Drive software version
The SM-I/O 24V Protected can only be used with the following drive software version:
Index ..............................................................................39
SM-I/O 24V Protected User Guide3
Issue Number: 2www.controltechniques.com
1How to use this guide
1.1Intended personnel
This guide is intended for personnel who have the necessary training and experience in
system design, installation, commissioning and maintenance.
1.2Information
This guide contains information covering the identification of the Solutions Module,
terminal layout for installation, fitting of the Solutions Module to the drive, parameter
details and diagnosis information. Additional to the aforementioned are the
specifications of the Solutions Module.
4SM-I/O 24V Protected User Guide
www.controltechniques.comIssue Number: 2
2Introduction
2.1Features
The SM-I/O 24V Protected is designed as an over voltage protected I/O Solution
Module.
The Solutions Module is able to withstand a +48V input voltage being applied to the
+24V Digital I/O terminals.
The SM-I/O 24V Protected can be used on the following products:
•Unidrive SP
•Commander SK
•Commander GP20
The SM-I/O 24V Protected increases the I/O capability of the drive by adding the
following to the existing I/O:
•2 x Analogue current outputs
•4 x Digital inputs/outputs*
•3 x Digital inputs
•2 x Relay (30Vdc contact rating)**
All connections from the Solutions Module to the drive are made via the drive connector.
Connections from external equipment to the relay, digital I/O and analogue outputs are
made via a 17-way pluggable screw connector.
On the Unidrive SP a total of three SM-I/O 24V Protected modules can be fitted at any
one time. On the Commander SK only one can be fitted, on the Commander GP20 two
can be fitted.
*Only three digital outputs are available with Commander SK.
1. The label located on the underside of the Solutions Module.
2. The colour coding across the front of the Solutions Module, with the SM-I/O 24V
Protected being cobalt blue.
SM-I/O 24V Protected User Guide5
Issue Number: 2www.controltechniques.com
Figure 2-2 SM-I/O 24V Protected label
S
olutions Module
name
SM-I/O 24V Protected
Hardware
issue
number
Issue: 2.00
Ser No : 3000005001
STDJ41
2.2.1Date code format
The date code is split into two sections: a letter followed by a number.
The letter indicates the year, and the number indicates the week number (within the
year) in which the Solutions Module was built.
The letters go in alphabetical order, starting with A in 1990 (B in 1991, C in 1992 etc.).
Example:
A date code of L35 would correspond to week 35 of year 2002.
2.3Conventions used in this guide
The configuration of the host drive and Solutions Module is done using menus and
parameters. A menu is a logical collection of parameters that have similar functionality.
In the case of a Solutions Module, the parameters will appear in menu 15 for the
Commander SK, and in menu 15, 16 or 17 for the Unidrive SP and 15, 16 on the
Commander GP20 depending on the slot the module is fitted into. The menu is
determined by the number before the decimal point.
The method used to determine the menu or parameter is as follows:
•Pr xx.00 - signifies any menu and parameter number 00.
•Pr x.XX - where x signifies the menu allocated to the Solutions Module (this could
be 15, 16 or 17 on the Unidrive SP, 15 or 16 on Commander GP20 but will always
be 15 on the Commander SK) and XX signifies the parameter number.
Customer
and date code
Serial number
6SM-I/O 24V Protected User Guide
www.controltechniques.comIssue Number: 2
2.4Solutions Module I/O
How to use this guide Safety Information
NOTE
NOTE
NOTE
Solution Module I/O only operates in positive logic mode.
All I/O and relays are user programmable for function and signal processing.
All new source and destination routing only changes to new set up locations when the
drive is reset.
NOTE
By default, the digital inputs/outputs on the Solutions Module are configured to operate
as inputs, except Digital I/O 4 which is configured as an output (input only for
Commander SK).
NOTE
The logic state of a digital input will operate even without a destination parameter
programmed.
2.5Digital I/O
All digital I/O complies with IEC 61131-2, clause 3.3.1 type 1, (i.e. >2mA @ +15Vdc).
For type 2 input, the user will need to add extra load externally.
Three terminals are dedicated digital inputs (4 with Commander SK); the functionality of
these inputs is as follows:
•The logic state of the input is monitored by a RO parameter
•The logic state can be inverted
•The digital input can be programmed to any unprotected parameter. The destination
parameter value will always be either 0 or 1 depending on the state of the input.
Programmable digital inputs / outputs 4**
Four terminals are programmable as either digital inputs or output terminals (3 with
Commander SK), the functionality of these terminals is as follows:
Input
•The logic state of each input is monitored by a RO parameter
•The logic state can be inverted
•The digital input can be programmed to any unprotected parameter. The destination
parameter value will always be either 0 or 1 depending on the state of the input
Output
•The logic state of each output is monitored by a RO parameter
•The logic state can be inverted
•The digital outputs can be sourced from any parameter.
In the case where an integer parameter is used as the source, the threshold of
the output switching between low and high states is 50% of the parameter’s
maximum.
E.g. Source parameter = Pr 18.11 (maximum = 32767)
50% of 32767 = 16383 (due to integer truncation)
Therefore, if Pr 18.11 ≥ 16383 the output will be high
SM-I/O 24V Protected User Guide7
Issue Number: 2www.controltechniques.com
•The four digital outputs of the Solutions Module (three digital outputs with
Commander SK) are able to source 40 mA to the total combination of output
channels (e.g. 4 x 10mA or 1 x 40mA). When the current drawn exceeds safe limits,
all the outputs will be disabled through hardware and trip the drive to alert the user
to the fault condition.
**A maximum of three digital outputs are available with Commander SK.
2.6Analogue output
FunctionQuantity
Unipolar current output2
Two terminals have a dedicated analogue output with the following functions:
•The output can be used to convey the value of any valid source parameter to
external equipment*.
