Models Vission VSM-91 To VSS-601
59
Page 60
Slide Wiring Diagram for Models Vission VSS-751 To VSS-1801
60
Page 61
Command Shaft Rotation and Travel
COMMAND SHAFT ROT A TION NO. OF TURNS / ROT A TION ANGLE / SLIDE TRAVEL COMP . CAP ACITY V OLUME CAP ACITY VOLUME MODEL INC DEC INC D EC TURNS/ANGLE/TRAVEL TURNS/ANGLE/TRAVEL
VSR 111 CW CCW CW CCW 0.91 / 328 / 3.568" 0.52 / 187 / 2.045" VSR 151 CW CCW CW CCW 0.91 / 328 / 3.568" 0.52 / 187 / 2.045" VSR 221 CW CCW CW CCW 0.91 / 328 / 3.568" 0.52 / 187 / 2.045" VSR 301 CW CCW CW CCW 0.91 / 328 / 3.568" 0.52 / 187 / 2.045" VSS 451 CW CCW CW CCW 0.91 / 328 / 3.568" 0.52 / 187 / 2.045" VSS 601 CW CCW CW CCW 0.91 / 328 / 3.568" 0.52 / 187 / 2.045" VSS 751 CCW CW CCW CW 1.09 / 392 / 4.283" 0.63 / 227 / 2.473" VSS 901 CCW CW CCW CW 1.09 / 392 / 4.283" 0.63 / 227 / 2.473" VSS 1051 CCW CW CCW CW 1.22 / 439 / 4.777" 0.74 / 266 / 2.889" VSS 1201 CCW CW CCW CW 1.22 / 439 / 4.777" 0.74 / 266 / 2.889" VSS 1501 CCW CW CCW CW 1.36 / 490 / 5.325" 0.82 / 295 / 3.200" VSS 1801 CCW CW CCW CW 1.36 / 490 / 5.325" 0.82 / 295 / 3.200" VSM 71 CW CCW CW CCW 0.80 / 288 / 3.141" 0.45 / 162 / 1.767" VSM 91 CW CCW CW CCW 0.80 / 288 / 3.141" 0.45 / 162 / 1.767" VSM 101 CW CCW CW CCW 0.80 / 288 / 3.141" 0.45 / 162 / 1.767" VSM 151 CW CCW CW CCW 0.80 / 288 / 3.141" 0.45 / 162 / 1.767" VSM 181 CW CCW CW CCW 0.80 / 288 / 3.141" 0.45 / 162 / 1.767" VSM 201 CW CCW CW CCW 0.80 / 288 / 3.141" 0.45 / 162 / 1.767" VSM 301 CW CCW CW CCW 0.80 / 288 / 3.141" 0.45 / 162 / 1.767" VSM 361 CW CCW CW CCW 0.80 / 288 / 3.141" 0.45 / 162 / 1.767" VSM 401 CW CCW CW CCW 0.80 / 288 / 3.141" 0.45 / 162 / 1.767" VSM 501 CCW CW CCW CW 0.91 / 328 / 3.568" 0.52 / 187 / 2.045" VSM 601 CCW CW CCW CW 0.91 / 328 / 3.568" 0.52 / 187 / 2.045" VSM 701 CCW CW CCW CW 0.91 / 328 / 3.568" 0.52 / 187 / 2.045"
Note:These refer to the old stlye gear mototrs and DO NOT apply to the optical motors.
NOTES:
a) The large gear on the command shaft has 50 teeth. The teeth are counted when moving the command shaft from the minimum stop position to
the maximum stop position.
b) The manual operating shaft on the gear motor should be turned the opposite direction of the desired command shaft rotation. c) The capacity and volume control motors are equipped with a brake, if it is necessary to operate the control motors manually, the brake must be
disengaged. The brake can be disengaged by pushing on the motor shaft on the cone end. The shaft should be centered in its travel. Do not use excessive force manually operating the motor or damage may result.
T able 1
61
Page 62
Calibration For Earlier Style Mechanical Gearmotor/Potentiometers
· Capacity Slide V alve Potentiometer Calibra­tion – Move the capacity slides to their mini-
mum position. This can be accomplished by either electrically actuating the slide valve motor through the Force Outputs On or by manually actuating the slide valve motor. T o manually actuate the motor, release the brake and turn the hex nut on the gear motor in the proper direction to move the capacity slides to their minimum position (see Table 1).
