Emerson Varec 5000X3, Varec 5000X2, Varec 5000X1, Varec 5000X6, Varec 5010X1 Installation, Operation And Maintanance Instructions

...
VAREC SERIES 5000/5010 FLAME ARRESTERS
InstructIon, operatIon and maIntenance manual
Before installation these instructions must be fully read and understood
5010 series ­horizontal
5000 series ­vertical
DISCLAIMER OF WARRANTIES
The contract between the seller and the buyer states the entire obligation of the seller. The contents of this instruction manual shall not become part of or modify any prior or existing agreement, commitment or relationship between the seller and buyer. There are no express or implied warranties set out in this instruction manual. The only warranties that apply are those in the existing contract between the seller and buyer. The Varec 5000/5010 Series flame arresters have not been tested by Varec under all possible operational conditions and Varec does not have all the data relative to your application. The information in this instruction manual is not all inclusive and does not and cannot take into account all unique situations. Consequently, you should review this product literature in view of your application. If you have any further questions, please contact Varec for assistance.
SAFETY PRECAUTIONS
Read and understand this instruction manual before installing, operating or performing maintenance on varec 5000/5010 series flame arresters. Follow all precautions and warnings noted herein when installing, operating or performing maintenance on this equipment.
WARNING
Flame arresters should be installed upstream and not more than 15 feet from the ignition source for use in accordance with UL approval. Flame arresters must be isolated from the gas piping before performing maintenance. All gas must be blocked and pressure safely vented. Flame arresters are not capable of stopping a flame front in mixtures of air with hydrogen, acetylene, ethylene oxide, or carbon disulfide.
Safety precaution definitions:
CAUTION
Damage to equipment may result if this precaution is disregarded.
WARNING
Direct injury to personnel or damage to equipment which can cause injury to personnel may result if this precaution is not followed.
GENERAL
The Varec Model 5000/5010 Series flame arresters are designed to stop the propagation of flame from external sources. They are used on storage tank roofs, digester covers and in waste gas piping systems. These units are installed where fire protection is required in combination with pressure relief or shut-off valves in vapor balancing, recovery or open vent piping systems.
NOTE
Varec flame arresters bearing UL approval are tested for use on oil storage tanks, installed not more than 15 feet from the open end of the vent pipe (reference UL 525). These test conditions may not represent the actual service conditions or piping system design. API publication 2028 states that the arresters should be independently tested under actual service conditions before installation.
LIMITATIONS OF SELLER'S LIABILITY
If it is determined that this instruction manual created some new warranties, Varec’s liability shall be limited to repair or replacement under the standard warranty clause. In no case shall Varec’s liability exceed that stated as Limitations of Remedy in the contract between Varec and our customer.
Emerson.com/FinalControl
WARNING
Flame arresters are not capable of stopping a flame front in mixtures of air with hydrogen, acetylene, ethylene oxide, or carbon disulfide.
Flame arrester should be installed upstream of and not more than 15 feet from the ignition source for use in accordance with UL aproval.
Engineering Doc. #33-07765 Rev. G
© 2017 Emerson. All Rights Reserved. VCIOM-03772-EN 18/02
VAREC SERIES 5000/5010 FLAME ARRESTER
InstructIon, operatIon and maIntenance manual
CONSTRUCTION
WARNING
The standard unit is constructed of a heavy cast housing containing a removable multiplate bank assembly with aluminum extensible frame. A fixed 316 S.S. frame is also available. Working pressure rating is 10 Psig (69.0 kPa). For material selection see Tables 4 and 6.
In all cases where the ratio of upper limit/lower limit exceeds 10, the use of flame arresters is not recommended. Also, the presence of any O is dangerous because of the lack of homogeneity which is possible in gas mixtures. Any surplus of oxygen provides the potential for rapid explosion.
2
PRACTICAL LIMITATIONS
While flame arresters decrease the possibility of flame propagation in a system, certain variables must be evaluated to ensure safety. The relative fire hazard of flammable mixtures can be judged by the upper and lower explosive limits. These limits are expressed as percent by volume of the gas or vapor in air. The explosive range is that span of concentrations lying between the lower and upper limits. The upper limit is the point at which the mixture is too rich to burn, i.e., contains too little oxygen to support combustion. The broader the explosive range, the easier it is to create an air-gas explosive mixture. Conversely, when the explosive range is narrow, the chance of developing a hazardous air-gas mixture decreases.
Table 1 gives the approximate limits of flammability of some single gases, vapors and industrial mixtures in air at common temperatures and at atmospheric pressure.
OPERATION
Flame arresters do not prevent ignition of flammable mixtures, but do prevent the propagation of a flame. The Varec 5000/5010 Series flame arresters stop flame propagation by absorbing and dissipating heat through the surface area of the bank sheets. Heat is absorbed as ignited gas attempts to pass through the small passages within the bank assembly. This action lowers the temperature of the gas below its ignition point and quenches the flame.