•The output operates in one of the following modes as set in Pr
and 20-4.
•A scaling factor can be applied to the analogue output signal*
*Only available on analogue output 1 with Commander SK.
2.7Relays
FunctionQuantity
Number of relays2 (1 on Commander SK)
The relay can be used to convey the logic state of any parameter to external equipment.
The logic state is processed as follows:
•Any source parameter is assigned to relay.
•The logic state can be inverted.
•The software state of the coil is monitored by a parameter.
x.39
: 0-20, 20-0, 4-20
8SM-I/O 24V Protected User Guide
www.controltechniques.comIssue Number: 2
3Safety Information
3.1Warnings, Cautions and Notes
A Warning contains information, which is essential for avoiding a safety hazard.
WARNING
How to use this guide
Safety Information
A Caution contains information, which is necessary for avoiding a risk of damage to the
product or other equipment.
CAUT ION
NOTE
A Note contains information, which helps to ensure correct operation of the product.
3.2Electrical safety - general warning
The voltages used in the drive can cause severe electrical shock and/or burns, and
could be lethal. Extreme care is necessary at all times when working with or adjacent to
the drive.
Specific warnings are given at the relevant places in this User Guide.
3.3System design and safety of personnel
The drive is intended as a component for professional incorporation into complete
equipment or a system. If installed incorrectly, the drive may present a safety hazard.
The drive uses high voltages and currents, carries a high level of stored electrical
energy, and is used to control equipment which can cause injury.
Close attention is required to the electrical installation and the system design to avoid
hazards either in normal operation or in the event of equipment malfunction. System
design, installation, commissioning and maintenance must be carried out by personnel
who have the necessary training and experience. They must read this safety information
and this User Guide carefully.
The STOP and SECURE DISABLE functions of the drive do not isolate dangerous
voltages from the output of the drive or from any external option unit. The supply must
be disconnected by an approved electrical isolation device before gaining access to the
electrical connections.
With the sole exception of the SECURE DISABLE function, none of the drive
functions must be used to ensure safety of personnel, i.e. they must not be used
for safety-related functions.
Note that the SECURE DISABLE function is only available as standard on the Unidrive
SP and Commander GP20. The Commander SK does not have a SECURE DISABLE
input.
Careful consideration must be given to the functions of the drive which might result in a
hazard, either through their intended behaviour or through incorrect operation due to a
fault. In any application where a malfunction of the drive or its control system could lead
to or allow damage, loss or injury, a risk analysis must be carried out, and where
necessary, further measures taken to reduce the risk - for example, an over-speed
protection device in case of failure of the speed control, or a fail-safe mechanical brake
SM-I/O 24V Protected User Guide9
Issue Number: 2www.controltechniques.com
in case of loss of motor braking.
The SECURE DISABLE function and secure input meet the requirements of EN954-1
category 3 for the prevention of unexpected starting of the drive. They may be used in a
safety-related application. The system designer is responsible for ensuring that the
complete system is safe and designed correctly according to the relevant safety
standards.
3.4Environmental limits
Instructions in the Unidrive SP User Guide, Commander GP20 User Guide,
Commander SK Getting Started Guide, Commander SK Technical Data Guide
regarding transport, storage, installation and use of the drive must be complied with,
including the specified environmental limits. Drives must not be subjected to excessive
physical force.
3.5Compliance with regulations
The installer is responsible for complying with all relevant regulations, such as national
wiring regulations, accident prevention regulations and electromagnetic compatibility
(EMC) regulations. Particular attention must be given to the cross-sectional areas of
conductors, the selection of fuses or other protection, and protective earth (ground)
connections.
The Unidrive SP User Guide, Commander GP20 User Guide and Commander SK Technical Data Guide contain instructions for achieving compliance with specific EMC
standards.
Within the European Union, all machinery in which this product is used must comply
with the following directives:
98/37/EC: Safety of machinery.
89/336/EEC: Electromagnetic Compatibility.
3.6Motor
Ensure the motor is installed in accordance with the manufacturer’s recommendations.
Ensure the motor shaft is not exposed.
Standard squirrel cage induction motors are designed for single speed operation. If it is
intended to use the capability of the drive to run a motor at speeds above its designed
maximum, it is strongly recommended that the manufacturer is consulted first.
Low speeds may cause the motor to overheat because the cooling fan becomes less
effective. The motor should be fitted with a protection thermistor. If necessary, an
electric forced vent fan should be used.
The values of the motor parameters set in the drive affect the protection of the motor.
The default values in the drive should not be relied upon.
It is essential that the correct value is entered in the motor rated current parameter:
Pr 0.46 for Unidrive SP / Commander GP20 and Pr 06 in Commander SK. This affects
the thermal protection of the motor.
3.7Adjusting parameters
Some parameters have a profound effect on the operation of the drive. They must not
be altered without careful consideration of the impact on the controlled system.
Measures must be taken to prevent unwanted changes due to error or tampering.
10SM-I/O 24V Protected User Guide
www.controltechniques.comIssue Number: 2
4Installing the Solutions Module
Before installing the Solutions Module, refer to Chapter 3 Safety Information on page 9.
WARNING
Do not remove the Solutions Module when the drive is powered-up. This could damage
CAUT ION
4.1Installation
4.1.1Unidrive SP / Commander GP20
Figure 4-1 Removing the Uni SP terminal cover
the drive and/or the Solutions Module.
Three Solutions Module slots are available on Unidrive SP and two on Commander
GP20. The Solutions Module can be plugged into any of these slots but it is
recommended that slot 3 be used for the first Solutions Module, then slot 2 and then slot
1 (slot 2 and then slot 1 on Commander GP20). This ensures the maximum mechanical
support for the Solutions Module once fitted. See Figure 4-2.
