Emerson Vilter MicroVission Operation And Service Manual

MicroVission Controller
Operation and service manual • Version 1.0

Important Message

READ CAREFULLY BEFORE OPERATING YOUR COMPRESSOR.
The following instructions have been prepared to assist in operation of VilterTM MicroVission Controllers.
The entire manual should be reviewed before attempting to operate.
VilterTM micro-controllers are thoroughly inspected at the factory. However, damage can occur in shipment. For this reason, the equipment should be thoroughly inspected upon arrival. Any damage noted should be reported immediately to the Transportation Company. This way, an authorized agent can examine the unit, determine the extent of damage and take necessary steps to rectify the claim with no serious or costly delays. At the same time, the local VilterTM representative or the home office should be notified of any claim made.
All inquires should include the VilterTM sales order number, compressor serial and model number. These can be found on the compressor nameplate on the compressor.
All requests for information, services or parts should be directed to:
VilterTM Manufacturing LLC
Customer Service Department
5555 South Packard Ave
Cudahy, WI 53110 USA
Telephone: 1-414-744-0111
Fax:1-414-744-3483
E-mail: info.vilter@emerson.com
Equipment Identification Numbers:
Vilter Order Number: _______________________Software Version: _________________ Vilter Order Number: _______________________Software Version: _________________ Vilter Order Number: _______________________Software Version: _________________ Vilter Order Number: _______________________Software Version: _________________
MicroVission Controller • Operation and Service Manual • Emerson • 35391MV 1.0
i
Section Page Number
Table of Contents
Important Message................................................................................................................................i
How To Use This Manual .........................................................................................................................TOC-7
Section 1 • Installation Recommendations
Proper Wiring Sizing ..............................................................................................................................1-1
Voltage Source ......................................................................................................................................1-1
Grounding .............................................................................................................................................1-2
Mixing Voltages .....................................................................................................................................1-2
DC signals .............................................................................................................................................. 1-2
Wiring Methods ..................................................................................................................................... 1-3
Best Practices .........................................................................................................................................1-4
Transformers, Fusing and UPS Sizing ...................................................................................................... 1-4
Section 2 • Hardware Architecture
Overview ...............................................................................................................................................2-1
Multi-I/O (Input/Output) Board ............................................................................................................. 2-1
Multi-IO Board Digital I/O ...................................................................................................................... 2-2
Multi-IO Board Analog I/O .....................................................................................................................2-4
Multi-IO Board Analog Input Jumper Tables ........................................................................................... 2-4
Digital In-Out Board ............................................................................................................................... 2-6
Analog Input Board ................................................................................................................................2-7
Analog Input Board Jumper Tables ......................................................................................................... 2-8
Section 3 • Main Screen
Overview ...............................................................................................................................................3-1
Top Status Bar ........................................................................................................................................3-2
Parameters Bar ......................................................................................................................................3-3
Control Parameters Box .........................................................................................................................3-4
Bottom Status Bar ..................................................................................................................................3-5
Splash Screen .........................................................................................................................................3-6
Manual Mode Run Buttons .....................................................................................................................3-6
Section 4 • Menu Screen
Overview ...............................................................................................................................................4-1
Navigation Buttons ...............................................................................................................................4-1
Section 5 • Compressor Control
Overview ...............................................................................................................................................5-1
How Compressor Control Setpoint Works? ............................................................................................5-1
Suction Pressure Control ........................................................................................................................ 5-2
Process Temperature Control ................................................................................................................. 5-3
Discharge Pressure Control .................................................................................................................... 5-4
Auto Cycle .............................................................................................................................................. 5-5
Active Control Mode ..............................................................................................................................5-8
Load Limiting ......................................................................................................................................... 5-9
Oil Control .............................................................................................................................................5-10
MicroVission Controller • Operation and Service Manual • Emerson • 35391MV
TOC - 1
Section Page Number
Table of Contents
Section 6 • Alarms and Trips Screen
Overview ...............................................................................................................................................6-1
Warnings. ..............................................................................................................................................6-1
Inhibits. .................................................................................................................................................6-1
Alarms... ................................................................................................................................................ 6-1
Trips .... .................................................................................................................................................. 6-1
Freeze Screens ..... .................................................................................................................................6-1
Logging - Event List ..... ..........................................................................................................................6-1
Alarms & Trips Setpoints .... .................................................................................................................... 6-2
MicroVission Safety Messages ................................................................................................................6-4
Section 7 • Timers
Overview ...............................................................................................................................................7-1
Timer Types ...........................................................................................................................................7-1
Section 8 • Instruments Calibration
Overview ...............................................................................................................................................8-1
I/O............... ..........................................................................................................................................8-1
Process & Temperature Inputs............... ................................................................................................. 8-1
Devices Calibration ................................................................................................................................8-1
Channel Calibration ...............................................................................................................................8-1
Analog Inputs - Pressure.........................................................................................................................8-2
Analog Input - Temperature ...................................................................................................................8-4
Analog Inputs ........................................................................................................................................8-6
Motor Current ........................................................................................................................................8-6
4-20mA Scale.........................................................................................................................................8-6
Process Temperature or Pressure ...........................................................................................................8-7
Auxiliary Inputs ...................................................................................................................................... 8-8
Device Calibration ..................................................................................................................................8-8
Channel Calibration ...............................................................................................................................8-8
Section 9 • Event List
Overview ...............................................................................................................................................9-1
Event list Columns ..................................................................................................................................9-1
Section 10 • Input / Output States Screen
Overview ...............................................................................................................................................10-1
Section 11 • User Access
Overview ...............................................................................................................................................11-1
Login .................................................................................................................................................. 11-2
Manage Accounts ..................................................................................................................................11-2
Screen Security Levels ............................................................................................................................11-3
TOC - 2
MicroVission Controller • Operation and Service Manual • Emerson • 35391MV
Section Page Number
Table of Contents
Section 12 • Configuration Screen
Overview ...............................................................................................................................................12-1
Units.... .................................................................................................................................................. 12-1
Compressor Control Section ..................................................................................................................12-2
Oil Monitoring .......................................................................................................................................12-2
Oil Level Trip ..........................................................................................................................................12-2
Touchscreen ..........................................................................................................................................12-2
Anti Recycle ...........................................................................................................................................12-3
Compressor Identification ......................................................................................................................12-3
Date and Time .......................................................................................................................................12-3
VNC Account .........................................................................................................................................12-4
Alarms and Trips ....................................................................................................................................12-4
Communication ..................................................................................................................................... 12-4
Active Remote Control ........................................................................................................................... 12-4
Direct I/O ............................................................................................................................................... 12-4
Run Permissive .......................................................................................................................................12-4
On Communication Failure ....................................................................................................................12-5
Ethernet ................................................................................................................................................12-5
Serial (Modbus RTU) ...............................................................................................................................12-6
Configurable Main Screen Settings .........................................................................................................12-6
I/O Configuration ...................................................................................................................................12-8
Section 13 • Data Backup
Overview ..............................................................................................................................................13-1
Refresh. .................................................................................................................................................13-1
Save/Load .............................................................................................................................................. 13-1
Available Devices ...................................................................................................................................13-2
Factory Reset .........................................................................................................................................13-3
Setpoints Report ....................................................................................................................................13-3
Database Backup Procedure...................................................................................................................13-4
Appendix A • Unloaders
Unloader Tables .....................................................................................................................................A-1
Appendix B • Communication Tables
MicroVission Communication Table ....................................................................................................... B-1
Alarm Status Words ...............................................................................................................................B-4
Warning Status Words ...........................................................................................................................B-5
Trip Status Words ...................................................................................................................................B-6
Appendix C • Remote Control and Monitoring
Introduction ..........................................................................................................................................C-1
Networking ...........................................................................................................................................C- 1
Communication Wire.............................................................................................................................C-1
Ethernet Cable Specifications............... ..................................................................................................C- 1
RS-482/485 Cable Specifications ............................................................................................................C- 1
Common Register Setup to Control the MicroVission (Compressor Control) Via Communications .........C- 2
Compressor Start and Stop Commands.............. ....................................................................................C- 3
Remote Control via Direct I/O (Hard-wired)............................................................................................C- 4
Control Scenario ....................................................................................................................................C- 4
Remote Monitoring ...............................................................................................................................C- 4
Communication Port Setup.............. ......................................................................................................C- 4
MicroVission Controller • Operation and Service Manual • Emerson • 35391MV
TOC - 3
Tables
Table 2-1. Digital I/O ..............................................................................................................................2-3
Table 2-2. Analog I/O ..............................................................................................................................2-4
Table 2-3. Multi-IO Board Analog Input Jumper Tables ............................................................................2-5
Table 2-4. Analog Input Board Jumper Tables ..........................................................................................2-8
Table 11-1. Security Access Levels .......................................................................................................... 11-3
Table A-0. Unloading Schemes ...............................................................................................................A-1
Table A-1. Type 1 Unloader - Cylinders: 2, 4, or 6 Unloading Percentage: 50% .........................................A-2
Table A-2. Type 2 Unloader - Cylinders: 4 Unloading Percentage: 25%, 50%, 75%
| Single cylinder Unloader wired to Unloader Output #1 ........................................................................A-2
Table A-3. Type 3 Unloader - Cylinders: 6 or 12 Unloading Percentage: 33%, 66% ....................................A-2
Table A-4. Type 4 Unloader - Cylinders: 8 or 16 Unloading Percentage: 25%, 50%, 75% ............................A-2
Table A-5. Type 5 Unloader - Cylinders: 8, 16 Unloading Percentage: 25%, 50% .......................................A-3
Table A-6. Type 6 Unloader - Cylinders: 4 or 8 Unloading Percentage: 50%, 100% ...................................A-3
Table A-7. Type 7 Unloader - Cylinders 6 or 12 Unloading Percentage: 33%, 66%, 100% ...........................A-3
Table A-8. Type 8 Unloader - Cylinders: 6 or 12 Unloading Percentage: 17%, 33%, 50%, 66%
Single cylinder Unloader wired to Unloader Output #1 ..........................................................................A-4
Table A-9. Type 9 Unloader - Cylinders: 6 or 12 Unloading Percentage: 17%, 33%, 50%, 66%, 83%
Single cylinder Unloader wired to Unloader Output #1 ...........................................................................A-4
Table A-10. Type 10 Unloader - Cylinders: 7 Unloading Percentage: 29%, 57% ........................................A-4
Table A-11. Type 11 - No Unloading ....................................................................................................... A-4
Table A-12. Type 12 Unloader - Cylinders: 3 Unloading Percentage: 33% ................................................A-4
Table A-13. Type 13 Unloader - Cylinders: 8, 16 Unloading Percentage: 25%, 50%, 75%, 100% .................A-5
Table A-14. Type 14 Unloader - Cylinders: 6 Unloading Percentage: 33%, 50%, 66% Unloading -
Single cylinder Unloader wired to Unloader Output #1 ...........................................................................A-5
Table A-15. Type 15 Unloader - Cylinders: 8 Unloading Percentage: 13%, 25%, 38%, 50%, 63%, 75%
Unloading - Single cylinder Unloader wired to Unloader Output #1 and Output #2 .................................A-5
Table A-16. Type 16 Unloader - Cylinders: 8 Unloading Percentage: 13%, 38%, 63% Unloading -
Single cylinder Unloader wired to Unloader Output #1 ...........................................................................A-6
Table A-17. Type 17 Unloader - Cylinders: 6 Unloading Percentage: 33%, 50%, 66% Unloading -
Single cylinder Unloader wired to Unloader Output #1 ...........................................................................A-6
Table A-18. Type 18 Unloader - Cylinders: 5 Unloading Percentage: 40%, 60%
Single cylinder Unloader wired to Unloader Output #1 ...........................................................................A-6
Table A-19. Type 19 Unloader - Cylinders: 3 Unloading Percentage: 33%, 66%
Single cylinder Unloader wired to Unloader Output #1 and Output #2 ...................................................A-7
Table A-20. Type 20 Unloader - Cylinder: 7 Unloading Percentage: 14%, 29%, 43%, 57%
Single cylinder Unloader wired to Unloader Output #1 ...........................................................................A-7
Table B-1. Digital Inputs Block ................................................................................................................ B-1
Table B-2. Digital Outputs Block ............................................................................................................. B-1
Table B-3. Analog Inputs Block ...............................................................................................................B-2
Table B-4. Analog Outputs Block ............................................................................................................B-2
Table B-5. Calculated Values Block .........................................................................................................B-2
Table B-6. Statuses Block ........................................................................................................................ B-3
Table B-7. Alarm Status Words ...............................................................................................................B-4
Table B-8. Warning Status Words ...........................................................................................................B-5
Table B-9. Trip Status Words (Words 1 & 2) ............................................................................................. B-6
Table B-9. Trip Status Words (Words 3 & 4) ............................................................................................. B-7
Table B-10. Commands Block ................................................................................................................. B-8
Table B-11. Compressor Control Setpoints Block ....................................................................................B-9
Table B-12. Auto Cycle Block ..................................................................................................................B-10
Table B-13. Stop Load & Force Unload Block ...........................................................................................B-11
TOC - 4
MicroVission Controller • Operation and Service Manual • Emerson • 35391MV
Tables and Figures
Table B-14. Oil Control Block .................................................................................................................. B-11
Table B-15. Alarms/Trips Block (Page 1) ..................................................................................................B-12
Table B-16. Alarms/Trips Block (Page 2) ..................................................................................................B-13
Table B-17. Alarms/Trips Block (Page 3) ..................................................................................................B-14
Table B-18. Timers Block (Page 1)...........................................................................................................B-14
Table B-19. Timers Block (Page 2)...........................................................................................................B-15
Table B-20. Configuration (Time) Block .................................................................................................. B-15
Table B-21. Configuration (Other) Block ................................................................................................. B-16
Figure 1-1. MicroVission with Individual Transformer .............................................................................1-1
Figure 1-2. EMI and MIcroVission ...........................................................................................................1-1
Figure 1-3. Ground Wiring .....................................................................................................................1-3
Figure 1-4. Mixed Voltage Wiring ...........................................................................................................1-3
Figure 1-5. Correct Transformer Wiring Method .................................................................................... 1-3
Figure 1-6. Incorrect Transformer Wiring Method ..................................................................................1-3
Figure 2-1. Hardware Architecture Overview .........................................................................................2-1
Figure 2-2. Multi I/O Board Layout ..........................................................................................................2-2
Figure 2-3. Digital Input-Output Board Layout ........................................................................................2-6
Figure 2-4. Analog Input Board Layout ...................................................................................................2-7
Figure 3-1. Main Screen..........................................................................................................................3-1
Figure 3-2. Top Status Bar ......................................................................................................................3-2
Figure 3-3. Parameters Bar .....................................................................................................................3-3
Figure 3-4. Start Dialog Box ....................................................................................................................3-4
Figure 3-5. Bottom Status Bar ................................................................................................................3-5
Figure 3-6. Warning Pop-Up Window ..................................................................................................... 3-6
Figure 3-7. Splash Screen .......................................................................................................................3-6
Figure 3-8. Manual Run Mode Buttons....................................................................................................3-6
Figure 4-1. Menu Screen ........................................................................................................................4-1
Figure 5-1. Compressor Control Screen - Suction Pressure Control ......................................................... 5-2
Figure 5-2. Compressor Control Screen - Process Temperature Control ..................................................5-3
Figure 5-3. Compressor Control Screen - Discharge Pressure Control .....................................................5-4
Figure 5-4. Compressor Control Screen - Auto Cycle (Suction Pressure) .................................................. 5-5
Figure 5-5. Compressor Control Screen - Auto Cycle (Process Temperature) ...........................................5-6
Figure 5-6. Compressor Control Screen - Auto Cycle (Discharge Pressure) ..............................................5-7
Figure 5-7. Compressor Control Screen – Active Control Mode - I/O Based Setpoint Control ...................5-8
Figure 5-8. Compressor Control Screen - Load Limiting ..........................................................................5-9
Figure 5-9. Compressor Control Screen - Oil Control ...............................................................................5-10
Figure 6-1. Alarms and Trips Setpoints (Page 1) ...................................................................................... 6-2
Figure 6-2. Alarms and Trips Setpoints (Page 2) ...................................................................................... 6-3
Figure 6-3. Alarms and Trips Setpoints (Page 3) ...................................................................................... 6-3
Figure 7-1. Timers Screen (Page 1) ......................................................................................................... 7-1
Figure 7-1. Timers Screen (Page 2) ......................................................................................................... 7-2
Figure 8-1.Instrument Calibration Screen Page 1 – Analog Inputs (Suction Pressure) ............................. 8-2
Figure 8-2. Instrument Calibration Screen Page 1 – Analog Inputs (Discharge Pressure) .........................8-2
Figure 8-3. Instrument Calibration Screen Page 1 – Analog Inputs (Oil Pressure) ....................................8-3
Figure 8-4. Instrument Calibration Screen Page 1 – Analog Inputs (Filter In Pressure) ............................. 8-3
Figure 8-5. Instrument Calibration Screen Page 1 – Analog Inputs (Filter Out Pressure) .......................... 8-4
MicroVission Controller • Operation and Service Manual • Emerson • 35391MV
TOC - 5
Figures
Figure 8-6. Instrument Calibration Screen Page 2 – Analog Inputs (Suction Temperature) ...................... 8-4
Figure 8-7. Instrument Calibration Screen Page 2 – Analog Inputs (Discharge Temperature) ..................8-5
Figure 8-8. Instrument Calibration Screen Page 2 – Analog Inputs (Oil Temperature) .............................8-5
Figure 8-9. Instrument Calibration Screen Page 3 – Analog Inputs (Motor Current) ................................8-6
Figure 8-10. Instrument Calibration Screen Page 3 – Analog Inputs (Process Temperature) ....................8-7
Figure 8-11. Instrument Calibration Screen Page 4 – Auxiliary Inputs (Discharge 2 Pressure) .................. 8-8
Figure 8-12. Instrument Calibration Screen Page 4 – Auxiliary Inputs (Discharge 2 Temperature) ........... 8-9
Figure 9-1. Event List Screen ...................................................................................................................9-1
Figure 10-1. Input/Output States Screen Page 1 - Live I/O Data ...............................................................10-1
Figure 10-2. Input/Output States Screen Page 2 - Live I/O Data ...............................................................10-2
Figure 10-3. Input/Output States Screen - Freeze Data (Trip Condition) .................................................. 10-2
Figure 10-4. Input/Output States Screen - Freeze Data ...........................................................................10-3
Figure 10-5. Input/Output States Screen – Auxiliary Analog Inputs ......................................................... 10-3
Figure 11-1. User Access Screen - Login .................................................................................................. 11-1
Figure 11-2. User Access Screen - Manage Accounts ...............................................................................11-2
Figure 12-1. Configuration Screen - Initial Setup (Page 1) ....................................................................... 12-1
Figure 12-2. Configuration Screen (Page 2) ............................................................................................12-3
Figure 12-3. Configuration Screen - Communication ..............................................................................12-5
Figure 12-4. Configuration Screen - Configurable Main Screen Settings .................................................. 12-6
Figure 12-5. Configurable Parameters on Main Screen ...........................................................................12-7
Figure 12-6. Configuration Screen - I/O Configuration ........................................................................... 12-8
Figure 13-1. Data Backup Screen - Save/Load ......................................................................................... 13-1
Figure 13-2. Data Backup Screen - Migrate and Factory Reset ................................................................. 13-2
Figure 13-3. Data Backup Screen - Setpoints Report ............................................................................... 13-3
Figure 13-4. SD Card Replacement .........................................................................................................13-6
Figure C-1. Configuration Screen (Page 3) ..............................................................................................C- 1
Figure C-2. Serial Communication Ports on Single Board Computer ........................................................ C-2
Figure C-3. Setting MicroVission in Remote Mode ..................................................................................C- 3
TOC - 6
MicroVission Controller • Operation and Service Manual • Emerson • 35391MV

How to Use This Manual

NOTE
Manual revision should match software version.
This manual contains instructions for the MicroVission Operation & Service Manual. It has been divided into 16 sections.
Section 1: Installation Recommendations
Section 2: Main Screen
Section 3: Hardware Architecture
Section 4: Menu Screen
Section 5: Compressor Control Screen
Section 6: Alarms and Trips Screen
Section 7: Timers Screen
Section 8: Instrument Calibration Screen
Section 9: Event List Screen
Section 10: Input/Output Screen
Section 11: User Access
Section 12: Conguration Screen
Section 13: Data Back-Up
Appendix A: Unloaders
Appendix B: Communication Tables
Appendix C: Remote Control and Monitoring
Safety precautions are shown throughout the manual. They are dened as the following:
WARNING - Warning statements are shown when there
are hazardous situations, if not avoided, will result in se-
rious injury or death.
CAUTION - Caution statements are shown when there
are potentially hazardous situations, if not avoided, will result in damage to equipment.
NOTE - Notes are shown when there are additional infor-
mation pertaining to the instructions explained.
NOTICE - Notices are shown when there are important
information that can help avoid system failure.
ADDITIONAL IMPORTANT NOTES
Due to continuing changes and unit updates, always refer to the www.Emerson.com/Vilter to make sure
you have the latest manual.
Any suggestions for manual improvements can be made to VilterTM Manufacturing at the contact infor-
mation on page i.
It is highly recommended that the manual be reviewed prior to servicing the MicroVission system parts.
Figures and tables are included to illustrate key concepts.
MicroVission Controller • Operation and Service Manual • Emerson • 35391MV
TOC - 7

Section 1 Installation Recommendations

Proper Wiring Sizing

Always size wire gauges as specied by the National Electrical Code (NEC) for electronic control devices.
For improved noise immunity, install one size larger
wire gauge than the NEC requirement to assure am­ple current-carrying capability.
Never under size wire gauges.

