Emerson Vission Control Manual

Vission Control Manual
2
Important Note
Before applying power to the VISSION MicroController panel, all wiring to the panel should be per NEC. Specifically check for proper voltage and that the neutral is grounded at the source. An equipment ground should also be run to the panel.
*See W iring Instructions and Diagrams before proceeding.
“Before powering the Vission control panel down”, it is a good idea to Backup Control Settings to insure that all previously changed setpoints have been properly saved. See section on saving changes. After back­ing up the setpoints DO NOT power down the V ission panel for at least 1 minute. This will allow adequate time for all setpoints to be properly saved.
Note: The screen shots depicted in this manual represent the screens corresponding to Vission program version # 2.4.41, the current version at time of printing. In our effort to continuously improve the functionality and ease-of-use of the Vission Micro-con­troller, the look of some screens may differ slightly than the representations shown here.
Equipment Indentification Numbers:
Vilter Order Number: __________________________Serial Number: _____________ Vilter Order Number: __________________________Serial Number: _____________ Vilter Order Number: __________________________Serial Number: _____________
3
4
Table of Contents
Important Note ............................................................................................................3
STANDARD VILTER WARRANTY STATEMENT .............................................6
Operational Flow Chart ............................................................................................. 8
Operational Flow Chart (cont.).................................................................................9
Wiring Instructions ...................................................................................................11
Wiring Instructions For Vission Only .....................................................................1 2
Wiring Diagram For Vission Only..........................................................................2 0
Main Screen...............................................................................................................22
Set Up Screen .............................................................................................................23
Version Screen ...........................................................................................................25
Maintenance Screen .................................................................................................26
Menu Screen ..............................................................................................................28
Common Buttons .......................................................................................................29
Compressor Control .................................................................................................30
Additional Compressor Controls ............................................................................32
Compressor Alarm and Trip....................................................................................35
Compressor Setpoints and Alarms ..........................................................................37
Miscellaneous Screens (Condenser Control) ........................................................41
Compressor Sequencing (Max 5 Compressors) .................................................... 4 3
Vilter Only Screen .....................................................................................................47
Diagnostics Force Output ........................................................................................48
Instrument Calibration .............................................................................................49
Calibration Procedure of Optical Actuators ..........................................................5 1
Installation Instructions For Replacement Of Optical Actuator .........................5 4
Slide Valve Actuator Troubleshooting Guide ......................................................... 5 5
Slide Wiring Diagram for Models Vission VSM-91 To VSS-601 ........................5 9
Slide Wiring Diagram for Models Vission VSS-751 To VSS-1801 .....................6 0
Command Shaft Rotation and Travel.....................................................................61
Calibration For Earlier Style Mechanical Gearmotor/Potentiometers ............. 6 2
Trend Chart ............................................................................................................... 6 4
Data Select Screen....................................................................................................65
Event List ...................................................................................................................66
Trouble Shooting Flowchart (Vission Only) ..........................................................6 8
5
Safety Failure Message ............................................................................................70
Supressor Kit Installation ........................................................................................ 7 3
Flash Card Installation Instructions.......................................................................74
Back Light Installation Instructions .......................................................................76
System Setpoints Alarms and Trips Work Sheet .................................................. 8 0
System Control Limit Values Work Sheet ..............................................................8 1
System Timer Values ................................................................................................. 8 2
Spare Parts ................................................................................................................84
Modifications for Analog Board (Vission/Vantage after July 2003) ...................8 5
Danfoss Liquid Injection Valves ..............................................................................87
Who to Contact .........................................................................................................88
6
STANDARD VILTER WARRANTY
STATEMENT
Seller warrants the products it manufactures to be free from defects in material and workmanship for a period of eighteen (18) months from the date of shipment from Seller s manufacturing plant or twelve (12) months from date of installation at the initial end users location, whichever occurs first. In addition, Seller provides the following extended warranties: (a) three (3) years from the date of shipment on single screw compressor internal rotating parts, (b) two (2) years from the date of shipment on reciprocating compressors and single screw and reciprocating compressor parts, and (c) two (2) years on all other parts on a single screw compressor unit. Such warranties do not apply to ordinary wear and tear. Seller does not warrant that the product complies with any particular law or regulation not explicitly set forth in the specifications, and Buyer is responsible for ensuring that the product contains all features necessary to safely perform in Buyers and its customers plants and operations. Buyer must notify Seller of any warranty claim within ten (10) days after such claim arises, otherwise Buyer waives all rights to such claim. Products supplied by Seller, which are manufac­tured by others, are not warranted by Seller, but rather Seller merely passes through the manufacturers warranty to Buyer.
