This guide provides basic guidelines for the Emerson Smart Wireless THUM Adapter. It does not provide
instructions for detailed configuration, diagnostics, maintenance, service, troubleshooting, or installations.
Refer to the THUM Adapter Reference Manual (document number 00809-0100-4075) for more instruction.
The manual and this guide are also available electronically on www.rosemount.com.
This device complies with Part 15 of the FCC Rules. Operation is subject to the following conditions. This
device may not cause harmful interference. This device must accept any interference received, including
interference that may cause undesired operation.
Explosions could result in death or serious injury.
Installation of this transmitter in an explosive environment must be in accordance with the appropriate local,
national, and international standards, codes, and practices. Review the Product Certifications section for any
restrictions associated with a safe installation.
Before connecting a Field Communicator in an explosive atmosphere, ensure the instruments are installed
in accordance with intrinsically safe or non-incendive field wiring practices.
Electrical shock can result in death or serious injury.
Avoid contact with the leads and terminals. High voltage that may be present on leads can cause electrical
shock.
This device must be installed to ensure a minimum antenna separation distance of 7.87-in. (20 cm) from all
persons.
During normal operation, or in fault condition, the THUM Adapter will cause a 2.5 V drop in the connected
loop. It is important to ensure that the power supply can provide at least 2.5 V more than the minimum
operating voltage of the wired device to make sure it works properly with the THUM Adapter installed. To
determine the minimum operating voltage for the wired device, review the wired device operation and
installation manual.
Power should not be applied to any wireless device until the Smart Wireless
Gateway (“Gateway”) is installed and functioning properly. Wireless devices
should also be powered up in order of proximity from the Gateway, beginning
with the closest. This will result in a simpler and faster network installation. Enable
Active Advertising on the Gateway to ensure that new devices join the network
faster. For more information see the Smart Wireless Gateway Manual (document
number 00809-0200-4420).
1.2 THUM Adapter position
THUM Adapter should be positioned vertically straight up, and should be
approximately 3 ft. (1 m) from any large structure, building or conductive surface
to allow for clear communication to other devices. If the THUM Adapter is
mounted horizontally wireless communication range may be decreased. The
THUM Adapter should not be mounted vertically straight down. See THUM
Adapter reference manual (document number 00809-0100-4075) for more
information.
Figure 1. THUM Adapter Position
1.3 Conduit entry
When installing the THUM Adapter into the conduit entry of a wired device, use
an approved thread sealant. Thread sealant provides a water tight seal. The
thread sealant also provides lubrication to ensure easy removal of the THUM
Adapter.
1.4 M20 conduit adapter
When using the M20 Conduit Adapter on the THUM Adapter, use an approved
thread sealant and tighten wrench tight to the THUM Adapter. When installing
the M20 conduit adapter into a conduit, tighten to 32.5 N-m/25 ft-lb to ensure
water tight seal.
3
Quick Start Guide
Field Communicator connections
In order for the Field Communicator to interface with the THUM Adapter, the
wired device must be powered. The Field Communicator must be put into poll
mode and should use the THUM Adapter address of 63.
1.5 Power supply
Minimum loop load of 250 Ohms.
The THUM Adapter communicates via and derives power from a standard
4–20 mA/HART® loop. The THUM Adapter causes a small voltage drop on the
loop which is linear from 2.25 V at 3.5 mA to 1.2 V at 25 mA. Under fault
conditions, the maximum voltage drop is 2.5 V. The THUM Adapter will not
affect the 4–20 mA signal under normal or fault conditions as long as the loop
has at least a 2.5 V margin at the maximum loop current (25 mA for a typical
4–20 mA/HART device).
Limit the power supply to 0.5 Amps maximum and voltage to 55 Vdc.
Loop currentTHUM Adapter voltage drop
3.5 mA2.25 V
25 mA1.2 V
June 2016
1.6 Load resistor
If required, add a load resistor as shown in Figure 8 on page 10, Figure 12 on
page 13, and Figure 16 on page 15. The resistor should be adequately rated for
the application (1W minimum) and be compatible with the supplied splice
connector which accepts wire sizes from 14 to 22 AWG.