Voltage Source

Transformers block a large percentage of Electromagnetic Interference (EMI). It is recom-
mended that the Vilter MicroVission should be iso­lated with its own control transformer for the most
reliable operation. See Figure 1-1: MicroVission with
Individual Transformer.
Avoid connecting MicroVission to breaker panels and central control transformers if possible as the
MicroVission is exposed to large amounts of EMI
emitted from the other devices connected to the sec-
ondary terminals of the transformer. See Figure 1-2:
EMI and MicroVission.
Figure 1-1. MicroVission with Individual Transformer
Figure 1-2. EMI and MicroVission
MicroVission Controller • Operation and Service Manual • Emerson • 35391MV 1.0
1 – 1
Section 1 Installation Recommendations

Grounding

Ensure that you run continuous grounds from the utility ground to the MicroVission. See Figure 1-3: Ground Wiring.
• Grounds must be copper or aluminum wire.
Never use conduit grounds.

Mixing Voltages

Separate different voltages from each other and separate AC from DC, see Figure 1-4: Mixed Voltage Wiring.
Each voltage level must be run in separate conduit:
o 460 VAC
o 230 VAC
o 120 VAC
o 24 VAC
o DC Signals
If your installation site has wireways or conduit trays, you must install dividers between the different voltages.

DC signals

If your installation site has wireways or conduit trays, you must install dividers between the different voltages.
Figure 1-3. Ground Wiring
Figure 1-4. Mixed Voltage Wiring
1 – 2
MicroVission Controller • Operation and Service Manual • Emerson • 35391MV 1.0
Section 1 Installation Recommendations

Wiring Methods

Each MicroVission panel should have its own individual
control transformer, see Figure 1-5: Correct Transformer Wiring method and Figure 1-6: Incorrect Transformer Wiring Method.
Figure 1-5. Correct Transformer Wiring Method
Figure 1-6. Incorrect Transformer Wiring Method
MicroVission Controller • Operation and Service Manual • Emerson • 35391MV 1.0
1 – 3
Section 1 Installation Recommendations

Best Practices

• Do:
Keep AC wires away from circuit boards.
Always run conduit into the bottom or sides of an enclosure.
• Use a water-tight conduit tting to keep water from entering the enclosure, if the conduit must be placed
in the top of an enclosure.
The MicroVission is supplied with pre-punched conduit holes for your use.
• Don’t:
Do not run wires through the MicroVission enclosure that are not related to the compressor control.
Do not add relays, timers, transformers, etc. In the MicroVission enclosure without rst checking with VilterTM.
• Do not run conduit into the top of an enclosure.
Do not run refrigerant tubing inside the enclosure.
Do not drill metal enclosures without taking proper precautions to protect circuit boards from damage.

Transformer, Fusing and UPS Sizing

The following information can be used to help determine the power requirements for a MicroVission panel. This infor­mation can be helpful for sizing transformers or UPS devices that will power the MicroVission panel.
The MicroVission panel contains a single power supply
(1) 24VDC @ 4.5 A (108 watts)
The DC loads that are attached to the power supply are divided approximately as follows;
1. Each press transducer +24VDC @ 30 mA each (x4) = 120 mA
2. Each RTD (negligible), (the hardware applies a 25 mA pulsed signal, which is not constant).
For estimating purposes, assume:
A total sum constant draw for total RTDs used 50 mA
3. Each 4-20mA transmitter for an RTD = 10 mA
So, for 120V fusing – consider 110 watts for the power supply, PLUS add any additional 120V loads that are con-
nected to the digital outputs + relays added to the panel.
1. Each unloader solenoid = 0.125 amps AC load
2. Each small solenoid = 50 watts (estimate – read the nameplate for exact load rating)
3. Large solenoids (water, hot gas) = 100 watts (estimate– read nameplate for exact load rating)
4. Each small pilot relay = 25 watts (estimate– read the nameplate for exact load rating)
5. Add load values for panel heaters if used, and heat trace tape if used
1 – 4
MicroVission Controller • Operation and Service Manual • Emerson • 35391MV 1.0

Section 2 Hardware Architecture

Overview

The MicroVission control panel utilizes the ARM PC tech-
nology with a Linux operating system. For hardware ar­chitecture, see Figure 2-1.
The MicroVission has the following attributes
• Low power, Industrial rated ARM CPU
10” XGA, high resolution LCD display. (Outdoor view- able LCD optional)
• 8-wire touch screen operator interface
• Flexible and expandable I/O
• NEMA-4 enclosure (NEMA-4X optional)
Industrial temperature range design
Figure 2-1. Hardware Architecture Overview

Multi-I/O (Input/Output) Board

This section explains about the Multi-IO board con-
taining Digital Input/Output and Analog Input/Output signals.
The Multi-IO board converts signals generated by the MicroVission program into 120VAC signals as well as de­tect external 120VAC inputs to signal the MicroVission program. All the signals shown by connectors 1, 2, 3 and 4 are digital, in that there are only two states available either ON or OFF. See board layout, Figure 2-2.
MicroVission Controller • Operation and Service Manual • Emerson • 35391MV 1.0
The Multi-IO board converts the varying DC signals into a signal that the MicroVission program can interpret. The signals are considered analog because the input DC sig­nal can vary from the minimum value to the maximum value. All the signals shown by connectors 6, 7, 8, 9 and 10 are analog inputs. This board can also convert signals from the MicroVission program into a current ranging from 4mA to 20mA. These are called analog outputs and shown by connectors 12 and 13. For more information about the board layout see Figure 2-2.
2 – 1
Section 2 Hardware Architecture
Figure 2-2. Multi I/O Board
Layout

Multi-IO Board Digital I/O

For information about each Digital I/O signal, see Table 2-1: Digital I/O.
Oil Return Solenoid Output
When state of Low Oil Level Digital Input is found Active Low, this output is energized. When state of Low Oil Level Digital Input is changed to Active High from Active Low state, this output will be de­energized only once Oil Recovery Solenoid Shutoff Delay Timer is Lapsed.
Unloader (#1 to #4) Output
These outputs are active only when the compressor is running. When the MicroVission determines that
the compressor should increase or decrease capac-
ity, these outputs will get de-energized or energized respectively in specic sequence as per Compressor Type set in Conguration screen. See Appendix A,
Unloaders section for more details.
2 – 2
MicroVission Controller • Operation and Service Manual • Emerson • 35391MV 1.0
Trip Output
This output is energized when the system has no Trips. If a trip is issued, the output de-energizes and stays de-energized until the trip condition is cleared.
Oil Crank Case Heater Output
This output is active and energized when the oil temperature is lower than the oil temperature set-
point. It is de-energized when the oil temperature is higher than the oil temperature setpoint.
Compressor Start Output
When the MicroVission signals the compres­sor to start, this output is energized. When the MicroVission signals the compressor to stop, this output is de-energized.
Section 2 Hardware Architecture
Remote Ready Output
This output is energized when the MicroVission panel is enabled for remote control. If the compres-
sor parameter does not satisfy start conditions or is
placed into the manual stop position, this output is
de-energized.
Setpoint 1/2 Input
• This input will be monitored when the MicroVission panel is enabled for remote control. When this input
is de-energized, the MicroVission will use Setpoint 1 as Control Setpoint for modulating the compres­sor capacity. When this input is energized, the
MicroVission will use Setpoint 2 as Control Setpoint
for modulating the compressor capacity. For using
Setpoint 2, the operator should make sure that No.
of Controllers is set to 2 in Conguration screen.
Remote Decrease Input
• This input will be monitored when the MicroVission panel is enabled for remote control. When this input
is energized, the MicroVission will unload compres­sor by one step.
Remote Increase Input
• This input will be monitored when the MicroVission panel is enabled for remote control. When this input
is energized, the MicroVission will load compressor by one step.
Remote Start/Stop Input
• This input will be monitored when the MicroVission panel is enabled for remote control or if Run Permissive option is enabled. When this input is en-
ergized, the compressor will be allowed to start in selected run mode. If the compressor is running and this input is found de-energized, the compressor will
be stopped and the compressor will have to wait for
next start until this input gets energized.
Low Oil Level Input
This input must be energized for the compressor to operate. If this input gets de-energized, the com-
pressor will be stopped and issue a Low Oil Level trip provided Oil Level Trip option is enabled in
Conguration screen.
High Level Shutdown Input:
The MicroVission monitors this digital input to check whether the power is removed from the input
module during compressor start. This input must be energized for the compressor to operate. If de­energized, the compressor will shut down and issue a High Level Shutdown trip.
Compressor Motor Starter Auxiliary Input:
This input looks for a feedback signal from the com­pressor starter, conrming that the compressor starter is energized.
Connector on Mul-IO
Board
X1 – 1 1 Oil Return Solenoid OUTPUT
X1 – 2 2 Unloader #4 OUTPUT
X1 – 3 3 Unloader #3 OUTPUT
X1 – 4 4 Unloader #2 OUTPUT
X2 – 1 5 Unloader #1 OUTPUT
X2 – 2 6 Trip OUTPUT
X2 – 3 7 Oil Crank Case Heater OUTPUT
X2 – 4 8 Compressor Start OUTPUT
X3 – 1 9 Remote Ready OUTPUT
X3 – 2 10 Setpoint 1/2 INPUT
X3 – 3 11 Remote Decrease INPUT
X3 – 4 12 Remote Increase INPUT
X4 – 1 13 Remote Start/ Stop INPUT
X4 – 2 14 Low Oil Level INPUT
X4 – 3 15 High Level Shutdown INPUT
Table 2-1. Digital I/O
I/O # Descripon Channel Type
X4 – 4 16 Compressor Motor Auxiliary INPUT
MicroVission Controller • Operation and Service Manual • Emerson • 35391MV 1.0
2 – 3
Section 2 Hardware Architecture
Connector on
Mul-IO Board
I/O # Descripon Channel Type Signals Type
X6 – 2 1 Process Temperature INPUT 0-5 V, 0-10 V, 4-20 mA, RTD, ICTD
X6 – 5 2 Oil Temperature INPUT 0-5 V, 0-10 V, 4-20 mA, RTD, ICTD
X7 – 2 3 Discharge Temperature INPUT 0-5 V, 0-10 V, 4-20 mA, RTD, ICTD
X7 – 5 4 Sucon Temperature INPUT 0-5 V, 0-10 V, 4-20 mA, RTD, ICTD
X8 – 2 5 Filter Out Pressure INPUT 0-5 V, 0-10 V, 4-20 mA, RTD, ICTD
X8 – 5 6 Filter In Pressure INPUT 0-5 V, 0-10 V, 4-20 mA, RTD, ICTD
X9 – 2 7 Oil Manifold Pressure INPUT 0-5 V, 0-10 V, 4-20 mA, RTD, ICTD
X9 – 5 8 Discharge Pressure INPUT 0-5 V, 0-10 V, 4-20 mA, RTD, ICTD
X10 – 2 9 Sucon Pressure INPUT 0-5 V, 0-10 V, 4-20 mA, RTD, ICTD
X10 – 5 10 Motor Amps (4-20 mA) INPUT 0-5 V, 0-10 V, 4-20 mA, RTD, ICTD
X12 – 1 11 Not Dened OUTPUT 4-20 mA
X12 – 3 12 Not Dened OUTPUT 4-20 mA
X12 – 5 13 Not Dened OUTPUT 4-20 mA
X13 – 1 14 Not Dened OUTPUT 4-20 mA
X13 – 3 15 Not Dened OUTPUT 4-20 mA
X13 – 5 16 Not Dened OUTPUT 4-20 mA
Table 2-2. Analog I/O

Multi-IO Board Analog I/O

For information about each Analog I/O signal, see Table 2-2: Analog I/O.
Process Temperature
Default signal is RTD. Process temperature calibra­tion is set in the calibration screen.
Oil Temperature
Default signal is RTD. Oil temperature calibration is set in the calibration screen.
Discharge Temperature
Default signal is RTD. Discharge temperature calibration is set in the calibration screen.
Suction Temperature
Default signal is RTD. Suction temperature calibra- tion is set in the calibration screen.
Filter Out Pressure
Default signal is 4-20mA. Filter Out pressure transducer range and calibration are set in the
calibration screen.
Filter In Pressure
Default signal is 4-20mA. Filter In pressure trans­ducer range and calibration are set in the calibration
screen.
Oil Manifold Pressure
Default signal is 4-20mA. Oil manifold pressure transducer range and calibration are set in the cali-
bration screen.
Discharge Pressure
Default signal is 4-20 mA. Discharge pressure trans­ducer range and calibration are set in the calibration
screen.
Suction Pressure
Default signal is 4-20 mA. Suction pressure trans­ducer range and calibration is set in the calibration
screen.
Motor Amps
Default signal is a 4-20 mA. The Motor Amps calibra- tion is set in the calibration screen.
2 – 4
MicroVission Controller • Operation and Service Manual • Emerson • 35391MV 1.0
Section 2 Hardware Architecture

Multi-IO Board Analog Input Jumper Tables

The following tables are used to congure each chan­nel of the Multi-IO board analog inputs, signal type and range desired by the operator, see Table 2-3.
Table 2-3. Multi-IO Board Analog Input Jumper Tables
Channel 1 Signal JP - 1 JP - 2 JP - 3 JP - 4
0-5 VDC OUT OUT OUT OUT
Analog
Input 1
Channel 3 Signal JP - 9 JP - 10 JP - 11 JP - 12
Analog
Input 3
Channel 5 Signal JP - 17 JP - 18 JP - 19 JP - 20
Analog
Input 5
4-20 mA IN OUT OUT OUT
ICTD OUT IN OUT OUT
0-10 VOLT OUT OUT IN OUT
RTD OUT OUT OUT IN
0-5 VDC OUT OUT OUT OUT
4-20 mA IN OUT OUT OUT
ICTD OUT IN OUT OUT
0-10 VOLT OUT OUT IN OUT
RTD OUT OUT OUT IN
0-5 VDC OUT OUT OUT OUT
4-20 mA IN OUT OUT OUT
ICTD OUT IN OUT OUT
0-10 VOLT OUT OUT IN OUT
RTD OUT OUT OUT IN
Channel 2 Signal JP - 5 JP - 6 JP - 7 JP - 8
0-5 VDC OUT OUT OUT OUT
Analog
Input 2
Channel 4 Signal JP - 13 JP - 14 JP - 15 JP - 16
Analog
Input 4
Channel 6 Signal JP - 21 JP - 22 JP - 23 JP - 24
Analog
Input 6
4-20 mA IN OUT OUT OUT
ICTD OUT IN OUT OUT
0-10 VOLT OUT OUT IN OUT
RTD OUT OUT OUT IN
0-5 VDC OUT OUT OUT OUT
4-20 mA IN OUT OUT OUT
ICTD OUT IN OUT OUT
0-10 VOLT OUT OUT IN OUT
RTD OUT OUT OUT IN
0-5 VDC OUT OUT OUT OUT
4-20 mA IN OUT OUT OUT
ICTD OUT IN OUT OUT
0-10 VOLT OUT OUT IN OUT
RTD OUT OUT OUT IN
Channel 7 Signal JP - 25 JP - 26 JP - 27 JP - 28
0-5 VDC OUT OUT OUT OUT
Analog
Input 7
Channel 9 Signal JP - 33 JP - 34 JP - 35 JP - 36
Analog
Input 9
MicroVission Controller • Operation and Service Manual • Emerson • 35391MV 1.0
4-20 mA IN OUT OUT OUT
ICTD OUT IN OUT OUT
0-10 VOLT OUT OUT IN OUT
RTD OUT OUT OUT IN
0-5 VDC OUT OUT OUT OUT
4-20 mA IN OUT OUT OUT
ICTD OUT IN OUT OUT
0-10 VOLT OUT OUT IN OUT
RTD OUT OUT OUT IN
Channel 8 Signal JP - 29 JP - 30 JP - 31 JP - 32
Analog
Input 8
Channel 10 Signal JP - 37 JP - 38 JP - 39 JP - 40
Analog
Input 10
0-5 VDC OUT OUT OUT OUT
4-20 mA IN OUT OUT OUT
ICTD OUT IN OUT OUT
0-10 VOLT OUT OUT IN OUT
RTD OUT OUT OUT IN
0-5 VDC OUT OUT OUT OUT
4-20 mA IN OUT OUT OUT
ICTD OUT IN OUT OUT
0-10 VOLT OUT OUT IN OUT
RTD OUT OUT OUT IN
2 – 5
Section 2 Hardware Architecture
Figure 2-3. Digital Input-Output Board Layout

Digital In-Out Board

The digital input - output board converts signals gener­ated by the MicroVission program into 120VAC signals as well as detect external 120VAC inputs to signal the MicroVission program. All the signals are digital and in that there are only two states available either ON or OFF. See board layout, Figure 2-3.
Signal LEDs
• In the following diagram, the Signal LEDs for out­put are marked in a Blue color and for input they are marked in a Light Blue color. These LEDs indi­cate when a 120VAC output is being produced or a 120VAC signal is detected.
Voltage LEDs
In the following diagram, the Voltage LEDs are marked in an Orange color. These LEDs indicate the correct voltage of both the 5V DC and 24V DC pow-
er sources.
2 – 6
MicroVission Controller • Operation and Service Manual • Emerson • 35391MV 1.0
Communication LEDs
In the following diagram, the Communication LEDs are marked in a Green color. These LEDs show the
active communications between the digital output
board and MicroVission CPU board.
Address Dipswitches
In the following diagram, the Address Dipswitches are marked in a Red color. These dipswitches are
used to assign each board its address position. The addresses are binary and therefore the address of a digital output board will either be address 1 (0001)
or 2 (0010).
Section 2 Hardware Architecture

Analog Input Board

The analog input board converts the varying DC signals into a signal that the MicroVission program can inter­pret. The signals are considered analog because the in­put DC signal can vary from the minimum value to the maximum value. See Figure 2-4.
Conguration Jumpers
In the following diagram, the conguration jumpers are marked in purple color. The jumpers allow the
operator to congure the signal type and range for incoming analog signals. For the correct jumper set­ting for a given application, see Table 2-4. Analog
Input Jumper Tables.
Voltage LEDs
In the following diagram, the Voltage LEDs are marked in Orange color. These LEDs indicate the correct voltage of both the 5V DC and 24V DC pow-
er sources.
Communication LEDs
In the following diagram, the Communication LEDs are marked in Green color. These LEDs show the ac-
tive communications between the digital output
board and the MicroVission CPU board.
Address Dipswitches
In the following diagram, the Address Dipswitches are marked in Red color. These dipswitches are
used to assign each board its address position. The addresses are binary and therefore the address of a analog input board will be address 1 (0001) or 2
(0010).
Figure 2-4. Analog Input Board Layout
MicroVission Controller • Operation and Service Manual • Emerson • 35391MV 1.0
2 – 7
Section 2 Hardware Architecture