SELLER EXPRESSL Y DISCLAIMS ALL OTHER W ARRANTIES, WHETHER EXPRESS OR IMPLIED, INCLUDING THE IMPLIED W ARRANTIES OF MERCHANT ABILITY AND FITNESS FOR A P ARTICULAR PURPOSE.
Unless otherwise agreed in writing, Buyers sole remedy for breach of warranty is, at Sellers option, the repair of the defect, the correction of the service, or the providing a replacement part FOB Sellers office. Seller will not be responsible for costs of dismantling, lost refrigerant, reassembling, or transporting the product. Further, Seller will not be liable for any other direct, indirect, consequential, incidental, or special damages arising out of a breach of warranty. THESE W ARRANTY REMEDIES ARE EXCLUSIVE AND ALL OTHER WARRANTY REMEDIES ARE EXCLUDED. Products or parts for which a warranty claim is made are to be returned transportation prepaid to Sellers factory. Any improper use, corrosion, neglect, accident, operation beyond rated capacity, substitution of parts not approved by Seller, or any alteration or repair by others which, in Sellers judgement, adversely affects the Product, shall void all warranties and warranty obligations. Further, Seller shall not be liable under the above warranties should Buyer be in default of its payment obligations to Seller under this Agreement or any credit agreement.
7
Operational Flow Chart
8
Operational Flow Chart (cont.)
9
10
Wiring Instructions
11
Wiring Instructions For Vission Only
5-1= Main Power to Panel 5-2= Heater #1 power 5-5= Heater #2 Power
12
Wiring Instructions For Vission Only
Mandatory Wiring
Step #2 Motor Starter Contactor Connection The contact to the pull in the motor starter contactor is a dry
contact, place a "HOT" wire from the starter circuit on 7-1. Place the wire to energize the starter contactor on 7-2.
CON 1
CON 2
CON 3
CON 4
CON 5
CON 6
CON 7
Lug
View Inside Of Vission Panel
CON 1
CON 2
CON 3
CON 4
CON 5
CON 6
CON 7
1-1 1-2 Safety 1-3 1-4 1-5 1-6 " 1-7 1-8 1-9 1-10
2-1 2-2 2-3 2-4 2-5 2-6 2-7 2-8 2-9 2-10
3-1 "N" 3-2 3-3 3-4 3-5 "N" 3-6 3-7 3-8 3-9 3-10
4-1 4-2 4-3 4-4 4-5 4-6 4-7 4-8 4-9 4-10
5-1 5-2 5-3 5-4 5-5 5-6 5-7 5-8 5-9 5-10
6-1 6-2 6-3 6-4 6-5 6-6 6-7 6-8 6-9 6-10
7-1 7-2 7-3 7-4 7-5 7-6 7-7 7-8 7-9 7-10
13
Wiring Instructions For Vission Only
Mandatory Wiring