Figure 4-2 Fitting and removing a Solutions
Module into the Unidrive SP
How to use this guide Safety InformationIntroduction
Solutions Module
Installing the
Pz2
1 N m (8.8 lb in)
SM slot 1
(Menu 15)
SM slot 2
(Menu 16)
SM slot 3
(Menu 17
1. Before installing a Solutions Module in any drive, ensure the AC supply has been
disconnected for at least 10 minutes.
2. Ensure that any +24V and low voltage DC power supplies (if used) have been
disconnected from the drive.
3. Check that the exterior of the Solutions Module is not damaged and the multiway
connector on the underside of the module is free from dirt and debris.
4. Do not install a damaged or dirty Solutions Module in the drive.
5. Remove the terminal cover from the drive as shown in Figure 4-1.
6. Position the drive connector of the Solutions Module over the appropriate connector
of the drive. Push the Solutions Module towards the rear of the drive until it locks
into place. Make the connections to the Solutions Module as appropriate.
7. Re-fit the terminal cover to the drive by reversing the procedure shown in Figure 4-1.
SM-I/O 24V Protected User Guide11
Issue Number: 2www.controltechniques.com
8. Connect the AC supply or low voltage DC supply (if used) to the drive.
9. When a Solutions Module is fitted to a Unidrive SP / Commander GP20 for the first
time, as the drive is powered-up, the drive will trip on SL1.dF or SL2.dF or SL3.dF
depending on which slot the Solutions Module is fitted to (SL1.dF or SL2.dF on
Commander GP20). A parameter save must be performed.
Set Pr xx.00 = 1000 (or 1001 in the case of solely using the 24V back-up power
supply) and press the Stop/Reset button. If a parameter save is not performed, the
drive will trip on the above trips the next time the drive is powered up.
NOTE
NOTE
NOTE
NOTE
When using the 24V back-up power supply only, the SLx.dF trip will not occur (as the
drive is already displaying a UU trip).
When fitting two or more Solutions Modules simultaneously, the SLx.dF trip is only
applicable to the module fitted in the lowest numerical slot.
If an SLx.dF trip is not seen after the first power-up, the Solutions Module is not fitted
properly to the drive. Power down the drive, remove and re-fit the Solutions Module.
Then power can be re-applied to the drive.
10. To access the advanced parameters refer to the Unidrive SP User Guide / Commander GP20 User Guide.
11. Check that Menu 15 (slot 1), 16 (slot 2), or 17 (slot 3) parameters are now available
(depending on which slot is used). Menu 15 (slot1), or 16 (slot 2) on Commander
GP20.
12. Check that Pr 15.01, Pr 16.01 or Pr 17.01 shows the correct code for the SM-I/O
24V Protected: 205. (Pr 15.01 or Pr 16.01 on Commander GP20).
13. Power the drive down and back up. The Solutions Module is now ready for
programming.
If the SM-I/O 24V Protected is changed for another type of Solutions Module, the drive
will trip as in step 9. Follow the above procedure.
14. If the checks in step 11 and step 12 fail, either the Solutions Module is not fully
inserted, or it is faulty.
15. If a trip code is now present refer to Chapter 6 Diagnostics on page 32.
12SM-I/O 24V Protected User Guide
www.controltechniques.comIssue Number: 2
4.1.2Commander SK
One Solutions Module slot is available on Commander SK. See Figure 4-4.
To allow a Solutions Module to be fitted to Commander SK, a protective cover must be
removed to allow access to the PCB edge connector (see Figure 4-3). This protective
WARNING
NOTE
cover provides protection from direct contact of the PCB edge connector by the user.
When this cover is removed and Solutions Module fitted, the Solutions Module provides
the protection from direct contact by the user. If the Solutions Module is then removed,
this PCB edge connector becomes exposed. The user is required to provide protection
in this case.
Figure 4-3 Removing the Commander SK
terminal cover
Pz1
0.4 N m (3.5 lb in)
1. Before installing a Solutions Module in any drive, ensure the AC supply has been
disconnected for at least 10 minutes.
2. Check that the exterior of the Solutions Module is not damaged and the multiway
connector on the underside of the module is free from dirt and debris.
3. Do not install a damaged or dirty Solutions Module in the drive.
4. Remove the terminal cover from the drive as shown in Figure 4-3.
5. Ensure that the plastic tab which covers the drive’s Solutions Module connector is
removed before fitting any option. See Figure 4-4.
Position the drive connector of the Solutions Module over the appropriate connector
of the drive. Push the Solutions Module towards the rear of the drive until it locks
into place. Make the connections to the Solutions Module as appropriate.
6. Re-fit the terminal cover to the drive by reversing the procedure shown in Figure 4-3.
7. Connect the AC supply to the drive.
8. When a Solutions Module is fitted to a Commander SK for the first time, as the drive
is powered-up, the drive will trip on SL.dF.
Press the STOP/RESET button to clear the trip
The Commander SK automatically saves the Solutions Module identity details to
memory which will avoid any future SL.dF trips.
9. To access the advanced parameters refer to the Commander SK Getting Started Guide.
If an SL.dF trip is not seen after the first power-up, the Solutions Module is not fitted
properly to the drive. Power down the drive, remove and re-fit the Solutions Module.
Then power can be re-applied to the drive.
10. Check that Menu 15 parameters are now available.
Figure 4-4 Fitting and removing a Solutions
Module into the Commander SK
How to use this guide Safety InformationIntroduction
SM-I/O 24V Protected User Guide13
Issue Number: 2www.controltechniques.com
11. Check that Pr 15.01 shows the correct code for the SM-I/O 24V Protected: 205.
12. Power the drive down and back up. The Solutions Module is now ready for
programming.