Analog Input Board Jumper Tables

The following tables are used to congure each channel of the analog input board signal type and range desired by the operator, see Table 2-4.
Table 2-4. Analog Input Board Jumper Tables
Channel 1 Signal JP - 1 JP - 2 JP - 3 JP - 27 JP - 35
Analog
Input 1-A*
Analog
input 1-B**
0-5 AMP OUT OUT OUT OUT IN
0-5 VOLT OUT OUT OUT OUT OUT
1-5 VOLT OUT OUT OUT OUT OUT
0-10 VOLT OUT OUT IN OUT OUT
4-20 mA IN OUT OUT OUT OUT
ICTD OUT IN OUT OUT OUT
RTD OUT OUT OUT IN OUT
* Use Analog Input 1-A when 0-5 AMP secondary current transformers are
installed in the motor starter.
** Use Analog Input 1-B when current
transformers are installed in the motor star ter.
Channel 2 Signal JP - 4 JP - 5 JP - 6 JP - 28
0-5 VOLT OUT OUT OUT OUT
1-5 VOLT OUT OUT OUT OUT
Analog
Input 2
0-10 VOLT OUT OUT IN OUT
4-20 mA IN OUT OUT OUT
ICTD OUT IN OUT OUT
RTD OUT OUT OUT IN
Channel 4 Signal JP - 10 JP - 11 JP - 12 JP - 30
0-5 VOLT OUT OUT OUT OUT
1-5 VOLT OUT OUT OUT OUT
Analog
Input 4
0-10 VOLT OUT OUT IN OUT
4-20 mA IN OUT OUT OUT
ICTD OUT IN OUT OUT
RTD OUT OUT OUT IN
Channel 3 Signal JP - 7 JP - 8 JP - 9 JP - 29
0-5 VOLT OUT OUT OUT OUT
1-5 VOLT OUT OUT OUT OUT
Analog
Input 3
0-10 VOLT OUT OUT IN OUT
4-20 mA IN OUT OUT OUT
ICTD OUT IN OUT OUT
RTD OUT OUT OUT IN
Channel 5 Signal JP - 13 JP - 14 JP - 15 JP - 31
0-5 VOLT OUT OUT OUT OUT
1-5 VOLT OUT OUT OUT OUT
Analog
Input 5
0-10 VOLT OUT OUT IN OUT
4-20 mA IN OUT OUT OUT
ICTD OUT IN OUT OUT
RTD OUT OUT OUT IN
2 – 8
MicroVission Controller • Operation and Service Manual • Emerson • 35391MV 1.0
Section 2 Hardware Architecture
Table 2-4. Analog Input Board Jumper Tables (continued)
Channel 6 Signal JP - 16 JP - 17 JP - 18 JP - 32
Analog
Input 6
0-5 VOLT OUT OUT OUT OUT
1-5 VOLT OUT OUT OUT OUT
0-10 VOLT OUT OUT IN OUT
4-20 mA IN OUT OUT OUT
ICTD OUT IN OUT OUT
RTD OUT OUT OUT IN
Channel 7 Signal JP - 19 JP - 20 JP - 21 JP - 33 JP – 25*
0-5 VOLT OUT OUT OUT OUT 2
1-5 VOLT OUT OUT OUT OUT 2
0-10 VOLT OUT OUT IN OUT 2
Analog
Input 7
4-20 mA IN OUT OUT OUT 2
ICTD OUT IN OUT OUT 2
RTD OUT OUT OUT IN 2
ACTUATOR OUT OUT OUT OUT 1
POTENTIOMETER OUT OUT OUT OUT 3
Channel 8 Signal JP - 22 JP - 23 JP - 24 JP - 34 JP – 26*
0-5 VOLT OUT OUT OUT OUT 2
1-5 VOLT OUT OUT OUT OUT 2
0-10 VOLT OUT OUT IN OUT 2
Analog
Input 8
4-20 mA IN OUT OUT OUT 2
ICTD OUT IN OUT OUT 2
RTD OUT OUT OUT IN 2
ACTUATOR OUT OUT OUT OUT 1
POTENTIOMETER OUT OUT OUT OUT 3
*JP-25
• Position 1 = sends +24VDC
(unregulated) to “supply”
terminal (2.2A limit)
• Position 2 = sends +24VDC
(regulated) to “supply”
terminal (25mA limit)
• Position 3 = sends +5VDC
(regulated) to “supply”
terminal
*JP-26
• Position 1 = sends +24VDC
(unregulated) to “supply”
terminal (2.2A limit)
• Position 2 = sends +24VDC
(regulated) to “supply”
terminal (25mA limit)
• Position 3 = sends +5VDC
(regulated) to “supply”
terminal
MicroVission Controller • Operation and Service Manual • Emerson • 35391MV 1.0
2 – 9
Section 3 Main Screen
Overview
The Main screen is the rst screen displayed after pow­ering up the MicroVission Panel. The Main screen is de­signed as the starting point for all other screens in the system. The interface displays the values of all important setpoints that can help you to get the status of the com­pressor at a glance.
The Main screen is divided into different sections such as Top Status Bar, Bottom Status Bar, Parameters Bar and
the Splash Screen. See Figure 3-1.
Whenever you navigate to any other screen, Top Status
Bar, Bottom Status Bar and Parameters Bar will remain
visible so that operator can always view the critical infor­mation. The Splash screen is the only dynamic section. All navigation to any other screens will be performed through the Main screen.
Information of Loaded and
Unloaded Cylinders. Loaded Cylinders are shown in Green
Function but­tons to perform compressor operations
Parameters Panel
Bottom status bar with user and time information. It also
displays the Run Hours and the currently logged In user
Progress Bar dis­plays the Load percentage
Information Bars for Maintenance Activities
and Active Safety Messages.

Top Status Bar

I/O and Status
Values are displayed as per the settings in Conguration Screen Page 4. For
more information,
see Conguration
section
Menu button to open the Menu screen.
For more infor­mation, see the Menu Screen section.
Buttons for Basic Functions and
display help.
MicroVission Controller • Operation and Service Manual • Emerson • 35391MV 1.0
Figure 3-1. Main Screen
3 – 1
Section 3 Main Screen
Top Status Bar
The standard view of the status bar displays the follow­ing information. From Left to Right, bar shows Control
Method, Current Run Mode & the difference between the desired control setpoint and actual value of the pro-
cess variable. See Figure 3-2.
The Top Status Bar also displays the information that re­quires user attention or intervention. This information is displayed by highlighting it in different color or by ash­ing the additional information bars over standard status
bar view.
Standard Bar - Black
The Standard Bar with Black color indicates the condi-
tion where the compressor motor is not running.
Standard Bar - Green
The Standard Bar with Green color displays the informa­tion that the compressor motor is currently running. On the Top Status Bar, the information bar in green color appears with information ashed on it. The Top Status Bar and one or more information bars alternatively ap­pears in a sequence.
Information Bar - Black
The Information Bar with Black color displays the opera­tional modes, which are different than the normal run-
ning condition. For example, the load limit condition. The compressor is unable to completely load due to some setpoint conditions, like high motor current. This is notied on the information bar with black color..
Information Bar - Yellow
The Information Bar with Yellow color displays the alarm
conditions. Alarm conditions do not stop the compres-
sor, but these are alerts to the operator that if they do not take any corrective action, this can result in a com-
pressor trip.
Information Bar - Red
The Information Bar with Red color displays the infor­mation that the compressor motor was stopped due to the condition listed on the Information Bar. Compressor
trips are designed to protect the equipment and any personnel operating the equipment.
3 – 2
Figure 3-2. Top Status Bar
MicroVission Controller • Operation and Service Manual • Emerson • 35391MV 1.0
Section 3 Main Screen

Parameters Bar

The parameters bar displays the common operational parameters that you want to view to understand the current compressor status at a glance. In addition to dis­playing the information, it also provides the operator ac­cess to critical buttons such as “Stop” & “Start buttons apart from “Reset” & “Remote” buttons. See Figure 3-3.
Start Button
When pressed, a start dialog box that gives the operator
several run options will appear: Auto, Manual or Remote.
See Figure 3-4.
Stop Button
When pressed, stops the compressor in all cases.
Reset Button
When pressed, clears any current alarms, trips and status messages that may be displayed on the information bar.
NOTE
If the condition that created the alarm, trip or status
message still exits after pressing the “Reset” button, the
message will reappear on the information bar.
Remote Button
When pressed, activates the remote lock out option.
This is a safety feature that prevents any external devices from assuming control and starting the compressor. To
release the remote lock out, the operator must press the
“Start” button and then the “Remote” button when the start dialog box appears.
MicroVission Controller • Operation and Service Manual • Emerson • 35391MV 1.0
Figure 3-3. Parameters Bar
3 – 3
Section 3 Main Screen

Control Parameter Box

The parameter boxes provide updated data on several
key control parameters.
Control Setpoint
The top box displays the desired control setpoint that is
set in the Compressor Control Screen.
Suction Press
Displays the current Suction Pressure value.
Suction Temp
Displays the current Suction Temperature value.
Discharge Press
Displays the current Discharge Pressure value.
Discharge Temp
Displays the current Discharge Temperature value.
Oil Press Diff This is calculated as Oil Manifold Pressure minus Suction Pressure
Oil Filter Diff
This is calculated depending on the Oil Monitoring set­ting in the Conguration screen. When Oil Monitoring Setting is set as:
a. No Oil Filter Monitoring Oil Filter Differential is not calculated and value
displayed is NA.
b. Only Oil Filter In Oil Filter Differential is calculated as Filter Inlet
Pressure minus Oil Manifold Pressure. c. Oil Filter In and Oil Filter Out Oil Filter Differential is calculated as Filter Inlet
Pressure minus Filter Outlet Pressure.
Oil Temp
Displays the current Oil Temperature value.
Motor Amperage
Displays the current motor current.
Press Ratio
Displays ratio of Absolute Discharge Pressure to Abso­lute Suction Pressure.
3 – 4
Figure 3-4. Start Dialog Box
MicroVission Controller • Operation and Service Manual • Emerson • 35391MV 1.0
Section 3 Main Screen

Bottom Status Bar

The bottom status bar gives the operator easy access to some basic functions and information. See Figure 3-5.
Status Bars
There are two status bars. The rst status bar displays
the information about scheduled maintenance activi-
ties. The second status bar displays all types of currently active safety information like warnings, inhibits, alarms and trips in their respective colors. All warning messages can be collectively seen in a pop-up window. This pop­up is displayed when a warning condition is present and status bar for displaying warnings is pressed. See Figure
3-6. At the bottom of the status bars, operator can view the
following information from left to right:
Current User (if any is logged in)
• Compressor Run Hours
• Current Date
• Current Time
At the right side of the status bars, operator can view the following function buttons:
Maintenance Button
Pressing the Maintenance button will give the operator access to the maintenance charts and sign off tables.
User Access Button
This button takes the operator to the login screen to cre­ate additional users or log in.
Log off Button
Pressing the log off button logs off the current user if any are logged in.
Help Button
Pressing the help button takes the operator to the help
screen where the operation and service manual can be read and access to the program information is also pro-
vided.
MicroVission Controller • Operation and Service Manual • Emerson • 35391MV 1.0
Figure 3-5. Bottom Status Bar
3 – 5
Section 3 Main Screen
Figure 3-6. Warning Pop-up Window

Splash Screen

The Splash screen is the dynamic portion of the screen that will change as the operator navigates through the
MicroVission panel screens.
The Splash screen area displays the status of loaded and unloaded cylinders through image, progress bar from 0% to 100% via blue gray bar to indicate ratio of loaded cylinders to total no. of cylinders on compressor, the congurable parameters as per settings on Page 4 of Conguration screen and the Menu button. Operator can navigate to the Menu screen by pressing Menu but­ton which in turn will allow navigation to other screens on MicroVission. See Figure 3-7.
Figure 3-7. Splash Screen

Manual Run Mode Buttons

When operator runs compressor in Manual run mode,
two buttons “+” (plus) and “-” (minus) will be available on display along both sides of progress bar, See Figure 3-8. The ”+” button & “-“ button will allow the operator to increase and decrease compressor capacity respec­tively in pre-dened steps as per No. of Cylinders and No. of Unloaders settings of Conguration screen.
Figure 3-8. Manual Run
Mode Buttons
3 – 6
MicroVission Controller • Operation and Service Manual • Emerson • 35391MV 1.0

Section 4 Menu Screen

Overview

The Menu screen is the launching point to every other section of the MicroVission panel software. Every screen navigated to from this screen will return to the menu screen upon exiting, see Figure 3-1.

Navigation Buttons

Compressor Control
Navigates to the Compressor Control screen where the
operator can set the various compressor control param­eters.
Event List
Navigates to the Event List screen where the operator can view the systems events such as trips or alarms in descending chronological order.
Input/ Output States
Allows viewing of the live data of all analog and digital input and outputs. Also allows viewing of a “snapshot” of all analog and digital input and outputs at the time of
the last compressor fault event.
Alarms and Trips Navigates to the Alarms and Trips screen where the op­erator can set the various alarm and trip parameters.
Timers
Navigates to the Timers screen where the operator can
set the various time related parameters.
Instrument Calibration
Navigates to the Instrument Calibration screen where the operator can calibrate all the system sensors.
Conguration
Navigates to Conguration screen where the operator can congure all the initial system parameters.
Data Backup
Navigates to the Data Backup screen where the opera­tor can back up setpoints, conguration parameters and calibration settings to a USB memory device. In addition, this allows the restoration of previously saved database les.
Main
Navigates back to the Main screen.
MicroVission Controller • Operation and Service Manual • Emerson • 35391MV 1.0
Figure 4-1. Menu Screen
4 – 1
Section 5 Compressor Control
Overview
The Compressor Control screens is where an operator
can set majority of the compressor settings. These set­tings dene how the compressor will operate and re­spond to changing loads. The compressor control screen consists of several pages, but in order not to overwhelm the operator with options, many of the pages may not
be visible.
NOTE
How the compressor is setup in the conguration screen will determine what compressor control pages are
displayed.
It is important to note that there isn’t one correct way to set these parameters. Every application is different and requires the operator to tune these settings to achieve
the best operation.
For Suction Pressure Control, Process Temperature
Control & Discharge Pressure Control operator can use
two different set of values for compressor control. These
values are categorized as Setpoint 1 and Setpoint 2.
Active Control Mode decides which set of values will be used to control the compressors.

How Compressor Control Setpoint works?

The MicroVission will load and unload reciprocating compressor cylinders to maintain the control setpoint.
The control setpoint can be either of suction pressure control setpoint, process temperature control setpoint
or discharge pressure control setpoint depending on
what the operator has selected as the control mode.
The following gure shows how the MicroVission uses
the setpoints and offset values to load / unload compres-
sor in steps after specic time interval.
MicroVission Controller • Operation and Service Manual • Emerson • 35391MV 1.0
5 – 1
Section 5 Compressor Control

Suction Pressure Control

When the Active Control Mode is set to “Suction Pressure SP1” or “Suction Pressure SP2”’, the control setpoint is
Suction Pressure Control.
Pressure Control Setpoint
The suction pressure of the compressor to operate when
the compressor is running in Auto, Remote Auto, or
Direct I/O Auto run mode.
Load Offset
The offset value when added to the “Pressure Control” setpoint, determines the suction pressure for loading
the compressor.
Load Interval
The time interval for which control algorithm will wait between the steps while loading the compressor.
When the suction pressure of the compressor is equal to or greater than the “Pressure Control” setpoint plus the “Load Offset” value, the control algorithm loads one step
and then waits for the load interval time. Once the load
interval time is lapsed, the control algorithm will again
check if the suction pressure is equal to or greater than the “Pressure Control” setpoint plus the “Load Offset” value. If yes, MicroVission loads the next step.
Unload Offset
The offset value when removed from the “Pressure
Control” setpoint, determines the suction pressure for
unloading the compressor.
Unload Interval
The time interval for which control algorithm will wait between the steps while unloading the compressor.
When the suction pressure of the compressor is less than
or equal to the “Pressure Control” setpoint minus the “Unload Offset” value, the control algorithm unloads
one step and then waits for the unload interval time. Once the unload interval time is lapsed, the control al-
gorithm will again check if the suction pressure is less than or equal to the “Pressure Control” setpoint minus the “Unload Offset” value. If yes, MicroVission unloads
the next step.
5 – 2
Figure 5-1. Compressor Control Screen - Suction Pressure Control
MicroVission Controller • Operation and Service Manual • Emerson • 35391MV 1.0
Section 5 Compressor Control

Process Temperature Control

When the Active Control Mode is set to “Process Temperature SP1” or “Process Temperature SP2”’, the
control setpoint is Process Temperature Control.
Temp Control Setpoint
The process temperature of the compressor to operate
when the compressor is running in Auto, Remote Auto,
or Direct I/O Auto run mode.
Load Offset
The offset value when added to the “Temp Control” set­point, determines the process temperature for loading
the compressor.
Load Interval
The time interval for which control algorithm will wait between the steps while loading the compressor.
When the process temperature of the compressor is
equal to or greater than the “Temp Control” setpoint plus the “Load Offset” value, the control algorithm loads
one step and then waits for the load interval time. Once
the load interval time is lapsed, the control algorithm
will again check if the process temperature is equal to or greater than the “Temp Control” setpoint plus the “Load Offset” value. If yes, MicroVission loads the next step.
Unload Offset
The offset value when removed from the “Temp Control”
setpoint, determines the process temperature for un-
loading the compressor.
Unload Interval
The time interval for which control algorithm will wait between the steps while unloading the compressor.
When the process temperature of the compressor is less
than or equal to the “Temp Control” setpoint minus the “Unload Offset” value, the control algorithm unloads
one step and then waits for the unload interval time. Once the unload interval time is lapsed, the control al-
gorithm will again check if the process temperature is less than or equal to the “Temp Control” setpoint minus the “Unload Offset” value. If yes, MicroVission unloads
the next step.
Figure 5-2. Compressor Control Screen - Process Temperature Control
MicroVission Controller • Operation and Service Manual • Emerson • 35391MV 1.0
5 – 3
Section 5 Compressor Control

Discharge Pressure Control

When the Active Control Mode is set to “Discharge Pres­sure SP1” or “Discharge Pressure SP2”’, the control set­point is Discharge Pressure Control.
Pressure Control Setpoint
The discharge pressure of the compressor to operate when the compressor is running in Auto, Remote Auto,
or Direct I/O Auto run mode.
Load Offset
The offset value when removed from the “Pressure Control” setpoint, determines the discharge pressure for loading the compressor.
Load Interval
The time interval for which control algorithm will wait between the steps while loading the compressor.
When the discharge pressure of the compressor is less than or equal to the “Pressure Control” setpoint minus the “Load Offset” value, the control algorithm loads one
step and then waits for the load interval time. Once the
load interval time is lapsed, the control algorithm will
again check if the discharge pressure is less than or equal to the “Pressure Control” setpoint minus the “Load Off­set” value. If yes, MicroVission loads the next step.
Unload Offset
The offset value when added to the “Pressure Control” setpoint, determines the discharge pressure for unload­ing the compressor.
Unload Interval
The time interval for which control algorithm will wait between the steps while unloading the compressor.
When the discharge pressure of the compressor is equal to or greater than the “Pressure Control” setpoint plus the “Unload Offset” value, the control algorithm un-
loads one step and then waits for the unload interval time. Once the unload interval time is lapsed, the con-
trol algorithm will again check if the discharge pressure is equal to or greater than the “Pressure Control” set­point plus the “Unload Offset” value. If yes, MicroVission
unloads the next step.
5 – 4
Figure 5-3. Compressor Control Screen - Discharge Pressure Control
MicroVission Controller • Operation and Service Manual • Emerson • 35391MV 1.0
Section 5 Compressor Control

Auto Cycle

The auto-cycle setpoints dene the control points in which the compressor will automatically cycle on and off when placed into “Auto” run mode. These setpoints can be “enabled” or “disabled” using the check box. The au­to-cycle function will operate only in local “Auto” mode and Direct I/O “Remote Auto” mode. If the auto cycle feature is enabled while running in any other remote mode, the function will simply be ignored.
Auto Cycle Suction Pressure
• Enable: Enables the Auto cycle control. Uncheck
the box to disable the Auto cycle setpoints.
• Start Pressure: When the suction pressure is equal to or greater than this setpoint, the compressor will
start.
• Start Delay: Before the compressor start, there is a
delay for the set time to ensure that suction pres­sure remains equal to or greater than the “Start
Pressure”.
• Stop Pressure: When the suction pressure is less
than or equal to this setpoint, the compressor will
stop.
• Stop Delay: Before the compressor stop, there is
a delay for the set time to ensure that the suction pressure remains less than or equal to the “Stop
Pressure”.
Auto Cycle Process Temperature
• Enable: Enables the Auto cycle control. Uncheck
the box to disable the Auto cycle setpoints.
• Start Temperature: When the process temperature
is equal to or greater than this setpoint, the com­pressor will start.
• Start Delay: Before the compressor start, there is a
delay for the set time to ensure that process tem­perature remains equal to or greater than the “Start
Temperature”.
• Stop Pressure: When the process temperature is
less than or equal to this setpoint, the compressor
will stop.
• Stop Delay: Before the compressor stop, there is
a delay for the set time to ensure that the process temperature remains less than or equal to the “Stop
Temperature”.
Figure 5-4. Compressor Control Screen - Auto Cycle (Suction Pressure)
MicroVission Controller • Operation and Service Manual • Emerson • 35391MV 1.0
5 – 5
Section 5 Compressor Control
Auto Cycle Discharge Pressure
• Enable: Enables the Auto cycle control. Uncheck
the box to disable the Auto cycle setpoints.
• Start Pressure: When the discharge pressure is less than or equal to this setpoint, the compressor will
start.
• Start Delay: Before the compressor start, there
is a delay for the set time to ensure that discharge pressure remains less than or equal to the “Start
Pressure”.
• Stop Pressure: When the discharge pressure is equal to or greater than this setpoint, the compres-
sor will stop.
• Stop Delay: Before the compressor stop, there is a
delay for the set time to ensure that the discharge pressure remains equal to or greater than the “Stop
Pressure”.
5 – 6
Figure 5-5. Compressor Control Screen – Auto Cycle (Process Temperature)
MicroVission Controller • Operation and Service Manual • Emerson • 35391MV 1.0
Section 5 Compressor Control
Figure 5-6. Compressor Control Screen - Auto Cycle (Discharge Pressure)
MicroVission Controller • Operation and Service Manual • Emerson • 35391MV 1.0
5 – 7
Section 5 Compressor Control

Active Control Mode

This drop-down box gives the operator the ability to change the type of Active Control Mode such as Succion Pressure, Process Temperature or Discharge Pressure.
The operator can also switch from Setpoint 1 (SP1) and Setpoint 2 (SP2) for each control method. The options
for drop-down box will depend on the number and type of control selected in the conguration screen.