Step #3 Motor St a rter Auxila ry C o nt a c t "HOT" to 4-5
Wire to en e r g ize to 1-1
CON 1
CON 2
CON 3
CON 4
CON 5
CON 6
CON 7
View Inside Of Vission Panel
CON 1
CON 2
CON 3
CON 4
CON 5
CON 6
CON 7
1-1 1-2 Safety 1-3 1-4 1-5 1-6 " 1-7 1-8 1-9 1-10
2-1 2-2 2-3 2-4 2-5 2-6 2-7 2-8 2-9 2-10
3-1 "N" 3-2 3-3 3-4 3-5 "N" 3-6 3-7 3-8 3-9 3-10
4-1 4-2 4-3 4-4 4-5 4-6 4-7 4-8 4-9 4-10
5-1 5-2 5-3 5-4 5-5 5-6 5-7 5-8 5-9 5-10
6-1 6-2 6-3 6-4 6-5 6-6 6-7 6-8 6-9 6-10
7-1 7-2 7-3 7-4 7-5 7-6 7-7 7-8 7-9 7-10
14
Wiring Instructions For Vission Only
Mandatory Wiring
Step #4 Oil Pump Starter Connection "HOT" to 6-1
Wire to energize on 6-2
CON 1
CON 2
CON 3
CON 4
CON 5
CON 6
CON 7
View Inside Of Vission Panel
CON 1
CON 2
CON 3
CON 4
CON 5
CON 6
CON 7
1-1 1-2 Safety 1-3 1-4 1-5 1-6 " 1-7 1-8 1-9 1-10
2-1 2-2 2-3 2-4 2-5 2-6 2-7 2-8 2-9 2-10
3-1 "N" 3-2 3-3 3-4 3-5 "N" 3-6 3-7 3-8 3-9 3-10
4-1 4-2 4-3 4-4 4-5 4-6 4-7 4-8 4-9 4-10
5-1 5-2 5-3 5-4 5-5 5-6 5-7 5-8 5-9 5-10
6-1 6-2 6-3 6-4 6-5 6-6 6-7 6-8 6-9 6-10
7-1 7-2 7-3 7-4 7-5 7-6 7-7 7-8 7-9 7-10
15
Wiring Instructions For Vission Only
Optional Wiring
Step #5 Auxiliary / Safety Wiring
A determination by the user is to be made if this option will be used. If it is
not
used, insure that a jumper is insta l led between L 2-1 and 1-2 If this option is used, remove the jum per 2-1 to 1-2 and place the high level cutout (typically, other cutouts or an E-stop could be used) common wire on 2-1 and the normally closed wire to 1-2.
CON 1
CON 2
CON 3
CON 4
CON 5
CON 6
CON 7
Lug
View Inside Of Vission Panel
CON 1
CON 2
CON 3
CON 4
CON 5
CON 6
CON 7
1-1 1-2 Safet y 1-3 1-4 1-5 1-6 " 1-7 1-8 1-9 1-10
2-1 2-2 2-3 2-4 2-5 2-6 2-7 2-8 2-9 2-10 3-1 "N" 3-2 3-3 3-4 3-5 "N" 3-6 3-7 3-8 3-9 3-10
4-1 4-2 4-3 4-4 4-5 4-6 4-7 4-8 4-9 4-10 5-1 5-2 5-3 5-4 5-5 5-6 5-7 5-8 5-9 5-10
6-1 6-2 6-3 6-4 6-5 6-6 6-7 6-8 6-9 6-10
7-1 7-2 7-3 7-4 7-5 7-6 7-7 7-8 7-9 7-10
16
Wiring Instructions For Vission Only
Optional Wiring
Step #6 Remote Start Wiri n g A determination by the user is to be made if this option will
be used. If it is
not
used, insure that a jumper is installed between L 2-1 and 1-5. If this option is used, remove the jum pe r 2-1 to 1-5 and place the dry remote start contact common wire on 2-1 and the normally open wire to 1-5.