NOTE
If the SM-I/O 24V Protected is changed for another type of Solutions Module, the drive
will trip as in step 8. Follow the above procedure.
13. If the checks in step 10 and step 11 fail, either the Solutions Module is not fully
inserted, or it is faulty.
14. If a trip code is now present refer to Chapter 6 Diagnostics on page 32.
4.2Terminal descriptions
Figure 4-5 SM-I/O 24V Protected terminals
1234567891011121314151617
Provide fuse or other over-current protection in the relay circuit.
WARNING
Table 4-1 Terminal descriptions
TermFunction
10V common
20V common
3Digital I/O 1
4Digital I/O 2
5Digital I/O 3
6Digital I/O 4*
7Digital input 5
8Digital input 6
9Digital input 7
10Analogue output 1
110V common
12Analogue output 2
130V common
14Relay 1 contact 1
15Relay 1 contact 2
16Relay 2 contact 1**
17Relay 2 contact 2**
17-way 3.81mm pluggable screw connector.
*Digital input only with Commander SK
**Not available on Commander SK
14SM-I/O 24V Protected User Guide
www.controltechniques.comIssue Number: 2
4.3Wiring, shield connections
To prevent noise being induced onto any of the analogue outputs it is advisable to use a
twisted pair cable shielded with overall shield.
If used, the shield connections should be terminated at one of the zero volts terminals
on the Solutions Module and to the zero volts of the signal source if available. The
termination of the shield should be kept as short as possible to prevent any noise being
induced at this point.
Figure 4-6 Shield connections (current mode)
How to use this guide Safety InformationIntroduction
SM-I/O 24V Protected User Guide15
Issue Number: 2www.controltechniques.com
5Parameters
5.1Introduction
The parameters listed in this chapter are used for programming and monitoring the SMI/O 24V Protected.
5.1.1Parameter update times
The SM-IO 24V Protected is an intelligent Solutions Module. The update times for the
parameters are defined by the drive type in use. The following apply only when the
Solutions Module is used with a Unidrive SP:
Parameters shown as "Background" are updated at least once every 30ms.
If a destination pointer parameter is set up to pass data to a drive parameter including
parameters in the menu for this option module, the parameter is updated once every
4ms.
If a source pointer parameter is set up to get data from a drive parameter including
parameters in the menu for this option, the drive parameter is read once every 4ms.
The following apply only when the Solutions Module is used with a Commander SK:
The module has two parameter update times; background and fast update. The actual
update times for the two types of parameter are dependent upon the number of I/O used
(i.e. that are mapped to a valid source or destination) on the module.
The update rate for fast update parameters can be calculated with the following
expression:
t
(ms) = ((Number of I/O used) + 2 ) * 2ms
FU
The update time for background level parameters can be calculated with the following
expression:
t
(ms) = tFU * 33
BU
Only source and destination parameters that are routed to a valid parameter are
updated at the fast rate.
Number of I/O source/
destinations active
16 198
28 264
310 330
412 396
514 462
616 528
718 594
820 616
922 726
1024792
Fast Update Time (ms)Background Update Time
(ms)
16SM-I/O 24V Protected User Guide
www.controltechniques.comIssue Number: 2
NOTE
NOTE
WARNING
The analogue output 2 source is always active (source always Pr 4.02 with Commander
SK), therefore the minimum fast update time with any other I/O active will be 8ms. The
background update time will be a minimum of 264ms.
On the Unidrive SP, the “x” in the parameter number (e.g. Pr x.01), is either Menu 15
(slot 1), 16 (slot 2) or 17 (slot 3) depending on which slot is used.
On the Commander GP20, the “x” in the parameter number (e.g. Pr x.01), is either Menu
15 (slot 1), or 16 (slot 2) depending on which slot is used.
On Commander SK the “x” in the parameter number is Menu 15.
Before attempting to adjust any parameters, refer to Chapter 3 Safety Information on
page 9.
Table 5-1 Key to parameter coding
CodingAttribute
RWRead/write: can be written by the user
RORead only: can only be read by the user
Bit1 bit parameter
BiBipolar parameter
UniUnipolar parameter
TxtText: the parameter uses text strings instead of numbers.
Filtered: some parameters which can have rapidly changing values are
FI
filtered when displayed on the drive keypad for easy viewing.
DEDestination: indicates that this parameter can be a destination parameter.
Rating dependant: this parameter is likely to have different values and
ranges with drives of different voltage and current ratings. These
RA
parameters are not transferred by SMARTCARDS / SmartSticks when the
rating of the destination drive is different from the source drive.
Not cloned: not transferred to or from SMARTCARDS / SmartSticks during
NC
cloning.
PTProtected: cannot be used as a destination.
User save: saved in drive EEPROM when the user initiates a parameter
US
save.
PSPower-down save: automatically saved in drive EEPROM at power-down.