Load Limiting

The stop load and force unload feature’s primary pur­pose is an attempt to prevent the compressor from trip-
ping off due to instrument reading. For example, if the suction pressure drops very low, the compressor will trip off for safety reasons. However, the stop load and force unload algorithm recognizes the potential trip and ei­ther stops the compressor from loading up or even un­loads the compressor step-by-step to prevent the trip.
I/O Based Setpoint Control
This checkbox when enabled, monitors the Remote
Setpoint #1/#2 Digital Input (10th Digital Channel on Multi IO Board). When Compressor is running in Auto /
Remote(Auto) run mode, the selection of Active Control Setpoint depends upon the state of Remote Setpoint
#1/#2 Digital Input. When Remote Setpoint #1/#2 Digital Input is Energized, Active Control Mode will be Setpoint 2. When Remote Setpoint #1/#2 Digital Input is De-Energized, Active Control Mode will be Setpoint 1.
NOTE
This checkbox will be displayed only when “Direct I/O” is
disabled in Conguration Screen.
Stop Load Setpoints
High Suction Pressure
When the suction pressure value is equal to or greater than this setpoint, algorithm will not allow loading of the compressor. However, if the suction pressure value drops below this setpoint, algorithm will allow loading of the compressor.
High Discharge Pressure
When the discharge pressure value is equal to or greater than this setpoint, algorithm will not allow loading of the compressor. However, if the discharge pressure value drops below this setpoint, algorithm will allow loading of the compressor.
Figure 5-7. Compressor Control Screen – Active Control Mode - I/O Based Setpoint Control
5 – 8
MicroVission Controller • Operation and Service Manual • Emerson • 35391MV 1.0
Section 5 Compressor Control
Low Suction Pressure
When the suction pressure value is equal to or less than this setpoint, algorithm will not allow loading
of the compressor. However, if the suction pressure
value exceeds this setpoint, algorithm will allow loading of the compressor.
High Motor Current
When the motor current value is equal to or greater than this setpoint, algorithm will not allow loading
of the compressor. However, if the motor current
value drops below this setpoint, algorithm will allow loading of the compressor.
Force Unload Setpoints
High Suction Pressure
• When the suction pressure value is equal to or great­er than this setpoint, algorithm will unload the com­pressor by one step. Algorithm will continue unload­ing the compressor step-by-step to minimum load
until the suction pressure value drops below this setpoint.
High Discharge Pressure
When the discharge pressure value is equal to or greater than this setpoint, algorithm will unload the compressor by one step. Algorithm will continue un­loading the compressor step-by-step to minimum load until the discharge pressure value drops below
this setpoint.
Low Suction Pressure
• When the suction pressure value is equal to or less than this setpoint, algorithm will unload the com­pressor by one step. Algorithm will continue un­loading the compressor step-by-step to minimum
load until the suction pressure value exceeds this setpoint.
High Motor Current
• When the motor current value is equal to or greater than this setpoint, algorithm will unload the com­pressor by one step. Algorithm will continue un­loading the compressor step-by-step to minimum
load until the motor current value drops below this setpoint.
Unload Timer
This is the time duration that force unload algo­rithm will use while unloading each step during
the force unload condition. For example, when the
suction pressure value is equal to or greater than the “High Suction Pressure” Force Unload setpoint, the algorithm will unload one step and wait for the time as dened by this setpoint. Once the time set is lapsed, the algorithm will check again if the suction pressure value is equal to or greater than the “High Suction Pressure” Force Unload setpoint. If yes, the algorithm will unload one more step.
Figure 5-8. Compressor Control Screen - Load Limiting
MicroVission Controller • Operation and Service Manual • Emerson • 35391MV 1.0
5 – 9
Section 5 Compressor Control

Oil Control

This setpoint denes how the MicroVission will manage
the crankcase’s oil. When the compressor is used in cold climatic conditions, it might be possible that compres­sor does not start due to low crankcase oil temperature.
Oil Crankcase Heater Temperature
• When the oil temperature falls below this setpoint,
the oil heater (7th Digital Channel on Multi IO Board)
will turn ON. Note, there is a 2°F differential associ­ated with this setpoint. For example, when set at 100 °F, the oil heater will turn ON at 98 °F and turn OFF at 102 °F.
5 – 10
Figure 5-9. Compressor Control Screen - Oil Control
MicroVission Controller • Operation and Service Manual • Emerson • 35391MV 1.0

Section 6 • Alarms and Trips

Overview

The Alarms and Trips screen provides the options to view
and adjust settings for compressor safety and alarm settings.

Warnings

The MicroVission uses Warnings to notify the operator of the parameters that might inhibit the compressor when started. Warnings are monitored only when com­pressor is not running. Unless other specied, Warnings use alarm setpoints for detection and message genera­tion. The Warning condition occurs when the value of a parameter drops below or rises above the congured alarm setpoint when the compressor is not running.
All warning messages can be collectively seen in a pop­up window. This pop-up is displayed when a warning
condition is present and the bottom status bar is pressed.
When the warning condition earlier present is cleared or not anymore present, the corresponding warning mes­sage will be automatically removed from bottom status
bar.

Alarms

The MicroVission uses Alarms to notify the operator of running parameters that if left unchecked could result in the compressor shutting down due to a trip. Alarms are only active when compressor is running. The Alarm con-
dition occurs if the value of a parameter drops below or
rises above the congured Alarm setpoint for a continu­ous delay time (default 5 seconds).
Alarms are shown in a Yellow color banner
on the top and the bottom status bars

Trips

Trips are the conditions that exceed the safety limits of the compressor or refrigeration system and stops the compressor. Trips are only active when compressor is running. The Trip condition occurs if the value of a pa­rameter drops below or rises above the congured Trip setpoint for continuous delay time (default 5 seconds). During Trip condition, compressor run mode will get changed to idle from running.
Warnings are shown in an Orange color banner
on the bottom status bar

Inhibits

The MicroVission uses start Inhibits to prevent the com-
pressor from starting to protect the compressor and the refrigeration system. Inhibits are only active during Pre­Start condition. While starting the compressor, inhibits are checked rst before the motor is started. Failed start due to an inhibit do not count toward any of the anti-re­cycle timer including Hot Starts. Unless other specied,
inhibits use alarm setpoints to abort compressor start
and message generation. The Inhibit condition occurs if
the value of a parameter drops below or rises above the
congured alarm setpoint during the compressor start.
Inhibits are shown in a Red color banner
on the top and bottom status bars
Trips are shown in a Red color banner
on the top and bottom status bars
NOTE
When more than one safety condition is active/present, Safety message for each condition (Except Warning) will
get displayed on Top Status Bar in rotating manner.

Freeze Screens

Trips also trigger the input/output screen to take snap­shot of all input and output values as Freeze 1 screen.
The Freeze screens are very useful as a troubleshooting
tool for the operator. Refer to Input/Output States sec-
tion for a typical Freeze Data (Trip) screen.

Logging – Event List

All Inhibits, Alarm and Trip conditions are logged in the Event List so the operator can get the complete opera­tional history. The operator can access the Event List
from the Menu screen.
MicroVission Controller • Operation and Service Manual • Emerson • 35391MV 1.0
6 – 1
Section 6 • Alarms and Trips

Alarms & Trips setpoints

This screen provides three different pages to congure Alarm and Trip setpoints along with corresponding delay tabs for conguration of delay time.
6 – 2
Figure 6-1. Alarms & Trips Setpoints (Page 1)
MicroVission Controller • Operation and Service Manual • Emerson • 35391MV 1.0
Section 6 • Alarms and Trips
Figure 6-2. Alarms & Trips Setpoints (Page 2)
Figure 6-3. Alarms & Trips Setpoints (Page 3)
MicroVission Controller • Operation and Service Manual • Emerson • 35391MV 1.0
6 – 3
Section 6 • Alarms and Trips

MicroVission Safety Messages

The following table lists all possible Warning, Inhibit, Alarm and Trip Messages generated by MicroVission while monitoring safety parameters.
Warnings Inhibits Alarms Trips
Not Running (Idle) Pre-Start Running Running
Low Sucon Pressure:
Below Messages will be displayed on Main screen when Sucon Pressure value drops below congured set­points. Refer Figure 6- 1 for Alarm & Trip setpoints.
There are two dierent set of Alarm & Trip setpoints which will be acve depending on Acve Control Mode
selected from Compressor Control screen.
Low Sucon Pressure
Warning
Sucon Pressure <= Low
Sucon Pressure Alarm
Setpoint 1 / Setpoint 2
High Discharge Pressure:
Low Sucon Pressure Inhibit
Sucon Pressure <= Low Sucon
Pressure Alarm Setpoint 1 / Set-
point 2
Low Sucon Pressure
Alarm
Sucon Pressure <=
Low Sucon Pressure
Alarm Setpoint 1 /
Setpoint 2
Low Sucon Pressure Trip
Sucon Pressure <= Low
Sucon Pressure Alarm
Setpoint 1 / Setpoint 2
Below Messages will be displayed on Main Screen when Discharge Pressure value rises above congured set­points. Refer Figure 6- 1 for Alarm & Trip setpoints.
There are two dierent set of Alarm & Trip setpoints which will be acve depending on Acve Control Mode
selected from Compressor Control screen.
High Discharge Pressure
Warning
Discharge Pressure >=
High Discharge Pressure
Alarm Setpoint 1 / Set-
point 2
High Discharge Pressure Inhibit
Discharge Pressure >= High Dis-
charge Pressure Alarm Setpoint 1 /
Setpoint 2
High Discharge Pres-
sure Alarm
Discharge Pressure >=
High Discharge Pres-
sure Alarm Setpoint 1
/ Setpoint 2
High Discharge Pressure
Trip
Discharge Pressure >=
High Discharge Pressure
Trip Setpoint 1 / Setpoint
2
Low Process Temperature:
Below Messages will be displayed on Main Screen when Process Temperature value drops below congured
setpoints. Refer Figure 6- 1 for Alarm & Trip setpoints.
There are two dierent set of Alarm & Trip setpoints which will be acve depending on Acve Control Mode
selected from Compressor Control screen.
These safees will be only acve when Acve Control Mode selected from Compressor Control screen is “Pro­cess Temperature SP1” or “Process Temperature SP2”.
Low Process Temperature
Warning
Process Temperature <=
Low Process Tempera-
ture Alarm Setpoint 1 /
Setpoint 2
Low Process Temperature Inhibit
Process Temperature <= Low Pro-
cess Temperature Alarm Setpoint 1
/ Setpoint 2
Low Process Tempera-
ture Alarm
Process Tempera-
ture <= Low Process
Temperature Alarm
Setpoint 1 / Setpoint 2
Low Process Temperature
Trip
Process Temperature <=
Low Process Temperature
Trip Setpoint 1 / Setpoint
2
6 – 4
MicroVission Controller • Operation and Service Manual • Emerson • 35391MV 1.0
Section 6 • Alarms and Trips
Warnings Inhibits Alarms Trips
Not Running (Idle) Pre-Start Running Running
High Process Temperature:
Below Messages will be displayed on Main Screen when Process Temperature value rises below congured
setpoints. Refer Figure 6- 1 for Alarm setpoints.
There are two dierent set of Alarm setpoints which will be acve depending on Acve Control Mode selected
from Compressor Control screen.
These safees will be only acve when Acve Control Mode selected from Compressor Control is “Process Tem­perature SP1” or “Process Temperature SP2”.
Low Sucon Temperature:
High Process
Temperature Alarm
Process Tempera-
ture >= High Process
Temperature Alarm
Setpoint 1 / Setpoint 2
Below Messages will be displayed on Main Screen when Sucon Temperature value drops below congured
setpoints. Refer Figure 6- 2 for Alarm & Trip setpoints.
Low Sucon Temperature
Warning
Sucon Temperature <=
Low Sucon Temperature
Alarm Setpoint
Low Sucon Temperature Inhibit
Sucon Temperature <= Low Suc-
on Temperature Alarm Setpoint
Low Sucon Tempera-
ture Alarm
Sucon Tempera-
ture <= Low Sucon
Temperature Alarm
Setpoint
Low Sucon Temperature
Trip
Sucon Temperature <=
Low Sucon Temperature
Trip Setpoint
High Discharge Temperature:
Below Messages will be displayed on Main Screen when Discharge Temperature value rises above congured
setpoints. Refer Figure 6- 2 for Alarm & Trip setpoints.
High Discharge Temperature Alarm & High Discharge Temperature Trip safees will be monitored only once
High Discharge Temp Bypass Timer is lapsed.
High Discharge
Temperature Warning
Discharge Temperature >=
High Discharge Tempera-
ture Alarm Setpoint
High Discharge Temperature Inhibit
Discharge Temperature >= High Dis­charge Temperature Alarm Setpoint
High Discharge
Temperature Alarm
Discharge Tempera-
ture >= High Discharge
Temperature Alarm
Setpoint
High Discharge
Temperature Trip
Discharge Temperature >= High Discharge Tem-
perature Trip Setpoint
MicroVission Controller • Operation and Service Manual • Emerson • 35391MV 1.0
6 – 5
Section 6 • Alarms and Trips
Low Crankcase Oil Temperature - Start:
Below Messages will be displayed on Main screen when Oil Temperature value drops below congured set­points. Refer Figure 6- 2 for Alarm & Trip setpoints.
These safees will be only acve when Crankcase Oil Temp Changeover Timer is running.
Warnings Inhibits Alarms Trips
Not Running (Idle) Pre-Start Running Running
Low Crankcase Oil Tem­perature Start Warning
Oil Temperature <= Low
Crankcase Oil Tempera-
ture – Start Alarm Set-
point
Low Crankcase Oil Temperature - Run:
Below Messages will be displayed on Main screen when Oil Temperature value drops below congured set­points. Refer Figure 6- 2 for Alarm & Trip setpoints.
These safees will be only acve once Crankcase Oil Temp Changeover Timer is lapsed.
Low Crankcase Oil Temperature
Start Inhibit
Oil Temperature <= Low Crankcase
Oil Temperature – Start Alarm
Setpoint
Low Crankcase Oil
Temperature Alarm
Oil Temperature <=
Low Crankcase Oil
Temperature – Start
Alarm Setpoint
Low Crankcase Oil
Temperature Alarm
Oil Temperature <=
Low Crankcase Oil
Temperature – Run
Alarm Setpoint
Low Crankcase Oil Tem-
perature Trip
Oil Temperature <= Low
Crankcase Oil Tempera-
ture – Start Trip Setpoint
Low Crankcase Oil Tem-
perature Trip
Oil Temperature <= Low
Crankcase Oil Tempera-
ture – Run Trip Setpoint
High Crankcase Oil Temperature:
Below Messages will be displayed on Main screen when Oil Temperature value rises above congured setpoints.
Refer Figure 6- 2 for Alarm & Trip setpoints.
High Crankcase Oil Tem-
perature Warning
Oil Temperature >= High
Crankcase Oil Tempera-
ture Alarm Setpoint
6 – 6
High Crankcase Oil Temperature
Inhibit
Oil Temperature >= High Crankcase
Oil Temperature Alarm Setpoint
MicroVission Controller • Operation and Service Manual • Emerson • 35391MV 1.0
High Crankcase Oil
Temperature Alarm
Oil Temperature >=
High Crankcase Oil
Temperature Alarm
Setpoint
High Crankcase Oil Tem-
perature Trip
Oil Temperature >= High
Crankcase Oil Tempera-
ture Trip Setpoint
Section 6 • Alarms and Trips
Warnings Inhibits Alarms Trips
Not Running (Idle) Pre-Start Running Running
Low Oil Pressure Di.:
Below Messages will be displayed on Main Screen when Oil Pressure Di. value drops below congured set­points. Refer Figure 6-3 for Alarm & Trip setpoints.
These safees will be only acve once Oil Pressure Bypass Timer is lapsed.
Oil Pressure Calculaon is as follows: Oil Pressure = Oil Manifold Pressure – Sucon Pressure
Low Oil Pressure Di
Alarm
Oil Pressure Di. <=
Low Oil Pressure Di.
Alarm Setpoint
Low Oil Pressure Di Trip
Oil Pressure Di. <= Low
Oil Pressure Di. Trip
Setpoint
High Filter Di. Pressure - Start:
Below Messages will be displayed on Main screen when Filter Di. Pressure value rises above congured set­points. Refer Figure 6- 3 for Alarm & Trip setpoints.
These safees will be only acve if below two condions are met:
When Oil Monitoring opon selected in Conguraon Screen is “Oil Filter In & Oil Filter Out” or “Only Oil
1) Filter In”.
2)
When Filter Di. Pressure Changeover Timer is running.
Filter Di. Pressure Calculaon for Oil Monitoring opons, “Oil Filter In & Oil Filter Out” & “Only Oil Filter In” will be respecvely as below:
Filter Di. Pressure = Oil Filter Inlet Pressure – Oil Filter Outlet Pressure.
a)
b)
Filter Di. Pressure = Oil Filter Inlet Pressure – Oil Manifold Pressure.
High Filter Di Pressure
Start Warning
Filter Di. Pressure >=
High Filter Di. Pressure –
Start Alarm Setpoint
MicroVission Controller • Operation and Service Manual • Emerson • 35391MV 1.0
High Filter Di Pressure Start
Inhibit
Filter Di. Pressure >= High Filter
Di. Pressure – Start Alarm Set-
point
High Filter Di Pres-
sure Alarm
Filter Di. Pressure >=
High Filter Di. Pres-
sure – Start Alarm
Setpoint
High Filter Di Pressure
Trip
Filter Di. Pressure >=
High Filter Di. Pressure –
Start Trip Setpoint
6 – 7
Section 6 • Alarms and Trips
Warnings Inhibits Alarms Trips
Not Running (Idle) Pre-Start Running Running
High Filter Di. Pressure - Run:
Below Messages will be displayed on Main screen when Filter Di. Pressure value rises above congured set­points. Refer Figure 6- 3 for Alarm & Trip setpoints.
These safees will be only acve if below two condions are met:
1)
When Oil Monitoring opon selected in Conguraon Screen is “Oil Filter In & Oil Filter Out” or “Only Oil
Filter In”.
When Filter Di. Pressure Changeover Timer is lapsed.
2)
Filter Di. Pressure Calculaon for Oil Monitoring opons, “Oil Filter In & Oil Filter Out” & “Only Oil Filter In” will be respecvely as below:
a)
Filter Di. Pressure = Oil Filter Inlet Pressure – Oil Filter Outlet Pressure
b)
Filter Di. Pressure = Oil Filter Inlet Pressure – Oil Manifold Pressure
High Filter Di
Pressure Alarm
Filter Di. Pressure
>= High Filter Di.
Pressure – Run Alarm
Setpoint
High Filter Di Pressure
Trip
Filter Di. Pressure >=
High Filter Di. Pressure –
Run Trip Setpoint
High Motor Amps:
Below Messages will be displayed on Main Screen when Motor Amps value rises above congured setpoints.
Refer Figure 6- 3 for Alarm setpoints.
These safees will be only acve once High Motor Amps Bypass Timer is lapsed.
High Motor Amps
Alarm
Motor Amps >= High
Motor Amps Alarm
Setpoint
High Motor Amps Trip
Motor Amps >= High Mo-
tor Amps Trip Setpoint
High Discharge #2 Pressure:
Below Messages will be displayed on Main Screen when Discharge #2 Pressure value rises above congured
setpoints. Refer Figure 6- 1 for Alarm & Trip setpoints.
There are two dierent set of Alarm & Trip setpoints which will be acve depending on Acve Control Mode
selected from Compressor Control screen.
These safees will be only acve when No. of Cylinders set in Conguraon screen is “12 cyl” or “16 cyl”.
High Discharge 2 Pressure
Warning
Discharge #2 Pressure >= High Discharge Pres­sure Alarm Setpoint 1 /
Setpoint 2
6 – 8
High Discharge 2 Pressure Inhibit
Discharge #2 Pressure >= High
Discharge Pressure Alarm Setpoint
1 / Setpoint 2
MicroVission Controller • Operation and Service Manual • Emerson • 35391MV 1.0
High Discharge 2
Pressure Alarm
Discharge #2 Pressure
>= High Discharge
Pressure Alarm Set-
point 1 / Setpoint 2
High Discharge 2 Pressure
Trip
Discharge #2 Pressure >=
High Discharge Pressure
Trip Setpoint 1 / Setpoint
2
Section 6 • Alarms and Trips
Warnings Inhibits Alarms Trips
Not Running (Idle) Pre-Start Running Running
High Discharge #2 Temperature:
Below Messages will be displayed on Main Screen when Discharge #2 Temperature value rises above congured
setpoints. Refer Figure 6- 2 for Alarm & Trip setpoints.
These safees will be only acve if below two condions are met:
When No. of Cylinders set in Conguraon screen is “12 cyl” or “16 cyl”.
1)
2)
High Discharge Temp Bypass Timer is lapsed.
High Discharge 2
Temperature Warning
Discharge #2 Temperature
>= High Discharge Tem-
perature Alarm Setpoint
Discharge #2 Temperature >= High
High Discharge 2
Temperature Inhibit
Discharge Temperature Alarm
Setpoint
High Discharge 2
Temperature Alarm
Discharge #2 Tempera-
ture >= High Discharge
Temperature Alarm
Setpoint
High Discharge 2
Temperature Trip
Discharge #2 Tempera-
ture >= High Discharge
Temperature Trip Set-
point
Remote Comm. Time-out:
Below Messages will be displayed on Main Screen when there is no remote communicaon to the MicroVission for me as set in Compressor Failure Detect Timer. Refer Timers screen for setpoint.
Remote Comm. Time-out Alarm will be only monitored if “Revert to Local Control” opon is set for On Commu­nicaon Failure seng in Conguraon screen.
Remote Comm. Time-out Trip will be only monitored if “Stop Compressor with Trip” opon is set for On Com­municaon Failure seng in Conguraon screen.
Remote Comm Time
out Alarm
Remote Comm. Inac-
ve Time >= Compres-
sor Failure Detect
Timer
Remote Comm Time out
Trip
Remote Comm. Inacve
Time >= Compressor Fail-
ure Detect Timer
Compressor Interlock:
Below message will be displayed on Main Screen in following cases:
1)
When Motor Auxiliary Contact Fails to Close during Compressor Start.
2)
When Motor Auxiliary Contact Opens when Compressor is Running.
Compressor Interlock Inhibit Compressor Interlock Trip
Motor Auxiliary Contact Fails to
Close when Compressor is Starng
MicroVission Controller • Operation and Service Manual • Emerson • 35391MV 1.0
Motor Auxiliary Contact
Opens when Compressor
is Running
6 – 9
Section 6 • Alarms and Trips
Warnings Inhibits Alarms Trips
Not Running (Idle) Pre-Start Running Running
High Level Shutdown:
Below messages will be displayed when power is removed from the input module.
High Level Shutdown switch is wired to the digital input normally closed. Usually connected to a oat switch on a vessel containing liquid refrigerant. In case of mulple switches, any open switch will generate a relevant mes­sage depending on compressor operang mode.
When “Idle Time Trip” checkbox is enabled in Conguraon screen, High Level Shutdown Trip will be monitored
even when compressor is idle.
High Level Shutdown
Warning
High Level Shutdown Digi-
tal Input is Acve Low
High Level Shutdown Inhibit High Level Shutdown Trip
High Level Shutdown Digital Input
is Acve Low during Compressor
Start
High Level Shutdown
Digital Input is Acve
Low while Compressor is
Running
Starter:
Below message will be displayed on Main Screen when Motor Auxiliary Contact Fails to Open aer Compressor
shutdown.
Starter Shutdown Trip
Motor Auxiliary Contact is
Closed aer Compressor
is Stopped
False Start:
Below message will be displayed on Main screen in following cases when Compressor is Idle.
1)
Motor Auxiliary Contact is Closed.
Measured Motor Current Value is greater than Maximum Load Rang in Amperes.
2)
6 – 10
MicroVission Controller • Operation and Service Manual • Emerson • 35391MV 1.0
False Start
Motor Auxiliary Contact is
Closed
OR
Motor Amperage > 20 %
Maximum Amps
Section 6 • Alarms and Trips
Warnings Inhibits Alarms Trips
Not Running (Idle) Pre-Start Running Running
IO Comm.:
Below message will be displayed on Main Screen when there is problem in Serial Modbus Communicaon be­tween IO Boards & MicroVission SBC Board.
Low Oil Level:
Below messages will be displayed on Main Screen if Low Oil Level Digital Input is found Acve Low.
Low Oil Level Trip will be only acve when “Oil Level Trip” checkbox is enabled in Conguraon screen.
Low Oil Level Warning Low Oil Level Inhibit Low Oil Level Alarm Low Oil Level Trip
I/O Comm Trip
Problem found in Com-
municaon between SBC
& IO Boards
Low Oil Level Digital
Low Oil Level Digital Input
is Acve Low
Low Discharge Pressure:
Below Messages will be displayed on Main Screen when there is a failure while reading Discharge Pressure
value from Measuring Instrument. There is no user congured setpoint.
Low Discharge Pressure
Warning
Discharge Pressure <=
-66.5 Psig
Low Discharge Temperature:
Below Messages will be displayed on Main Screen when there is a failure while reading Discharge Temperature
value from Measuring Instrument. There is no user congured setpoint.
Low Discharge Tempera-
ture Warning
Low Oil Level Digital Input is Acve
Low
Low Discharge Pressure Inhibit
Discharge Pressure <= -66.5 Psig
Low Discharge Temperature Inhibit
Input is Acve Low >=
Low Oil Level Alarm
Delay Time
Low Oil Level Digital Input
is Acve Low >= Low Oil
Level Trip Delay Time
Low Discharge Pressure
Trip
Discharge Pressure <=
-66.5 Psig
Low Discharge Tempera-
ture Trip
Discharge Temperature <=
-100 °F
MicroVission Controller • Operation and Service Manual • Emerson • 35391MV 1.0
Discharge Temperature <= -100 °F
Discharge Temperature
<= -100 °F
6 – 11
Section 6 • Alarms and Trips
Warnings Inhibits Alarms Trips
Not Running (Idle) Pre-Start Running Running
Low Oil Filter In Pressure:
Below Messages will be displayed on Main Screen when there is a failure while reading Filter Inlet Pressure
value from Measuring Instrument. There is no user congured setpoint.
Low Oil Filter In Pressure
Warning
Filter Inlet Pressure <=
-66.5 Psig
Low Oil Filter Out Pressure:
Below Messages will be displayed on Main Screen when there is a failure while reading Filter Outlet Pressure
value from Measuring Instrument. There is no user congured setpoint.
Low Oil Filter Out Pressure Warning
Filter Outlet Pressure <=
-66.5 Psig
Low Discharge #2 Pressure:
Below Messages will be displayed on Main Screen when there is a failure while reading Discharge 2 Pressure
value from Measuring Instrument. There is no user congured setpoint.
These safees will be only acve when No. of Cylinders set in Conguraon screen is “12 cyl” or “16 cyl”.
Low Discharge 2 Pressure
Warning
Low Oil Filter In Pressure Inhibit
Filter Inlet Pressure <= -66.5 Psig
Low Oil Filter Out Pressure Inhibit
Filter Outlet Pressure <= -66.5 Psig
Low Discharge 2 Pressure Inhibit
Low Oil Filter In Pressure
Trip
Filter Inlet Pressure <=
-66.5 Psig
Low Oil Filter Out
Pressure Trip
Filter Outlet Pressure <=
-66.5 Psig
Low Discharge 2 Pressure
Trip
Discharge 2 Pressure <=
-66.5 Psig
Low Discharge #2 Temperature:
Below Messages will be displayed on Main Screen when there is a failure while reading Discharge 2 Tempera-
ture value from Measuring Instrument. There is no user congured setpoint.
These safees will be only acve when No. of Cylinders set in Conguraon screen is “12 cyl” or “16 cyl”.
Low Discharge 2
Temperature Warning
Discharge 2 Temperature
<= -100 °F
6 – 12
Discharge 2 Pressure <= -66.5 Psig
Low Discharge 2 Temperature
Inhibit
Discharge 2 Temperature <= -100 °F
MicroVission Controller • Operation and Service Manual • Emerson • 35391MV 1.0
Discharge 2 Pressure <=
-66.5 Psig
Low Discharge 2
Temperature Trip
Discharge 2 Temperature
<= -100 °F