IMPORTANT
After the slide valves have contacted the inter­nal stop, release the tension in the mechanism by actuating the brake and then manually turn the command shaft back one tooth on the com­mand shaft gear . Failure to do so may result in premature failure of the gear motor.
Remove one of the ¼” socket head cap screws from the potentiometer bracket, loosen the other and turn the potentiometer shaft until a millivolt reading of between 900 and 1100 is displayed in the Current window above the Set Min button. Mesh the potenti­ometer gear with the command shaft gear and replace the ¼” socket head cap screw. The millivolt reading must remain between 900 and 1100 millivolts. Without changing the gear mesh, remove one ¼” screw, and apply Loctite #242 to the threads. Reinstall the screw finger tight, then repeat the procedure on the remaining screw (do not change the orientation of the lockwashers on the screws). The gear lash must be adjusted so there is no side load on the potentiometer shaft. Tighten and torque the ¼” socket head cap screw to 16 ft/lbs. Recheck the millivolt reading. It must be between 900 and 1100 millivolts. If not, the gear mesh will have to be readjusted.
At this point, press the Set Min button in the Capacity Slide V alve Potentiometer win­dow. Realize that the Current Cap window
will show a value, but it has no meaning at this point. Now turn the command shaft to the fully loaded position. With the slide valve against the mechanical stop, release the tension in the mechanism by actuating the brake and manually turn the command shaft back one tooth on the command shaft gear. This is the maximum millivolt posi­tion. Now press the Set Max button. Cali­bration of the slide is completed AFTER pressing the Main button, to exit the Slide Calibration Screen. Now if you re-enter the Slide Calibration Screen, the correct value will be displayed in the Current Cap win­dow and on the Main screen.
· Volume Slide Potentiometer Calibration –
Move the volume slides to their minimum position. This can be accomplished by ei­ther electrically actuating the slide valve motor through the Slide Calibration Screen INC and DEC buttons, or by manually actu­ating the slide valve motor. To manually actuate the motor, release the brake and turn the hex nut on the gear motor in the proper direction to move the volume slides to their minimum position (see Table 1).
IMPORTANT
After the slide valves have contacted the inter­nal stop, release the tension in the mechanism by actuating the brake and then manually turn the command shaft back one tooth on the com­mand shaft gear . Failure to do so may result in premature failure of the gear motor.
Remove one of the ¼” socket head cap screws from the potentiometer bracket and loosen the other. Turn the potentiometer shaft until a millivolt reading of between 900 and 1100 is displayed. Mesh the potentiom­eter gear with the command shaft gear and replace the ¼” socket head cap screw. The millivolt reading must remain between 900
62
Page 63
Calibration For Earlier Style Mechanical Gearmotor/Potentiometers
and 1100 millivolts. W ithout changing the gear mesh, remove one ¼” screw, and apply Loctite #242 to the threads. Reinstall the screw finger tight, then repeat the procedure on the remain­ing screw (do not change the orientation of the lockwashers on the screws). The gear lash must be adjusted so there is no side load on the po­tentiometer shaft. Tighten and torque the ¼” socket head cap screw to 16 ft/lbs. Recheck the millivolt reading. It must be between 900 and 1100 millivolts. If not, the gear mesh will have to be readjusted.
At this point, press the Set Min button in the Volume Slide Valve Potentiometer window. Realize that the Current Vol window will show a value, but it has no meaning at this point. Now turn the command shaft to the fully loaded position. W ith the slide valve against the mechanical stop, release the tensions in the mechanism by actuating the brake and manually turn the command shaft back one tooth on the command shaft gear. This is the maximum millivolt position. Now press the Set Max button. Calibration of the slide is completed AFTER pressing the Main button, to exit the Slide Calibration Screen. Now if you re-enter the Slide Calibration Screen, the correct value will be displayed in the Current Vol window and on the Main screen.
Upgrading from Old Style Gear Motors to Optical Actuators.
Refer to the installation instructions that are supplied with the new Optical Actuators. (VPN 25972A)
63
Page 64
Trend Chart
The trend analysis screen shows recorded data for a logging range of either 60 minutes or 120 hours. Additionally, selections can be made to display segments of the logged data.
T o view which selections are being shown hit the data select button.
Note: When the panel is powered down, and powered back up, the “Trend Screen” will default to 120 hours even if you have chosen 60 minutes. Trend data is not retained.
64
Page 65
Data Select Screen
The user has the ability to select which value they would like to see displayed on the graph. Only four selections can be chosen at once to view, even though all data is being accumulated.
65
Page 66
Event List
T ouch Here
From the Menu screen, touch the Event List button. The screen on the next page will appear .