TABLE 1 - FLAMMABILITY LIMIT OF GASES AND VAPOR
Limits in air pressure
Product
Acetyldehyde 4.1 55 Ethyl-Alcohol 4.3 19 Methyl-Alcohol 7.3 36 Acetone 3 11 Ethyl-Bromide 6.7 11.3 Methyl-Chloride 10.7 17.4 Acetylene 2.5 81 Ehtyl-Chloride 3.8 15.4 Methyl-Ethyl-Ketone 1.8 10 Ammonia 15 28 Ethyl-Ether 1.9 48 Methyl-Formate 5.9 20 Benzene 1.4 7.1 Ethyl-Formate 2.7 13.5 Methyl-Proply-Ketone 1.5 8 Benzine 1.1 Ethylene 3.1 32 Natural gas 3.8 17 Blast furnace gas 35 74 Furfural 2.1 Noriane 0.8 Butadiene 2 11.5 Gasoline 1.4 7.6 Octane 1 Butane 1.9 8.5 Hexane 1.2 7.5 Pentane 1.5 7.8 Butylene 2 9.6 Heptane 1.2 6.7 Propane 2.1 9.5 Carbon Disulphide 1.25 44 Hydrocyanic acid 6 41 Propyl-Alcohol 2.1 13.5 Carbon Monoxide 12.5 74 Hydrogen 4 75 Propylene 2.4 10.3 Cyclohexane 1.3 8 Hydrogen-Sulhide 4.3 5 Pyridine 1.8 12.4 Cyclopropane 2.4 10.4 Isobutane 1.8 8.4 Styrene 1.1 6.1 Decane 0.8 5.4 Isopentane 1.4 7.6 Toluene 1.4 6.7 Ethane 3 12.5 Isopropyl-Alcohol 2 12 Water gas 7 72 Ethyl-Acentate 2.5 9 Methane 5.3 14 Xylene 1 6
Reference: Bureau of Mines bulletin 503, Limits of flammability of gases and vapors, 1952
Lower Higher Lower Higher Lower Higher
Product
Limits in air pressure
Limits in air percent
Product
2
VAREC SERIES 5000/5010 FLAME ARRESTER
InstructIon, operatIon and maIntenance manual
INSTALLATION
The 5000 Series flame arrester (ref. Figure 2) is designed for vertical application in pipe lines and on tank or digester roofs. The 5010 Series flame arrester (ref. Figure 3) is designed for horizontal positioning in pipelines, however, it may be in either direction.
The cover, roof or piping system must have the appropriate flange(s) installed for mating with the flame arrester. Flame arrester with aluminum housings should be mated with an ANSI Class 125 F.F. flange. The 316 stainless steel housing should be mated with an ANSI Class 150 R.F. flange. The arrester must be located with clearance allowed for removal of the bank assembly.
The flange of vertical mounting must be plumb and level to ensure proper operation of the pressure relief valve (when used in combination with the flame arrester). The flange for horizontal mounting must be oriented to ensure that arrester drain hole will be at the extreme bottom (6 o’clock) position.
1. Remove the flame arrester from the shipping container or pallet.
2. Remove flange protectors. Inspect for and remove any packing or other loose material in the inlet/outlet chambers of the housing.
3. Remove cover and extract bank assembly. Inspect for shipping debris or damage and correct as required. Insert bank and replace cover. Tighten cap screws uniformly.
WARNING
The aluminum bank assembly weighs from 10 to 80 pounds and the 316 S.S. assembly is substantially heavier. Use the appropriate tools and equipment when handling these units to avoid injury.
4. Place the appropriate full face flange gasket (by others) on the flange.
CAUTION
If it is necessary to mate an ANSI Class 125 F.F. flange with an ANSI Class 150 R.F. flange, use the proper spacer to convert the raised face to a flat face.
5. Place the arrester on the flange, and position the unit so that the bank assembly can be readily extracted for inspection and maintenance.
NOTE
When installing the Model 5010 in a horizontal position, check the drain hole to see that it is functional. Install the appropriate drain piping along with a Varec Drip trap or an isolation valve.
6. Install mounting hardware and tighten uniformly.
The flame arrester is now installed and ready for use.
MAINTENANCE
Maintenance is the most important factor in the operation of the flame arrester. The bank sheets must be kept clean to prevent a decrease in gas flow through the system and loss of heat absorbing efficiency.
WARNING
Failure to properly maintain the unit could result in reduction of safety and impairment of system operation.
A regular inspection program is important. The frequency of inspection is determined by the application. Consideration should be given to the amount and nature of water or solids in the gas and the corrosivity of the process stream. Generally, the first inspection should be made 30 days after commissioning. Inspections should continue on a 30 day schedule unless excessive deposits or accumulation of foreign matter are found. If so, the frequency of inspections should be increased. Adjust inspection frequency to maintain free and unrestricted flow through the arrester.
WARNING
Flame arrester must be isolated from the gas piping before removing cover plate. All gas must be blocked and pressure safely vented. Ensure that arrester is cool after a fire, or wear appropriate protective clothing.
1. Remove cover cap screws and cover plate. Pull out bank assembly by pulling on bank handle. If desired, the bank assembly may be removed from the housing.
WARNING
The aluminum bank assembly weighs from 10 to 80 pounds and the 316 S.S. assembly is substantially heavier. Use the appropriate tools and equipment when handling these units to avoid injury.
a. Extend the aluminum frame to its full open
position. Both sides of each grid sheet may be inspected and cleaned without removal from the frame.
b. The 316 S.S. frame is non-extensible and
must be disassembled to access the bank sheets.
2. Check for corrosion, bent, warped or otherwise damaged sheets that could cause an opening for a direct flame path. Replace with a new bank assembly if necessary.
3. Bank assembly cleaning procedure is based on the type of residue to be removed. Determine if residue type is Group I, II, or III. Follow the cleaning procedures for the selected group.
WARNING
Use all volatile and flammable solvents carefully to avoid ignition or prolonged breathing. Use protective clothing and gloves when using acid to avoid burns from contact with skin.
3
Loading...
+ 5 hidden pages