Section 7 Timers

Overview

The Timers screen allows the operator to view and adjust
timer settings associated with the compressor opera­tion. There are different types of timers that the opera-
tor should be aware of listed below. For Timers Screen
pages, see Figures 7-1 & 7-2.
Changeover
The changeover timers will change from one type con­trol to another once the compressor has started and then the time has expired.
Bypass
The bypass timers prevent certain alarm and trip checks from occurring until the compressor has started and
then the time has expired.

Timer Setpoints

Following are the setpoints that the operator can cong­ure on MicroVission.
Load Increase Start Delay
At compressor startup, the compressor capacity will be
at minimum load for this time. This is to allow compres-
sor and system conditions to stabilize. After this timer expires, the system modulates the compressor capacity according to the system demands.
Compressor Interlock Bypass
Once the MicroVission has sent a command to the com-
pressor starter to start, it expects the return signal. This timer denes how much time to wait for that signal be­fore setting a trip condition.
Delays
The delay timers require the condition to occur for the specied amount of time.
Timers
A general timer requiring the time to be expire before
the listed event can occur.
Low Oil Pressure Diff. Bypass
This is the time for which the “Low Oil Pressure” safety
setpoints will remain inactive. After the timer has ex-
pired, the “Low Oil Pressure” safety setpoints will be­come active and safeties related to “Low Oil Pressure” will get monitored.
Figure 7-1. Timers Screen (Page 1)
MicroVission Controller • Operation and Service Manual • Emerson • 35391MV 1.0
7 – 1
Section 7 Timers
Low Crankcase Oil Temperature Changeover
This is the time for which the “Low Crankcase Oil Temperature – Start” safety setpoints will remain ac­tive. After the timer has expired, the “Low Crankcase Oil Temperature – Start” safety setpoints will become inactive and the “Low Crankcase Oil Temperature – Run” safety setpoints will become active.
High Discharge Temperature Bypass
This is the time for which the “High Discharge Temperature” safety setpoints will remain inactive. After the timer has expired, the “High Discharge Temperature” safety setpoints will become active and safeties related to “High Discharge Temperature” will get monitored.
High F ilter Diff. Pressure Changeover
This is the time for which the “High Filter Diff. Pressure – Start” safety setpoints will remain active. After the timer has expired, the “High Filter Diff. Pressure – Start” safety setpoints will become inactive and the “High Filter Diff. Pressure – Run” safety setpoints will become active.
High Motor Amps Bypass
Starting motors can typically pull much more than cur­rent than its rated full load amps for a short time. This
timer ignores that sudden inrush of current for the speci­ed time.
Communication Failure Detect Timer
This timer forces the compressor to wait for the set time
before displaying “Remote Comm Timeout” Alarm or “Remote Comm Time-out” Trip when there is no remote communication to MicroVission for the congured time.
True Anti-Recycle Timer
Once the compressor turns off, this timer will keep the compressor OFF for the time set in this setpoint. This
timer is used to prevent short cycling of the compressor.
NOTE
The operator will be able to modify True Anti-Recycle Timer setpoint only if “True” option is set for Anti-
Recycle setting in the Conguration screen.
7 – 2
Figure 7-2. Timers Screen (Page 2)
MicroVission Controller • Operation and Service Manual • Emerson • 35391MV 1.0
Section 7 Timers
Accumulative Anti-Recycle Timer
This timer forces a specied time between the consecu­tive compressor starts. When the compressor starts,
this timer resets the time and starts accumulating the running time. Once the compressor shuts down, it will
not be allowed to restart for the remainder of time left
on the Accumulative Anti-Recycle Timer. Unlike the True Anti-Recycle Timer, if the compressor has run for the en­tire time of the Accumulative Anti- Recycle Timer and
then if compressor shuts down, the compressor will be
allowed to restart immediately.
The operator will be able to modify Accumulative Anti­Recycle Timer setpoint only if “Accumulative” option is
set for Anti-Recycle setting in the Conguration screen.
Hot Starts per Hour
This counter will count the number of compressor starts
in an hour. This counter will reset only when the time
between two compressor starts is at least an hour. If in an hour’s time, counter reaches to its set value, then the compressor will not be allowed to start until an hour is complete from the time when the counter was last re­set. This counter allows consecutive compressor starts,
but once the counter reaches to the set value, it requires
a one-hour window between compressor starts for the counter to reset.
NOTE
Oil Recovery Solenoid Shutoff Delay
This is the time for which Oil Recovery Solenoid Digital
Output will remain ON when the state of Low Oil Level
Digital Input is changed from Active Low to Active High. When this timer expires, the state of Oil Recovery Solenoid Digital Output will change to OFF.
Low Oil Level Alarm Delay
This is time for which “Low Oil Level Alarm” will not be generated once “Low Oil Level” Digital Input is found Active Low. If state of “Low Oil Level” Digital Input re­mains Active Low continuously for this time, then alarm condition will be generated and “Low Oil Level Alarm” message will be displayed on the Main screen.
Low Oil Level Trip Delay
This is time for which “Low Oil Level Trip” will not be gen­erated once “Low Oil Level” Digital Input is found Active Low. If state of “Low Oil Level” Digital Input remains Active Low continuously for this time, then trip condi­tion will be generated and “Low Oil Level Trip” message will be displayed on the Main screen.
NOTE
The operator will be able to detect and see “Low Oil Level Trip” message on Main screen only if “Oil Level Trip”
checkbox is Enabled in the Conguration screen
NOTE
The operator will be able to modify Hot Starts per Hour setpoint only if “Hot Starts” option is set for Anti-Recycle
setting in the Conguration screen.
MicroVission Controller • Operation and Service Manual • Emerson • 35391MV 1.0
7 – 3

Section 8 Instruments Calibration

Overview

The Instrument Calibration screen allows the operator
to dene how the MicroVission will interpret the signal from any devices connected to panel’s analog inputs. The Instrument Calibration screen is organized in four pages. Each page is then divided into individual tabs for every device.
I/O
Each tab has this section that provides basic information for that device.
A/D bit Value
This eld displays the actual value read by MicroVission analog to digital convertors. This value is unaffected by any changes to the calibrations settings. If a device is
connected to the associated input, there will be some
value displayed in this eld.
Calibrated Value
This eld displays the calibrated value which is the result
of the calibration process. Calibrated value for Pressure
& Temperature values will be displayed in pressure / tem­perature unit as congured in Conguration Screen.
All instruments are calibrated using a two-point linear calibration process. Any device that has a non-linear re-
sponse to environmental stimuli will not be able to be
calibrated through the MicroVission.

Pressure & Temperature Inputs

The most commonly used Instruments are pressure and temperature sensors. The rst two pages of the
Instrument Calibration Screen are dedicated to these
Instruments; see Figure 8-1 up to Figure 8-12.
Each tab on these two pages are divided into two sec-
tions, Device Calibration and Channel Calibration.

Devices Calibration

The Device Calibration section is where the operation
parameters of the Instrument are dened.
Default Devices
By selecting this option, the operator will have access
to several common devices via a drop-down list. The
devices are predened and if one is selected, then all
the setpoints will be set for the operator.
Custom Device
This option allows the operator to choose the minimum
and maximum value of the Instrument being used.
The Instrument Calibration screen provides a set of rang-
es for default devices. You must select an appropriate
range to calibrate the sensor. If you do not nd a correct range, you can specify the custom range.
Based on the calibration range that you select or specify, the MicroVission displays the calibrated value. This cali­brated value of the respective analog input is also shown
on the Main screen.

Channel Calibration

The Channel Calibration section denes the type of sig­nal sent by the Instrument.
Offset
Once the two-point calibration is completed, it is com-
mon for a small error to exist. By entering the value of
the error from the calibrated value and the actual value
into the “Adjustment” entry box, that error will be add­ed/subtracted from the “Total Offset”. The offset is ap-
plied to the calibrated value which should correct the error.
Range
This option is available when the “Custom Device” op­tion is selected. Here the operator denes the signal type and range transmitted by the Instrument. The op­erator can select from several predened ranges in the
drop-down list or enter a value.
MicroVission Controller • Operation and Service Manual • Emerson • 35391MV 1.0
8 – 1
Section 8 Instruments Calibration

Analog Inputs – Pressure

On the Instrument Calibration Screen Page 1, the opera­tor can calibrate following pressure sensors:
• Suction Pressure
Discharge Pressure
• Oil Pressure
• Filter In
• Filter Out
Figure 8-1. Instrument Calibration Screen Page 1 – Analog Inputs (Suction Pressure)
Figure 8-2. Instrument Calibration Screen Page 1 – Analog Inputs (Discharge Pressure)
8 – 2
MicroVission Controller • Operation and Service Manual • Emerson • 35391MV 1.0
Section 8 Instruments Calibration
Figure 8-3. Instrument Calibration Screen Page 1 – Analog Inputs (Oil Pressure)
Figure 8-4. Instrument Calibration Screen Page 1 – Analog Inputs (Filter In Pressure)
MicroVission Controller • Operation and Service Manual • Emerson • 35391MV 1.0
8 – 3
Section 8 Instruments Calibration
Figure 8-5. Instrument Calibration Screen Page 1 – Analog Inputs (Filter Out Pressure)

Analog Inputs – Temperature

On the Instrument Calibration Screen Page 2, the opera­tor can calibrate following temperature sensors.
• Suction Temperature
Discharge Temperature
• Oil Temperature
Figure 8-6. Instrument Calibration Screen Page 2 – Analog Inputs (Suction Temperature)
8 – 4
MicroVission Controller • Operation and Service Manual • Emerson • 35391MV 1.0
Section 8 Instruments Calibration
Figure 8-7. Instrument Calibration Screen Page 2 – Analog Inputs (Discharge Temperature)
Figure 8-8. Instrument Calibration Screen Page 2 – Analog Inputs (Oil Temperature)
MicroVission Controller • Operation and Service Manual • Emerson • 35391MV 1.0
8 – 5
Section 8 Instruments Calibration

Analog Inputs

Page 3 of Instrument Calibration Screen is dedicated to
instruments used for Motor Current and Process Control.