How to use this guide Safety InformationIntroduction
Solutions Module
Installing the
Parameters
DiagnosticsTerminal specificationProtectionIndex
SM-I/O 24V Protected User Guide17
Issue Number: 2www.controltechniques.com
5.2Single line descriptions
Parameter
x.01 Solutions Module ID0 to 599205RO UniPT US
x.02
Solutions Module Main Software Version
x.03 T5 digital I/O 3 stateOFF (0) or On (1)
x.04 T6 digital I/O 4 state**OFF (0) or On (1)
x.05 T7 digital input 5 stateOFF (0) or On (1)
x.06 T8 digital input 6 stateOFF (0) or On (1)
x.07 T9 digital input 7 stateOFF (0) or On (1)
x.08 Relay 1 stateOFF (0) or On (1)
x.09 T3 digital I/O 1 stateOFF (0) or On (1)
x.10 T4 digital I/O 2 stateOFF (0) or On (1)
x.11 T3 digital I/O 1 invertOFF (0) or On (1)OFF (0)RW BitUS
x.12 T4 digital I/O 2 invertOFF (0) or On (1)OFF (0)RW BitUS
x.13 T5 digital I/O 3 invertOFF (0) or On (1)OFF (0)RW BitUS
x.14 T6 digital I/O 4 invert**OFF (0) or On (1)OFF (0)RW BitUS
T7 digital input 5 invert
x.15
T8 digital input 6 invert
x.16
x.17
T9 digital input 7 invert
x.18 Relay 1 invertOFF (0) or On (1)OFF (0)RW BitUS
x.19 Not used
x.20 Digital I/O read word0 to 255RO UniNC PT
x.21 T3 digital I/O 1 source/destinationPr 0.00 to Pr 21.51Pr 0.00RW Uni DEUS
x.22 T4 digital I/O 2 source/destinationPr 0.00 to Pr 21.51Pr 0.00RW Uni DEUS
x.23 T5 digital I/O 3 source/destinationPr 0.00 to Pr 21.51Pr 0.00RW Uni DEUS
x.24 T6 digital I/O 4 source/destination***Pr 0.00 to Pr 21.51Pr 0.00RW Uni DEUS
x.25 T7 digital input 5 destinationPr 0.00 to Pr 21.51Pr 0.00RW Uni DEUS
x.26 T8 digital input 6 destinationPr 0.00 to Pr 21.51Pr 0.00RW Uni DEUS
x.27 T9 digital input 7 destinationPr 0.00 to Pr 21.51Pr 0.00RW Uni DEUS
x.28 Relay 1 sourcePr 0.00 to Pr 21.51Pr 0.00RW UniUS
x.29* T6 digital I/O 4 output selectOFF (0) or On (1)On (1)RW BitUS
x.30 Not used
x.31 T3 digital I/O 1 output selectOFF (0) or On (1)OFF (0)RW BitUS
x.32 T4 digital I/O 2 output selectOFF (0) or On (1)OFF (0)RW BitUS
x.33 T5 digital I/O 3 output selectOFF (0) or On (1)OFF (0)RW BitUS
x.34 Not used
x.35 Not used
x.36 Not used
x.37 Not used
x.38 Not used
x.39 Analogue output mode
x.40 Relay 2 stateOFF (0) or On (1)
x.41 Not used
x.42 Relay 2 invertOFF (0) or On (1)OFF (0)RW BitUS
x.43 Relay 2 sourcePr 0.00 to Pr 21.51Pr 0.00RW UniUS
x.44 Not used
x.45* Analogue output 2 scaling0.000 to 4.0001.000RW UniUS
x.46 Not used
x.47* Analogue output 2 sourcePr 0.00 to Pr 21.51Pr 0.00RW UniUS
x.48 Analogue output 1 sourcePr 0.00 to Pr 21.51Pr 0.00RW UniUS
x.49 Analogue output 1 scaling0.000 to 4.0001.000RW UniUS
x.50 Solutions Module error status0 to 255
Solutions Module software sub-version
x.51
*Parameter not available with Commander SK
** Digital input only with Commander SK
*** Destination only with Commander SK
Range(
Ú)Default(Ö)
0.00 to 99.99RO UniNC PT
OFF (0) or On (1)OFF (0)RW BitUS
OFF (0) or On (1)OFF (0)RW BitUS
OFF (0) or On (1)OFF (0)RW BitUS
How to use this guide Safety InformationIntroduction
10
Key
Input
terminals
Output
terminals
The parameters are all shown at their default settings
0.XX
0.XX
Read-write (RW)
paramete r
Read-only (RO)
paramete r
Solutions Module
Installing the
Parameters
DiagnosticsTerminal specificationProtectionIndex
SM-I/O 24V Protected User Guide23
Issue Number: 2www.controltechniques.com
Figure 5-6 Analogue output logic diagram (Commander SK only)
10
Key
Input
terminals
Output
terminals
The parameters are all shown at their default settings
0.XX
0.XX
Read-write (RW)
paramet er
Read-only (RO)
paramet er
Pr
4.02
24SM-I/O 24V Protected User Guide
www.controltechniques.comIssue Number: 2
5.4Parameter descriptions
x.01Option ID code
ROUniPTUS
Ú
Update rate: Write on power-up
On Unidrive SP / Commander GP20 the menu for the relevant slot appears for the new
Solutions Module category with the default parameter values for the new category. For
Commander SK it will always be menu 15.
When no Solutions Module is fitted in the relevant slot this parameter is zero. When a
Solutions Module is fitted this parameter displays the identification code as shown
below.
The new parameter values are not stored in the drive EEPROM until the user performs
a parameter save by setting Pr xx.00 to 1000 (or 1001 in the case of solely using the
24V back-up power supply) and pressing the stop/reset button. When parameters are
saved by the user in the drive EEPROM, the option code of the currently fitted Solutions
Module is saved in the drive EEPROM. If the drive is subsequently powered-up with a
different Solutions Module fitted, or no Solutions Module is fitted when one was
previously fitted, the drive will trip on SLx.dF or SLx.nF.