66
Page 67
Event List
The Event List will give a chronological record of the last 40 events recorded by the controller. These events can be filtered by selecting the Filter box on the upper left of the screen.
67
Page 68
Trouble Shooting Flowchart (Vission Only)
Check to make sure 120V AC is run to “L1” on the Relay board. This is the board on the inside left back of the panel. “L1” is the fifth connector down from the top and the top terminal. The neutral should be brought to any “N” on the relay board.
MicroController does not boot up, no lights on any boards.
MicroController appears to be booted, lights seen on boards and E­stop switch, but no touch screen is evident.
MicroController boots up but all data temperatures and pressures are zeroed and do not update.
Check F1 fuse on relay board.
Check F1 fuse on the power supply, located on the front of the door. If all of the above is okay , the power supply may be bad. Check DC voltages on the single board computer interface board, which is the big green board above the power supply. Along the right edge of this board, just above the power sup­ply connector J14, are test points. If proper voltages are not located at these test points, the power supply may be faulty.
Check cable connections located on the LCD Inverter board. This board is located inside the door on the LCD touch screen back plane above the single board computer. The connector with the pink and white wires, located on the left center of the board is the power supply to the board. The connector on the top right of the board with the black wires has the data wires. If these are inserted correctly, the problem could be bad solder joint on the LCD Inverter board or a component failure.
Check Analog board jumpers J41 & J46. They should be on pins 1 & 2 (center and right pins).
Check the upper DIP switch on the analog board. This identi fies the node address of the Analog board. Only switch #1 should be on, the rest off.
The MicroController has (2) boards running separate programs. The Analog board located inside the panel on the back right calculates pressures, temperatures, amps and monitors inputs. The single board computer requests this data for action and display. The single board computer will instruct the Analog board to activate outputs or relays as needed. Communica tion between the boards is RS-485 running at 115200 baud. The cable is basically phone cable with phone jack style con nectors. The connector to the single board computer is on the touch screen back panel and is labeled RS-485 Com2 to Ana log Bd. The connector on the Analog board is located on the bottom of the board. There are 2 connectors on the analog board, either one can be used.
68
If this cable is open or disconnected, there will be no commu­nications between the boards. The top two green lights on the Analog board (D10 & D11), located on the bottom left of the board, will be off. The pressures and temperatures will not update. Ensure the cable is plugged in correctly. T ry rebooting again. If the problem persists, try moving the cable on the Analog board to the other connector. If not successful, try a different cable on the Analog board to the other connector on the board. If not successful, try a different cable. Any phone style cord should work. If neither of these help, contact the Vilter Home Office.
Page 69
Trouble Shooting Flowchart (Vission Only)
A bank of pressure or temperature channels no longer function.
There are four fuses on the Analog board that limit the current on the 24VDC to the Analog channels. The fuses are 500 milliamp, located near the power supply connec­tors and brown in color. LEDs next to the fuses give a visual indication of the status of the fuse, however, it is best to pull the fuse and check them with an ohmmeter. If any are blown, find the shorted device that is responsible for the blown fuse and replace.
F1 protects the +24VDC supply to the pressure transduc­ers and relays.
F2 protects the –12VDC supply which is subregulated to 5VDC required for multiplexers, analog to digital converts and temperature channels.
F3 protects the +12VDC supply, which is subregulated to +5VDC, required for multiplexers, analog to digital con­verters, and temperature channel.
F4 protects the main +5VDC supply required for most of the components on the analog board.
A pressure channel reads a negative number over -140
A temperature channel reads a large negative value over -400°
Screen Cursor will not retain cali­bration.
If F1 blows, the pressure transducers will produce errone­ous readings and the relays on the relay board will drop out (de-energize). If F2, F3 or F4 blows, all analog readings will be affected.
This indicates the transducer wiring or transducer is either open or shorted. Check wiring to print. Check fuses F1, F2, F3 and F4 on analog board.
This indicates the RTD wiring or RTD is open. Check wiring to print.Check fuses F1, F2, F3 & F4 on analog board.
Calibrate the screen cursor, TWICE, per the instructions provided in the manual.
Go to “IP Address” screen and clear IP Address. Re-enter the same IP address
Go to Change Date/Time and clear both. Re-enter appropriate date and time.
Save changes and backup settings. Power off the panel. Power on the panel.
Verify the screen cursor follows the fingertip correctly.