Motor Current

The MicroVission measures the motor current value us-
ing the 4-20 mA signal transmitted from the external
device.
The calibration process for Motor Current is slightly dif­ferent from all other calibration procedures. The mo­tor current must be calibrated while the compressor
is running at close to full amps as much as possible. In addition, the operator will need a value into the “Enter Desired Value” entry box that is equal to the measured value in amps by a calibrating measurement device. After entering the measured value, the displayed motor current in “Calibrated Value” eld may still be off slightly. In this case re-enter the desired value and the displayed value should get progressively closer.

4-20mA Scale

4mA: Not editable by the operator. Denes the minimum value in Amps represented by 4mA input..
20mA: Denes the maximum value in Amps that represented by 20mA input.
• Enter Desired Value: The operator enters the correct
current value. Each entry will re-calculate the point
slope calculations of the current calibration.
Total Error: Not editable by the operator. Displays
the total error offset of the value from the “Enter
Desired Value” setpoint.
8 – 6
Figure 8-9. Instrument Calibration Screen Page 3 – Analog Inputs (Motor Current)
MicroVission Controller • Operation and Service Manual • Emerson • 35391MV 1.0
Section 8 Instruments Calibration
Process Temperature or Pressure
The Process Control tab on this page will display either Process Temperature or Process Pressure depending on the “Process Control” type selected by the operator in the Conguration screen. For more information, see Conguration section.
The tab is divided into two sections, Device Calibration and Channel Calibration with Default Devices and
Custom Device as well as Offset and Range Calibration
features as described for the standard Pressure and Temperature Inputs.
Figure 8-10. Instrument Calibration Screen Page 3 – Analog Inputs (Process Temperature)
MicroVission Controller • Operation and Service Manual • Emerson • 35391MV 1.0
8 – 7
Section 8 Instruments Calibration

Auxiliary Inputs

Page 4 of the Calibration screen allows the operator to dene the parameters of an installed auxiliary analog instrument. These instruments are usually not part of a typical compressor set-up but MicroVission provides a way for the operator to add additional capabilities. The layout of this screen is typical to the pressure and tem-
perature calibration screens.

Device Calibration

These setpoints allow the operator to dene what the in­put from the auxiliary instrument means in terms of unit and range. If a temperature measuring instrument is
connected, then the operator would select temperature
from the “Units” dropdown box then set the minimum
and maximum value for the scale.

Channel Calibration

The Channel Calibration section denes the type of sig­nal sent by the Instrument.
• Offset: Once the two-point calibration is complet-
ed, it is common for a small error to exist. By enter­ing the value of the error from the calibrated value and the actual value into the “Adjustment” entry
box, that error will be added/subtracted from the
“Total Offset”. The offset is applied to the calibrated
value which should correct the error.
Range: Here the operator denes the signal type
and range transmitted by the Instrument. The op­erator can select from several predened ranges in
the drop-down list or enter a value.
Figure 8-11. Instrument Calibration Screen Page 4 – Auxiliary Inputs (Discharge 2 Pressure)
8 – 8
MicroVission Controller • Operation and Service Manual • Emerson • 35391MV 1.0
Section 8 Instruments Calibration
Figure 8-12. Instrument Calibration Screen Page 4 – Auxiliary Inputs (Discharge 2 Temperature)
MicroVission Controller • Operation and Service Manual • Emerson • 35391MV 1.0
8 – 9

Section 9 Event List

Overview

The Event List screen is designed to display the list of all compressor events are arranged in chronological order with the latest event appearing at the top. The infor-
mation available on the screen helps operator to un­derstand the operation of the compressor and trouble-
shooting. This screen is divided into four columns and
can list up to 128 separate events. The operator can also
download the information on the event list through the
Data Backup Screen.

Event List Columns

• Date: Displays the date of the event in MM/DD/
YYYY format.
• Time: Displays the time of the event in HH:MM:SS format. The time data displays AM/PM informa­tion when 12-hour format is congured in the Conguration screen.
• Event Type: Displays the type of message for a list­ing. The common event types are “Start”, “Stop”, “Trip”, “Inhibit”, “Alarm”, “Info”, and “System”.
These helps the operator to understand the mean-
ing of the “Message” column.
• Message: The information that describes the event.
The operator can use “Update” button to refresh the
event list data when this screen is open, instead of exit-
ing the screen and re-entering to see the latest events
data.
Figure 9-1. Event List Screen
MicroVission Controller • Operation and Service Manual • Emerson • 35391MV 1.0
9 – 1

Section 10 Input / Output States Screen

Overview

This screen displays “Live Data” of all the Analog Inputs / Outputs and Digital Inputs / Outputs being monitored. There are two pages of Inputs / Outputs (I/O) available for viewing, see Figures 10-1 & 10-2.
This screen also takes a snapshot of all the I/O points
when the operator presses on “Freeze Data” button or if
the compressor experiences a trip condition. The Freeze
page displays the title that indicates whether the Freeze data is saved due to trip condition or “Freeze Data” but­ton was pressed by the operator, see Figures 10-3 & 10-
4. Latest Freeze data is shown in Freeze 1 tab. Up to ve Freeze pages can be saved. The oldest Freeze page will be removed when more than ve Freeze events occur.
These freeze events can be downloaded to a USB drive
through Data Backup screen.
NOTE
The format in which time is displayed on the Freeze page does not change depending on time format selected in the Conguration screen. Also values for Auxiliary Analog Inputs like Discharge 2 Pressure & Discharge 2 Temperature will be only shown when Analog Input 1 Board is enabled from the Conguration screen, see
Figure 10-5.
Figure 10-1. Input/Output States Screen Page 1 - Live I/O Data
MicroVission Controller • Operation and Service Manual • Emerson • 35391MV 1.0
10 – 1
Section 10 Input / Output States Screen
Figure 10-2. Input/Output States Screen Page 2 - Live I/O Data
10 – 2
Figure 10-3. Input/Output States Screen - Freeze Data (Trip Condition)
MicroVission Controller • Operation and Service Manual • Emerson • 35391MV 1.0
Section 10 Input / Output States Screen
Figure 10-4. Input/Output States Screen - Freeze Data
Figure 10-5. Input/Output States Screen – Auxiliary Analog Inputs
MicroVission Controller • Operation and Service Manual • Emerson • 35391MV 1.0
10 – 3

Section 11 User Access

Overview

The User Access is the screen where all operators go to log in.
In the MicroVission, each screen has a security level that provides the necessary permissions to the operator, technicians and/or supervisors to modify different sets of setpoints. The MicroVission has four levels of security, see Figure 11-1.
Level 0 – This is the default level where no operator is logged in. The functions available to the operator are very limited and basically only allows them to start
and stop the compressor.
Level 1 – This is a technician level of access. All the setpoints needed to operate and adjust the perfor­mance of the compressor will be available to an op­erator with this level of access.
Level 2 – This is a supervisor level of access. Setpoints
that require a higher level of knowledge such as cali­brating instrument will be available to an operator
with this level of access.
Level 3 – This is considered a contractor level of ac- cess. The setpoints available at this level have the
most potential of causing damage to the compressor. Therefore, this access is restricted to those only with the highest level of competence.
The User Access screen also provides options to add new
operators and modify or delete existing operators. Any operator can add an additional operator but can only add operator of lesser or equal security level.
The MicroVission will be shipped with a Level 3 operator
and password pre-assigned to the installing contractor. The contractor can then assign all users with security lev-
els as needed.
The procedure to assign user access levels is to rst press
the User Access button. The User Access screen will ap-
pear with the preassigned level 3 operator name visible within the “Operators” section. Highlight the name,
then enter the password associated with that name of
the user, then press Enter key to close the keyboard. Then press the “Apply” button. Press the “Manage Accounts” tab to begin the process of entering another Operator name, and assigning password and user level of this additional user. Lastly – remember to press the “Add/Update” button to add this user to the list, then press the “Apply” button before exiting this screen to make this change permanent.
Figure 11-1. User Access Screen - Login
MicroVission Controller • Operation and Service Manual • Emerson • 35391MV 1.0
11 – 1
Section 11 User Access

Login

The Login tab is where an operator will enter the user­name and password to gain access to MicroVisssion
screens. If the username and password match with the
existing user then the operators name will be applied to the lower status bar and the operator will be given ac­cess to screens of equal security level.
Operators
This window displays all operators that have been
added to the MicroVisssion user tables. If a name of an operator is selected from this window, the name is
added to the “Operator Name” entry box.
Operator Name
This entry box is for the operator’s username. The opera­tor can either select the username from the “Operators” window or enter the username manually by touching the entry box and entering the name via the pop-up keyboard.
Operator Password
This entry box is for operator’s password. The password can be entered by touching the password entry box and entering the password via pop-up keyboard.

Manage Accounts

The Manage Accounts tab allows addition, removal and modication of authorized users. See Figure 11-2.
Operators
This window contains the list of authorized users already added to the MicroVisssion. Selecting a name from this list will add that name to the “Operator Name” entry
box.
Operator Name
This entry box is for operator’s username who is to be added, removed or modied. The operator can either select the username from the “Operators” window or enter the username manually by touching the entry box and entering the name via the pop-up keyboard.
Operator Password
This entry box is for the operator’s password. The password can be entered by touching the “Operator Password” entry box and entering the password via the pop-up keyboard.
11 – 2
Figure 11-2. User Access Screen - Manage Accounts
MicroVission Controller • Operation and Service Manual • Emerson • 35391MV 1.0
Section 11 User Access
Verify Password
This entry box is to verify the operator’s password. The password can be entered by touching the “Verify Password” entry box and entering the password via the pop-up keyboard.
Security Level
This drop-down list allows selection of security level for the account being added or modied. Only levels that are equal to or less than the operator’s own security level
will be shown.
Add / Update
Pressing this button will initiate the creation or modica­tion of the specied account.
Delete
Pressing this button will delete the specied account.

Screen Security Levels

The following table lists all screen and their base security
levels, see Table 11-1. Most screens have more than
one security level. The base security level gives the user access to the setpoints that can change the performance of the compressor. The secondary security level is typically level 3 and is reserved for those setpoints that require a high level of care and knowledge of the system to make changes safely without damaging the system.
Table 11-1. Security Access Levels
Security Access Levels
Page User Level *Note
Event List Security Level 0 View
Input/ Output States Security Level 0 View/create freeze screen
Help Security Level 0 -
Alarms & Trips Security Level 1* Level 3 required for constraints
Compressor Control Security Level 1* Level 3 required for constraints
Instrument Calibration Security Level 2 -
Conguration Security Level 2* Level 3 required for page 5
Timers Security Level 2* Level 3 required for constraints
VNC Account Security Level 3 -
MicroVission Controller • Operation and Service Manual • Emerson • 35391MV 1.0
11 – 3

Section 12 Configuration Screen

Overview

The conguration screen is where most of the MicroVission features are enabled and congured. The initial setup of the MicroVission will generally start here, see Figure 12-1. Based on what is selected, different por-
tions of the MicroVission will be available to the operator.

Units

This section sets how values will be represented through­out the MicroVission program.
Temp. Units
• Drop-down box to select the temperature units
from “Fahrenheit” and “Celsius”. Once selected, all screen temperatures will be displayed in the select-
ed units
Press. Units
• Drop-down box to select the pressure units from
“Psig”, “Bar” and “Kpa”. Once selected, all screen pressures will be displayed in the selected units.
Run Hours
Offers the ability to change the compressor run hours. This is typically used when replacing an older micro controller on an existing compressor with a
new MicroVission.
No. of Cylinders
The operator should set appropriate setting as per the compressor connected. This setting informs the control program to properly process the number of analog channels for your compressor. For instance, if 12 or 16 cylinders is selected, then the control pro­gram processes a second discharge pressure safety and second discharge temperature safety.
No. of Unloaders
• The operator should set appropriate setting as per the compressor connected. This setting informs the control program to control unloader digital outputs which in turn modulates the capacity of compres­sor in steps. Each setting option displays the num­ber of unloaders and the unload percentage steps for the compressor. This setting is based on “No. of Cylinders”. For more information about Unloaders,
see Appendix: Unloaders.
Figure 12-1. Conguration Screen - Initial Setup (Page 1)
MicroVission Controller • Operation and Service Manual • Emerson • 35391MV
12 – 1
Section 12 Configuration Screen

Compressor Control Section

Vilter compressors typically run in one of the three con­trol modes: Suction Pressure Control, Process Control or
Discharge Pressure Control. Discharge Pressure Control is mutually exclusive with Suction Pressure Control & Process Control. When Discharge Pressure Control is se-
lected, Suction Pressure Control & Process Control are
grayed out and cannot be selected. Similarly, if Suction
Pressure Control and/or Process Control is selected,
Discharge Pressure Control is grayed out and cannot be
selected.
• Suction Pressure Control: This denes the Suction
Pressure input as the process variable and all con­trols will be based on Suction Pressure. The operator has the option to select up to two controllers where each can have its own set of setpoints.
• Process Control: This denes the Process Control
input as the process variable and all controls will be based on either Process Temperature or Process Pressure. The operator has the option to select up to two controllers where each can have its own set of setpoints. The operator has to select one of the pro­cess control modes, either temperature or pressure as a process variable. Temperature and Pressure op-
tions are mutually exclusive.
• Discharge Pressure Control: This denes the Discharge Pressure input as the process variable and all controls will be based on Discharge Pressure. The
operator has the option to select up to two control­lers where each can have its own set of setpoints.

Oil Monitoring

This section provides the options to monitor the Oil
Filter related Analog Inputs. The operator will be able to set any of one option related to Oil Filter from below
three options:
• No Oil Filter Monitoring: When this option is se­lected, Filter Inlet Pressure & Filter Outlet Pressure
inputs will not get monitored. Oil Filter Differential Pressure will not get calculated. Safeties related to “High Filter Differential Pressure” will not be active.
• Only Oil Filter In: When this option is selected, Only Filter Inlet Pressure input will get monitored while Filter Outlet Pressure input will not get monitored. Oil Filter Differential Pressure will get calculated as
Filter Inlet Pressure minus Oil Manifold Pressure.
Safeties related to “High Filter Differential Pressure”
will be active and monitored.
• Oil Filter In and Oil Filter Out: When this op­tion is selected, both Filter Inlet Pressure input &
Filter Outlet Pressure will get monitored. Oil Filter Differential Pressure will get calculated as Filter
Inlet Pressure minus Filter Outlet Pressure. Safeties
related to “High Filter Differential Pressure” will be active and monitoredBased on the option you select for oil monitoring, the MicroVission Controller dis­plays the warning and trip message for the low oil lter pressure.
You can also select an option to trip the compressor if
the oil level drops below the required level.
12 – 2

Oil Level Trip

This checkbox when enabled, allows the operator to
monitor “Low Oil Level Trip”. When this option is en­abled, MicroVission program will monitor state of “Low Oil Level” Digital Input. The digital input will be low when compressor oil level drops below the minimum required level. For more information on monitoring related to
safeties, see Timers section.

Touch Screen

The “Calibrate” button puts the screen into calibration mode. Calibration of the touchscreen is only required if the operator nds that the pointer’s arrow is not follow­ing the nger while trying to operate on the MicroVis-
sion screens. In calibration mode, the operator needs to touch the
pointers as shown on the screen starting with the top­left corner. After touching the pointer, next pointer will
be shown. The operator need to touch on all four point-
ers shown on corners of the screen in the given sequence
to complete the calibration.
MicroVission Controller • Operation and Service Manual • Emerson • 35391MV
Section 12 Configuration Screen

Anti-Recycle

Anti-Recycle denes the method of motor protection
due to repeated motor starts. The operator has three options for protection:
• Hot Starts: This option will allow only a certain
number of compressor starts in an hour before set-
ting the time to the anti-recycle timer. The number of starts to be allowed is set through the “Hot Starts
per Hour” setpoint of the Timers screen.
• True : This option adds the time to anti-recycle tim­er once the compressor is shutdown, hence forcing a specic wait time once compressor is stopped and next compressor start. The wait time required is set through the “True Anti-Recycle Timer” setpoint of
the Timers screen. The compressor motor cannot
be started if there is anti-recycle time left.
• Accumulative: This option immediately adds the time to anti-recycle timer once the compressor is started. The time to be added is set through the “Accumulative Anti-Recycle Timer” setpoint of the Timers screen. Unlike the True Anti-Recycle Timer,
if the compressor has run for the entire time of the Accumulative Anti-Recycle Timer and then the com­pressor stops, the compressor will be allowed to re-
start immediately.
The operator can view anti-recycle time on the Main screen if “Anti-Recycle” option is selected in Congurable Main Screen Settings on Page 4.
Compressor Identication
This section sets the identication for a MicroVission
unit.
• Name: Unique identier that is used for all
MicroVission units.
• Panel ID: Panel Identier used by controller when communicating with multiple panels.
• Order Num: Identies the Order Number of the
purchase of the compressor. This number will be
needed if the operator requires help/support from
the Vilter.

Date and Time

These section sets the date and time of the MicroVission.
Accurate date and time are essential for accurate log­ging and troubleshooting. Setting these parameters will
set the hardware clock embedded in the MicroVission
CPU. If the time is not retained after powering down the
panel, the operator should check and/or replace the coin
style battery on the panel SBC behind the touchscreen.
• Year: Entry box to set the current year.
• Month: Entry box to set the current month.
• Day: Entry box to set the current date.
• Format: Selection to choose between 24 hours and
12 hours clock.
Figure 12-2. Conguration Screen (Page 2)
MicroVission Controller • Operation and Service Manual • Emerson • 35391MV
12 – 3
Section 12 Configuration Screen
• Hour: Entry box to set the clock hours. AM or PM
drop-down box will be available if the 12 hours for­mat is selected.
• Minute: Entry box to set the clock minutes.
• Second: Entry box to set the clock seconds.

VNC Account

MicroVission panels can be accessed remotely by using a
VNC client over TCP/ IP network. This section allows the
operator to change default VNC password and VNC port number. For more information, see Figure 12-2.
• New Password: The operator will add the password
by touching the entry box and typing the password
via the pop-up.
• Verify New Password: The operator will re-enter
the password by touching the entry box and typing the password via the pop-up keyboard.
• Port Number: The operator will change the port number for the VNC server by touching the entry box and typing the port number via pop-up key-
pad. Default port number is 5900. The operator can
assign the port number in the range from 5900 to
6000.

Alarms and Trips

The “Idle Time Trip” checkbox works in conjunction with the “High Level Shutdown” digital input. If checkbox is
enabled, when the compressor is in idle state and this
digital input is off, the compressor should give a trip message.

Direct I/O

Enables the Direct I/O Inputs. When checkbox is en-
abled, the operator can select any one Direct I/O option from “Auto Control” and “(Digital) Manual Control”.
• Auto Control: This option will allow the operator to run compressor in Direct I/O Auto Run Mode. The
algorithm will use setpoints of Compressor Control screen for loading & unloading of compressor cylinders.
• (Digital) Manual Control: This option will allow the operator to run compressor in Direct I/O Manual
Run Mode. The algorithm will monitor the state of “Remote Increase” & “Remote Decrease” Digital Inputs for loading & unloading compressor cylinders respectively. If “Remote Increase” Digital Input is ON & “Remote Decrease” Digital Input is OFF then the compressor will load one step. Similarly, if “Remote Increase” Digital Input is OFF & “Remote Decrease” Digital Input is ON then the compressor will unload
one step.
The operator should ensure following conditions are
met to run the compressor in Direct I/O Run Mode:
1. “Direct I/O” checkbox is enabled
2. “Active Remote Control” setting is set to “Direct I/O”
3. “Remote Start/Stop” Digital Input is ON
Once above conditions are met, the operator can
start compressor in Direct I/O Run mode by pressing on “START” button in Main screen and then selecting “Remote” option in pop-up window.

Communication

The communication section is the control center for all communications to the MicroVission panel. It is possible to have multiple modes of communications enabled and
used. However, only one mode can be used to control
the MicroVission, which would be the one selected in
the “Active Remote Control” drop-down box.
For a complete list of communication registers, see
Appendix B, Communication Table.