1.7 Loop
To ensure proper operation, the THUM Adapter should not be installed on a HART
loop with other active HART masters. HART masters that are active periodically,
such as a field communicator can be used on a loop with a THUM Adapter.
4
June 2016
A
Green
Red
Black
White
Yellow
B
C
D
+
-
Green
Red
Black
White
Yellow
A
B
C
+
-
D
Quick Start Guide
2.0 Bench top configuration
When performing bench top configuration it is suggested that you connect the
THUM Adapter to a wired device. If this is not possible, the following wiring
diagrams can be used. For bench top configuration, ensure the power supply
used is limited to 0.5 Amps maximum.
Figure 2. THUM Adapter Only, Powered by a Current Source
A. THUM AdapterC. 20 mA current source
B. GroundD. HART Modem
Figure 3. THUM Adapter Only, Powered by a 24 V Power Supply with 1200
Ohm Resistor to Limit Current to 20 mA
A. THUM AdapterC. 20 V power supply
B. GroundD. HART Modem
5
Quick Start Guide
3.0 Physical installation
The THUM Adapter can be installed in one of two configurations:
1. Direct mount: The THUM Adapter is connected directly to the conduit entry
of the wired device.
2. Remote mount: The THUM Adapter is mounted separate from the wired
device housing and then connected to the wired device using conduit or other
suitable means.
Figure 4. Direct Mount
June 2016
4.0 Direct mount
1. Install the HART device according to standard installation practices and the
manufacturer’s instructions, being sure to use an approved thread sealant on
all connections.
2. Attach the THUM Adapter to the wired device as shown in Figure 4 on page 6.
3. Connect the THUM Adapter to the HART wired device using the wiring
diagrams below. See Figure 21 on page 19, Figure 8 on page 10, Figure 10 on
page 11, and Figure 12 on page 13 on the following pages.
4. Close the housing cover on the HART wired device, so that metal touches
metal, but do not over tighten to prevent damaging the unit.
Note
Two splice connectors are included with the THUM Adapter. The first is a two connection
splice. The second is a three connection splice for use with a resistor, if there is not enough
resistance in the loop. Both of these splice connectors can accept 14 to 22 gauge wire. See
wired device reference manual for information on the required loop resistance.
6
June 2016
Quick Start Guide
5.0 Remote mount
Figure 5. Remote Mount
1. Install the HART device according to standard installation practices and the
manufacturer’s instructions, being sure to use an approved thread sealant on
all connections.
2. The THUM Adapter should be mounted as shown in Figure 5 on page 7.
3. Ground the Remote Mount Kit per local practices.
4. Connect the THUM Adapter to the wired device using standard practices. Wire
running from the THUM Adapter to the wired device should be shielded or in
conduit when installed in electrically noisy environments.
5. Connect the THUM Adapter to the HART wired device using the wiring
diagrams below. See Figure 21 on page 19, Figure 8 on page 10, Figure 10 on
page 11, and Figure 12 on page 13 on the following pages.
6. Close the housing cover on the HART wired device, so that metal touches
metal, but do not over tighten to prevent damaging the unit.
Note
Two splice connectors are included with the THUM Adapter. The first is a two connection
splice. The second is a three connection splice for use with a resistor, if there is not enough
resistance in the loop. Both of these splice connectors can accept 14 to 22 gauge wire. See
wired device reference manual for information on the required loop resistance.