69
Page 70
Safety Failure Message
Suction Pressure SP#1 Fail - This message will appear when the suction pressure falls below the
safety setting of the Lo Suction Pressure Trip Setpoint No.1. In addition, this message will appear when the suction pressure reading rises above 300 PSI, indicating an open transducer or bad analog channel.
Suction Pressure SP#2 Fail - This message will appear when the suction pressure falls below the
safety setting of the Lo Suction Pressure Trip Setpoint No.2. In addition, this message will appear when the suction pressure reading rises above 300 PSI, indicating an open transducer.
Discharge Pressure SP#1 Fail – This message will appear when the discharge pressure exceeds the
safety setting of the Hi Dsch Press Trip Setpoint No. 1 . In addition, this message will appear when the discharge pressure reading falls below 30” Hg, indicating a shorted transducer.
Discharge Pressure SP#2 Fail – This message will appear when the discharge pressure exceeds the
safety setting of the Hi Dsch Press Trip Setpoint No. 2 . In addition, this message will appear when the discharge pressure reading falls below 30” Hg, indicating a shorted transducer
Suction T emp Fail – This message will appear when the suction temperature falls below the
safety setting of the Low Suction Temperature Trip setpoint. In addition, this message will appear when the suction temperature rises above 400 degrees, indicating an open RTD.
Discharge Temp Fail – This message will appear when the discharge temperature rises above
the safety setting of the High Discharge Temperature Trip setpoint. In addition, this message will appear when the discharge temperature falls below -30 degrees, indicating a shorted RTD.
Oil Separator Start T emp Fail – This message will appear when the Oil Separator Temp is below the
Low Oil Separator Start Temp Trip setpoint. In addition this message will appear after the Oil Separator Temp Safety Changeover timer times out and the Oil Separator temperature fails to rise above the Low Oil Separator Start Temp Reset after the compressor is started.
Oil Separator Run Temp Fail – This message will appear when the Oil Separator Temp is below the
Low Oil Separator Run Temp Reset setpoint after the Oil Separator T emp Safety Changeover timer times out.
Percent Capacity Fail – This message will appear if the percent capacity reading exceeds 300%
or goes below –15%.
70
Page 71
Safety Failure Message
Percent Volume Fail – This message will appear if the percent volume reading exceeds 300% or
goes below –15%.
Lo Control T emperature Fail – This message will appear when the Process Control Temperature falls
below the safety setting of the Lo Control Temperature Trip Setpoint. In addition, this message will appear when the Process Control Temperature rises above 300 degrees F, indicating an open RTD.
Lo Start Oil Pressure Fail – This message will appear with the Prelub Oil Pressure (Manifold minus
Discharge) has remained below the Prelub Oil Pressure Reset setpoint. The Prelub Oil Pressure must be above the Prelub Oil Pressure for a time period of the Minimum Compressor Prelub time. It will continue to try to do this for a time period of the Prelub Oil Pump Time Limit. When the Prelub Oil Pressure fails to achieve this, then the failure message will occur.
Lo Oil Pressure Fail – This message will appear when the Running Oil Pressure (Manifold minus
Suction) has remained below the low Oil Pressure Reset setpoint when the Oil Pressure Bypass at Compressor Start timer times out. This message will also appear when the Runnning Oil Pressure falls below the Low Oil Pressure trip setpoint after the Oil Pressure Bypass at Compressor Start timer times out.
Lo Oil Injection Temp Fail – This message will appear when the Oil Injection temperature falls below
the Low Oil Injection Temperature trip setpoint. This message will also appear when the Oil Injection temperature fails to rise above the Low Oil Injection Temperature reset setpoint after the Low Oil Injection Temp Bypass timer times out.
Hi Oil Injection Temp Fail – This message will appear when the Oil Injection temperature rises above
the High Oil Injection Temperature trip setpoint.
Manifold Pressure Fail – This message will appear with the manifold pressure rises above 300 PSI
or falls below 30” Hg.
Filter Inlet Pressure Fail – This message will appear with the manifold pressure rises above 300 PSI
or falls below 30” Hg.
Start Filter Diff Press Fail – This message will appear if the Filter Differential pressure rises above the
High Fltr Diff Press – Start setpoint before the Filter Differential Pressure Safety Changeover timer times out.
71
Page 72
Safety Failure Message
Run Filter Diff Press Fail – This message will appear if the Filter Differential pressure rises above the
High Fltr Diff Press – Run setpoint after the Filter Differential Pressure Safety Changeover timer times out.
Maximum Amperage Fail – This message will appear if the motor amperage rises above the Hi Motor
Amps trip setpoint.