Active Remote Control

Select the mode of remote control. The operator any
one option from Direct I/O, Ethernet, Serial and None.
12 – 4
MicroVission Controller • Operation and Service Manual • Emerson • 35391MV

Run Permissive

When this checkbox is enabled, MicroVission moni-
tors the “Remote Start/Stop” Digital Input. If “Remote Start/Stop” Digital Input is energized (turned ON), the
compressor can start in the selected run mode (Auto
/ Manual / Remote). If the “Remote Start/Stop” Digital Input is de-energized (turned OFF), the compressor will wait until the Digital Input is energized.
When this check box is disabled, MicroVission will not
monitor the state of “Remote Start/Stop” Digital Input during the compressor start.
Section 12 Configuration Screen

On Communication Failure

This feature of the MicroVission offers the ability to de­ne how the MicroVission will handle communication
failure.
The operator can select any one options from below two
options:
• Revert to Local Control: Once the compressor
has started running in the Remote Run Mode, the “Communication Failure Detect Timer” as cong-
ured in Timers screen will start. If no further com­munication with MicroVission takes place for the
congured time, the MicroVission will be placed in Local Auto Mode. MicroVission will also display “Remote Comm Timeout” Alarm Message and add
time-stamped alarm event to Event List screen.
• Stop Compressor with Trip: Once the compressor
has started running in the Remote Run Mode, the “Communication Failure Detect Timer” as cong-
ured in Timers screen will start. If no further com­munication with MicroVission takes place for the
congured time, the compressor will be stopped due to “Remote Comm Timeout” Trip. MicroVission will also display “Remote Comm Timeout” Trip Message and add time-stamped trip event to Event
List screen.

Ethernet

This checkbox when selected, enables the network set-
tings for the Ethernet port. Other settings will be allowed
for selection when this option is enabled.
• IP Address: Entry box to set the IP Address.
• Subnet Mask: Entry box to set the Subnet Mask.
• Gateway: Entry box to set the Gateway Address.
• Protocol: Drop-down box to select the type of pro-
tocol used to remotely control the MicroVission. Available options are “Modbus TCP” and “Ethernet
IP”.
• Node Address: Address used by the MicroVission when communicating with multiple panels.
Figure 12-3. Conguration Screen - Communication
MicroVission Controller • Operation and Service Manual • Emerson • 35391MV
12 – 5
Section 12 Configuration Screen

Serial (Modbus RTU)

This checkbox when selected, enables the Serial Modbus
RTU port. Other settings will be allowed for selection
when this option is enabled.
• Node Address: Address used by the MicroVission when communicating with multiple panels.
• Port: The MicroVission has two ways to communi- cate on serial bus, either via the in-built serial port
P12/RS485 or through the USB port. This drop-
down box allows the operator to choose which one will be used.
• Baud Rate: Sets the baud rate for the serial communication.
• Data Bits: Fixed at 8 Data bits.
• Stop Bits: Identies the end of character for
re-synchronizing.
• Parity: Identies the type of error detection.
Congurable Main Screen Settings
In this section provides options for selection of twelve
custom elds for display of their values on the Main
screen.
Each row will have two dropdown boxes. The rst drop­down box will have options like “Standard Analog I/O”, “Standard Digital I/O” and “Status Value” to select the type of value to be displayed on the Main Screen. Based on the rst dropdown box selection, the second drop-
down box will show list of values for selection. The value
set from the second dropdown box will get displayed on Main Screen. See Figure 12-4 & 12-5 for details.
For Analog Inputs, the calibrated values will be shown on Main Screen. For Digital Inputs, values will be displayed as “HIGH” & “LOW” depending on the current state of digital input if Energized or De-Energized respectively. For Digital Outputs, values will be displayed as “ON” & “OFF” depending on whether MicroVission is trying to drive output High or Low respectively. For Status Values, calculated values or Anti-Recycle Time value will be dis­played. If value set in second dropdown box is “None”, that row will be displayed blank on Main screen.
12 – 6
Figure 12-4. Conguration Screen – Congurable Main Screen Settings
MicroVission Controller • Operation and Service Manual • Emerson • 35391MV
Section 12 Configuration Screen
Figure 12-5. Congurable Parameters on Main Screen
MicroVission Controller • Operation and Service Manual • Emerson • 35391MV
12 – 7
Section 12 Configuration Screen
I/O Conguration
If any additional I/O cards are added to the MicroVission, this is where these cards are enabled for use by its algo-
rithms. Some features of the MicroVission will not be
available unless specic expansion cards are selected, see Figure 12-6.
• Analog Input 1: Enables the optional Analog Input
card 1.
• Digital Input/Output 1: Enables the optional Digital
Input/Output card 1.
12 – 8
Figure 12-6. Conguration Screen - I/O Conguration
MicroVission Controller • Operation and Service Manual • Emerson • 35391MV

Section 13 Data Backup

Overview

The Database Backup screen provides the operator a
way to extract information out of the MicroVission for backup purposes or diagnostics. See Figure 13-1: Data
Backup Screen - Save/Load.
From this screen, the operator can download all the
Setpoint Databases, Maintenance Logs, Event Lists,
Freeze Data, Trend Data and Compressor Run Hours to
a portable USB ash drive. That information can then be
uploaded back to the MicroVission in the case of data
corruption or to update the MicroVission program.
Additionally, this screen also allows the operator to reset all values to the factory defaults.
All the information saved to the USB ash drive is open information, meaning none of the data is encrypted and operator is free to examine it. The log les are all saved
as simple ASCII text and the databases can be examined with SQLite.

Refresh

• The Refresh button is used to initiate a scan of the
USB ports and list any devices found in the “Available
Devices” window.

Save / Load

In this section, operator can either save the MicroVission
setpoints and log information to a USB ash drive or load from a USB ash drive back to the MicroVission.
Save
Selecting Save allows the operator to save MicroVission data to a USB ash drive using the in-
formation provided on the screen. The button on
the top right side will be labeled “Save” when this is
selected.
Load:
Selecting Load allows the operator to load data from a USB ash drive to the MicroVission using the informa­tion provided on the screen. The button on the top
right side will be labeled “Load” when this is selected.
Figure 13-1. Data Backup Screen - Save/Load
MicroVission Controller • Operation and Service Manual • Emerson • 35391MV
13 – 1
Section 13 Data Backup
Available Devices
This window displays any USB ash drive plugged into
one of the MicroVission USB ports. Once one of the available devices is selected, the contents of the select-
ed device will be displayed in the “Select Folder / File” window. If the plugged in USB ash drive is not showing up, operator can try pressing the “Refresh” button at the
bottom of the screen.
Unfortunately, not all USB ash drives are compatible with the MicroVission and might not be shown in the
available devices list
Select Folder/File
This window displays the folders and les contained in the USB ash drive selected in the “Available Devices”
window. The information from the MicroVission will
be stored into a .zip le. So, a zip le will have to be
selected to load the data or overwritten when saved.
Once a zip le is selected, the name will be shown in the “Filename” window.
NOTE
Unmount
• By Pressing the Unmount button, any USB drive se­lected in the “Available Devices” window will be dis­connected from the operating system and can be safely removed from the USB port.
Back
• The Back button returns the operator to the preced-
ing window display of les and folders.
Filename
This window is where you can give a name to a saved backup le. This eld will automatically be populated if le is selected in the “Select Folder/File” window.
Settings
Using this table, the operator can choose to save or load all or part of information contained in the MicroVission.
Data Items
Using these checkboxes, the operator can choose to save or load all or part of information contained in the
MicroVission according to the selection of options.
13 – 2
Figure 13-2. Data Backup Screen - Migrate and Factory Reset
MicroVission Controller • Operation and Service Manual • Emerson • 35391MV
Section 13 Data Backup

Factory Reset:

The Factory reset button offers the operator the ability
to reset all the MicroVission setpoints back to the facto-
ry default settings or a specic database. If the operator nds that a screen will not load when selected, it is likely
that the database associated with that screen has been
corrupted. Unfortunately, data corruption is always a possibility in any system. So, this function was designed to help the operator to regain control, see Figure 13-2.
Reset
• This button initiates the process to revert the
MicroVission back to the factory default settings.

Setpoints Report

The setpoints report screen offers the operator ability to generate a setpoints report for all screens. The re­ports are stored as .csv les and can be saved to a USB drive from Save/Load screen by selecting the “Setpoints Report” option in Data Items section during backup of database. The .csv le can be imported in any spread sheet application. During operation, the operator can generate reports at any time. See Figure 13-3: Data
Backup Screen - Setpoints Report.
All/ Select:
Selecting “All” will include all screens in the report
that is generated. When “Select” option is selected,
the operator can choose which screens will be includ­ed in the report.
Generate:
This button initiates the process to generate set-
points report les
Figure 13-3. Data Backup Screen - Setpoints Report
MicroVission Controller • Operation and Service Manual • Emerson • 35391MV
13 – 3
Section 13 Data Backup

Database Backup Procedure

Upgrading the program in the MicroVission panel normally involves replacing the SD card. Note that all
compressor operation setpoints, calibration values and maintenance information is stored on the SD card.
So, when upgrading to a new program (new SD card), the task is simplied by using the “Database Backup” and “Database Restore” functions provided in the MicroVission to migrate the database of the original SD
card to the new SD card.
There are three main steps to this process:
1. Backup the database of original SD card (currently
in the MicroVission panel) – onto a thumb drive or ash drive.
2. Replace the original SD card with new SD card.
3. Restore the original database to new SD card.

Backup Database of Original SD Card

It is REQUIRED to manually reenter the Alarms and Trip settings when upgrading from some older version of programs. Therefore, it is highly recommended to cre­ate a hardcopy of all compressor operating setpoints, or to create and have handy a printout of the Setpoints Re-
port .csv le. It is also recommended to make a hardcopy of the con­guration information and maintenance information prior to changing SD cards. For the list of all the informa­tion that you should record, see the “Record operating setpoints and conguration information” section below.
NOTE
1. With the original SD card installed into the MicroVission SBC, insert the ash drive into the USB port. This port is located along the left side of the single board computer above the ethernet connec­tor. See Figure 13-4: SD Replacement.
2. Log into the MicroVission using your username and password (you will need to be Level 3 to upload
data).
3. Navigate to the Data Backup screen.
4. In the “Available Devices” window, you should see
something like “/media/usb0”. If you do not see anything in this window, press the “Refresh” button,
and wait about 5 seconds. After that press the but-
ton again. If you still do not see the device, then the MicroVission does not recognize the ash drive - try a different one. If you do see it, highlight it.
5. Now highlight the “Filename” eld (which will also contain “/media/usb0”). A keyboard will appear. Now type in the name of the le that you want for your database for this compressor. For instance, “cylinders_month_day_year” or something similar for identifying the le to the compressor. Then press “Enter” key on keyboard.
6. Now press the “Save” button. A “watch” icon will appear. Shortly thereafter, a popup box should ap­pear with a message that the save was successful and asking if you want to “unmount” the ash drive device. Press on “Yes” Button. If the “watch” icon re-
mains after a minute or so, then the MicroVission is
unable to close the backup le it has written to the thumb drive. Power down the MicroVission and try
the procedure with a different thumb drive.
The data migration procedure (moving the original SD card database to new SD card) uses a “thumb drive” or “ash drive” to transfer data from the original SD card
to the new SD card. Note there have been a few re-
cords of some thumb drives not being recognized by the MicroVission. If you have difculty in getting the MicroVission to recognize the thumb drive – then try a different one. Vilter has successfully tested many differ­ent manufacturers and sizes; a partial list is given below:
o SanDisk micro cruzer 2.0 GB
o Imation 2.0GB
o Kingston DataTraveler 512 MB
o SanDisk mini cruzer 128 MB
13 – 4
MicroVission Controller • Operation and Service Manual • Emerson • 35391MV

Replace Original SD card with New SD card

Now that the database le has been saved to the thumb drive, you can replace the “original” SD card with a new
SD card.
1. Power down the MicroVission.
2. Remove the thumb drive and take out the “original” SD card and install the new one.
3. Label both the old and new card to identify the com- pressor it is for.
Section 13 Data Backup

Restore Original Database to New SD card

Now that the new card is inserted, power up the MicroVission panel. The MicroVission boots up in a min­ute or so.
• Once the MicroVission is booted up, press on the
“User Access” button.
• Insert the thumb drive in to the USB port.
Navigate to the Data Backup screen. You should
again see the USB thumb drive listed in the “Available
Devices” window.
Select the Load function (above the “Available
Devices” eld), and then highlight the device that is listed in the “Available Devices” window.
In the “Select Folder/File” window, nd the backup le for this compressor, and highlight it.
Now press the “Load” button.
a) A pop-up window will appear with a message
Loading new databases will require a program restart. Continue?”. Press “Yes”.
b) Another pop-up window might appear with
a message “One or more settings selected for loading were missing from the archive. And it will list what is missing. Continue loading any­way?”. Press “Yes”.
c) Another pop-up box might appear with a
message asking if you want to use the IP address it found. Press “OK”.
A pop-up box appears with a message “Settings were successfully loaded. Program will restart”. Press “OK“.
When the OK button is pressed, the panel will reboot.
Now using the “hand documented” settings that you re­corded, compare the setpoints on that list against those in the MicroVission. They should all be OK. Here are the
KNOWN issues that we have found with this procedure.
If you have communication connection issues after
restoring the database, you may have to “re-enter” the IP address that is shown on page 3 of the con­guration screen. If you experience problems after the “Restore” function – then re-enter your commu­nication settings.
Record Operating Setpoints And Conguration
Information
Before powering down the MicroVission to replace the SD card, copy the following operating setpoints and conguration information.
1. Conguration Screen - Page 1
a. No. of Cylinders and No. of Unloaders
b. Compressor Control Type & Number of
Controllers
c. Oil Monitoring Settings
d. Anti-Recycle Settings
2. Conguration Screen - Page 2
a. Order Number
3. Conguration Screen - Page 3
a. Active Remote Control Setting
b. If Active Remote Control = Direct I/O, docu-
ment “type” of Direct I/O selection.
c. Ethernet Settings
4. Conguration Screen, Page 5
a. Optional I/O boards
5. Compressor Control Setpoints – all
6. Alarms and Trips Setpoints – all
7. Timer Setpoints – all
8. Instrument Calibration, Pressure page
a. Record Transducer Range selection for Suction
Pressure, Discharge Pressure, Oil Pressure, Filter
Inlet Pressure & Filter Outlet Pressure.
b.Record ‘Total Offset” value for Suction
Pressure, Discharge Pressure, Oil Pressure, Filter
Inlet Pressure & Filter Outlet Pressure.
9. Instrument Calibration - Temperature page
a. Record Transducer Range selection for
Suction Temperature, Discharge Temperature,
Oil Temperature & Process Temperature
b. Record “Total Offset” value for Suction
Temperature, Discharge Temperature, Oil
Temperature & Process Temperature
10. Instrument Calibration – Motor Current Settings
11. Compressor Runtime.
MicroVission Controller • Operation and Service Manual • Emerson • 35391MV
13 – 5
Section 13 Data Backup

Replace SD card

1. Power down the MicroVission panel.
2. Remove old SD card and install new SD card.
3. Power up the MicroVission panel.
Re-Enter Operating Setpoints And Conguration
Information
1. Logon as “admin” user (default password = admin).
2. Re-enter all values in Conguration screen. The most vital thing is to re-enter the correct No. of Cyl­inders and No. of Unloaders. Re-enter the Compres-
sor Runtime on page 2 of the conguration screen. Ensure you re-select any optional boards that are installed, and apply those additions.
3. Re-enter all Control Limits.
4. Re-enter all Alarm and Trip setpoints. The most vital
thing is - under the “Delay” tab, enter 5 seconds for all alarm and trip delays.
5. Re-enter all Timer Setpoints.
6. Re-enter all Instrument Calibration offsets for pres­sure transducers. Insure that the Suction Pressure
transducer range is properly selected (typically 0-200psia 4-20mA) – but double check proper set­ting.
13 – 6
Figure 13-4. SD Card Replacement
MicroVission Controller • Operation and Service Manual • Emerson • 35391MV

Appendix A Unloaders

Unloader Tables

The following Table lists the different types of Unloading Schemes provided for balancing Vilter Reciprocating Compressor’s capacity to varying load requirements.
Type Unloaders
TYPE1 2, 4 or 6 cylinders with 50% unloading
TYPE2 4 cylinders with 25%, 50%, 75% unloading. Single cylinder on Unloader Output #1
TYPE3 6 or 12 cylinders with 33%, 66% unloading
TYPE4 8 or 16 cylinders with 25%, 50% unloading
TYPE5 8 or 16 cylinders with 25%, 50%, 75% unloading
TYPE6 4 or 8 cylinders with 50%, 100% unloading
TYPE7 6 or 12 cylinders with 33%, 66%, 100% unloading
TYPE8 6 or 12 cylinders with 17%, 33%, 50%, 66% unloading. Single cylinder on Unloader Output #1
TYPE9 6 or 12 cylinders with 17%, 33%, 50%, 66%, 83% unloading. Single cylinder on Unloader Output #1
TYPE10 7 cylinders with 29%, 57% unloading
TYPE11 Compressor with NO unloading
TYPE12 3 cylinders with 33% unloading
TYPE13 8 or 16 cylinders with 25%, 50%, 75%, 100% unloading
TYPE14 6 cylinders with 33%, 50%, 66% unloading. Single cylinder on Unloader Output #1
TYPE15 8 cylinders with 13%, 25%, 38%, 50%, 63%, 75% unloading. Single cylinder on Unloader Output #1
and Output #2
TYPE16 8 cylinders with 13%, 38%, 63% unloading. Single cylinder on Unloader Output #1
TYPE17 6 cylinders with 33%, 50%, 66% unloading. Single cylinder on Unloader Output #1
TYPE18 5 cylinders with 40%, 60% unloading. Single cylinder on Unloader Output #1
TYPE19 3 cylinders with 33%, 66% unloading. Single cylinder on Unloader Output #1 and Output #2
TYPE20 7 cylinders with 14%, 29%, 43%, 57% unloading. Single cylinder on Unloader Output #1