0 to 599
Ö
Feedback
Automation
Fieldbus
Dumb
module
Uni SP Comm GP20 Comm SK
99
99 9
Compatibility
9
How to use this guide Safety InformationIntroduction
Solutions Module
Installing the
Parameters
DiagnosticsTerminal specificationProtectionIndex
SM-I/O 24V Protected User Guide25
Issue Number: 2www.controltechniques.com
Commander SK
The new parameter values are stored automatically by the drive. If the drive is
subsequently powered up with a different Solutions Module fitted, or no Solutions
Module is fitted when one was previously fitted, the drive will trip on SL.dF or SL.nF.
x.02Solutions Module main software version
ROUniNCPT
Ú
Update rate: Write on power-up
This module contains two processors, and thus two software versions. Pr x.02 shows
the version number of the main module processor. Pr x.51, which is normally used to
give a sub-version number, shows the software version in the slave processor.
x.03T5 digital I/O 3 state
x.04T6 digital I/O 4 state*
x.05T7 digital input 5 state
x.06
x.07T9 digital input 7 state
x.08Relay 1 state
x.09T3 digital I/O 1 state
x.10T4 digital I/O 2 state
ROBitNCPT
Ú
Update rate: 4ms write
00.00 to 99.99
T8 digital input 6 state
OFF (0) or On (1)
Ö
Ö
These parameters indicate the input and output states of the terminals.
*Digital output 4 is not available with Commander SK.
NOTE
The update rates stated are when used with Unidrive SP / Commander GP20.
26SM-I/O 24V Protected User Guide
www.controltechniques.comIssue Number: 2
x.11T3 digital I/O 1 invert
x.12T4 digital I/O 2 invert
x.13T5 digital I/O 3 invert
x.14T6 digital I/O 4 invert*
x.15T7 digital input 5 invert
x.16T8 digital input 6 invert
x.17T9 digital input 7 invert
x.18Relay 1 invert
RWBitUS
Ú
OFF (0) or On (1)
Ö
OFF (0)
Update rate: 4ms read
*Digital output 4 is not available with Commander SK.
Setting these parameters to On(1) causes the input sense to the destination parameter
to be inverted or the output sense from the source to be inverted.
x.20Digital I/O read word
ROUniNCPTUS
Ú
0 to 255
Ö
Update rate: 500µs write
This word is used to determine the status of the digital I/O by reading one parameter.
The bits in this word reflect the state of Pr x.03 to Pr x.10.
BitDigital I/OParameter
0T3 (Digital I/O 1)Pr x.09500µs / 4ms
1T4 (Digital I/O 2)Pr x.10500µs / 4ms
2T5 (Digital I/O 3)Pr x.03500µs / 4ms
3T6 (Digital I/O 4)**Pr x.04500µs / 4ms
4T7 (Digital input 5)Pr x.05500µs / -
5 T8 (Digital input 6)Pr x.06500µs / -
6 T9 (Digital input 7)Pr x.07500µs / -
7T14 / T15 (Digital output 8 relay)Pr x.08- / 4ms
Bit Update Rate
Input/Output*
*Update rates when used with Unidrive SP / Commander GP20.
**Digital input 4 state only with Commander SK.
How to use this guide Safety InformationIntroduction
Solutions Module
Installing the
Parameters
DiagnosticsTerminal specificationProtectionIndex
SM-I/O 24V Protected User Guide27
Issue Number: 2www.controltechniques.com
x.21T3 digital I/O 1 source/destination
x.22T4 digital I/O 2 source/destination
x.23T5 digital I/O 3 source/destination
x.24T6 digital I/O 4 source/destination*
x.25T7 digital input 5 destination
x.26T8 digital input 6 destination
x.27T9 digital input 7 destination
x.28Relay 1 source
RWUniDEUS
Ú
Update rate: Read on drive reset
*Digital input 4 destination only with Commander SK.
Source parameters define the parameter to be represented by the digital output
terminal.
Destination parameters define the parameter each of the programmable inputs is to
control.
RWBitUS
Ú
Update rate: Background read
*Parameter not available with Commander SK (T6 is a digital input only).
This parameter selects the function of terminal T6 as follows:
OFF (0) = digital input
On (1) = digital output
Pr 0.00 to Pr 21.51
x.29*T6 digital I/O 4 output select
OFF (0) or On (1)
Ö
Ö
Pr 0.00
On (1)
x.31T3 digital I/O 1 output select
x.32T4 digital I/O 2 output select
x.33T5 digital I/O 3 output select
RWBitUS
Ú
Update rate: Background read
These parameters select the function of terminals T3 to T5 as follows:
OFF (0) = digital input
On (1) = digital output
OFF (0) or On (1)
Ö
OFF (0)
28SM-I/O 24V Protected User Guide
www.controltechniques.comIssue Number: 2
x.39Analogue output mode
RWUniUS
0-20, 20-0, 4-20, 20-4
Ú
Update rate: Background read
This parameter sets the output mode for terminals 10 and 12 as follows:
Parameter value Parameter stringMode
00-200-20mA
120-020-0mA
24-204-20mA
320-420-4mA
4*VoLtNot useable
*Only with Commander SK and not useable.
x.40Relay 2 state
ROBitNCPT
Ú
Update rate: 4ms write
RWBitUS
Ú
Update rate: 4ms read
RWUniDEUS
Ú
Update rate: 4ms read
OFF (0) or On (1)
x.42Relay 2 invert
OFF (0) or On (1)
x.43Relay 2 source
Pr 0.00 to Pr 21.51
Ö
Ö
Ö
Ö
0-20
OFF (0)
Pr 0.00
How to use this guide Safety InformationIntroduction
Solutions Module
Installing the
Parameters
DiagnosticsTerminal specificationProtectionIndex
x.45*Analogue output 2 scaling
RWUniUS
Ú
Update rate: Background read
*Parameter not available with Commander SK.
This parameter can be used to scale the analogue output if so desired
SM-I/O 24V Protected User Guide29
Issue Number: 2www.controltechniques.com
0.000 to 4.000
Ö
1.000
NOTE
x.47*Analogue output 2 source
RWUniUS
Ú
Update rate: Read on reset
*Parameter not available with Commander SK (Analogue output 2 is a load output
only [Pr 4.02]).