Motor Starter Aux Contact Fail – This message will appear if the Motor Auxiliary contact fails to close
before the Compressor Starter Auxiliary Contact Bypass timer times out. Refer to wiring diagram.
Auxiliary Safety#1 Input Fail – This message will appear when power is removed from the input module
that is designated as “Auxiliary #1 Safety” (please refer to your wiring diagram).
Lo Oil Separator Level Fail – This message may appear when power is removed from the input module
that is designated as “Lo Separator Oil Level Trip” (please refer to your wiring diagram). This safety has an associated delay. The associated delay timer is the Lo Oil Separator Level Bypass Timer. This safety will activate only after the oil level has been low after the timer times out.
72
Page 73
Supressor Kit Installation
73
Page 74
Flash Card Installation Instructions
Note: Bef ore Powering Down To Repl ace F lash ca rd, You Must
Copy Down All Setpoints As These Will Need To Be Re-entered When New Flashcard Is Installed.
Hit The Emergency Stop Botton Located In Front Of the Panel
Verify Unit is Shut Down Completely
VANTAGE/V ISSION
EMERGENCY STOP BUTTON
Discon n e ct t he Connec t o r An d Ribbon A s Shown
Verify Lockout Disconnect On Compressor Start. This Ensures Compressor Does Not Start.
Proceed As Follows
View Inside Of Door
Remove (4) S cre ws, One In Each Corner Of Board
74
Flip Board Over To View Flash Card
Page 75
Flash Card Installation Instructions
Remove Flashcard And Replace
Press Latch To Release Flashcard
Flip Board Back Into Posti on Secure Board To Mounts
With Previously Removed Screws
Reconnect Connectors and Ribbons
Note: You Must Re-enterSetpoints And Reca librate SlideVa lves.
See Section On Setpoint Values And the S ection On Optical Actuators.
75
Page 76
Back Light Installation Instructions
Remove (Four) Nut s Remove Board
Flip Board Over
Unplug Connector Dis c on ne ct Ri bb on
Remove (Fo ur) Screws And Turn Board Over
76
Page 77
Back Light Installation Instructions
Remove Small Screw And Slide Back Light Out As Shown
Sli d e Ne w Back Li gh t In And Secu re W i t h P r evi ou s l y Removed S crew
77
Page 78
Back Light Installation Instructions
r
d
n
t
n
d
Connect Ribbon An d Plug Connecto r B a ck In
Place Boa
Back I
o Postion A
Secure
Place Board Back Onto Back Of Panel And Secure W it h Pr eviously Removed Nuts
78
Page 79
Transducer Wiring
79
Page 80
System Setpoints Alarms and Trips Work Sheet
SAFETY SYSTEM VALUES VALUE LIMITS DEFAULT VALUES SETPOINTS ALARM TRIP RESET ALARM TRIP RESET ALARM TRIP RESET
LO SUCTION TEMP -99/300 -99/300 -99/300 -45 -50 -40
HI DISCHARGE TEMP -30/260 -30/260 -30/260 205 210 200
LO OIL SEP START TEMP 50/200 50/200 50/200 75 70 80
LO OIL SEP RUN TEMP 50/200 50/200 50/200 105 100 110
LO OIL INJECT TEMP 50/160 50/160 50/160 95 90 100
HI OIL INJECT TEMP -99/160 -99/160 -99/160 140 145 135
LO CONTROL TEMP (3) (2) -99/210 -99/210 -99/210 -50 -55 -45
HI CONTROL TEMP (3) (2) -99/210 - - - - - - 100 - - - - - -
LO SUCT PRESS SETPOINT #1 30”/300 30”/300 30”/300 3” 4” 3” SETPOINT #2 30”/300 30”/300 30”/300 1” 2” 1”
HI DISCHARGE PRESS SETPOINT #1 30”/350 30”/350 30”/350 210 220 205 SETPOINT #2 30”/350 30”/350 30”/350 220 230 215
PRELUB OIL PRESSURE - - - 4/300 4/300 - - - 4 5
LO OIL PRESSURE (2) 18/300 18/300 18/300 38 35 40
HI START FLTR DIFF PR 30”/50 30”/50 30”/50 50 50 25
HI OIL RUN FILTER DIFF PR(1) 30”/40 30”/40 30”/40 12 15 10
HI AMPS LIMIT (4)(5) 0/1000 0/1000 0/1000 15 15 - - -
NOTES:
(1) If your unit is equipped with new style filters (Vilter Part #3109B or 3110B), the Alarm should be set at 37 psig, T rip at 4 0 psig and Reset
at 35 psig. (2) For boosters, set Alarm at 28 psig, Trip at 25 psig, Reset at 30 psig. (3) Set Alarm at 60% and Trip at 70% of full load motor nameplate amps. Only if Process Temp Control (4) Set Alarm at 120% and Trip at 125% of full load motor nameplate amps.