Table A-0. Unloading Schemes

MicroVission Controller • Operation and Service Manual • Emerson • 2017VM-16 1.0
A – 1
Appendix A Unloaders
Unloader Tables
The following tables provide the status of Unloader Outputs for each type of unloading scheme at every step.
Table A-1. Type 1 Unloader - Cylinders: 2, 4, or 6 Unloading Percentage: 50% *
% Load Compressor Start Output Unloader Output #1 % Unload
0 (OFF) 0 0 100
50 1 1 50
100 1 0 0
Table A-2. Type 2 Unloader - Cylinders: 4 Unloading Percentage: 25%, 50%, 75% | Single cylinder on Unloader Output #1 *
% Load Compressor Start Output
0 (OFF) 0 0 0 100
25 1 1 1 75
50 1 0 1 50
75 1 1 0 25
100 1 0 0 0
Unloader Output #1
(single cylinder)
Unloader Output #2
(double cylinder)
% Unload
Table A-3. Type 3 Unloader - Cylinders: 6 or 12 Unloading Percentage: 33%, 66% *
% Load Compressor Start Output Unloader Output #1 Unloader Output #2 % Unload
0 (OFF) 0 0 0 100
33 1 1 1 66
66 1 0 1 33
100 1 0 0 0
Table A-4. Type 4 Unloader - Cylinders: 8 or 16 Unloading Percentage: 25%, 50% *
% Load Compressor Start Output Unloader Output #1 Unloader Output #2 % Unload
0 (OFF) 0 0 0 100
50 1 1 1 50
75 1 0 1 25
100 1 0 0 0
* 0 = output OFF 1 = output ON
A – 2
MicroVission Controller • Operation and Service Manual • Emerson • 2017VM-16 1.0
Appendix A Unloaders
Table A-5. Type 5 Unloader - Cylinders: 8, 16 Unloading Percentage: 25%, 50%, 75% *
% Load Compressor Start Output Unloader Output #1 Unloader Output #2 Unloader Output #3 % Unload
0 (OFF) 0 0 0 0 100
25 1 1 1 1 75
50 1 0 1 1 50
75 1 0 0 1 25
100 1 0 0 0 0
Table A-6. Type 6 Unloader - Cylinders: 4 or 8 Unloading Percentage: 50%, 100% *
% Load Compressor Start Output Unloader Output #1 Unloader Output #2 % Unload
0 (OFF) 0 0 0 100
0 (ON) 1 1 1 100
50 1 0 1 50
100 1 0 0 0
Table A-7. Type 7 Unloader - Cylinders: 6 or 12 Unloading Percentage: 33%, 66%, 100% *
% Load Compressor Start Output Unloader Output #1 Unloader Output #2 Unloader Output #3 % Unload
0 (OFF) 0 0 0 0 100
0 (ON) 1 1 1 1 100
33 1 0 1 1 66
66 1 0 0 1 33
100 1 0 0 0 0
Table A-8. Type 8 Unloader - Cylinders: 6 or 12 Unloading Percentage: 17%, 33%, 50%, 66% |Single cylinder on Unloader Output #1 *
% Load Compressor Start Output
0 (OFF) 0 0 0 0 100
33 1 0 1 1 66
50 1 1 0 1 50
66 1 0 0 1 33
83 1 1 0 0 17
100 1 0 0 0 0
Unloader Output #1
(single cylinder)
Unloader Output #2
(double cylinder)
Unloader Output #3
(double cylinder)
% Unload
* 0 = output OFF 1 = output ON
MicroVission Controller • Operation and Service Manual • Emerson • 2017VM-16 1.0
A – 3
Appendix A Unloaders
Table A-9. Type 9 Unloader - Cylinders: 6 or 12 Unloading Percentage: 17%, 33%, 50%, 66%, 83% Single cylinder on Unloader Output #1 *
% Load Compressor Start Output
0 (OFF) 0 0 0 0 100
17 1 1 1 1 83
33 1 0 1 1 66
50 1 1 0 1 50
66 1 0 0 1 33
83 1 1 0 0 17
100 1 0 0 0 0
Unloader Output
#1 (single cylinder)
Unloader Output #2
(double cylinder)
Unloader Output #3
(double cylinder)
% Unload
Table A-10. Type 10 Unloader - Cylinders: 7 Unloading Percentage: 29%, 57% *
% Load Compressor Start Output Unloader Output #1 Unloader Output #2 % Unload
0 (OFF) 0 0 0 100
43 1 1 1 57
71 1 0 1 29
100 1 0 0 0
Table A-11. Type 11 - Compressor with no Unloading *
% Load Compressor Start Output
0 (OFF) 0
100 1
Table A-12. Type 12 Unloader - Cylinders: 3 Unloading Percentage: 33% *
% Load Compressor Start Output
0 (OFF) 0 0 100
66 1 1 33
100 1 0 0
Unloader Output #1
(single cylinder)
% Unload
* 0 = output OFF 1 = output ON
A – 4
MicroVission Controller • Operation and Service Manual • Emerson • 2017VM-16 1.0
Appendix A Unloaders
Table A-13. Type 13 Unloader - Cylinders: 8, 16 Unloading Percentage: 25%, 50%, 75%, 100% *
% Load Compressor Start Output
0 (OFF) 0 0 0 0 0 100
0 (ON) 1 1 1 1 1 100
25 1 0 1 1 1 75
50 1 0 0 1 1 50
75 1 0 0 0 1 25
100 1 0 0 0 0 0
Unloader
Output #1
Unloader
Output #2
Unloader
Output #3
Unloader
Output #4
% Unload
Table A-14. Type 14 Unloader - Cylinders: 6 Unloading Percentage: 33%, 50%, 66% Unloading - Single cylinder on Unloader Output #1 *
Unloader
% Load Compressor Start Output
0 (OFF) 0 0 0 0 100
33 1 0 1 1 66
50 1 1 0 1 50
66 1 0 0 1 33
100 1 0 0 0 0
Output #1
(single cylinder)
Unloader
Output #2
(double cylinder)
Unloader
Output #3
(double cylinder)
% Unload
Table A-15. Type 15 Unloader - Cylinders: 8 Unloading Percentage: 13%, 25%, 38%, 50%, 63%, 75% Unloading - Single cylinder on Unloader Output #1 and Output #2 *
Unloader
% Load Compressor Start Output
0 (OFF) 0 0 0 0 0 100
25 1 1 1 1 1 75
37 1 0 1 1 1 63
50 1 0 0 1 1 50
62 1 0 1 0 1 38
75 1 0 0 0 1 25
87 1 0 1 0 0 13
100 1 0 0 0 0 0
Output #1
(single cylinder)
Unloader
Output #2
(single cylinder)
Unloader
Output #3
(double
cylinder)
Unloader
Output #4
(double
cylinder)
% Unload
* 0 = output OFF 1 = output ON
MicroVission Controller • Operation and Service Manual • Emerson • 2017VM-16 1.0
A – 5
Appendix A Unloaders
Unloading Percentage: 13%, 38%, 63% Unloading - Single cylinder on Unloader Output #1 *

Table A-16. Type 16 Unloader - Cylinders: 8

% Load Compressor Start Output
0 (OFF) 0 0 0 0 100
37 1 1 1 1 63
62 1 1 0 1 38
87 1 1 0 0 13
100 1 0 0 0 0
Unloader Output #1
(single cylinder)
Unloader
Output #2
(double cylinder)
Unloader
Output #3
(double cylinder)
% Unload
Table A-17. Type 17 Unloader - Cylinders: 6 Unloading Percentage: 33%, 50%, 66% Unloading - Single cylinder on Unloader Output #1 *
% Load Compressor Start Output
0 (OFF) 0 0 0 0 100
33 1 0 1 1 66
50 1 1 0 1 50
66 1 0 0 1 33
100 1 0 0 0 0
Unloader Output #1
(single cylinder)
Unloader Output #2
(double cylinder)
Unloader Output #3
(double cylinder)
% Unload
Table A-18. Type 18 Unloader - Cylinders: 5 Unloading Percentage: 40%, 60% | Single cylinder on Unloader Output #1 *
% Load Compressor Start Output
0 (OFF) 0 0 0 100
40 1 1 1 60
60 1 0 1 40
100 1 0 0 0
Unloader Output #1
(single cylinder)
Unloader Output #2
(double cylinder)
% Unload
* 0 = output OFF 1 = output ON
A – 6
MicroVission Controller • Operation and Service Manual • Emerson • 2017VM-16 1.0
Appendix A Unloaders
Table A-19. Type 19 Unloader - Cylinders: 3 Unloading Percentage: 33%, 66% Single cylinder on Unloader Output #1 and Output #2*
% Load Compressor Start Output
0 (OFF) 0 0 0 100
33 1 1 1 66
66 1 0 1 33
100 1 0 0 0
Unloader Output #1
(single cylinder)
Unloader Output #2
(single cylinder)
% Unload
Table A-20. Type 20 Unloader - Cylinders: 7 Unloading Percentage: 14%, 29%, 43%, 57% Single cylinder on Unloader Output #1
% Load Compressor Start Output
0 (OFF) 0 0 0 0 100
43 1 0 1 1 57
57 1 1 1 0 43
71 1 0 0 1 29
86 1 1 0 0 14
100 1 0 0 0 0
Unloader Output #1
(single cylinder)
Unloader Output #2
(double cylinder)
Unloader Output #3
(double cylinder)
% Unload
* 0 = output OFF 1 = output ON
MicroVission Controller • Operation and Service Manual • Emerson • 2017VM-16 1.0
A – 7

Appendix B Communication Tables

MicroVission Communication Table

Scope: MicroVission Programs – version 1.0 .
NOTES:
All ENUM variables are of INT (Integer) type
All F-INT data types represent oating point values as INT types multiplied by 10
All Pressures are in Psig
• All Temperatures are in Fahrenheit
Modbus TCP addressing is PLC-style (Base 1) addressing
On Error, Modbus TCP server only returns an error code of “Illegal Data Address”
All registers returned (INT and F-INT) are 2 bytes long
For Ethernet/IP, use INT data type and PLC-5 Word Range Read/Write MSG instructions
Remote commands cannot be issued if the panel is in the “Remote Lock” mode
Polling rates should not be less than 5 secs
Writes to the MicroVission should only occur when a value needs to be changed
Lower Range and Higher Range values mentioned are default values of MicroVission setpoints
Users can modify Lower Range & Higher Range values from MicroVission Panel and accordingly maintain their own table
Ethernet IP
Address
Modbus
Address
Digital Inputs Data Type Value Mode
N50:0 40001 Setpoint 1/2 INT 0 = OFF, 1 = ON Read NA NA
N50:1 40002 Remote Decrease INT 0 = OFF, 1 = ON Read NA NA
N50:2 40003 Remote Increase INT 0 = OFF, 1 = ON Read NA NA
N50:3 40004 Remote Start/Stop INT 0 = OFF, 1 = ON Read NA NA
N50:4 40005 Low Oil Level INT 0 = OFF, 1 = ON Read NA NA
N50:5 40006 High Level Shutdown INT 0 = OFF, 1 = ON Read NA NA
N50:6 40007 Compressor Auxiliary INT 0 = OFF, 1 = ON Read NA NA

Table B-1. Digital Inputs Block

Lower
Range
Higher
Range

Table B-2. Digital Outputs Block

Ethernet IP
Address
N51:0 40030 Oil Return Solenoid INT 0 = OFF, 1 = ON Read NA NA
N51:1 40031 Unloader #4 INT 0 = OFF, 1 = ON Read NA NA
N51:2 40032 Unloader #3 INT 0 = OFF, 1 = ON Read NA NA
N51:3 40033 Unloader #2 INT 0 = OFF, 1 = ON Read NA NA
N51:4 40034 Unloader #1 INT 0 = OFF, 1 = ON Read NA NA
N51:5 40035 Trip INT
N51:6 40036 Oil Crank Case Heater INT 0 = OFF, 1 = ON Read NA NA
N51:7 40037 Compressor Start INT 0 = OFF, 1 = ON Read NA NA
N51:8 40038 Remote Ready INT 0 = OFF, 1 = ON Read NA NA
MicroVission Controller • Operation and Service Manual • Emerson • 2017VM-16 1.0
Modbus
Address
Digital Outputs Data Type Value Mode
0 = OFF, 1 = ON
(ON when no Trip)
Read NA NA
Lower
Range
Higher
Range
B - 1
Appendix B Communication Tables
Table B-3. Analog Inputs Block
Ethernet IP
Address
N52:0 40060 Process Control F-INT Read NA NA
N52:1 40061 Oil Temperature F-INT Read NA NA
N52:2 40062 Discharge Temperature F-INT Read NA NA
N52:3 40063 Sucon Temperature F-INT Read NA NA
N52:4 40064 Filter Outlet Pressure F-INT Read NA NA
N52:5 40065 Filter Inlet Pressure F-INT Read NA NA
N52:6 40066 Oil Manifold Pressure F-INT Read NA NA
N52:7 40067 Discharge Pressure F-INT Read NA NA
N52:8 40068 Sucon Pressure F-INT Read NA NA
N52:9 40069 Motor Amps F-INT Read NA NA
Modbus
Address
Analog Inputs Data Type Value Mode
Lower
Range
Higher
Range

Table B-4. Analog Outputs Block

Ethernet IP
Address
N53:0 40100 Compressor VFD Speed F-INT Currently Unused Read NA NA
N53:1 40101 Not Assigned F-INT Currently Unused Read NA NA
N53:2 40102 Not Assigned F-INT Currently Unused Read NA NA
N53:3 40103 Not Assigned F-INT Currently Unused Read NA NA
N53:4 40104 Not Assigned F-INT Currently Unused Read NA NA
N53:5 40105 Not Assigned F-INT Currently Unused Read NA NA
Modbus
Address
Analog Outputs Data Type Value Mode
Lower
Range

Table B-5. Calculated Values Block

Ethernet IP
Address
Modbus
Address
Calculated Values Data Type Value Mode
Lower
Range
Higher
Range
Higher
Range
N54:0 40120 Filter Dierenal Pressure F-INT Read NA NA
N54:1 40121 Pressure Rao F-INT Read NA NA
N54:2 40122 Oil Pressure Dierenal F-INT Read NA NA
B - 2
MicroVission Controller • Operation and Service Manual • Emerson • 2017VM-16 1.0
Appendix B Communication Tables
Ethernet IP
Address
N55:0 40140 An-Recycle Time (Minutes) INT Read NA NA
N55:1 40141 Compressor Status ENUM Read NA NA
N55:2 40142 Alarm Status Word #1 WORD Read NA NA
N55:3 40143 Alarm Status Word #2 WORD Read NA NA
N55:4 40144 Warning Status Word #1 WORD Read NA NA
N55:5 40145 Warning Status Word #2 WORD Read NA NA
N55:6 40146 Trip Status Word #1 WORD Read NA NA
N55:7 40147 Trip Status Word #2 WORD Read NA NA
N55:8 40148 Trip Status Word #3 WORD Read NA NA
N55:9 40149 Trip Status Word #4 WORD Read NA NA
N55:10 40150 Current Run Mode ENUM
Modbus Address
Statuses

Table B-6. Statuses Block

Data Type
0 = Idle 1 = Waing 2 = Starng 3 = Manual 4 = Auto 5 = Remote Auto 6 = Remote Manual 7 = Remote Step Hold % 8 = Remote Ready (Idle) 9 = Direct I/O Auto 10 = Direct I/O Manual 11 = Direct I/O Step
Hold %
12 = Auto Sequencing
Value Mode
Read NA NA
Lower
Range
Higher
Range
Bit 0 = High Sucon
Pressure
Bit 1 = High Discharge
Pressure
N55:11 40151 Status Message WORD
N55:12 40152 Remote Lock Mode INT 0 = OFF, 1 = ON Read NA NA
N55:13 40153 Runme Hours (x1000) INT
N55:14 40154 Runme Hours (1-999) INT Read NA NA
MicroVission Controller • Operation and Service Manual • Emerson • 2017VM-16 1.0
Bit 2 = Low Sucon
Pressure Bit 3 = High Motor Cur­rent
Bit 4 = Auto Cycle Bit 5 = Run Permissive
Read NA NA
Read NA NA
B - 3
Appendix B Communication Tables

Alarm Status Words

Statuses: Alarm Status Word(s) – currently 17 alarms, so both Alarm Status Word 1 and 2 are used, with each posi­tion indicating an alarm:
MSB LSB
[Bit 15, Bit 14, Bit 13 ... Bit 3, Bit 2, Bit 1, Bit 0]

Table B-7. Alarm Status Words

Word 1 Word 2
Bit 0 = Low Sucon Pressure Alarm Bit 0 = Remote Comm Time out
Bit 1 = Low Process Temperature Alarm Bit 1 = Unused
Bit 2 = Low Process Pressure Alarm Bit 2 = Unused
Bit 3 = Low Sucon Temperature Alarm Bit 3 = Unused
Bit 4 = Low Crankcase Oil Temperature Alarm Bit 4 = Unused
Bit 5 = Low Oil Pressure Di. Alarm Bit 5 = Unused
Bit 6 = Low Oil Level Alarm Bit 6 = Unused
Bit 7 = High Discharge Pressure Alarm Bit 7 = Unused
Bit 8 = High Discharge 2 Pressure Alarm Bit 8 = Unused
Bit 9 = High Process Temperature Alarm Bit 9 = Unused
Bit 10 = High Process Pressure Alarm Bit 10 = Unused
Bit 11 = High Discharge Temperature Alarm Bit 11 = Unused
Bit 12 = High Discharge 2 Temperature Alarm Bit 12 = Unused
Bit 13 = High Crankcase Oil Temperature Alarm Bit 13 = Unused
Bit 14 = High Filter Dierenal Pressure Alarm Bit 14 = Unused
Bit 15 = High Motor Current Alarm Bit 15 = Unused
B - 4
MicroVission Controller • Operation and Service Manual • Emerson • 2017VM-16 1.0
Appendix B Communication Tables

Warning Status Words

Statuses: Warning Status Word(s) – currently 20 warnings, so both Warning Status Word 1 and 2 are used, with each position indicating an alarm:
MSB LSB
Word 1 Word 2
Bit 0 = Low Sucon Pressure Warning Bit 0 = Low Discharge 2 Pressure Warning
Bit 1 = Low Process Temperature Warning Bit 1 = Low Discharge 2 Temperature Warning
Bit 2 = Low Process Pressure Warning Bit 2 = Low Oil Filter In Pressure Warning
Bit 3 = Low Sucon Temperature Warning Bit 3 = Low Oil Filter Out Pressure Warning
Bit 4 = Low Crankcase Oil Temperature Start Warning Bit 4 = Unused
Bit 5 = Low Oil Level Warning Bit 5 = Unused
Bit 6 = High Discharge Pressure Warning Bit 6 = Unused
[Bit 15, Bit 14, Bit 13 ... Bit 3, Bit 2, Bit 1, Bit 0]

Table B-8. Warning Status Words

Bit 7 = High Discharge 2 Pressure Warning Bit 7 = Unused
Bit 8 = High Process Pressure Warning Bit 8 = Unused
Bit 9 = High Discharge Temperature Warning Bit 9 = Unused
Bit 10 = High Discharge 2 Temperature Warning Bit 10 = Unused
Bit 11 = High Crankcase Oil Temperature Warning Bit 11 = Unused
Bit 12 = High Filter Di. Pressure Start Warning Bit 12 = Unused
Bit 13 = High Level Shutdown Warning Bit 13 = Unused
Bit 14 = Low Discharge Pressure Warning Bit 14 = Unused
Bit 15 = Low Discharge Temperature Warning Bit 15 = Unused
MicroVission Controller • Operation and Service Manual • Emerson • 2017VM-16 1.0
B - 5
Appendix B Communication Tables

Trip Status Words

Statuses: Trip Status Word(s) – currently 48 trips, so all Trip Status Words 1, 2, 3 and 4 are used, with each position indicating an alarm:
MSB LSB
[Bit 15, Bit 14, Bit 13 ... Bit 3, Bit 2, Bit 1, Bit 0]

Table B-9. Trip Status Words (Words 1 & 2)

Word 1 Word 2
Bit 0 = Low Sucon Pressure Inhibit Bit 0 = Low Discharge Temperature Inhibit
Bit 1 = Low Process Temperature Inhibit Bit 1 = Low Discharge 2 Pressure Inhibit
Bit 2 = Low Process Pressure Inhibit Bit 2 = Low Discharge 2 Temperature Inhibit
Bit 3 = Low Crankcase Oil Temperature Start Inhibit Bit 3 = Low Oil Filter In Pressure Inhibit
Bit 4 = Low Oil Level Inhibit Bit 4 = Low Oil Filter Out Pressure Inhibit
Bit 5 = Low Sucon Temperature Inhibit Bit 5 = Unused
Bit 6 = High Discharge Pressure Inhibit Bit 6 = Unused
Bit 7 = High Discharge 2 Pressure Inhibit Bit 7 = Unused
Bit 8 = High Process Pressure Inhibit Bit 8 = Unused
Bit 9 = High Discharge Temperature Inhibit Bit 9 = Unused
Bit 10 = High Discharge 2 Temperature Inhibit Bit 10 = Unused
Bit 11 = High Crankcase Oil Temperature Inhibit Bit 11 = Unused
Bit 12 = High Filter Dierenal Pressure Start Inhibit Bit 12 = Unused
Bit 13 = Compressor Interlock Inhibit Bit 13 = Unused
Bit 14 = High Level Shutdown Inhibit Bit 14 = Unused
Bit 15 = Low Discharge Pressure Inhibit Bit 15 = Unused
B - 6
MicroVission Controller • Operation and Service Manual • Emerson • 2017VM-16 1.0
Appendix B Communication Tables

Table B-9. Trip Status Words (Words 3 & 4)

Bit 0 = Low Sucon Pressure Trip Bit 0 = Compressor Interlock Trip
Bit 1 = Low Process Temperature Trip Bit 1 = False Start
Bit 2 = Low Process Pressure Trip Bit 2 = Starter Shutdown Trip
Bit 3 = Low Sucon Temperature Trip Bit 3 = Remote Comm Time out
Bit 4 = Low Crankcase Oil Temperature Trip Bit 4 = IO Comm Trip
Bit 5 = Low Oil Pressure Di. Trip Bit 5 = Low Discharge Pressure Trip
Bit 6 = Low Oil Level Trip Bit 6 = Low Discharge Temperature Trip
Bit 7 = High Discharge Pressure Trip Bit 7 = Low Discharge 2 Pressure Trip
Bit 8 = High Discharge 2 Pressure Trip Bit 8 = Low Discharge 2 Temperature Trip
Bit 9 = High Process Pressure Trip Bit 9 = Low Oil Filter In Pressure Trip
Bit 10 = High Discharge Temperature Trip Bit 10 = Low Oil Filter Out Pressure Trip
Bit 11 = High Discharge 2 Temperature Trip Bit 11 = Unused
Bit 12 = High Crankcase Oil Temperature Trip Bit 12 = Unused
Bit 13 = High Filter Dierenal Pressure Trip Bit 13 = Unused
Bit 14 = High Level Shutdown Trip Bit 14 = Unused
Bit 15 = High Motor Amps Trip Bit 15 = Unused
Word 3 Word 4
MicroVission Controller • Operation and Service Manual • Emerson • 2017VM-16 1.0
B - 7
Loading...