CON 1
CON 2
CON 3
CON 4
CON 5
CON 6
CON 7
Lug
View Inside Of Vission Panel
CON 1
CON 2
CON 3
CON 4
CON 5
CON 6
CON 7
1-1 1-2 Safety 1-3 1-4 1-5 1-6 " 1-7 1-8 1-9 1-10
2-1 2-2 2-3 2-4 2-5 2-6 2-7 2-8 2-9 2-10 3-1 "N" 3-2 3-3 3-4 3-5 "N" 3-6 3-7 3-8 3-9 3-10
4-1 4-2 4-3 4-4 4-5 4-6 4-7 4-8 4-9 4-10 5-1 5-2 5-3 5-4 5-5 5-6 5-7 5-8 5-9 5-10
6-1 6-2 6-3 6-4 6-5 6-6 6-7 6-8 6-9 6-10
7-1 7-2 7-3 7-4 7-5 7-6 7-7 7-8 7-9 7-10
17
Wiring Instructions For Vission Only
Optional Wiring
Step #7 Setpoint #1/#2 Selection W iring A determination by the user is to be made if this option will
be used. This optional input does not need to be closed for the compressor to run no jumper is required. If this option is to be used, Place the dry contact common wire on L 2-7 and normally open on 1-3
CON 1
CON 2
CON 3
CON 4
CON 5
CON 6
CON 7
Lug
View Inside Of Vission Panel
CON 1
CON 2
CON 3
CON 4
CON 5
CON 6
CON 7
1-1 1-2 Safety 1-3 1-4 1-5 1-6 " 1-7 1-8 1-9 1-10
2-1 2-2 2-3 2-4 2-5 2-6 2-7 2-8 2-9 2-10 3-1 "N" 3-2 3-3 3-4 3-5 "N" 3-6 3-7 3-8 3-9 3-10
4-1 4-2 4-3 4-4 4-5 4-6 4-7 4-8 4-9 4-10 5-1 5-2 5-3 5-4 5-5 5-6 5-7 5-8 5-9 5-10
6-1 6-2 6-3 6-4 6-5 6-6 6-7 6-8 6-9 6-10
7-1 7-2 7-3 7-4 7-5 7-6 7-7 7-8 7-9 7-10
18
Note Page
19
Wiring Diagram For
Vission Only
20
Wiring Diagram For
Vission Only
21
The Main Screen
Main Screen
This screen has been designed to give the operator an overall view of all operating parameters affecting the compressor pack­age. This screen should always be displayed
when maintenance items and setpoint items are not being performed. The date on the
screen is updated every ½ second. Status information such as Alarms and Trips are displayed on the screen.
This Screen contains buttons to navigate to setpoint, setup and maintenance screens.
Status information on the compressor, oil pump, oil heater and run mode.
Start/Stop buttons. Hour meter. Motor amperage. Refrigerant. Real time compressor
and package operating conditions. Volume and Capacity Slide locations.
22
From the Main screen, touch the Setup but- ton. After entering an authorized user name password, the screen pictured below will ap­pear.
·Operator Name – This is the same list that appears in the login dialog. Names in this list can be selected for deletion. To change a name or password, you delete the name and enter a new name/password pair. The VILTER operator name cannot be deleted. Emergency passwords provided by a Vilter representative for the VILTER name are good only on the date for which they are issued. They are intended to permit navi­gation to this screen for setup or repair of this list.
Set Up Screen
·Language – The user screens can be seen in English, French, and Spanish, depend ing on the option selected. Some text will still display in English even when another language is selected.
·Pressure Units – Select units of measure for pressure readings. Choices are psi, kg cm2 and kPa. This section only, affects pressures displayed on main screen. On all other screens, units are displayed in psi. On the main screen with psi selected, negative gauge pressures will display as inches of mercury vacuum with the unit “Hg. On other screens, negative numbers are scaled as “psi”.
·Temperature Units – Select units of mea sure for temperature. Choices are Fahren heit or Celsius.
·Refrigerant – The choice R717 (Ammonia).
T ouch Here
23
Set Up Screen
· Anti-Recycle – The operator can select from
the following AntiRecycle options: True, Ac­cumulative, Modified, or Hot Starts. These select the strategy used to prevent excessive start/stop cycles of the compressor. Timers and counters used to enforce anti-recycling are adjusted and monitored in the Compres­sor Timer Settings screen, reached from the Menu screen. Help for the Timer Settings screen explains how the different settings and strategies operate.
· Compressor Control Via – Operator can
choose the method or mode of compressor control. This determines which measured vari­able is used in making loading (capacity con­trol) decisions. The choice selected here de­termines which setpoints are made available for adjustment on the Compressor Control Setpoints screen.