The parameter required to be represented as an analogue signal by the analogue
output on terminal 12, should be programmed into this parameter.
RWUniUS
Ú
Update rate: Read on reset
The parameter required to be represented as an analogue signal by the analogue
output on terminal 10, should be programmed into this parameter.
RWUniUS
Ú
Update rate: Background read
This parameter can be used to scale the analogue output if so desired.
ROUniNCPT
Ú
Update rate: Background read
The error status is provided so that only one option error trip is required for each
Solutions Module slot. If an error occurs, the reason for the error is written to this
parameter and the drive may produce a ‘SLx.Er’ trip, where x is the slot number (SL.Er
on Commander SK). A value of zero indicates that the Solutions Module has not
detected an error, a non-zero value indicates that an error has been detected. (See
Chapter 6 Diagnostics for the meaning of the values in this parameter.) When the drive
is reset, this parameter is cleared for the relevant Solutions Module.
This Solutions Module includes a temperature monitoring circuit. If the PCB temperature
exceeds 90°C, the drive fan is forced to operate at full speed (for a minimum of 10s). If
the temperature falls below 90°C, the fan can operate normally again. If the PCB
temperature exceeds 100°C, the drive is tripped and the error status is set to 74.
If the PCB temperature exceeds 90°C on the Commander SK, the fan will operate at full
speed for a minimum of 20s.
Pr 0.00 to Pr 21.51
x.48Analogue output 1 source
Pr 0.00 to Pr 21.51
x.49Analogue output 1 scaling
0.000 to 4.000
x.50Solutions Module error status
0 to 255
Ö
Ö
Ö
Ö
Pr 0.00
Pr 0.00
1.000
30SM-I/O 24V Protected User Guide
www.controltechniques.comIssue Number: 2
x.51Solutions Module software sub-version
ROUniNCPT
Ú
0 to 99
Ö
Update rate: Write on power-up
This module contains two processors, and thus two software versions. Pr x.02 shows
the version number of the main module processor. Pr x.51, which is normally used to
give a sub-version number, shows the software version in the slave processor.
How to use this guide Safety InformationIntroduction
Solutions Module
Installing the
Parameters
SM-I/O 24V Protected User Guide31
Issue Number: 2www.controltechniques.com
DiagnosticsTerminal specificationProtectionIndex
6Diagnostics
S
If the drive trips, the output is disabled so that the drive stops controlling the motor. The
display indicates that a trip has occurred as shown in Figure 6-1 and Figure 6-3.
Trips are listed in section 6.2 Unidrive SP / Commander GP20 trip descriptions on
page 34 and section 6.3 Commander SK trip descriptions on page 35 based on the trip
indication shown on the drive display. Refer to Figure 6-1 for Unidrive SP / Commander
GP20 and Figure 6-3 for Commander SK.
If a display is not used on the Unidrive SP / Commander GP20, the drive LED Status
indicator will flash if the drive has tripped. Refer to Figure 6-2.
The trip indication can be read in Pr 10.20 providing a trip number.
6.1Displaying the trip history
6.1.1Unidrive SP / Commander GP20
The drive retains a log of the last 10 trips that have occurred in Pr
the corresponding time for each trip in Pr
from the powered-up clock (if Pr
Pr 10.20 is the most recent trip, or the current trip if the drive is in a trip condition (with
the time of the trip stored in Pr 10.43). Pr 10.29 is the oldest trip (with the time of the trip
stored in Pr 10.51). Each time a new trip occurs, all the parameters move down one,
such that the current trip (and time) is stored in Pr 10.20 (and Pr 10.43) and the oldest
trip (and time) is lost from the bottom of the log.
If any parameter between Pr 10.20 and Pr 10.29 inclusive is read by serial
communications, then the trip number in section 6.2 Unidrive SP / Commander GP20 trip descriptions on page 34 is the value transmitted.
Figure 6-1 Unidrive SP / Commander GP20 keypad status modes
6.28
= 0) or from the run time clock (if Pr
tatus Mode
10.43
to Pr
10.20
10.51
. The time of the trip is recorded
to Pr
6.28
10.29
= 1).
and
Healthy Status
Trip Statu sAlarm Status
Drive status
= tripped
Trip type (UU
= undervolts)
32SM-I/O 24V Protected User Guide
www.controltechniques.comIssue Number: 2
Figure 6-2 Location of the status LED
p
S
Status LED
How to use this guide Safety InformationIntroduction
Any trip can be initiated by writing the relevant trip number to Pr 10.38. If any trips
shown as user trips are initiated the trip string is "txxx", where xxx is the trip number.
Trips can be reset after 1.0s if the cause of the trip has been rectified.
A full list of drive trips can be found in the Unidrive SP User Guide / Commander GP20
User Guide.
6.1.2Commander SK
The drive retains a log of the last 10 trips that have occurred in Pr 10.20 to Pr 10.29.
Pr 10.20 is the most recent trip, or the current trip if the drive is in a trip condition, and
Pr 10.29 is the oldest trip. Each time a new trip occurs, all the parameters move down
one, such that the current trip (and time) is stored in Pr 10.20 and the oldest trip is lost
from the bottom of the log.
If any parameter between Pr 10.20 and Pr 10.29 inclusive is read by serial
communications, then the trip number in section 6.3 Commander SK trip descriptions on page 35 is the value transmitted.
MMM
Non flashing:
Normal status
Flashing:
status
Tri
Figure 6-3 Commander SK keypad status modes
tatus Mode
Alarm StatusHealthy StatusTrip Status
Drive status = tripped
Trip type = UU (undervolts)
Solutions Module
Installing the
Parameters
Diagnostics
Terminal specificationProtectionIndex
Any trip can be initiated by writing the relevant trip number to Pr 10.38. If any trips
shown as user trips are initiated the trip string is "t0xx", where xx is the trip number.