80
Page 81
System Control Limit Values Work Sheet
SYSTEM CONTROL LIMIT VALUES WORKSHEET
CONTROL SYSTEM VALUES VALUE LIMITS DEF AUL T VALUES LIMITS CUT IN CUT OUT CUT IN CUTOUT CUT IN CUT OUT
SUCTION PRESSURE ON/OFF (1) SETPOINT #1 30”/150 30”/150 10 6 SETPOINT #2 30”/150 30”/150 15 11 SUCT PR CAP INCREASE (1) SETPOINT #1 30”/150 30”/150 20 25 SETPOINT #2 30”/150 30”/150 20 25 SUCT PR CAP DECREASE (1) SETPOINT #1 30”/150 30”/150 18 23 SETPOINT #2 30”/150 30”/150 18 23 HIGH DSCH PRESS UNLD (1) SETPOINT #1 0/300 0/300 200 190 SETPOINT #2 0/300 0/300 210 200 LIQ INJECTION SOLENOID CONTROL ON OFF ON OFF TEMP VIA: OIL INJECTION TEMPERATURE 200°F 50°F 120°F 105°F OIL SEPARATOR TEMPERATURE 200°F 50°F 120°F 105°F OILPMP RESTART (D/S) 1.0/8.0 1.0/8.0 2.8 3.0 OIL S EPARA T OR H EATER 80/130 80/130 95 105 CAP CTRL °F ON/OFF (2) SETPOINT #1 -99/200 -99/200 20 10 SETPOINT #2 -99/200 -99/200 25 15 CAP CTRL °F INCR (2) SETPOINT #1 -99/300 -99/300 28 27 SETPOINT #2 -99/300 -99/300 33 32 CAP CTRL °F DECR (2) SETPOINT #1 -99/200 -99/200 24 25 SETPOINT #2 -99/200 -99/200 29 30 LAG, CAPACITY STEP (3) 0/100 - - - 10 - - ­VOL SLIDE ADJ FACTOR -100/100 - - - 0% - - ­MINIMUM RUN CAPACITY 10% / 90% - - - 30 - - ­LEAD, MAXIMUM CAP FLAG (3) 50/100 50/100 95 90 ECONOMIZER SOLENOID 0% / 100% 0% / 100% 80% 75%‘ VOL ADJ CAP RANGE 0/100 - - - 100% 100% LOW SUCTION PRESS LOAD LIMIT SETPOINT #1 SETPOINT #2 LOW SUCTION PRESSURE LOAD LIMIT ON OFF ON O FF SETPOINT #1 30 35 SETPOINT #2 40 45 MOTOR AMPS LOAD LIMIT (4) SETPOINT #1 0/999 0/999 5 10 SETPOINT #2 0/999 0/999 5 10
CURRENT TRANSFORMER (1) 100-1000/AMPS 100/5 AMPS
C/T RATIO C/T RATIO C/T RATIO
NOTES: (1) Must be field set. (2) Set only if temperature is used for capacity control. (3) Set only if Lead/Lag option is selected. (4) Set FLA at nameplate amps, MAX at nameplate + service factor.
81
Page 82
System Timer Values
The values or options in the screen displays shown must be entered before start-up.