· Delete Operator – Operator can choose to
delete operator names from the authorized op­erator listing. A name in the list is selected by touching it. The selected name will be deleted from the list when this button is pushed. If you delete all the names (besides VIL TER), be sure you add at least one before leaving this screen.
· Add Operator – The button opens a dialog
for entry of a new name/password pair. Noth­ing (leaving the password text box blank) is a legal password. The password is not ob­scured as it is typed in, so untrusted parties should not be permitted to view the screen during entry. The password is not confirmed with a repeat entry, so verify it visually before pressing okay. Up to 25 name/password pairs can be added. The Operator Name list box will acquire a scroll bar when it fills.
·
Slide Non-Movement – Alarm enable and dis­able buttons permit selecting whether an alarm should be generated when failure of slides to move is detected.
· Setpoint #1 Oil Pump #2 Oil Pump – For
single stage and high stage operation, part time or normal oil pump fuction are used. The oil pump shuts off after discharge pressure has risen sufficiently to drive oil injection. Oil pump operating mode is independently settable for setpoint groups # 1 and # 2.
· Modbus Slave Network Address – When mul-
tiple MicroControllers are connected on a Modbus Network, each controller must have a unique address from the other MicroControllers on the network. Duplicate node addresses are not allowed. The node address of each V ission is determined through the SETUP menu. The MicroController that will initiate all conversation on the network MUST be defined as node 100 (this is defined as the “master” node). All other node num­bers should be in the range of 101 through
174.
This must be set when the extra special port (Com4) is used to control or monitor the com­pressor via Modbus. It also must be set when the multi-compressor sequencing feature is used. Even though Ethernet is used for the comms, this address establishes the compressor’s identity and role in the sequenc­ing logic.
· Reset After Power Fail – When Auto is se-
lected, the compressor will attempt to restart on powering up if it was running in ‘Auto’ when powered down and enabling conditions are met. When ‘Manual’ is selected, the com­pressor powers up into the ‘Stop’ mode and an explicit command to run is required from an operator or comms channel.
· Min Run Capacity – When enabled, the Mini-
mum Run Capacity setting on the Addition Compressor Setpoints screen operates as de­scribed in the help for that screen. When multiple compressor sequencing is used, se­lecting Disable here does not interfere with use of the Min Run Capacity setting in the se­quencing logic.
24
Log On, Off,or Save Changes
Set Up Screen
Press Log on/Save Button and the above screen will appear. When altering setpoints, log on is necessary. Select appropriate user name and enter password to change setpoints. This screen is also used to backup and save setpoints by pressing (Backup Settings).
After performing a “Back up Setting” operation, DO NOT power down the Vission/Vantage panel for atleast 1 minute. This will allow adequate time to insure all setpoints have been properly stored.
Version Screen
T o View if a customized program has been installed in your unit, go to the main screen and press VERSION, a screen will appear with the program version and the make model of the unit.
25
Maintenance Screen
T ouch Here
From the Main screen touch the Maintenance button.
“Service Item Required” message indicates that the compressor runtime hours has accumulated to a value - or a point- where service Maintenance is required.
>From the main screen, press the “Maintenance” button. A chart will be shown to indicate what service is required
- based on the number of hours the compressor has run.
After the all required service work has been accomplished, press the “Service” button located on the Maintenance screen. A “Services Completed” screen will appear. Press on each service that has been completed. A “check” will appear next to each item that has been pressed. When all required services have been completed, and the appropriate box has been checked in the “Services Completed” screen, then the “Service Item Required” message will disappear on the main screen.
Note: All of the service items listed for that interval must be checked before the “Servicing Item Required” message will disappear.
26
Maintenance Screen
This screen shows the chart of routine maintenance to be performed on the machine at hourly intervals from 200 hours to 120,000 hours.
The Service Button from the Maintenance Screen will bring you to this screen. When entering service items that were completed, make sure to check all items that are listed to be done at that
service interval.
27
Loading...
+ 63 hidden pages