Trips can be reset after 1.0s if the cause of the trip has been rectified.
A full list of drive trips can be found in the Commander SK Advanced User Guide.
SM-I/O 24V Protected User Guide33
Issue Number: 2www.controltechniques.com
6.2Unidrive SP / Commander GP20 trip descriptions
Trip no.StringDiagnosis
200, 205,
210
201, 206,
211
202, 207,
212
SLX.HFSolutions Module hardware fault
Ensure Solutions Module is fitted correctly
Return Soltutions Module to supplier
SLX.tOSolutions Module watchdog time-out
Press reset
If the trip persists, contact the supplier of the drive
SLX.ErError detected with Solutions Module where X is the slot number
Pr x.50Fault description
0No errors
1Digital outputs overloaded
2Digital inputs overloaded
3Communications Error
74Solutions Module over temperature (>100°C)
203, 208,
213
204, 209,
214
215SL.rtdDrive mode has changed and Solutions Module parameter
SLX.nFSolutions Module has been removed
Ensure Solutions Module is fitted correctly
Save parameters and reset drive
Replace Solutions Module
SLX.dFSolutions Module fitted in slot X has changed
Save parameters and reset
routing is now incorrect
Press reset
If the trip persists, contact the supplier of the drive
For further information on the above trips, see the Diagnostics section of the Unidrive SP User Guide or the Commander GP20 User Guide.
34SM-I/O 24V Protected User Guide
www.controltechniques.comIssue Number: 2
6.3Commander SK trip descriptions
Trip no.StringDiagnosis
200SL.HFSolutions Module hardware fault
Ensure Solutions Module is fitted correctly
Return Solutions Module to supplier
201SL.tOSolutions Module watchdog time-out
Press reset
If the trip persists, contact the supplier of the drive
202SL.ErError detected with Solutions Module
Pr x.50Fault description
0No errors
1Digital outputs overloaded
2Digital inputs overloaded
3Communications Error
74Solutions Module over temperature (>100°C)
203SL.nFSolutions Module has been removed
Ensure Solutions Module is fitted correctly
Replace Solutions Module
204SL.dFSolutions Module fitted has changed
Power down and back up
For further information on the above trips, see Menu 10 in the Commander SK Advanced User Guide.
How to use this guide Safety InformationIntroduction
Solutions Module
Installing the
Parameters
SM-I/O 24V Protected User Guide35
Issue Number: 2www.controltechniques.com
Diagnostics
Terminal specificationProtectionIndex
7Terminal specification
NOTE
Digital inputs are positive logic only.
0V
1
0V
2
Digital I/O 1
3
Digital I/O 2
4
Digital I/O 3
5
Digital I/O 4*
6
TypeProgrammable positive logic digital input or output
Operating as an input
Absolute maximum voltage range
Load>2mA @ 15Vdc
Input switching threshold10V ±0.8V
Operating as an output
Maximum output current40mA
Total of all 4 outputs40mA
Output voltage when servicing 10mA20.5V to 27V
Typical input current @ 15V2.8mA
Typical input current @ 5V0.9mA
Digital input 5
7
Digital input 6
8
Digital input 7
9
TypePositive logic digital input
Absolute maximum voltage range
Load>2mA @ 15Vdc
Input switching threshold10V to ±0.8V
Typical input current @ 15V2.8mA
Typical input current @ 5V0.9mA
+60V (drive trip generated when input exceeds
+35V)
-30V
+60V (drive trip generated when input exceeds
+35V)
-30V
*Digital input 4 only with Commander SK.
Analogue output 1
10
Type of outputUnipolar current source
Current range0-20, 20-0, 4-20, 20-4 (mA)
Maximum offset (0Ω load)±1mA typical
Maximum output voltage for stated accuracy12V
Maximum load resistance600Ω
Resolution12 bits
Scale accuracy5%
36SM-I/O 24V Protected User Guide
www.controltechniques.comIssue Number: 2
WARNING
0V
11
Analogue output 2
12
Type of outputUnipolar current source
Current range0-20, 20-0, 4-20, 20-4 (mA)
Maximum offset (0Ω load)±1mA typical
Maximum output voltage for stated accuracy12V
Maximum load resistance600Ω
Resolution12 bits
Scale accuracy5%
0V
13
Relay 1 contact 1
14
Relay 1 contact 2
15
Relay 2 contact 1*
16
Relay 2 contact 2*
17
Contact rating
Contact minimum recommended rating12V 100mA
Normally open contacts
2A AC 50Vrms
6A DC 30V resistive load (1.5A DC 60V for UL
requirement)
0.3A DC 50V inductive load (L/R = 40ms)
*Not on Commander SK
Provide fuse or other over-current protection in relay circuit.
How to use this guide Safety InformationIntroduction
Solutions Module
Installing the
ParametersDiagnostics
The relay contacts give galvanic isolation from all other drive circuits. They do not
provide additional safety isolation from other circuits on the Solutions Module.
WARNING
SM-I/O 24V Protected User Guide37
Issue Number: 2www.controltechniques.com
specification
Ter min al
ProtectionIndex
8Protection
8.1E.M.C immunity
The Solutions Module must not be damaged and performance must not be adversely
affected.
Digital inputs / Digital IO can withstand + 60V with respect to the user terminal 0V. A
drive trip is generated when the input voltage exceeds +35V.
Other terminals can withstand indefinitely without damage or degradation ±36V with
respect to the user terminal 0V (user 0V or drive 0V) when the drive is powered,
unpowered and during the transitions.