SYSTEM CONTROL LIMIT VALUES WORKSHEET
TIMER V ALUES SYSTEM V ALUES V ALUE LIMITS DEFAULT V ALUES
A T ST ART CAPACITY DECREASE 0/999 SEC 15 SEC
CAP ACITY INCREASE MOTOR ON 0/255 SEC 2 SEC
CAP ACITY DECREASE MOT OR ON 0/255 SEC 2 SEC
CMP STARTER AUX CONTACT BYPASS 0/255 SEC 10 SEC
CAP INCREASE MOTOR OFF 0/255 SEC 20 SEC
CAP DECREASE MOTOR OFF 0/255 SEC 10 SEC
VOL SLIDE ADJ TIMER 0/255 SEC 20 SEC
MINIMUM CAP PRELUB TIME 0/255 SEC 5 SEC
RUN CYCLE OIL PRESS BYPASS 0/90 SEC 60 SEC
PRELUB PUMP TIME LIMIT 0/255 SEC 255 SEC
FL TR DIFF PR SAFETY CHANGEOVER 0/999 SEC 60 SEC
LO OIL SEP LEVEL BYPASS TIMER 0/120 SEC 60 SEC
AUTO REST AR T AFTER POWER FAIL 1/240 MIN 5 MIN
OIL SEP TEMP SAFETY CHANGEOVER 0/15 MIN 5 MIN
LO OIL INJ TEMP SFTY CHANGEOVER 0/15 MIN 6 MIN
ANTIRECYCLE STRT TIMER (MIN) (1) 0/30 MIN 20 MIN
FORCE START LAG COMP (MIN) (2) 0/60 MIN 30 MIN
HOT STRTS/HR COUNTER (COUNTS) (1) 1/10 COUNTS 3 COUNTS
NOTES: (1) Must be field set. (2) Set only if Lead/Lag option is selected.
82
Page 83
DOOR LAYOUT
VISSION
micro-controller
STOP
EMERGENCY
SUBPANEL LAYOUT
SEE DETAIL-A
SEE DETAIL-B
DETAIL-B
STANDARD JUMPER SETTINGS
TRANSDUCER JUMPER CONFIGURATION
4-20 mA
EXTERNAL
DETAIL-A
RTD JUMPER CONFIGURATION
STANDARD JUMPER SETTINGS
4-20 mA
INTERNAL
RTD
83
Page 84
Spare Parts
PART DESCRIPTION VILTER PART NUMBER QTY.
Analog Board (VISSION PANEL) 3011A 1 Analog & Relay Board (VANTAGE PANEL) 3011C1 1 Control Relay, 4PDT 3011B1 1 Control Relay, DPDT 3011A1 1 Control Relay, SPDT 3011Z 1 Input Module 2895M (120v) 1 Output Module 2895N (120v) 1 Output Module Fuse 2895P 1 Panel Fuse, ½ Amp 3011V 1 Panel Fuse, 10 Amp 3011W 1 Panel Fuse, 4 Amp 2895P 1 Power Supply 3011K 1 Relay Board (VISSION) 3011B 1 Pressure Transducer 2783J 1 Resistance Temperature Detector 2611G 1 Fuse Kit (VISSION PANEL) 3011F 1 Fuse Kit (VANTAGE PANEL) 3011F1 1 VISSION SBC Sub-Assembly 3011ML 1 Modbus Cable 3011X 1 VISSION Cable Kit 3011Y 1 RTD/Transducer Cable 3122B 1 Cable Kit (VANTAGE PANEL) 3011Y1 1 Modbus Cable Kit (VANTAGE PANEL) 3011X1 1 CORD SET RK4T-4/ 5618Turk 3122B 1 64m Flashcard 3011FC-1 1 Lighted Emergancy Switch 3011H 1 Snubbers 3030C 1 Supressor Kit KT785 1
*Supplied with 120VAC. input& output modules.
84
Page 85
Modifications for Analog Board (Vission/Vantage after July 2003)
Using Danfoss T ransducers with 2783J qualified boards
The analog boards used in the Vission and Vantage panels after July 2003 have been modified to ac­commodate the use of Danfoss transducers (VPN 2783J). These analog boards are denoted as “2783J qualified” boards. The use of 2783J qualified boards with Danfoss transducers require that scaling fac­tors for the Danfoss pressure transducers be checked and modified if necessary.
The scale factors for all transducers are located at a specific Index location in V ission/V antage database. Refer to Figure 1. This table shows the proper scale factors for each type of transducer as well as the Index location of the scaling factor for each trans­ducer.
Vission and Vantage (VSS and SOI units) Vission (VRS units)
Transducer Index Value* Transducer Index Value*
Suction N658 3950 Suction N658 3950 Discharge N659 3950 Discharge N659 3950 Man/Filter Out N660 3950 Manifold N660 3950 Filter In N661 3950 Filter Inlet N661 3950
Filter Outlet (Retrofit) N664 3950
Vission and Vantage (Cool Compression units) Vantage (Recip)
Transducer Index Value* Transducer Index Value*
Suction N658 3950 Suction N658 3950 Discharge N659 3950 Discharge#1 N659 3950 Man/Filter Out N660 3950 Filter Out N660 3950
Filter Inlet N661 3950 Discharge#2 N662 3950 Oil Manifold N663 3950
Crankcase N664 3950
Figure 1. Transducer Index Table and Scale Factors
N660 3950
Value* : The value 3950 shown is the Scale Factor for transducers manufactured by Ametek and Setra. This does NOT include Danfoss transducers. If Danfoss transducers are being used with
2783J qualified boards, the “Value” at the Indexes shown above needs to be modified to 4297.