7
Quick Start Guide
5.1 Wiring diagrams
The following is a list of the figure titles and page numbers for each direct mount
and remote mount wiring diagram:
Figure 6 - “Direct Mount Wiring Diagram for 2-Wire Device” on page 9
Figure 7 - “Remote Mount Wiring Diagram for 2-Wire Device” on page 10
Figure 8 - “Direct Mount Wiring Diagram for 2-Wire Device with Resistor” on
page 10
Figure 9 - “Remote Mount Wiring Diagram for 2-Wire Device with Resistor” on
page 11
Figure 10 - “Direct Mount Wiring Diagram for 4-Wire Passive Device” on page 11
Figure 11 - “Remote Mount Wiring Diagram for 4-Wire Passive Device” on
page 12
Figure 12 - “Direct Mount Wiring Diagram for 4-Wire Passive Device with
Resistor” on page 13
Figure 13 - “Remote Mount Wiring Diagram for 4-Wire Passive Device with
Resistor” on page 13
June 2016
Figure 14 - “Direct Mount Wiring Diagram for 4-Wire Active Device” on page 14
Figure 15 - “Remote Mount Wiring Diagram for 4-Wire Active Device” on page 15
Figure 16 - “Direct Mount Wiring Diagram for 4-Wire Active Device with
Resistor” on page 15
Figure 17 - “Remote Mount Wiring Diagram for 4-Wire Active Device with
Resistor” on page 16
Figure 18 - “Direct Mount Wiring Diagram for 4-Wire Active Device with No 4–20
mA Loop” on page 17
Figure 19 - “Remote Mount Wiring Diagram for 4-Wire Active Device with No
4–20 mA Loop” on page 18
Figure 20 - “THUM Adapter only, Powered by a 24 V Power Supply with 1200
Ohm resistor to limit current to 20 mA” on page 19
Figure 21 - “THUM Adapter only, Powered by a 24 V Power Supply with 1200
Ohm resistor to limit current to 20 mA” on page 19
8
June 2016
A
Green
Red
Black
White
Yellow
4 -20 mA Loop +
4 -20 mA Loop -
B
C
D
E
F
- PWR/COMM
+ PWR/COMM
Figure 6. Direct Mount Wiring Diagram for 2-Wire Device
A. THUM AdapterD. Splice connector
B. Wired deviceE. Load resistor ≥ 250 Ω
C. GroundF. Power supply
Quick Start Guide
Note
In order for the THUM Adapter to function properly there must be at least 250 Ohms
resistance in the loop. If the 4–20 mA loop does not have the required resistance, wire a
resistor as shown in Figure 8 on page 10, Figure 12 on page 13, or Figure 16 on page 15 as
applicable.
9
Quick Start Guide
A
Green
Red
Black
White
Yellow
4 -20 mA Loop -
F
B
C
E
D
- PWR/COMM
+ PWR/COMM
4 -20 mA Loop +
Figure 7. Remote Mount Wiring Diagram for 2-Wire Device
A
B
Red
Green
C
White
Yellow
Black
4 -20 mA Loop +
4 -20 mA Loop -
June 2016
F
+ COMM
- COMM
D
To Wired Device
E
A. THUM AdapterD. Shield wire
B. Remote mount housingE. Load resistor ≥ 250 Ω
C. GroundF. Power supply
Figure 8. Direct Mount Wiring Diagram for 2-Wire Device with Resistor
A. THUM AdapterD. Splice connector
B. Wired device E. Load resistor ≥ 250 Ω
C. GroundF. Power supply
10
June 2016
A
B
C
Green
White
Yellow
Red
Black
D
E
+ COMM
- COMM
To Wired Device
4 - 20 mA Loop +
4 - 20 mA Loop -
+
-
F
Figure 9. Remote Mount Wiring Diagram for 2-Wire Device with Resistor
Quick Start Guide
A. THUM AdapterD. Shield wire
B. Remote mount housingE. Load resistor ≥ 250 Ω
C. GroundF. Power supply
Figure 10. Direct Mount Wiring Diagram for 4-Wire Passive Device
A
Green
A. THUM AdapterD. Splice connector
B. Wired device E. Load resistor ≥ 250 Ω
C. GroundF. Power supply
Red
Black
White
Yellow
COMM +
COMM -
B
C
Power -
Power +
D
4 - 20 mA Loop +
4 -20 mA Loop -
F
E
11