The procedure on the next page describes how to modify the scaling factor.
85
Page 86
Modifications for Analog Board (Vission/Vantage after July 2003)
The procedure to Change Scale Factors on 2783J Qualified Board
1. From the Main Screen, press the Menu button.
2. From the Menu Screen, press the V ilter ONLY screen.
3. Logon
4. From the Vilter ONLY screen, press the Raw Data Screen button. You will now see a screen labeled “Data T est”, containing 4 columns, 2 labeled “Index” and 2 labeled “Value”.
5. Press the “Set” button and then press one of the blank boxes under either one of the Index col­umns.
6. A keypad will be displayed. Now type in “N658” (without the quote marks). Press the OK button. (Per the table, this is the Index for the Suction Pressure transducer.)
7. Y ou are now returned to the “Data T est” screen. Y ou will see “N658” in the box that you touched, and you will see the value 3950 in the corre­sponding “Value” box. This is the scale factor that will be changed.
8. Now press the “Set” button again, and press the “Value” box that contains the value 3950. A numeric keypad will now be visible.
9. Press the Clear button. Now press the buttons 4297, followed by pressing the “Enter” button. You will now be returned to the “Data Test” screen, and the Value field that previously con­tained 3950 now contains the Value 4297. Per the table below, you have now corrected the scaling factor for the Suction Pressure trans­ducer.
10. Continue this process, entering in “Index” val­ues and changing the scaling factors for all trans­ducers. (Reference Figure 1 below.)
11. When completed, press the OK button and re­turn back to the main screen.
12. Now go to the LOGON screen and perform a “BACKUP SETTINGS”. After a minute or so, the new scale factors will be “active”.
13. You may now need to recalibrate your trans­ducers again, as the new scale factors will af­fect the current readings of the transducers. If you have gauges on your system, you can do this using your gauge readings. When you have completed re-calibration of all your transduc­ers, do another “BACKUP SETTINGS”.
2895A 3011A Vission 3011C1 Vantage 3011A Vission 3011C1 Vantage
Ametek Yes Yes Yes Yes Yes
VPN 2783G
Danfoss No* No No Yes-Rescale Yes-Rescale
VPN 2783J
Setra Yes Yes Yes Yes Yes
VPN 2783K
Table II The acceptable mix of analog boards and transducers.
No* = this combination of board and transducer will result in a very slight scaling error (2 percent error over entire 0-300 PSIG range of transducer). Vilter does not recommend using the Danfoss transducer with a 2895A board.
Warning -If a Danfoss Transducer is used with a non-qualified 2783J Analog Board, the transducer will not properly read pressures over 165 PSIG.
86
(2783J qualified) (2783J qualified)
Page 87
Setup Screen
Danfoss Liquid Injection Valves
1. Press “Setup”
2 . Select “Enable” for Liquid Pos. Valve
3. Press “OK”
4 . Press “Vilter Only”, you will be prompted to Log In 5 . Press “Liquid Inj. Temp Control” then you will see the
screen as in the attached picture “Liquid Inj. Control”, the values you see there are default and can be changed according to your application.
Vilter Only Screen
NOTE:
Consult the VSS / VSM / VSR Unit Manual for proper Danfoss ICM valve setup procedure.
Liquid Inj. Temp Control Screen
87
Page 88
Who to Contact
If service is required, first contact your equipment distributor or contact A Vilter Technical Service Representative at:
V ilter Manufacturing LLC
5555 South Packard Ave.
PO Box 8904
Cudahy , WI 53110-8904
T el: 414-744-011 1
Fax: 414-744-1769
e-mail: info.vilter@emerson.com
www.vilter.com
Note: It will be necessary to have your V ilter order number available when contacting Vilter Manufacturing Corporation for service support.
Disclaimer: Specifications are subject to change without notification.
88
Page 89
89
Page 90
EmersonClimate.com
Vilter Manufacturing LLC P.O. Box 8904 Cudahy, WI 53110-8904 P 414 744 0111 F 414 744 1769
www.vilter.com
Vilter Manufacturing LLC are trademarks of Emerson Electric Co. or one of its affi liated companies.
©2011 Emerson Climate Technoligies, Inc. All rights reserved. Printed in the USA.
35391SA Rev 06
Loading...